Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹90.8 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | ₹90.8 L Quoted ₹92.6 L | L1 | Accepted-AOC L1 bidder |
| 2 | L2₹1.1 Cr+₹20.2 L (21.8%)Rejected-Finance NOT SPECIFIED | ₹1.1 Cr+₹20.2 L (21.8%) | L2 | Rejected-Finance Other than L1 |
| 3 | L3₹1.4 Cr+₹47.1 L (50.8%)Rejected-Finance H M APARTMENT 4C S J ROAD ATHGAON GUWAHATI 781001 | GUWAHATI | KAMRUP METRO | ASSAM | 781001 | ₹1.4 Cr+₹47.1 L (50.8%) | L3 | Rejected-Finance Other than L1 |
| Sl No | Description | Qty | Unit | United Sales Corporation L2 | PURBANCHAL BUILDERS L1 | M/S. SUBHAS CONSTRUCTION CO. L3 |
|---|---|---|---|---|---|---|
| 1.00 | Taking down unserviceable/old ACSR conductor any size from over head lines, poles by removing binding wire and removal from site complete all as specified and directed. | 22 | Qtl | 200 ₹4,400 | 99 ₹2,178 Lowest | 700 ₹15,400 |
| 2.00 | M & L for Dismantling unserviceable cross arms, clamps etc complete all as specified and directed.. | 14 | Qtl | 200 ₹2,800 | 99 ₹1,386 Lowest | 700 ₹9,800 |
| 3.00 | M & L for Dismantling insulator any type, any size from HT/LT poles complete all as specified and directed. | 80 | Each | 10 ₹800 | 9 ₹720 | 5 ₹400 Lowest |
| 4.00 | Dismantling old steel pole/struts any size all as directed by engineer in charge all as directed. | 8 | Each | 100 ₹800 Lowest | 199 ₹1,592 | 500 ₹4,000 |
| 5.00 | Dismantling stay assembly complete all as specified and directed.
Note: Demolition of concrete, etc. and excavation to be measured separately. | 8 | Each | 25 ₹200 Lowest | 99 ₹792 | 250 ₹2,000 |
| 6.00 | Supply and installation testing commssiong of 500 KVA, 11/0.433 KV, AC, 3 PHASE, 50 HZ, ONAN Cooled Oil Immersed copper wound Outdoor type Step Down Transformer complete with first filling of IS : 335 ISI Marked Filtered & Dehydrated Transformer Oil and other standard fittings, HT 11 KV 3 Phase, LT 433 volts, 3 phase 4 wire with off load tapping on HT side to vary secondary voltage within limit, all as per IS 1180:2014 (level 3) of capacity 500 KVA core type copper wound, oil immersed, naturally cooled, oil nature, air nature (ONAN) with external cooling tubes/fins, delta connected on primary side (HV) and Star connected on secondary side (LV) in accordance with vector symbol DYN-11 (Vector group) with neutral brought out on secondary side (LV side) and 7 position OFF-LOAD tap changer having taping range of +/- 7.5% complete with all accessories, connection and fixed externally with suitable rating of motor, gear box and enclosure, the maximum temperature rise should not exceed 45 degree Celcisu n oil and 55 degree celsisu in HV/LV winding when measured by resistance method after continious fll load run on an ambient temperature of 40 degree celcius. The transformer shall be IS 1180:2014 Part -I (level 3) with amd. No. 1,2,3 & 4. Total Losses @50% Load not more than 1354W and Total Losses @100% Load not more than 3909W including and shall comprise of the following:- (i) One cable box on HT side (Primary side) consisting of 03 Nos of porcelain bushing with copper rod, complete with nuts and washers with two numbers cable glands suitable for reception/taking out of XLPE insulated heavy duty armoured cable including glands, joints and jointing material complete. (ii) One cable box on LT side (secondary) consisting of 04 Nos of porcelain bushing with copper rod, complete with nuts and washers with two numbers cable glands suitable for reception/taking out of XLPE insulated heavy duty armoured cable including glands, joints and jointing material complete. (iii) Oil conservator with filter type drain valve and oil level gauge. (iv) Dehydrating breather with first fills dehydrating agents (Silica gel). (v) Explosive vent (vi) Thermometer pocket on tank cover. (vii) One number 100mm dia, dial type thermometer, vapour pressure type having range 0-120 degree celcius with metal guard having max perimeter reading temperature indicator with resisting device for transformer. (viii) Two earthing terminal on tank cover to facilitate fixing of 32x6mm GI strip for earthing of neutral body. (ix) Rating plate and terminal marking plate. (x) Oil level gauge (xi) Oil drain filter valve. (xii) Lifting hooks. (xiii) Oil filling holes with cap/plug with connecting plate complete. (xiv) MS wheels 04 Nos with lock pins including making of plinth for transformer are required on ground and as directed. (xv) Oil temp/winding temp lubricating with marshaling box. | 1 | Each | 25,00,000 ₹25,00,000 | 17,59,999 ₹17,59,999 Lowest | 42,00,000 ₹42,00,000 |
| 7.00 | Shifting of distribution transformer 63 to 500 KVA capacity and any locaion inside the cantt or deposit to MES store yard for further disposal action complete all as specified and directed. | 1 | Each Job | 10,000 ₹10,000 | 5,999 ₹5,999 Lowest | 40,000 ₹40,000 |
| 8.01 | M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 16 sqmm 4 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed. | 2,500 | RM | 275 ₹6,87,500 | 229 ₹5,72,500 Lowest | 375 ₹9,37,500 |
| 8.02 | M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 25 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed. | 2,450 | RM | 300 ₹7,35,000 | 299 ₹7,32,550 Lowest | 418 ₹10,24,100 |
| 8.03 | M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 35 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed. | 1,300 | RM | 350 ₹4,55,000 | 329 ₹4,27,700 Lowest | 495 ₹6,43,500 |
Tender Value
₹1.0 Cr
EMD Value
₹1.8 L
Closing Date
4 Dec 2025, 6:00 pmClosed
CWE Shillong
HQ CWE Shillong, SE Falls, Shillong - 793011
ADDN/ALTN FOR UPGRADATION OF EXTERNAL ELECTRIFICATION SYSTEM FROM PANJABARI GATE TO TCP ROAD AT NARANGI UNDER GE NARANGI
2025_MES_736302_2
8920/NAR/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Narangi
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,000
GE Narangi
₹1.8 L
Yes
16 Jan 2026
20 Nov 2025
6 Dec 2025
20 Nov 2025
4 Dec 2025
27 Nov 2025
Amount
Taking down unserviceable/old ACSR conductor any size from over head lines, poles by removing binding wire and removal from site complete all as specified and directed.
M & L for Dismantling unserviceable cross arms, clamps etc complete all as specified and directed..
M & L for Dismantling insulator any type, any size from HT/LT poles complete all as specified and directed.
Dismantling old steel pole/struts any size all as directed by engineer in charge all as directed.
Dismantling stay assembly complete all as specified and directed. Note: Demolition of concrete, etc. and excavation to be measured separately.
Supply and installation testing commssiong of 500 KVA, 11/0.433 KV, AC, 3 PHASE, 50 HZ, ONAN Cooled Oil Immersed copper wound Outdoor type Step Down Transformer complete with first filling of IS : 335 ISI Marked Filtered & Dehydrated Transformer Oil and other standard fittings, HT 11 KV 3 Phase, LT 433 volts, 3 phase 4 wire with off load tapping on HT side to vary secondary voltage within limit, all as per IS 1180:2014 (level 3) of capacity 500 KVA core type copper wound, oil immersed, naturally cooled, oil nature, air nature (ONAN) with external cooling tubes/fins, delta connected on primary side (HV) and Star connected on secondary side (LV) in accordance with vector symbol DYN-11 (Vector group) with neutral brought out on secondary side (LV side) and 7 position OFF-LOAD tap changer having taping range of +/- 7.5% complete with all accessories, connection and fixed externally with suitable rating of motor, gear box and enclosure, the maximum temperature rise should not exceed 45 degree Celcisu n oil and 55 degree celsisu in HV/LV winding when measured by resistance method after continious fll load run on an ambient temperature of 40 degree celcius. The transformer shall be IS 1180:2014 Part -I (level 3) with amd. No. 1,2,3 & 4. Total Losses @50% Load not more than 1354W and Total Losses @100% Load not more than 3909W including and shall comprise of the following:- (i) One cable box on HT side (Primary side) consisting of 03 Nos of porcelain bushing with copper rod, complete with nuts and washers with two numbers cable glands suitable for reception/taking out of XLPE insulated heavy duty armoured cable including glands, joints and jointing material complete. (ii) One cable box on LT side (secondary) consisting of 04 Nos of porcelain bushing with copper rod, complete with nuts and washers with two numbers cable glands suitable for reception/taking out of XLPE insulated heavy duty armoured cable including glands, joints and jointing material complete. (iii) Oil conservator with filter type drain valve and oil level gauge. (iv) Dehydrating breather with first fills dehydrating agents (Silica gel). (v) Explosive vent (vi) Thermometer pocket on tank cover. (vii) One number 100mm dia, dial type thermometer, vapour pressure type having range 0-120 degree celcius with metal guard having max perimeter reading temperature indicator with resisting device for transformer. (viii) Two earthing terminal on tank cover to facilitate fixing of 32x6mm GI strip for earthing of neutral body. (ix) Rating plate and terminal marking plate. (x) Oil level gauge (xi) Oil drain filter valve. (xii) Lifting hooks. (xiii) Oil filling holes with cap/plug with connecting plate complete. (xiv) MS wheels 04 Nos with lock pins including making of plinth for transformer are required on ground and as directed. (xv) Oil temp/winding temp lubricating with marshaling box.
Shifting of distribution transformer 63 to 500 KVA capacity and any locaion inside the cantt or deposit to MES store yard for further disposal action complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 16 sqmm 4 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 25 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 35 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 50 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 70 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 95 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 120 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 185 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
M & L for XLPE insulated, PVC sheathed, armoured, heavy duty electric under ground cable, with stranded aluminium conductor, 1100 Volts grade of size 400 sqmm 3.5 core laid in trenches /floor or fixed on wall/pole complete all as specified and directed.
Excavation in trenches n.exc 1.5mtr wide and n.exc. 1.5m in depth for foundation and getting out in soft/loose soil complete all as specified and directed.
Supply & laying Sand coarse dry as in cushioning of underground electric cable in trenches, laid to a uniform thickness of 23cm (15cm under the cable & 8cm over the cable) and gently punned down to 18cm thickness complete all as specified and as directed. Note :- Only punned down sand shall be measured.
M&L for bricks sub class ‘B’ brick old size for cable protection laid in flat in trenches over the cable perpendicular to the direction of cable complete all as specified and directed.
Returning filling in including spreading, levelling, watering and well ramming in layers n.exc. 25cm complete all as specified and directed.
Removing of excavated soil not exc 50cm & depositing where as directed at a level n.exc 1.5m above starting point complete all as specified and directed.
M&L for GI pipe light grade 40mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and directed.
M&L for GI pipe light grade 50mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and directed.
M&L for GI pipe light grade 80mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and directed.
M&L for GI pipe light grade 100mm bore dia with all fittings to be laid in trenches or in floors,including taking down rusted one complete all as speciffied and as directed.
M&L for cement concrete 1:4:8 type D-2 using 40 mm graded crushed stone aggregate as in foundation complete all as specified and directed.
M&L for Boring of holes under road / Cutting of roads for passing cable any size and any type including make good damaged surface with cement concrete 1:4:8 type D2 (using 40mm graded stone aggregate)/ black bitumin carpet complete all as specified and directed.
M & L for jointing heat shrinkable after removing faulty cable, straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 25 to 50 sqmm 3½ core 1100 volts grade and necessary testing after jointing complete all as specified and directed.
M & L for jointing heat shrinkable after removing faulty cable , straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 70 to 120 sqmm 3½ core 1100 volts grade and necessary testing after jointing complete all as specified and directed.
M & L for jointing heat shrinkable after removing faulty cable , straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 150 to 185 sqmm 3½ core 1100 volts grade and necessary testing after jointing, complete all as specified and directed.
M & L for jointing heat shrinkable after removing faulty cable , straight joints for PVC armoured heavy duty underground cable including joint kits complete for making joints suitable for aluminium Conductor cable 240 to 400 sqmm 3½ core 1100 volts grade and necessary testing after jointing, complete all as specified and directed.
Supply & fixing of LT Panel Board floor mounted outdoor cubical type (CPRI Approved) with compartments for each out going and incoming feeders made of CRCA of 3.15 mm thick MS sheet power coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame including earthwork & PCC foundation of suitable size for fixing panel as specified and directed by Engr-in-Charge with double hinged with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switcher gear and termination of switch gear and the nuts/ bolts etc used are to be made of rust proof material, incl tinned Aluminium bus bar as per IS TPN LT AC, 50 Hz , 415 V, 1200 Amp capacity complete with powder coating and comprising of the following accessories:- Incoming: a) ACB , 4P, 800 Amp, 50 KA MOD with Microprocessor based with LSIG protection alongwith complete connected assy as per OEM Manual draw out type complte all as specified and directed- 01 No. Outgoing: a) MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 250 Amps with breaking capacity 25 KA-05 Nos. b) MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 400 Amps with breaking capacity 25 KA-01 No. c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kW, etc with all connected CTs d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
Supply & fixing of LT Panel Board floor mounted outdoor cubical type (CPRI Approved) with compartments for each out going and incoming feeders made of CRCA of 3.15 mm thick MS sheet power coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame including earthwork & PCC foundation of suitable size for fixing panel as specified and directed by Engr-in-Charge with double hinged with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switcher gear and termination of switch gear and the nuts/ bolts etc used are to be made of rust proof material, incl tinned Aluminium bus bar as per IS TPN LT AC, 50 Hz , 415 V, 600 Amp capacity complete with powder coating and comprising of the following accessories:- Incoming: a)MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 400 Amps with breaking capacity 36 KA-01 No. Outgoing: a) MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 160 Amps with breaking capacity 25 KA-04 Nos. b) MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 63 Amps with breaking capacity 25 KA-02 Nos. c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kW, etc with all connected CTs d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
Supply & fixing of LT Panel Board floor mounted outdoor cubical type (CPRI Approved) with compartments for each out going and incoming feeders made of CRCA of 3.15 mm thick MS sheet power coated of suitable size with support of angle iron of 50 x 50 x 6 mm angle iron bottom legs frame including earthwork & PCC foundation of suitable size for fixing panel as specified and directed by Engr-in-Charge with double hinged with front and rear opening, hinged doors with projected an raised platform of suitable size weather and water proof with necessary locking arrangements along with lugs, cable glands of various sizes for existing cables, danger notice plate, strickering of Switcher gear and termination of switch gear and the nuts/ bolts etc used are to be made of rust proof material, incl tinned Aluminium bus bar as per IS TPN LT AC, 50 Hz , 415 V, 400 Amp capacity complete with powder coating and comprising of the following accessories:- Incoming: a)MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 250 Amps with breaking capacity 36 KA-01 No. Outgoing: a) MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 100 Amps with breaking capacity 25 KA-01 No. b) MCCB 4 Pole, 415 V, Adjustable range 0.7 to 1 In, 63 Amps with breaking capacity 25 KA-04 Nos. c) Intelligent Panel meter to measure voltage, current, frequency, power factor, kW, etc with all connected CTs d) LED indicating lamps with colour Red, Yellow, Blue - 01 Set
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing strip of 25 x 4 mm galvanised mild steel wire by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe light grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing including taking down old earthing complete all as specified and as directed.
M&L for earthing with copper earth plate of size 600 x 600 x 3.15 mm & copper earth strip 20 x 3 mm buried in ground vertically to a depth not less than 3.0 metre below ground level with top edge earth electrode at a depth not less than 2.40 metre deep below ground level including suitable quantity of backfill chemical compound for filling in each pit to cover earth electrode minimum 150 mm all around and electrode shall be jointed with the copper strip of size 32 x 6 mm by exhothermic weld complete with earth pit chamber of size 300 x 300 mm and RCC cover for demarking the location of earth electrode complete all as specified and directed.
M&L for making round hole of size 20mm dia on top and 1 mtr above ground level on each pole and laying PVC sheathed 3 core cable in pole alongwith street light complete all as specified and directed.
Supply and fix street light junction box made of high quality polycarbonate with IP-66 protection (Dust and vermin proof according to IEC-60529) Totally insulated made of halogen and silica free recyclable material having high quality gasket made out of polyurethane, locking arrangement with cable gland suitable upto 10 sqmm cable and necessary fixing arrangements such as Busbar, insulators, clamps, nuts, bolts etc complete all as specified and directed.
United Sales Corporation (BID ID -3485758)
M/S. SUBHAS CONSTRUCTION CO. (BID ID -3495548)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.17 MB
8920tender2.pdf
Tender Documents • 1.15 MB
BOQ_829315.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .