Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹55.6 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹59.5 L+₹3.9 L (7.10%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹64.7 L+₹9.1 L (16.3%)Admitted-Finance UDHAMPUR | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | JAI CHANDI MAA ENTERPRISES L1 | VEENA CONSTRUCTION CO. L2 | M/S VAISHNO TRADERS L3 |
|---|---|---|---|---|---|---|
| 1.00Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at village Seen Brahmana and Dandi Kanel W.No. 01 and 03 (Khandra) under UT Capex Budget 2025-26. | ||||||
| 1.01 | 9 mtr. Long ST Pole (ST 410 SP-33) | 10 | No. | 10,000 ₹1,70,000 | 10,000 ₹1,65,000 Lowest | 30,000 ₹1,70,000 |
| 1.02 | GI V Cross -arm with top Bracket including clamps | 160 | Kg. | 1,600 ₹17,600 Lowest | 1,600 ₹22,400 | 1,600 ₹19,200 |
| 1.03 | GI Channel X-arm including clamps and Angle for braces | 90 | Kg. | 900 ₹9,900 Lowest | 900 ₹12,600 | 900 ₹10,800 |
| 1.04 | 30 mm sq. ACSR Weasel conductor | 1.65 | Km. | 1,650 ₹1,650 | 825 ₹825 Lowest | 3,300 ₹3,300 |
| 1.05 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. | 30 | No. | 300 ₹5,700 | 900 ₹6,900 | 600 ₹5,100 Lowest |
| 1.06 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting | 12 | No. | 120 ₹3,480 | 600 ₹5,400 | 240 ₹2,040 Lowest |
| 1.07 | Galvanized Nuts and Bolts | 10 | Kg | 100 ₹1,100 Lowest | 100 ₹1,200 | 100 ₹1,100 Lowest |
| 1.08 | Danger Plates with clamps | 10 | No. | 100 ₹1,000 | 200 ₹1,400 | 200 ₹800 Lowest |
| 1.09 | Anti Climbing device with clamps | 10 | No. | 100 ₹1,100 | 500 ₹2,500 | 200 ₹800 Lowest |
Tender Value
Refer Docs
EMD Value
₹1.4 L
Closing Date
8 Sept 2025, 3:00 pmClosed
Executive Engineer
Executive Engineer Electric Division Udhampur
Creation of 25/63/100 KVA Sub Stationalong with HT/LT network
2025_PDD_283542_1
ED/UDH/21 OF 2025-26 dated 06-08-2025
Open Tender
Electrical Works
Turn-key
90 days
in district Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,000
Executive Engineer,ED Udhampur JPDCL
₹1.4 L
11 Sept 2025
7 Aug 2025
9 Sept 2025
7 Aug 2025
8 Sept 2025
7 Aug 2025
7 Aug 2025 - 7 Sept 2025
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at village Seen Brahmana and Dandi Kanel W.No. 01 and 03 (Khandra) under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at village Seen Brahmana and Dandi Kanel W.No. 01 and 03 (Khandra) under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 25 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
70 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at village Seen Brahmana and Dandi Kanel W.No. 01 and 03 (Khandra) under UT Capex Budget 2025-26.
8 Mtr. Long Pole( ST-410 SP15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at W.No. 04 Chalora Mohalla Pyt. Malhar under UT Capex Budget 2025-26.
9 mtr. Long PCC Pole (WL PCC 300 KG)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at W.No. 04 Chalora Mohalla Pyt. Malhar under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at W.No. 04 Chalora Mohalla Pyt. Malhar under UT Capex Budget 2025-26.
8 Mtr. Long PCC Pole( WL PCC 200kg)
GI U Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST and PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Chakhar W.No. 07 under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
9 mtr. Long PCC Pole (WL PCC 300 KG)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr long ST poles with two coat of Aluminium paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Chakhar W.No. 07 under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Chakhar W.No. 07 under UT Capex Budget 2025-26.
8 Mtr. Long PCC Pole( WL pcc 200kg)
GI U Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Tehsil office Complex Majalta under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Tehsil office Complex Majalta under UT Capex Budget 2025-26.
8 Mtr. Long PCC Pole( wl pcc 200kg)
GI U Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 100 KVA Sub Station at Sattaini-III near Patha under UT Capex Budget 2025-26.
9 mtr. Long PCC Pole (WL PCC 300 KG)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 100 KVA Sub Station at Sattaini-III near Patha under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 100 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 100 KVA Sub Station at Sattaini-III near Patha under UT Capex Budget 2025-26.
8 Mtr. Long PCC Pole( wl pcc 200kg)
GI U Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 100 KVA Sub Station at Sayal opposite kabirstan under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 100 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
3-phase 4 wire LT Prodigy meter
Danger Plates with clamps
GI Barbed wire for Anticlimbing
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long PCC poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 100 KVA Sub Station at Sayal opposite kabirstan under UT Capex Budget 2025-26.
8 Mtr. Long PCC Pole( wl pcc 200kg)
GI U Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 100 KVA Sub Station at Rathian Opposite Jandial Temple for improvement of low voltage (Recomended by principal Secretary to Government) under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 100 KVA Sub Station at Rathian Opposite Jandial Temple for improvement of low voltage (Recomended by principal Secretary to Government) under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 100 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 100 KVA Sub Station at Rathian Opposite Jandial Temple for improvement of low voltage (Recomended by principal Secretary to Government) under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI U Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Tildu Pachound under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Tildu Pachound under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Tildu Pachound under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Gali Kulsar W.No. 02 Lower Mada under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Gali Kulsar W.No. 02 Lower Mada under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Gali Kulsar W.No. 02 Lower Mada under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 100 KVA Sub Station at W.No. 02 Village Tandar under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 100 KVA Sub Station at W.No. 02 Village Tandar under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 100 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 100 KVA Sub Station at W.No. 02 Village Tandar under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Sradi Mohalla Nimbla Kidmoo under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Sradi Mohalla Nimbla Kidmoo under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6mm, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Sradi Mohalla Nimbla Kidmoo under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at Manjla Naalu/Kansair village Jandrore under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 25 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
70 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Manjla Naalu/Kansair village Jandrore under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Katheel Ganju East under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 63 KVA Sub Station at Katheel Ganju East under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 63 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
PG Clamps
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Danger Plates with clamps
GI Barbed wire for Anticlimbing
3-phase 4 wire LT Prodigy meter
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Painting of 9 mtr ST poles with two coat of Aluminium Paint and one coat of Red oxide (Asian/Nerolac make).
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Katheel ganju East under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11KV line on 9 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 25 KVA Sub Station at Mohra Mnali near the house of Jeet Kumar under UT Capex Budget 2025-26.
9 mtr. Long ST Pole (ST 410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Angle for braces
30 mm sq. ACSR Weasel conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting
Galvanized Nuts and Bolts
Danger Plates with clamps
Anti Climbing device with clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm for LT
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Creation of 25 KVA Sub Station at Mohra Mnali near the house of Jeet Kumar under UT Capex Budget 2025-26.
11/0.433kV, 3-phase 25 KVA Distribution Transformer (To be issued by Department at Divisional Store of ED Udhampur)
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11 KV GO, AB Switch 3-phase, 3-pole, 200 Amp. Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
70 mm² Single Core Cable,1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST 410 SP-33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
LT Fuse Switch made of angle Iron 50X50X6, with aluminium Bus Bar strip 50X6mm fixed on Bus Bar Insualtor including clamps for fixing of switch
Cement Bottoming 1:2:4 mix as per REC Standards 0.5 cum per pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line on 8 mtr long ST poles, with 30 mm sq. ACSR Weasel Conductor for Creation of 63 KVA Sub Station at Mohra Mnali near the house of Jeet Kumar under UT Capex Budget 2025-26.
8 mtr. Long ST Pole (ST 410 SP-15)
GI M Clamps for Shackle Insulator
30 mm sq. ACSR Weasel Condutor.
Shakle Insulator
Galvinized Nuts and Bolts.
Danger Plates with clamps
Anti Climbing device with clamps
Earthing composite by GI pipe 40 mm or GI Rod 20 mm 2.5 mtr. long through GI strip
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
VEENA CONSTRUCTION CO. (BID ID -2457714)
M/S VAISHNO TRADERS (BID ID -2484635)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .