| Sl No | Description | Qty | Unit | M/S SURAJ PARTAP SINGH L2 | M/S M.H Electricals L3 | M/S COMBINE GROUP OF ENGINEERS L1 | Madina Electrical Works L4 |
|---|---|---|---|---|---|---|---|
| 1.00SITC for creation of 25 KVA Sub-station along with HT/LT network at Chhiral under the jurisdiction of Sub-Division Dharmari. | |||||||
| 1.01 | 11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate | 1 | No | 92,000 ₹92,000 | 65,000 ₹65,000 | 85,000 ₹85,000 | 70,000 ₹70,000 |
| 1.02 | 8 mtr long Pole ST-410, SP15 | 2 | Nos | 16,200 ₹32,400 | 14,000 ₹28,000 | 8,200 ₹16,400 | 10,000 ₹20,000 |
| 1.03 | Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type | 1 | Set | 2,500 ₹2,500 | 3,000 ₹3,000 | 12,000 ₹12,000 | 5,000 ₹5,000 |
| 1.04 | 11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type | 1 | Set | 2,200 ₹2,200 | 11,000 ₹11,000 | 22,000 ₹22,000 | 9,000 ₹9,000 |
| 1.05 | 11kV Horn Gap Fuse set 3-phase, 200 Amp | 1 | Set | 2,000 ₹2,000 | 3,500 ₹3,500 | 18,000 ₹18,000 | 5,000 ₹5,000 |
| 1.06 | 25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type | 40 | Mtr | 100 ₹4,000 | 150 ₹6,000 | 75 ₹3,000 | 250 ₹10,000 |
| 1.07 | 11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm | 3 | No | 150 ₹450 | 350 ₹1,050 | 300 ₹900 | 550 ₹1,650 |
| 1.08 | GI Channel/Angle/Flat of different sizes including clamps | 250 | Kg | 80 ₹20,000 | 130 ₹32,500 | 100 ₹25,000 | 150 ₹37,500 |
| 1.09 | Galvanised Nuts & Bolts | 8 | Kg | 90 ₹720 | 150 ₹1,200 | 100 ₹800 | 150 ₹1,200 |
Tender Value
₹50 L
EMD Value
₹1 L
Closing Date
24 Dec 2025, 2:00 pmClosed
Executive Engineer Electric Division JPDCL Reasi
Executive Engineer Electric Division JPDCL Reasi
Supply, Installation, Testing and Commissioning for creation of sub-stations along with HT Tapline and LT network under UT CAPEX 2025-26 at different locations of Electric Division JPDCL Reasi
2025_PDD_298579_1
e NIT 35 of 2025-26
Open Tender
Electrical Works
60 days
Reasi
Please refer Tender documents.
6 documents required · 6 mandatory
₹2,000
Executive Engineer Electric Division JPDCL Reasi
₹1 L
27 Dec 2025
19 Dec 2025
24 Dec 2025
19 Dec 2025
24 Dec 2025
19 Dec 2025
19 Dec 2025 - 23 Dec 2025
Amount
SITC for creation of 25 KVA Sub-station along with HT/LT network at Chhiral under the jurisdiction of Sub-Division Dharmari.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 25 KVA Sub-station along with HT/LT network at Therla Ramanbass under the jurisdiction of Sub-Division Dharmari.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15 (Already at site only erection testing and commmissioning to be charged)
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15 (Already at site only erection testing and commmissioning to be charged)
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 25 KVA Sub-station along with HT/LT network at Ward No 03 Ponda Mohalla village Salalkotli under the jurisdiction of Sub-Division Dharmari.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 25 KVA Sub-station along with HT/LT network at Dabbar Mohalla, Sarh under the jurisdiction of Sub-Division Dharmari.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
SITC for creation of 25 KVA Sub-station along with HT/LT network at Dhamni Pyt Channa B under the jurisdiction of Sub-Division Dharmari.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 25 KVA Sub-station along with HT/LT network at Patta near Atta Chakki Mill under the jurisdiction of Sub-Division Pouni.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 25 KVA Sub-station along with HT/LT network at Kalhar under the jurisdiction of Sub-Division Pouni.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 25 KVA Sub-station along with HT/LT network at Sarangdhar Block Bhomag under the jurisdiction of Sub-Division Reasi.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 25 KVA Sub-station along with HT/LT network at Ward No 4, Devigarh Block Bhomag under the jurisdiction of Sub-Division Reasi.
11/0.433KV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
25 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 63 KVA Sub-station along with HT/LT network at Bharakh Neoti under the jurisdiction of Sub-Division Pouni.
11/0.433KV, 3-phase 63 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
70 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Painting of Poles with Aluminium Paint
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 100 KVA Sub-station along with HT/LT network at Ward No 02 Vijaypur under the jurisdiction of Sub-Division Reasi.
11/0.433KV, 3-phase 100 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
185 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Painting of Poles with Aluminium Paint
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
SITC for creation of 100 KVA Sub-station along with HT/LT network at Chiral under the jurisdiction of Sub-Division Reasi.
11/0.433KV, 3-phase 100 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) and with LV cable box having detachable Aluminium Gland plate
8 mtr long Pole ST-410, SP15
Gapless Surge Arrestor, 9kV, 10kA, LA with polymer housing, Station type
11KV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, vertical type
11kV Horn Gap Fuse set 3-phase, 200 Amp
185 sqmm cable 1.1kv grade, PVC insulated stranded conductor FRLS type
11kV Polymeric composite Disc Insulator 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of different sizes including clamps
Galvanised Nuts & Bolts
Earthing of substation - Excavation of earthing pit of dia 650mm & depth 3000mm, installation ofEarthing pipe of 40mm nominal bore & 4mm wall thickness & length 2.5 mtr long as per IS 1239. GI strip for neutral earthing of size 25mm x 3mm for connection of transformer body, GO set & lightening arrestor as per IS 2629/85, GI nuts & bolts, refilled with earth enhancement materials and earth chamber made of brick masonary with RCC slab cover.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Painting of Poles with Aluminium Paint
32/63 Amp TPN Switch disconnector fuse unit
8 mtr long Pole ST-410SP-15
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
ACSR Weasel Conductor (30 Sq.mm)
11kV Polymeric composite Pin Insulator 12kV, 5kN,Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
11kV Polymeric composite Disc Insulator with GI fittings 12kV,minfailing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvinized Nuts and Bolts
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip (25x3) mm.
Red Oxide
Aluminium Paint
8 mtr long Pole ST-410, SP15
GI M Clamp for shackle Insulator
ACSR Squirrel Conductor
16 KN Polymer Shackle Insulators
Galvanised Nuts & Bolts
Danger Plates with clamps
Aluminium Paint
Earthing Complete by GI Pipe 40mm or GI Rod 20 mm 2.5 Meter long through GI Strip
Anti-Climbing Device with Clamps
Galvanised Stay setwith 50x8mm stay clamp, Guy Insulator (2 Nos), Anchor Plate (200x200x6mm) nuts and Bolts, 2Nos Turn Buckles, 1.8 long, 16mm diameter solid GS Stay rod & 7/3.15mm dia GI Standard wire complete
M/S SURAJ PARTAP SINGH (BID ID -2678503)
M/S M.H Electricals (BID ID -2677318)
Madina Electrical Works (BID ID -2678410)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.21 MB
BOQ_967779.xls
BOQ • 0.45 MB
SBD35.pdf
Tender Documents • 1.85 MB
Download all tender documents and submit your bid