| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.3 LAccepted-AOC 123 B CENTRAL AVENUE SAINIK FARMS NEW DELHI 110062 | NEW DELHI | NEW DELHI | DELHI | 110062 | L1 | Accepted-AOC Accepted | |
| 2 | L2₹31.3 L+₹35,855.80 (1.16%)Rejected-AOC 5 A KALPANA NAGAR 7TH CROSSING MORAR GWALIOR MP | GWALIOR | GWALIOR | MADHYA PRADESH | 474006 | L2 | Rejected-AOC Rejected | |
| 3 | L3₹40.8 L+₹9.8 L (31.8%)Rejected-AOC | L3 | Rejected-AOC Rejected |
Tender Value
₹41.5 L
EMD Value
₹83,040
Closing Date
24 Aug 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE JHANSI
HQ CWE JHANSI
REPAIR AND MAINT OF HT EXTERNAL ELECTRIC SUPPLY, LT SUPPLY AND CONNECTED WORKS AT MORAR CANTT UNDER GE GWALIOR
2021_MES_463125_1
CWE/JHA/GWL/TOKEN/50 OF 2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GWALIOR
As per tender documents
8 documents required · 8 mandatory
₹500
GE GWALIOR
₹83,040
Yes
20 Oct 2021
27 Jul 2021
30 Aug 2021
27 Jul 2021
24 Aug 2021
12 Aug 2021
60 days
Amount
Material and labour for transportation of transformer from site/E & M yard to workshop for repair of capacity 50 to 500 KVA complete incl Disconnection of transformer any make indoor/outdoor type from LV/HV side including disconnection of earthing GI strips and taking down transformer from plinth/04 pole structure/02 pole structure with the help of chain pulley/crane incl megger test, ratio test, magnetic balance test. Short circuit test and reinstallation the transformer after repair to its original position and making all LV/HV connections incl earthing and testing complelte all as specified and directed by Engineer in charge. Note:- Shifting of transformer from site/yard to wkshop and return back from workshop to site/yard shall be measured as single unit. Necessary tools and equipments with labour for shifting of the transformer and transportation to workshop and back deemed to be included in the quoted rate.
Material and labour for draining out transformer oil from the transformer of any make indoor/out door and store in a clean barrel for re-use and disconnection of internal electrical connection by taking out the top cover complete, cleaning of tank, removal of sludge etc by lifting the core with complete LV/HV coil of transformer and segregating to serviceable and unserviceable coils shall be kept aside for reuse after complete varnishing and testing of each coil including removal of complete core and accessories such as HV/LV bushings with metal parts, oil temp indicator, winding temp indicator and disconnection of tap changer. Assembling of yoke fitting, assembling of LV/HV coil in completely intact position over the CCSI laminated core the HT coils shall be fixed over the LV coils by providing the insulation barriers and making the assembly complete in intact position (insulation material shall be measured and paid separately) including assembling of core mounted on channel connecting all the internal connections, soldering brazing of HV/LV connections by silver electrodes including replacement of leads complete by providing tubular insulation of tap changer assembly and its connections and lowering of complete assembly in tank with suitable locking arrangements re fixing the top cover of transformer including the other accessories and making the transformer leak proof complete all as specified and directed for the following capacity.
50 KVA to 100 KVA
100 and upto 250 KVA
250 KVA upto 500 KVA
Material and labour for winding of HV/LV coils of transformer DPC copper winding wire grade of existing gauge and size complete all as specified and directed.
M&L for winding of HV/LV Coil of transformer DPC aluminium winding wire grade of existing gauge and size complete all as specified and directed.
M&L for insulation material PCB electrical grade such as barriers, coil to coil insulation block and rings insulation cylinders, ebonies sleeves etc all as specified and directed for 50 KVA to 500 KVA transformer complete all as specified and directed.
M&L for ovening of complete core assembly including HV/LV coils in oven for minimm 72 hrs for achieving desired insulation value complete all as specified and as directed. Note:- Re opening shall be done without any extra cost if the desired result are not found after fixing the coils back to its original position in the tank.
S&F in renewal of heavy duty oil level indicator clean prismatic type with necessary gasket etc suitable for transformer up to 500 KVA capacity complete all as specified and directed.
S&F cork sheet gasket kit cut to shape for the top covers and other required places of the transformer of following capacity of transformer complete all as specified and directed.
50 KVA to 100 KVA
100 and upto 250 KVA
250 KVA upto 500 KVA
M&L for pouring fresh/topping up transformer oil for 33/11 KV and 11/0.433 KV transformer confirming to IS-335 in the transformer of any capacity complete duly filtered having dielectric breaking strength not less than 60 KV all as specified and as directed.
M&L for cleaning of surface of transformer of capacity by scrapping out old paint and painting of transformer by two coats of synthetic enamel gray paint externally over a coat of red oxide including writing of SM/MES No on the transformer complete all as specified and directed for the following capacity.
50 KVA to 100 KVA
100 and upto 250 KVA
250 KVA upto 500 KVA
M&L for opening up top cover of transformer installed in position, disconnecting connections and reconnecting after renewal of worn out/defective parts such as check nuts,washers, LT bushes, HT bushes, Tap changers etc, refixing the top cover in position after completion of the reqpir work complete all as specified and directed for the following capacity of transformer. Note : Defective parts shall be measured and paid seperately.
50 KVA to 100 KVA complete all as specified and directed.
100 and upto 250 KVA
250 KVA upto 500 KVA
S&F of LT bush with low Voltage brass studs with checks nuts , washers etc of 11 KV grade and LT bushing parts such as porcelain, clamp nuts and bolts etc complete all as specified and directed for the following capacity of transformer.
50KVA to 100 KVA complete all as specified and directed.
100 and upto 250 KVA
250 KVA upto 500 KVA
S & F of HT bush with High Voltage brass studs with checks nuts , washers etc of 11 KV grade and HT bushing parts such as porcelain, clamp nuts and bolts etc complete all as specified and directed for the following capacity of transformer.
50KVA to 100 KVA
100 and upto 250 KVA
250 KVA upto 500 KVA
Supply and fixing Breather assembly with silica gel and mounting packing with bolt & nuts complete all as specified and directed for the following capacity of transformer.
50KVA to 100 KVA
100 and upto 250 KVA
250 KVA upto 500 KVA
Supply and fixing Breather assembly with silica complete for 1.6 MVA to 5 MVA transformer all as specified and directed.
S&F gas and oil actuated relay [Buchholtz Relay] for 33/11 KV 1.6 MVA and 5 MVA transformer equipment having contacts which close following oil surge or low oil level conditions complete all as specified and directed.
Supply and fixing Tap changer assembly complete all as specified and directed for the following capacity of transformer.
50 KVA to 100 KVA
100 and upto 250 KVA
250 KVA upto 500 KVA
M&L for dehydration and filtration of transformer oil for 33/11 KV and 11/0.433 KV transformer to achieve dielectric breaking strength (BDV) not less than 45KV/22 KV any capacity to transformer by suitable filtration machine complete all as specified and directed.
Supply and fix transformer oil temperature gauge of standard size suitable for 100 to 500 KVA transformers 11 KV/433 volts analogue type including removing the existing u/s one complete all as specified and directed.
Supply and fixing PT (Voltage Transformer) for 33 KV out door VCB,oil immersed, 33 KV, 33000/110 V, VA-5 CLASS 1 RATED FRIQUENCY 50 HZ complete all as specified and directed. Make - CG/kappa/Alsthom/Laxmi/Pragti
M&L for replacement of outdoor control junction boxes of required sizes for 33/11 KV CT/PT/VCB/SF6 breaker conrol cables with copper connection strips/lugs, nuts & bolts, washers, ms clamps etc complete all as specified and directed.
S&F Switch Air break gang operated triple pole (3 insulators in each phase mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level current rating 400 Amps suitable for 33 KV complete with locking arrangement horizontal/verticle complete set of 3 with one No’s operating rod ccomplete all as specified and directed.
S&F in repair copper control cable for 33 KV transformer protection system 4 core 2.5 Sqmm armoured complete all as specified and directed. Make-Polycab/National/Gloster/Finolex
Spray of agricultural based chemical inside the installation to control the growth of unwanted herb etc incl cleaning of the grass herbs bushes etc from the installation complete all as specified and directed.
M&L for 150 mm thick 40mm graded aggregate spreed and levelling in 33 or 11 KV sub station yard 10mm deep including removing the unwanted grass form yard complete all as specified and directed.
Disconnection of transformer of cap 1.6 MVA/5 MVA out door type 33/11 KV from LV/HV side including earthing GI strips and other DC sources, control wiring , Relays, protection, metering etc and taking down/removing transformer from plinth with the help of crane for all as specified and directed.
Transportation of Transformer from site E/M yard to workshop and from workshop to site /E/M yard for repairing/ depositing etc of capacity 1.6 MVA/5 MVA complete all as specified and directed.
Carrying out tests such as megger test, ratio test, magnetic balance test. Short circuit test including opening the lid after draining out oil in clean barrels for reuse if servisable or re useable after testing the oil complete all as specified and directed.
Taking out complete core assembly with HV and LV coils tap changer assembly and connected items after opening of top cover of transformer. Complete inspection of core assembly carefully, cleaning of complete core assembly with pressure pump with transformer oil, necessary repearing as required, making necessary insulation etc and refixing the core assembly in tank locking with locking nut and bolts. Making all internal connections with required silver rods, copper strips etc. Refising top cover with new gaskit, nuts and bolts etc and making the transformer leak proof complete all as specified and directed.
Material and labour for ovening of complete assembly including HV/LV coils of transformer 1.6/5 MVA in oven for at least 72 Hrs for achieving desired insulation value and complete removal of assembly (Note re-ovening shall be done if the desired result was not found with out any extra cost) complete all as specified and directed.
S&F cork sheet gaskit cut to shape for the top covers radiator valves conservator assembly bucolz and other required places of the transformer of capacity 1.6 MVA/5 MVA, 33/11KV complete all as specified and directed.
Installation, commissioning, testing of 1.6 MVA/5 MVA transformer by connecting all HT 33/11 KV connections, earthing connections, control cables for various protections, indications, metering, connection and buczols connections and testing all as specified and directed.
S&F in repairs OTI & WTI for 1.6 MVA/5 MVA 33/11 KV transformer complete all as specified and directed.
S&F in replacement HT bushing 33KV side for 33/11 KV 1.6 MVA/5 MVA transformer complete with copper spindal and connected items complete all as specified and directed.
S&F in replacement HT bushing 11KV side for 33/11 KV 1.6 MVA/5 MVA transformer complete with copper spindal and connected items complete all as specified and directed.
Supply and installation in replacement of 33 KV, single phase, outdoor oil cooled, CT of ration 400/5-5 Amp, class 1/0/5P10 burden 15 VA complete all as specified and directed.
All as per item No 36 but 11 KV CT. complete all as specified and directed.
Supply and installation in replacement of 11 KV, single phase, outdoor oil cooled PT of ratio 3/110/V/rt3, Class 0/5/3, burden 50 VA complete all as specified and a s directed.
Excavation in trenches not exceeding 1.5m wide and not exc. 1.5m depth and getting out in hard/dense soil complete all as specified and as directed.
Excavation in trenches exceeding 1.5m wide and not exc. 1.5m depth and getting out in hard/dense soil complete all as specified and as directed.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exc. 25cmin soft/loose soil complete all as specified and as directed.
Removal of excavated soil to a distance not exc 50 m and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed.
M&L for sand cushioning in trenches for cable protection including consolidation complete all as specified and directed.
M&L for Sub class 'B' bricks laid dry width wise across the line of cable in treanchs as cable protection complete all as specified and directed.
Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminiium conductor, 11000 volts grade cross sectional area 95 sq. mm 3 Core earthed complete all as specified and directed. Make :- Finolex/Gloster/Polycab/Plaza/KEI
All as per item No 45 but 70 Sqmm 3 core complete all as specified and directed. Make :- Finolex/Gloster/Polycab/Plaza/KEI
S&F cable joining kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed. Make :- Raychem/Denson/Birla-3M
M & L for GI Pipe light grade complete with fittings laid in floor/ trenches/ wall as cable protection of 100 mm dia complete all as specified and directed.
M & L for Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11 metres long) including painting of pole 1.2 RM height from top of coping of the pole and writing the pole no complete all as specified and directed. Make :- National tubing compan Ltd Kanpur/Quality steel products Ltd/India electric Poles/P.S Steel tube Pvt Ltd
M&L for HT cable route indicator precast made from PCC 1:3:6 of size 600mm x 230mm x 100 including excavation PCC for foundation and painting and writing as "11 kv cable" incl preparation of surfaces both sides complete all as specified and directed.
M&L for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed by Engineer-in-Charge.
Boring of holes under road, pavement, hard standing by trenches technology using ultra sound technique and necessary machine including HDPE pipe of 100mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed.
M&L for PCC 1:2:4 type B-0 using 12.5 mm graded BT stone aggregate as in bed block for hold fast or coping including necessary form work complete all as specified and directed.
M&L for reinforced concrete pipes of dia 150mm , class NP2 laid and jointed complete with collars complete all as specified and directed.
M&L for lightening arresters expulsion type 33 KV grade complete with all fittings, transmission class, discharge capacity 65 Kilo Amps complete all as specified and as directed.
M/S SANTOSH CONSTRUCTION CO
Om Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .