Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.4 LAccepted-AOC 205 PARSHAV VIHAR PLOT NO 50 IP EXTN PARPARGANJ DELHI 110092 | EAST | DELHI | 110092 | L1 | Accepted-AOC Lowest tenderer | |
| 2 | L2₹40.8 L+₹1.4 L (3.54%)Rejected-Finance | L2 | Rejected-Finance Not the lowest tenderer | |
| 3 | L3₹43.5 L+₹4.1 L (10.4%)Rejected-Finance RZ A2 2 CHANAKYA PLACE PART I OPP C 1A BLOCK JANAK PURI NEW DELHI 110059 | NEW DELHI | WEST DELHI | DELHI | 110059 | L3 | Rejected-Finance Not the lowest tenderer |
Tender Value
₹50.0 L
EMD Value
₹99,980
Closing Date
31 Dec 2019, 6:00 pmClosed
GE E/M BASE HOSP DELHI CANTT
GE E/M BASE HOSP DELHI CANTT
REPAIR/REPLACEMENT AND MAINT OF CENTRAL AC PLANT COMPRESSOR COOLING TOWER AND CONNECTED MISC E/M WORKS AT BASE HOSPITAL UNDER GE E/M BASE HOSPITAL DELHI CANTT-10
2019_MES_288220_2
GE/BH-37/2019-20
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE E/M BASE HOSP DELHI CANTT
Meeting enlistment criteria of MES with regard to having satisfactory completed requisite value works annual turnover, working capital, fixed assets. No recovery outstanding in any govt dept security clearance etc.
7 documents required · 7 mandatory
₹500
GE E/M BASE HOSP DELHI CANTT
₹99,980
Yes
7 Feb 2020
4 Dec 2019
2 Jan 2020
4 Dec 2019
31 Dec 2019
17 Dec 2019
Amount
Dismantling of compressor of central AC plant complete with connected copper pipe line and loading unloading mechanism & pump down the existing refrigerant in separate cylinder, disconnecting of electric motor of compressor, refrigerant line, gauges pipe and carry out the over hauling of compressor, compressor model:- 05018, Make:- Voltas (R-22) and capacity of plant:- 15 TR including replacement of springs, aluminium washer packing, screw, lath work, cleaning detergent, cotton waste, compressor oil etc and cleaning the suction filter, oil filter, replacing the defective parts compete system for safe guard the gas with self pumping down system or with total recovery unit system and (i) Charging of nitrogen Gas in unit & complete system at 300 psi pressure and checking of any dropping of pressure / leakage up to 72 Hrs after replacement of compressor & rectification of leakage if any. (ii) Vaccumisation of complete system for minimum 2 days for dropping of vacuum pressure & rectification of leakage if any. (iii) Charging of complete system with R - 22 gas for maintaining the system pressure up to HP - 175 psi & LP - 65 psi. (iv) Measure the inlet and outdoor temperature of Chiller unit for performance checking and maintaining temp. as per require site. (v) Testing & commissioning of compressor after completion. Note:- (a) Spares of compressor shall be measured and paid separately under respective item of this schedule. (b) Any other minor items required for overhauling except described here -in - after shall be supplied by the contractor with out any extra cost to the deptt and the rates for the same shall deemed to be included in the quoted rates.
Supply only in replacement PISTON with PIN & Rings
Supply only in replacement CYL.LINER with suction valve (R-22)
Supply only in replacement OIL pump
Supply only in replacement Discharge valve assembly (R-22)
Supply only in replacement Oil pressure regulation valve
Supply only in replacement Set of gasket
Supply only in replacement Set of neoprene ' O' RINGS
Supply only in replacement Set of Dowty ring
Supply only in replacement Set of SEALING RING
Supply only in replacement SPRING FOR SAFETY HEAD
Supply only in replacement HALF SECTION OF BRG. STD.
Supply only in replacement BEARING WITH BUSHING STD
Supply only in replacement DOWEL FOR BUSHING COLLAR
Supply only in replacement CONNECTING ROD ASSEMBLY
Supply only in replacement OIL STRAINER
Supply only in replacement CRANKSHAFT
Supply only in replacement SINGLE FRAME ASSEMBLY
Supply only in replacement UNLOADING mechanism CYLINDER ASSEMBLY Kit.
Supply only in replacement SHAFT SEAL ASSEMBLY
Dismantling of compressor of central AC plant complete with connected copper pipe line and loading unloading mechanism & pump down the existing refrigerant in separate cylinder, disconnecting of electric motor of compressor, refrigerant line, gauges pipe and carry out the general over hauling of compressor, compressor model:- SMC/8/100, Make:- Accel (R-22) including replacement of springs, aluminium washer packing, screw, lath work, cleaning detergent, cotton waste, compressor oil etc and cleaning the suction filter, oil filter, replacing the defective parts compete system for safe guard the gas with self pumping down system or with total recovery unit system and (i) Charging of nitrogen Gas in unit & complete system at 300 psi pressure and checking of any dropping of pressure / leakage up to 72 Hrs after replacement of compressor & rectification of leakage if any. (ii) Vaccumisation of complete system for minimum 2 days for dropping of vacuum pressure & rectification of leakage if any.(iii) Charging of complete system with R - 22 gas for maintaining the system pressure up to HP - 175 psi & LP - 65 psi.... (iv) Measure the inlet and outdoor temperature of Chiller unit for performance checking and maintaining temp. as per require site. (v) Testing & commissioning of compressor after completion. Note:- (a) Spares of compressor shall be measured and paid separately under respective item of this schedule. (b) Any other minor items required for overhauling except described here -in - after shall be supplied by the contractor with out any extra cost to the deptt and the rates for the same shall deemed to be included in the quoted rates.
Supply only in replacement PISTON with PIN & Rings (ACCEL Part No. ASL1018R)
Supply only in replacement CYL.LINER with suction valve (R-22) (ACCEL Part No. ASL1019A)
Supply only in replacement OIL pump (ACCEL Part No. ASL1011A)
Supply only in replacement Discharge valve assembly (R-22) (ACCEL Part No. ASL1020 A)
Supply only in replacement Oil pressure regulation valve (ACCEL Part No. ASL1022 R)
Supply only in replacement Set of gasket (ACCEL Part No. ASL1853)
Supply only in replacement Set of neoprene ' O' RINGS (ACCEL Part No. ASL1854)
Supply only in replacement Set of Dowty ring (ACCEL Part No. ASL1855)
Supply only in replacement Set of SEALING RING (ACCEL Part No. ASL1856)
Supply only in replacement SPRING FOR SAFETY HEAD (ACCEL Part No. B-12)
Supply only in replacement HALF SECTION OF BRG. STD. (ACCEL Part No. E-02)
Supply only in replacement BEARING WITH BUSHING STD (ACCEL Part No. C-03)
Supply only in replacement CONNECTING ROD ASSEMBLY (ACCEL Part No. ASL1017 A)
Supply only in replacement OIL STRAINER (ACCEL Part No. ASL1033 A)
Supply only in replacement CRANKSHAFT - FOR SMC/8/100 (ACCEL Part No. ASL1816 A)
Supply only in replacement SINGLE FRAME ASSEMBLY (ACCEL Part No. UN-FRM-100)
Supply only in replacement UNLOADING mechanism CYLINDER ASSEMBLY (ACCEL Part No. ASL1012A-1)
Supply only in replacement ULOADING mechanism CYLINDER ASSEMBLY (ACCEL Part No. ASL1012A-2)
Supply only in replacement ULOADING mechanism CYLINDER ASSEMBLY (ACCEL Part No. ASL1012A-3)
Supply only in replacement ULOADING mechanism CYLINDER ASSEMBLY (ACCEL Part No. ASL1012A-4)
Supply only in replacement SHAFT SEAL ASSEMBLY (ACCEL Part No. ASL1010 R)
Supply only in replacement BUSHING FOR PISTON PIN (ACCEL Part No. E-07)
Dismantling of compressor of central AC plant for overhauling complete with connected copper pipe line and loading unloading mechanism & pump down the existing refrigerant in separate cylinder, disconnecting of electric motor of compressor, refrigerant line, gauges pipe and carry out the over hauling of compressor, compressor model:- JS44FN508 Make:- BLUE STAR(R-22) HSN CODE 995469 including S & F in replacement of springs, aluminium washer packing, screw, lath work, cleaning detergent, cotton waste, changing of compressor oil, oil pump etc and cleaning the suction filter, oil filter, replacing the defective parts compete system for safe guard the gas with self pumping down system or with total recovery unit system (i) Charging of nitrogen Gas in unit & complete system at 300 psi pressure and checking of any dropping of pressure / leakage up to 72 Hrs after replacement of compressor & rectification of leakage if any. (ii) Vaccumisation of complete system for minimum 2 days for dropping of vacuum pressure & rectification of leakage if any. (iii) Charging of complete system with R - 22 gas for maintaining the system pressure up to HP - 175 psi & LP - 65 psi.... (iv) Measure the inlet and outdoor temperature of Chiller unit for performance checking and maintaining temp. as per require site. (v) Testing & commissioning of compressor after completion. Note 01: Contractor shall produce MoU of agreement between OEM and contractor firm from Whom contractor shall carry out the overhauling of compressor. Note 02: Contractor should arrange necessary T & P and manpower to take out unserviceable part of plant and transporting the same to workshop for overhauling and re fixing the same at existing position after overhauling all as specified and directed by engineer in charge. The Quoted rates inclusive all and no extra co host admissible in this regard Note 03 : contractor shall arrange necessary vehicle from factory inspection by AGE E/M and JE E/M for this dismentalized AC parts and after completing of overhauling. So for two times during for overhauling of complete engine in workshop vehicle will arrange and rate of that inclusive in quoted rate. Note 04: contractor shall make necessary arrangement of testing of the engine 100% load condition and testing can be carried out 06 hours period. Gas, Compressor oil and other minor items required, if any for making it functioning shall be responsibility of contractor and rate quoted by contractor shall deemed to be inclusive of this factor.
Supply, installation, testing and commissioning in repair controller for chiller of type shell & tube Make blue star, capacity 60 TR, Model No. YCH 77A complete all as specified and as directed.
Supply, installation, testing and commissioning in repair sensor as per HSN code : 995469 for chiller of type shell & tube Make blue star, capacity 60 TR, Model No. YCH 77A complete all as specified and as directed.
Supply, installation, testing and commissioning in repair flow switch as per HSN code : 995469 for chiller of type shell & tube Make blue star, capacity 60 TR, Model No. YCH 77A complete all as specified and as directed.
S & F in repair low or high pressure gauge/oil pressure gauge of compressor of central type AC plant of 3 X 60 TR capacity complete all as specified and as directed.
S & F in repair syphon for low or high pressure gauge/oil pressure gauge of compressor of central type AC plant of 3 X 60 TR capacity complete all as specified and as directed.
M & L for Loading and unloading including transportation to and fro (if required) of compressor with other connected parts and accessories of 3 X 60 TR blue star make AC plant complete all as specified and as directed.
M & L for servicing the electrical connections of 3 X 60 TR blue star make AC plant complete all as specified and as directed.
M&L for taking out Cooling Tower Motor of following capacity, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified and as directed: -
2 HP Cooling Tower Motor, Make-Oswal, Model-OM-57
3 HP Cooling Tower Motor, Make-Oswal
7.5 HP Cooling Tower Motor, Make-Oswal
M&L for repairing /servicing AHU Fan Motor of following capacity, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed.
2 HP AHU fan motor, Make-Kirloskar, Crompton Greaves.
5 HP AHU fan motor, Make-Kirloskar, Crompton Greaves.
7.5 HP AHU fan motor, Make-Kirloskar, bearcat bile, ABB.
10 HP AHU fan motor, Make-ABB.
15 HP AHU fan motor, Make-Siemens
30 HP AHU fan motor, Make-CG
S & F in repair oil pressure cut out for ACCEL MAKE compressor of central type AC plant of any capacity complete all as specified and as directed. (Accel part No. V-11)
S & F in repair oil pressure cut out for VOLTAS MAKE compressor of central type AC plant of any capacity complete all as specified and as directed.
S & F in repair high pressure cut out for Accel make compressor of central type AC plant of any capacity complete all as specified and as directed. (Accel part No. V-13)
S & F in repair high pressure cut out for Voltas make compressor of central type AC plant of any capacity complete all as specified and as directed.
S & F in repair low pressure cut out for Accel make compressor of central type AC plant of any capacity complete all as specified and as directed. (Accel part No. V-12)
S & F in repair low pressure cut out for Voltas make compressor of central type AC plant of any capacity complete all as specified and as directed.
S & F in repair low pressure gauge/oil pressure gauge for Accel make compressor of central type AC plant of any capacity complete all as specified and as directed. (Accel part No. V-03)
S & F in repair low pressure gauge/oil pressure gauge for Voltas make compressor of central type AC plant of any capacity complete all as specified and as directed.
S & F in repair high pressure gauge for Accel make compressor of central type AC plant of any capacity complete all as specified and as directed. (Accel part No. V-04)
S & F in repair high pressure gauge for Voltas make compressor of central type AC plant of any capacity complete all as specified and as directed.
S & F in repair three way solenoid valve suitable for (Accel make compressor, compressor model-SMC/8/100) central type AC plant of any capacity complete all as specified and as directed. (Solenoid valve Accel part No.U-1N)
S & F in repair three way solenoid valve suitable for (Voltas make compressor, compressor model-05018 central type AC plant of any capacity complete all as specified and as directed.
M&L for repairing /servicing the centrifugal pump of following capacities by disconnecting the pump from motor, opening for inspection, replacing the worn out parts like gland bush, bearings, gland bolts and nuts, gland packing, gasket, water seal etc including repairing to pump shaft by remetalling, grinding, polishing and reassembling complete pump & refixing in same position & connecting including replacing the rusted nuts, bolts, washers etc and testing complete all as specified and directed and taking out electric motor from the centrifugal pump set, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding wire of suitable size including insulating materials, varnishing and drying, reassembling, refixing in same position & connecting complete including testing and commissioning complete all as specified & directed: -
Condenser or Chiller Pump of capacity 3 HP, Head Range-10-26M,LPS-6, Make : Kirloskar
Condenser or Chiller Pump of capacity 4 HP, Head Range-10-26M,LPS-6, Make : Kirloskar
Condenser or Chiller Pump of capacity 7.5 HP, Head Range-10-20M,10-35M & 18-29M,LPS-14 , Make : Kirloskar
Condenser or Chiller Pump of capacity 10 HP, Head Range-6-38M, Make : Kirloskar
Condenser or Chiller Pump of capacity 11 HP, Head Range-10-35M, Make : Kirloskar
Dismantling of existing corrosion proof PVC fill from the induced draft type cooling tower of fibre glass reinforced plastic (FRP) casting rectangular/other type construction for Cooling tower of following capacity complete with all accessories and supply and fix new corrosion proof PVC fill and inlet louvers, drift , eliminators hot water distribution chamber and nozzles etc complete all as specified and as directed: -
CAPACITY-35TR, MAKE -DELTA,MODEL-5035&9032
CAPACITY-125 TR, MAKE -DELTA,MODEL-5064
CAPACITY-180 TR, MAKE -DELTA,MODEL-5081
Supply & charge the refrigerant R22 Gas complete all as specified and directed. (Make:- Mafron/Freon)
M&L for Painting of complete water cooled central AC Plant and DX type AC plant of following capacity (comprising 3 Nos compressor of following capacity, pipe lines, valves, pump sets, cooling tower steel surface, AHU pipe lines and chiller pipes etc) by preparation of old painted surface, removing of dirt / dust / oil grease etc and applying two coat of synthetic enamel paint complete all as specified and directed: -
3X15TR AC PLANT.
3X60TR AC PLANT.
3X75TR AC PLANT.
S & F in repair fully automatic star delta starter suitable for 3 phase, 415V, 15 HP rating induction motor, containing Electric over current protection relay range 0.5 to 30 Amp with external CT 960 Amp, AC-3, 25 Amp rating contractor and back up protection HRC fuse of suitable rating etc complete all as specified and as directed. Make:BCH Cat No.- NASKALEN or equivalent Model of L&T/ SIEMENS /ABB
S&F in repair single phase preventer suitable for 3 phase supply 415 volt complete all as specified and as directed. Make:- SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
S&F in repair 3 pole, ML3 contactor, 415 volt including NO or NC AUXILIARY contacts also including connecting complete all as specified and as directed. Make:- SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
S&F in repair 3 pole power contactor 415 V, type MNX 25 including NO or NC auxiliary contact block, coil voltage 230 V including connecting complete all as specified and as directed. Make SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
S&F in repair 3 pole power contactor 415 V, type MNX 18 including NO or NC auxiliary contact BLOCK, Coil voltage 230 V, 50 Hz including connecting complete all as specified and as directed. Make SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
S&F in repair 4 pole power contactor 415 V, type MNX 12 , 3 pole including NO or NC auxiliary contact Block, Coil voltage 230 V, 50 HZ including connecting complete all as specified and as directed. Make SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
S&F in repair 3 pole power contactor 415 V, type MNX 32 including NO or NC auxiliary contact block, coil voltage 230 V with including connecting complete all as specified and as directed. Make SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
S&F in repair 3 pole, ML2 contactor including NO or NC AUXILIARY contacts also including connecting complete all as specified and as directed. Make:- SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
S&F in repair 3 pole, ML6 contactor, 415 volt including NO or NC AUXILIARY contacts also including connecting complete all as specified and as directed. Make:- SIEMENS / L&T / BHARATIA CUTTLER HAMMER / C&S
M&L for taking out compressor Motor (motor cap.:-20 HP, MAKE- CROMPTON, SEAMENS & ABB ) of AC plant and Dis mantling the motor with disconnecting the same from the compressor and remove rubber coupling and its connected accessories and transporting to reputed work shop for rewinding, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed
M&L for taking out compressor Motor (Motor cap-15 HP, MAKE- CROMPTON ) of AC plant and Dis mantling the motor with disconnecting the same from the compressor and remove rubber coupling and its connected accessories and transporting to reputed work shop for rewinding, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed.
M&L for taking out compressor Motor (Motor cap-25 HP, MAKE- HINDUSTHAN AND ABB) of AC plant and Dis mantling the motor with disconnecting the same from the compressor and remove rubber coupling and its connected accessories and transporting to reputed work shop for rewinding, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed.
M&L for taking out compressor Motor (Motor cap-40 HP, MAKE-KIRLOSKAR) of AC plant and Dis mantling the motor with disconnecting the same from the compressor and remove rubber coupling and its connected accessories and transporting to reputed work shop for rewinding, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed.
M&L for taking out compressor Motor (Motor cap- 50 HP, MAKE-GENERAL ELECTRIC POWER INDIA) of AC plant and Dis mantling the motor with disconnecting the same from the compressor and remove rubber coupling and its connected accessories and transporting to reputed work shop for rewinding, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed.
M&L for taking out compressor Motor cap-100 HP, MAKE-CROMPTON) of AC PLANT and Dis mantling the motor with disconnecting the same from the compressor and remove rubber coupling and its connected accessories and transporting to reputed work shop for rewinding, opening the motor, cutting & removing old and burnt winding wire, rewinding the motor with new super enamelled copper winding of suitable size including insulating materials, varnishing, drying, replacement of both driven end non driven end bearings and base plate, reassembling, refixing in same position & connecting including testing and commissioning complete all as specified & directed.
S&F in repair with testing and commissioning totally enclosed weatherproof/waterproof electric CT Fan Motor with following specification complete all as specified and as directed:- three phase squirrel cage motor, Capacity 5 HP, 960 RPM, 415V, 50HZ with all connected accessories and all fitting suitable for 100 TR cooling tower, CT Model-5062, CT Make-delta and Motor Make-Oswal/ New India .
S&F in repair CT Fan complete section Fan, Fan Dia-1500 mm , connected GI nut bolts and accessories all fitting suitable for 100 TR cooling tower complete all as specified and as directed. CT Model-5062, CT Make-Delta, FAN Make:- Kruger/nectar
S&F in repair all accessories corrosion proof PVC Filling, inlet louvers, drift, PVC eliminators, PVC water distribution chamber and nozzles( self rotating sprinklers) GI nut bolt (included float valve)and all fitting complete all as specified and as directed. Note:- (a) The spray system should be work satisfactory even with 50% reduced flow of water. (b)The induced draught cooling tower should be operate according to the counter flow principle. (c) cooling tower specification for PVC filling (Delta Make) (i) Capacity - 100 TR (ii) Model - 5062 (iii) Water Flow - 360 LPM (iv) Water in - 36.4° C (v) Water out - 32.2° C (vi) Design wet bulb temp - 28.3° C
S&F in repair round type shape and FRP induced draft type counter flow, casting by fibre glass reinforced ,casing & basin(FRP), over all dimension (H X Dia)-3700x3000(mm), MSHDG type mechanical equipment supports, electroplated hardware, drain connections, suitable GI inspection ladder, steel supporting structure, anti vibration mounting etc, suitable for 100 TR cooling tower, CT Model-5062 and CT Make-delta complete as per manufacturer's design/specifications with all fittings complete all as specified and as directed.
S&F in repair with testing and commissioning totally enclosed weatherproof/waterproof electric CT Fan Motor with following specification:- three phase squirrel cage motor, Capacity 7.5 HP, 960 RPM, 415V, 50HZ with all connected accessories and all fitting suitable for 125 TR cooling tower complete all as specified and as directed. CT Model-5064, CT Make-Delta and Motor Make-Oswal/ New India.
S&F in repair CT Fan complete section Fan, Fan Dia-1500 mm , connected GI nut bolts and accessories all fitting suitable for 125 TR cooling tower complete all as specified and as directed. CT Model-5064, CT Make-Delta, FAN Make:- Kruger/nectar
S&F in repair all accessories corrosion proof PVC Filling, inlet louvers, drift, PVC eliminators, PVC water distribution chamber and nozzles( self rotating sprinklers) GI nut bolt (included float valve)and all fitting complete all as specified and as directed. Note:- (a) The spray system should be work satisfactory even with 50% reduced flow of water. (b)The induced draught cooling tower should be operate according to the counter flow principle. (c) Cooling tower specification for PVC filling (Delta Make) (i) Capacity - 125 TR (ii) Model - 5064 (iii) Water Flow - 450 LPM (iv) Water in - 36.4° C (v) Water out - 32.2° C (vi) Design wet bulb temp - 28.3° C
S&F in repair round type shape and FRP induced draft type counter flow, casting by fibre glass reinforced ,casing & basin(FRP), over all dimension (H X Dia)-3700x3000(mm), MSHDG type mechanical equipment supports, electroplated hardware, drain connections, suitable GI inspection ladder, steel supporting structure, anti vibration mounting etc, suitable for 125 TR cooling tower, CT Model-5064 and CT Make-delta complete as per manufacturer's design/specifications with all fittings.
S&F in repair with testing and commissioning totally enclosed weatherproof/waterproof electric CT Fan Motor with following specification:- three phase squirrel cage motor, Capacity 7.5 HP, 720 RPM, 415V, 50HZ with all connected accessories and all fitting suitable for 180 TR complete all as specified and as directed. Cooling tower, CT Model-5081, CT Make-delta and Motor Make-Oswal/ New India .
S&F in repair CT Fan complete section Fan, Fan Dia-1800 mm , connected GI nut bolts and accessories all fitting suitable for 180 TR cooling tower complete all as specified and as directed. CT Model-5081, CT Make-Delta, FAN Make:- Kruger/Nicotra
S&F in repair all accessories corrosion proof PVC Filling, inlet louvers, drift, PVC eliminators, PVC water distribution chamber and nozzles( self rotating sprinklers) GI nut bolt (included float valve) and all fitting complete all as specified and as directed. Note:- (a) The spray system should be work satisfactory even with 50% reduced flow of water. (b)The induced draught cooling tower should be operate according to the counter flow principle. (c) Cooling tower specification for PVC filling (Delta Make) (i) Capacity - 180 TR (ii) Model - 5081 (iii) Water Flow - 680 USGPM (iv) Water in - 97.5° F (v) Water out - 90° F (vi) Design wet bulb temp - 83° F (vii) Max approach for Cooling Tower - 5°F
S&F in repair round type shape and FRP induced draft type counter flow, casting by fibre glass reinforced ,casing & basin(FRP), over all dimension (H X Dia)-4400x3550(mm), MSHDG type mechanical equipment supports, electroplated hardware, drain connections, suitable GI inspection ladder, steel supporting structure, anti vibration mounting etc, suitable for 180 TR cooling tower, CT Model-5081 and CT Make-delta complete as per manufacturer's design/specifications with all fittings complete all as specified and as directed.
M & L in repair PCC 1:2:4 (Type B2) using 40mm graded stone aggregate as in foundation, filling and mass concrete for chiller, pumps, cooling tower etc complete all as specified and as directed.
M & L pre-cast PCC solid blocks masonry using PCC 1:3:6 (Type C1) using 20mm graded stone aggregate (exc 10 Cm in width) set in cement mortar 1:6 complete all as specified and as directed.
S&F in repair with anchor fastener angle iron , MS flat to support duct with angle iron, flats, nut bolt washers etc. Necessary welding work involved is also deemed to be included in quoted rate include cutting fabrication welding of angle iron / MS Flat, repair to RCC wall, cost of anchor fastener etc complete all as specified and as directed.
S & F in repair butterfly valve of following sizes with CI body, stainless steel disc, nitrile rubber seal & O ring suitable pressure rating also complete all as specified & directed:-
Suitable for 40mm bore pipe.
Suitable for 50mm bore pipe.
Suitable for 65mm bore pipe.
Suitable for 80mm bore pipe.
Suitable for 100mm bore pipe.
Suitable for 125mm bore pipe.
Suitable for 150mm bore pipe.
S&F in repair Y type Strainer of ductile Iron body flanged ends with stainless steel strainer of following sizes complete all as specified & directed:-
Suitable for 50mm bore pipe.
Suitable for 65mm bore pipe.
Suitable for 80mm bore pipe.
Suitable for 100mm bore pipe.
Suitable for 125mm bore pipe.
Suitable for 150mm bore pipe.
S&F in repair POT Strainer of ductile Iron body flanged ends with stainless steel strainer, existing rustling pipe cutting with nut bolt etc of following sizes complete all as specified & directed:-
Suitable for 125mm bore pipe.
Suitable for 150mm bore pipe.
S&F in repair gun metal Gate Valves complete of following sizes with fitting like nipples, elbows, tees, bends, sockets etc complete all as specified & directed:-
Suitable for 15mm bore pipe.
Suitable for 20mm bore pipe.
Suitable for 25mm bore pipe.
Suitable for 40mm bore pipe.
Suitable for 50mm bore pipe.
S&F in repair Sluice valve class PN 1.6 complete of following sizes with fitting like nipples, elbows, tees, bends, sockets etc complete all as specified & directed:-
Suitable for 80mm bore pipe.
Suitable for 100mm bore pipe.
S&F in repair of GI tubing medium class of following sizes, laid in trenches / floor/ fixing on pole / wall /in hard standing including necessary fittings etc complete all as specified & directed:-
25 mm internal dia.
50 mm internal dia.
S&F in repair condenser water or cooling tower piping of following sizes, MS 'C' class confirming to IS-1239 and IS- 3589 both revised till date as required with bends, reducers tees, supports vibration pipe supports, structures shall be painted with 2 coats of synthetic enamel paint over a coat of red oxide primer and complete all as per specified & directed:-
40 mm internal dia
50 mm internal dia
65 mm internal dia
80 mm internal dia
100 mm internal dia
125 mm internal dia
150mm internal dia
S&F in repair, installation, testing and commissioning of 15 TR capacity DX Type chiller unit complete with connected condensing unit, control Panel, expansion valve, scroll compressors and connected accessories, piping s and wiring. The unit shall be charged with refrigerant gas R407 and fixing on base frame supplied by OEM and fixed on anti vibration pad. Contractor shall be responsible to brazing necessary suction & discharge copper piping as per OEM recommendation up to connecting to existing main header of suction and discharge line (Make Blue star Model N0-05018 Scroll type or Equivalent model of in Carrier, Voltas) with following specifications:- (a) Nominal dimensions of L:W:H = 1350:600:1194 (in mm) (b)Weight/unit-500 kg (c) Hermetiv compresser (scroll type). (d) Power supply(Total power consumption)-11.4 KW (e) condenser shell and tube type (f) water flow rate Min-35 USGPM & Max-49 USGPM , (g) water connection in and out size-1-1/4", (h) Refrigerant connections - 01 nos (j) Liquid line-5/8" (k) suction line-1-3/8". Note:- (i) Charging of nitrogen Gas in unit & complete system at 300 psi pressure and checking of any dropping of pressure / leakage up to 72 Hrs after replacement of compressor & rectification of leakage if any. (ii) Vaccumisation of complete system for minimum 2 days for dropping of vacuum pressure & rectification of leakage if any.(iii) Charging of complete system with R - 22 gas for maintaining the system pressure up to HP - 175 psi & LP - 65 psi.... (iv) Measure the inlet and outdoor temperature of Chiller unit for performance checking and maintaining temp. as per require site. (v) Testing & commissioning of compressor after completion. (vi) Any other minor items required for installation,testing and commissioning except described here -in - after shall be supplied by the contractor with out any extra cost to the deptt and the rates for the same shall deemed to be included in the quoted rates.
Dismentaling of existing Dx type central AC plant Make- Voltas ,15 TR Cap with necessery pump down of complete system in empty cylinder with recovery unit cutting of liquid & gas copper tubing of existing chiller unit with disconnecting of electrical connection & control wiring with necessory T&P & skill manpower and loading and transporting to MES site and unloading inside MES store for safe custody all as per specified & directed. Note:- Old taking down complete system of 15TR shall be deposited to MES store yard from existing location .The rate include necessary transportation & Manpower to dismantling and transporting the unit.
Supplying, fabricating, installing and testing of sheet metal ducts of following thicknesses including necessary supports, flexible hangers with isolators, nut bolts, gasket, splitter dampers and vanes, volume control dampers etc. complete as per specification in accordance with the approved shop drawings and as required complete all as specified and as directed: -
24 gauge GI sheet (sheet thicknesss variation between 751 -1000 mm)
22 Gauge GI sheet (sheet thicknesss variation between 1001 -1200 mm)
M & L for external thermal insulation of ducts with approved sample of Nitrile Rubber 25 mm thick of insulation material and joints to be sealed properly complete all as specified and directed.
M/s Birja Nand
RUCHIKA ENGG.WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .