| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.2 LAccepted-AOC 227 NEW GANESH VIHAR ADARSH MILL ROAD GHOSIPURA LASHKAR GWALIOR 474012 M P | GWALIOR | MADHYA PRADESH | 474012 | L1 | Accepted-AOC AOC | |
| 2 | L2₹19.2 L+₹1.8 L (10.2%)Rejected-Finance | L2 | Rejected-Finance Not being a lowest tender | |
| 3 | L3₹21.7 L+₹4.2 L (24.0%)Rejected-Finance | L3 | Rejected-Finance Not being a lowest tender |
Tender Value
₹18.6 L
EMD Value
₹37,200
Closing Date
18 Dec 2020, 6:00 pmClosed
GE AF TA GWALIOR
GE AF TA GWALIOR
REPAIR/MAINT OF DG SET AND CONNECTED WORKS IN TECH AREA/SINGPUR AT AF STN GWALIOR
2020_MES_389629_1
8900/1261/GWL/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE AF TA GWALIOR
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE AF TA GWALIOR
₹37,200
Yes
8 Jan 2021
18 Nov 2020
21 Dec 2020
18 Nov 2020
18 Dec 2020
3 Dec 2020
Amount
M &L for Maintenance and servicing of standby DG Set complete including draining out of diesel from tank , cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the sump, cleaning the sump thoroughly and refilling the sump with new engine oil to it’s required level, replacing the fuel filter, lubricating oil filter , check & clean air cleaner , change air cleaner elements, check coolant level & make up the same ,drain the fuel filter & water separator ,filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replace the u/s brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, including M&L for changing of V-belts, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/ coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load and record shall be made in respect of RPM , oil pressure , oil temprature , coolent temprature, frequency , load current , battery charging , fuel consumption etc complete all as spicified and directed by Enginner in Charge for 7.5 KVA to 30 KVA D G set Make - Kirloskar/CG /Ruston/Cummins/ AhokA Leyland or any make .
All as per item No.1 here-in-before but for 40 KVA to 63 KVA DG Set Make :- Kirloskar/Cummins etc.
All as per item No.1 here-in-before but for 100 KVA to 125 KVA DG Set Make :- Kirloskar/Cummins etc.
All as per item No.1 here-in-before but for 160 KVA DG Set Make :- Kirloskar/Cummins etc.
All as per item No.1 here-in-before but for 200 KVA 250 KVA DG Set Make :- Kirloskar/Cummins etc.
All as per item No.1 here-in-before but for 320 KVA DG Set Make :- Kirloskar/Cummins etc.
All as per item No.1 here-in-before but for 380 KVA to 400 KVA DG Set Make :- Kirloskar/ Cummins etc
All as per item No.1 here-in-before but for 500 KVA DG Set Make :- Kirloskar/ Cummins etc Note for BOQ Item No 1.00 to 8.00 1. Engine oil for refilling will be measured and paid Seprately 2. Coolant for make up will be measured & paid separately 3. DHPP will be issued by dept for testing and top up in tank only. 4. The Make of Fuel filter , Oil Filter , V belt & component will be as per existing or suitable make. 5.Spray painting of DG set as per existing colour including preparation of old surfaces all as directed by Engineer -in -Charge . 6. The rate quoted against item No. 1 to 8 is deemed to be inclusive of any break down attendance / rectification during contract period with in 72 hours of complaint received, failing which penalty @ 3000.00 per day will be recoverd from work done statemenet till rectification . 7. A register for record of servicing & break down attendence shall be maintained by contractOR duly signed by JE /Engineer-in -Charge . 8. Cost of spares & labour charges for attending break down shall be paid under relevant item of this schedule here in after.
Supply only lubricating oil for DG Sets all as specified and directed. Make: Castrol
Supply only coolant for radiator all as specified and directed. Make :- TVS Note for Item No. 9 & 10:- Labour charges for filling of lubricant & coolant shall be included in item rate quoted against item No. 1 to 8 .
Dismantling the water pump of the DG Set, taking out and replacing the worn out parts with new parts, refixing the water pump after repair and testing complete all as specified and directed for following D G set:-
Up to 50 KVA DG set.
62.5 KVA to 63 KVA DG set.
100 KVA to 125 KVA DG set.
320 KVA to 500 KVA DG set
Material and labour for servicing of self-starter assembly of DG Set ,by disconnecting the self starter assembly from the engine and dismantling the self-starter assembly for followiong DG set and cleaning all accessories , replace worn out parts like carbon brush, bush, contact plates, jumping leads etc and re-tapping the field coil and varnishing all as directed for following DG set :
7.5 KVA 30 KVA DG set
40 KVA to 63 KVA DG set
100 KVA to 160 KVA DG set
200 KVA to 320 KVA DG set
380 KVA to 500 KVA DG set
Disconnection and dismantling the fuel injector pump assembly from its original position & servicing by cleaning / oiling / servicing of fuel injector pump assembly , removing and replacement fuel injector pump repair kit & fuel pipe including calibration complete & refixing the same all as directed by Engineer-in-charge for following DG set :-
7.5 KVA to 30 KVA DG set
40 KVA to 63 KVA DG set
100 KVA to 160 KVA DG set
200 KVA to 320 KVA DG set
380 KVA to 500 KVA DG set
S&F in repair RPM meter on DG set complete all as specified and directed.
S&F in repair oil pressure Gauge on DG set complete all as specified and directed.
S&F in repair oil temperature Gauge on DG set complete all as specified and directed.
S&F in repair water temperature Gauge on DG set complete all as specified and directed.
S&F PVC insulated standard copper conductor cable 2 mtr length each soldered with 2 Nos brass battery terminals suitable for 120/150/180 AH 12 V DC battery complete all as specified and directed.
Supply and fix in repairs the following DG spares including testing complete all as directed by Engineer-in-Charge :-
AVR unit complete for 40 KVA to 100 KVA DG Set
AVR unit complete for 125 KVA to 200 KVA DG Set
AVR unit complete for 250 KVA to 320 KVA DG Set
AVR unit complete for 320 KVA 500KVA DG Set
Silicon Rectifier
High pressure pipe complete set
Pipe assembly consisting of banjo bolt,copper washer,dual bango bolt ,leak of pipe etc.
Air cleaner
Diesel return pipe
Injector assembly
V Belt for fan radiator upto 500 KVA Set
Disconnection and taking out the turbo charger assembly complete from the Engine of any make of 40 KVA to 63 KVA DG Set, strip opening of turbo charger and replacement of turbo charger repair Kit , assembling the complete part of the turbo charger and fixing back to the engine the testing and commissioning for satisfactory working complete all as specified and directed.
Disconnection and taking out the turbo charger assembly complete from the Engine of any make of 100 KVA to160 KVA DG Set , strip opening of turbo charger and replacement of turbo charger repair Kit , assembling the complete part of the turbo charger and fixing back to the engine the testing and commissioning for satisfactory working complete all as specified and directed.
Disconnection and taking out the turbo charger assembly complete from the Engine of any make of 200 KVA to 250 KVA DG Set, strip opening of turbo charger and replacement of turbo charger repair Kit , assembling the complete part of the turbo charger and fixing back to the engine the testing and commissioning for satisfactory working complete all as specified and directed.
Disconnection and taking out the turbo charger assembly complete from the Engine of any make of 320 KVA to 500 KVA DG Set, strip opening of turbo charger and replacement of turbo charger repair Kit , assembling the complete part of the turbo charger and fixing back to the engine the testing and commissioning for satisfactory working complete all as specified and directed.
Supply & fix in repair self starter assembly 12 volt compleate for 7.5 KVA to 63 KVA DG set as per existing Make.
Supply & fix in repair self starter assembly 12 volt compleate for 100 KVA to 160 KVA DG set as per existing Make.
Supply & fix in repair self starter assembly 24 volt compleate for 200 KVA to 320 KVA DG set as per existing Make.
Supply & fix in repair self starter assembly 24 volt compleate for 380 KVA to 500 KVA DG set as per existing Make.
Supply & fix in repair Fly wheel ring by removing alternator from engine for 50 Kva to 63 KVA DG set complete all as specified and directed.
Supply & fix in repair Fly wheel ring by removing alternator from engine for 100 KVA to 125 KVA DG set complete all as specified and directed.
Supply & fix in repair Fly wheel ring by removing alternator from engine for 200/320 KVA DG set complete all as specified and directed.
Supply & fix in repair Fly wheel ring by removing alternator from engine for 380 to 500 KVA DG set complete all as specified and directed.
Supply & fixing in repair fuel pipe assembly set for supply and returning complete all as specified and directed.
Supply & fixing in repair the turbo charger assembly complete of 40 KVA to 100 KVA DG Set complete all as specified and directed.
Supply & fixing in repair the turbo charger assembly complete of 125 KVA to 200 KVA DG Set complete all as specified and directed.
Supply & fixing in repair the turbo charger assembly complete of 250 KVA to 500 KVA DG Set complete all as specified and directed.
S & F following items in AMF Panel of any description and in any position of capacity DG Set upto 500 KVA including checking AC/DC circuits, tightning of all power / control wiring connection and replacement of unserviceable control wiring with suitable size, single core, copper conductor, flexible, PVC insulated, unsheathed cable suitable upto 1100 volts confirming to IS-694, taking out, removing and replacement of unserviceable parts / spares / items to make AMF functional inclusing testing complete all as specified and directed.
Pla relay 24 Volts DC, 11pin, 2 change over, cat part No. 2C/O – MPC -24D of pla make or equivalent of Eagle man.
Pla relay 12 Volts DC, 11pin, 2 change over, cat part No. 2C/O – MPC -12D of pla make or equivalent of Eagle man.
Ammeter size 96 mm X 96mm, flush mounted digital type, three phase of class 1.0 complete all as specified and directed. Make: HPL / Rishab / MECO / Schneider.
Voltmeter size 96 mm X 96mm, flush mounted digital type, three phase, class 1.0 complete all as specified and directed. Make: HPL / Rishab / MECO / Schneider.
Frequency meter size 96 mm X 96mm, flush mounted digital type, three phase, class 0.2 complete all as specified and directed. Make: HPL /Rishab / MECO / Schneider.
Under voltage relay suitable for 3 phase 415 volts, AC supply complete all as specified and directed. Make: PIC / Aditya Electronic
Engine starting relay with sequence timer & master timer suitable for 12 / 24 Volts DC supply complete all as specified and directed. Make: PIC / Aditya Electronic
Electronic timer, time range from 3 seconds to 10 seconds , suitable of 12/ 24 Volts, 50 Hz, AC supply complete all as specified and directed. Make : L&T / PIC / Aditya Electronic.
Rectifier 4 plates, single phase, having charging rate 15–20 Amp per minute for 12/24 Volts DC battery charge complete all as specified and directed. Make : Usha / URI / Kirloskar.
Rectifier 8 plates, single phase, having charging rate 15–20 Amp per minute for 12/24 Volts DC battery charge complete all as specified and directed. Make : Usha / URI / Kirloskar.
LED Indicator 22.5mm for 12 /24 volts AC/DC supply complete all as specified and directed. Make: L&T/ BCH / Seimens / ABB.
Battery charging transformer 0 to 10 Amperes, 12 Volts DC tapping 0-12-18-24 Volts complete all as specified and directed.
MCB single pole, 10 KA, rating 6 to 32 Amps ‘C’ series, 240 volts complete all as specified and directed. Make :Legrand /Siemens / BCH/ /ABB/Havells/Standrd.
S&F in repair including testing of Power contactor , of following capacity, for 415 Volt AC supply complete all as specified and directed :-
Power contactor 3 pole, AC3 rating of 630 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : ABB / Siemens / BCH/ Schneider/GE
Power contactor 3 pole, AC3 rating of 580 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : ABB / Siemens / BCH/ Schneider/L&T/Havells
Power contactor 3 pole, AC3 rating of 500/550 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : ABB / Siemens / BCH/ Schneider/L&T/Havells
Power contactor 3 pole, AC3 rating of 400 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : ABB / Siemens / BCH/ Schneider/L&T/Havells
Power contactor 3 pole, AC3 rating of 325 Amps, with 2 NO + 2 NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : L&T MNX 325 / Siemens / BCH/ Schneider/Havells.
Power contactor 3 pole, AC3 rating of 210 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make :ABB / Siemens / BCH/ Schneider/L&T/Havells
Power contactor 3 pole, AC3 rating of 200/225 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : ABB / Siemens / BCH/ Schneider/L&T/Havells
Power contactor 3 pole, AC3 rating of 185 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : ABB / Siemens / BCH/ Schneider/L&T/Havells
Power contactor 3 pole, AC3 rating of 110/125 Amps, with 1NO + 1NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : ABB / Siemens / BCH/ Schneider/L&T/Havells .
Power contactor 3 pole, AC3 rating of 110 Amps, with 2 NO + 2 NC auxiliary contacts for AC circuit, 415 Volts complete all as specified and directed. Make : L&T: Model No MNX 110 or equivalent in make Siemens / BCH/ Schneider/Havells as approved by GE.
Dismantling of alternator assembly of DG Set of capacity 200 KVA to 400 KVA and taking out U/S Exitation winding and rewinding of excatation coil with supper enamelled copper winding all as per specified and directed.
M&L for repairing of canopy of DG set by carrying out repairing of door with replacement of broken hinges including nuts, bolts/welding etc as per requirement, cleaning of base of foundation and painting with black paint MS channel with two coats including touching of paint at cannopy where required complete all as specified and directed
S&F in repair maintenace free battery DC 12 Volts, 150 AH complete all as specified and directed. Make - Exide/Luminous or make as approved by GE
S&F in repair maintenance free battery DC 12 Volts, 180 AH complete all as specified and directed. Make - Exide/Luminous or make as approved by GE
Material and labour for dismantling and taking out and rewindind of Alternator stator assembly of 160 KVA DG Set and rewinding of approved suitable gauge super enamel insulated copper winding wire with necessary insulating materials reassembling and transportation to workshop and bring back to orginal installation and fixing,testing and commissioning complete all as specified and directed by Eng-in-charge.
All as per item No. 42 as above but for 20 KVA Alternator and exiting coil all as per directed by Engg-in-charge
M & L for disconnecting taking out excitation coil 125 KVA Alternator and Exeatation winding and rewinding of excatation coil with super enamelled copper winding wire of same gauge quanity,assembling of alternator, refitting and testing complete all as specified and directed.
Materal and labour for spray painting of old painted sarfaces of DG Set 200KVA and spray painting with approvd colour synthetic enamel paints including basechannel complete all as directed by Eng-in-charge.
All as item No. 45 as above but 125 KVA DG Set
S&F in replacement engine electronic (instrumentation) digital panel comprising of starting switch ON/OFF water temp display, hour meter cum RPM display, lubricant oil pressure display, lubricant oil tempreture display, battery charing display, safety alarm against high water temp and lubricant oil pressure for cummins/Kirloskar make DG Set of 250-500KVA capacity complete all as specified and directed
S&F in repair including testing of MCCB, of following capacity, having adjustable thermal magnetic release for 415 Volt AC supply complete all as specified and directed :-
MCCB, 4 pole, 100 Amps, breaking capacity Icu = 25 KA. Make: ABB / Legrand / Siemens / Havells /C&S/L&T/Schneider
MCCB 3 pole, 125 Amps, breaking capacity Icu = 25 KA. Make: ABB / Legrand / Siemens / Havells /C&S/L&T/Schneider
M/S Amit Traders
UNIVERSAL AGENCY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .