SE EWC AYODHYA
OFFICE OF THE SUPERINTENDING ENGINEER ELECTRICITY WORKS CIRCLE, AYODHYA
37/SE/EWC/AYO/2024-25
2024_MVVNL_959997_1
37/SE/EWC/AYO/2024-25
Open Tender
Electrical Works
Item Wise
90 days
AMBEDKAR NAGAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
SUPERINTENDING ENGINEER, ELECTRICITY WORKS CIRCLE
₹7,000
10 Oct 2024
2 Oct 2024
9 Oct 2024
2 Oct 2024
9 Oct 2024
2 Oct 2024
Amount
Safe Loading, Carriage and then safe unloading of the following material from Store Centres Under the jurisdiction of EEESD Ayodhaya to dump site proper stacking.
33 KV V Type channel cross arm
Bus Isolator
ACSR Dog Conductor (Sag charges, cutting and wastage)
33 KV Disc Insulator B & S type 70 KN polymer(additional)
33 KV VCB 800A, 750 MVA
33 KV P.T outdoor
33 KV Lightening Arrestor
C.T. O/D 33 KV CTR 200/100/1-1A
24 Volt Battery set
33 KV Single T/F control pannel
MS Angle for guarding 65x65x6 mm, 3500 mm long
GI Wire 8 SWG
GI Wire 6 SWG
24 Volt Battery charger
33 KV Pin Insulator polymer type (additional)
Installation of Lightening Arrestors Assembling and installation/ mounting of Lightening Arrestors on the L.A. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
Installation of Bus Isolators Assembling and installation of Bus isolator on the Isolator structure , adjusting of opening mechanism in proper alignment and grising and oiling so as to ensured smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
Installation of 33 KV VCB Installation of 33 KV 750 MVA 800 Amp VCB on 33 KV VCB structure along with earthing by G.I. strip 50x6 mm size with main earthmat of Switchyards complete in all respect including commissioning.
Installation Of CT Installation of CTs of ratio 200/100/1A on the CTs structure. The work includes fabrication for proper fixing if required.
Installation Of PT Assembling and installation/ mounting of P.T on the P.T. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
Stringing, sagging, binding and Jumpering of ACSR Dog conductor. 3 Phase of 33 KV Line including fixing, mounting of P.G.clamp suitable for Dog Conductor at sectional point. (Contractor shall provide necessary PG clamps etc)
Cradle Guarding of 33 KV line at road crossing, canal/telephone line crossing by fixing Guarding Angle 65x65x6 mm, 3500 mm at double pole and 2600 mm long at single pole by stringing and sagging of 3 No. G.I.wire with lacing and tightening with mounting. (Contractor shall provide Necessary clamps for fitting of guarding angle and 6 No. Eye hook&bolt 12x110 mm etc.)
Shifting carefully and installation of Single/double Transformer Control pannel in control room and its proper connection. By replacing the old and existing control panel from sgr room to storage location of Substaion
Fixing of additional 33 KV polymer Pin insulator, nut & bolts etc. at required places
Providing and Fixing of 33 KV Disc fitting at required places.
Fixing of additional 33 KV V-type cross arm with nut & bolts etc. at required places
Providing and fixing of P.G clamp for Dog conductor at required places .
Battery and Battery charger (Materials will be supplied by the contractor with all accessories except battery and charger)
Installation of 24 Volt Battery 200 AH ( 01 set=12 Nos, 2 Volt each with ISI 1651, IS nomenclature T 200 P) With its proper connection. (All the material will be supplied by the contractor)
Installation of Input voltage 230 V, AC one phase 50 hertz, output 24 Volt , 40 Amp DC Battery charger with its proper connection.
Stand / cabinet for battery set for proper stacking and storage
Opening of binding of loose old ACSR DOG Conductor, Tightening, stringing, binding and Jumpering of loose old ACSR Dog conductor in all respect. 3 Phase of existing 33KV Line & 11 kv line including fixing,mounting of P.G.clamp suitable for Dog Conductor at sectional point. (All the material will be arrange by the contractor)
Replacement of damage oil seal /Packing
Centrifuging of oil in 05 MVA TF
Reparing and maintenance if required do replacement of electrical and machnical components of Isolators ( i.e, Tripping coil, Tripping rod, MCB, Vaccum interrupter, Relay, replacement of damage internal wiring etc.) and do over overhaling of all mechanical parts of 33 KV VCB for proper mechanism work.
M/s S S Associates
Hindustan Electric Work
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .