CWE New Delhi
HQ CWE New Delhi, Rao Tula Ram Marg, Delhi Cantt-10
Manning and operation including repair/maint for air conditioning plant 3 x 90 TR capacity along with cooling appliances installed at NDC under GE New Delhi, Delhi Cantt-10
2020_MES_373015_2
CWE-ND/40/2020-21
Open Tender
Miscellaneous Works
Item Rate
335 days
Delhi Cantt
Please refer tender document
9 documents required · 9 mandatory
₹500
GE New Delhi
₹55,600
Yes
21 Dec 2020
22 Oct 2020
14 Nov 2020
22 Oct 2020
12 Nov 2020
29 Oct 2020
Amount
Manning & operation of central AC plant 3x90 TR capacity complete in two shifts per day as mentioned below :- Rates required to be quoted for execution under Srl item No 1.011 to 1.036 here in after :-
Refg Mechanic (Skilled) wages per person per day for Ist Shift- 0700 hrs to 1500 hrs
Employer's contribution towards EPF as mentioned in the tender documents.
Contribution towards ESIC as mentioned in the tender documents.
Contribution towards Bonus as mentioned in the tender documents.
Over head & profit on srl No 1.011 to 1.013 here-in-before
Labour welfare cess as mentioned in tender document.
Refg Mechanic (Skilled) wages per person per day for 2nd Shift- 1500 hrs to 2300 hrs
Employer's contribution towards EPF as mentioned in the tender documents.
Contribution towards ESIC as mentioned in the tender documents.
Contribution towards Bonus as mentioned in the tender documents.
Over head & profit on srl No 1.021 to 1.024 here-in-before
Labour welfare cess as mentioned in tender document.
Refg Mechanic (Skilled) wages per person per day for Special Shift- 1500 hrs to 1900 hrs
Employer's contribution towards EPF as mentioned in the tender documents.
Contribution towards ESIC as mentioned in the tender documents.
Contribution towards Bonus as mentioned in the tender documents.
Over head & profit on srl No 1.031 to 1.034 here-in-before
Labour welfare cess as mentioned in tender document.
Notes for item No. 1.00 to 1.36 :- (a) AC plant installed at NDC comprising of following equipments :- (i) 03 Nos- screw type compressor and chillers each of 90 TR capacity TRANE make model No ERTWA-211 having semi hermetic sealed compressor, shell and tube type condenser with microprocessor. (ii) 03 Nos-Condenser pumps 7.5KW/10HP capacity. (iii) 03 Nos - Chilled water pump 7.5 KW/10HP capacity. (iv) 01 No-FRP cooling tower with 5 HP fan motor. (v) 03 No- AHU of 7500 cfm, 8600cfm & 8800 cfm capacity with chilled and hot water coil, blower fan and motor, humidification package and the panel etc. (vi) 01 No -Hot water generator 285 KW capacity with its control panel. (vii) 01 Lot- Condenser water pipe line of size 150 mm to 50 mm dia including butterfly valves, NRV, Y strainer etc. (viii) 01 Lot- Chilled/hot water pipe line of size 150 mm to 50 mm dia including butterfly valves gate valves 3 way diverting valves and balancing valves. (ix) 01 No - Control desk for controlling 3 hrs AHU's installed at dinning hall, lecture hall, library and including cabling upto AHU's and equipment. (x) Main panel for operation of chillers condenser chilled water pumps & cooling lower incoming ACB panel 400 amps including its cabling upto equipment. (xi) 01 No- Make up water tank 500 ltrs capacity with connected pipe line for chilled/hot circuit piping.
Notes for item No. 1.00 to 1.36 (contd..) :- (b) Special shift shall be arranged on specific days instead of 2nd shift on requirement basis an intimation to this effect shall be intimated to the contractor well in advance for AC plant installed at NDC . (c) The contractor shall quote the rates for deputing the manpower and reliever arrangement as per existing labour rules. (d) In case any breakdown, the additional manpower if required will be arranged by the contractor. The cost will be deemed to be included in the quoted rates. (e) The contractor shall carryout daily routine checking of the complete system and rectify the minor/major defects noticed immediately cleanining of fine air filter once in two week and making a maintenance register to above maintenance and filler cleaned system one separate register to be maintained as complaint register received from NDC and taking signature from users after rectifying the defects if any, the contractor will arrange to clean all the grills/ducts on regular basis with vacuum cleaner & other. (f) The contractor will maintain a daily temp record book of the each AHU area room and daily signed by contractor and engineer-in-charge.
Comprehensive and preventive maintenance of equipment as spelt out in Srl No. 1.4 here-in-before including replacement of all worn out/defective parts as and when required/detected i.e. Bearing shafts impeller. Cables fins of CT, HW generator parts. Heating coils switches fuses indicating lamp, valve etc including T&P required for repair and transportation if any part required to take to workshop for repair. Note for item No 2.00 ;-Materials required to be replaced shall be measured and paid for separately under relevant 'supply only' item of BOQ . Balance items required for rectification of faults/defects if any shall be inclusive of rates quoted and shall also include fixing/filling/laying charges of items supplied in BOQ.
M&L for rewinding only of electric pump motor 3 phase 415 volt 7.5 KW /10HP with existing size of winding wire with super enamelled copper wire complete all as specified & directed .
All as per item No 3.00 here-in-before but of AHU 3 phase 415 volt 50 Hz 5 HP complete all as specified and directed .
M&L for painting of plant, pumps, panels, cooling tower, GI pipe line, water line etc complete all as specified and directed .
Supply & installation of cross linked closed cell thermal insulation of 30 mm over chilled water pipes of any size thermal conductivity of insulation would not exceed 0.038 w/mk at 400C. Material is fire retardant & self-extinguishing and certified class 1 certified as per BS 476 part &. It is CFC free. On combustion it would not emit HCN NO+ NO2 and SO2 + H2S gases. Smoke generated would be lighter than air and white in colour so as to allow easy exit passages in case of fire. Thermal insulation would be protected by thermal insulation protective coating of aluminium sheet not less than 0.30 mm thick in short length complete all as specified and directed.
Supply only of compressor oil suitable for 'Trane' make as recommended by trane for screw chiller Model : ERTWA-211.
Supply only pre filters 15 micron capacity of size 56cmx56cmx5cm Make-Athlete/Micron/Puromatic/Spectrum.
Supply only fine filter 5 micron capacity of size 56cmx56cmx5cm Make-Athlete/Micron/Puromatic/Spectrum.
Supply & charging refrigerant gas R-22 complete all as specified and directed .
Supply only water heating element 3 phase (3x6) 18 KW 415 volts for hot water generator confirming to IS marked(as per sample).
Supply only bearing suitable for 7.5KW/10 HP condenser pump Make-SKF/NBC/TATA.
All as per item No 12.00 here-in-before but for 5 HP complete all as specified and directed .
Supply and fix in replacement water pressure gauge 0 to 10.6 kg. complete all as specified and directed . Make-FIEBIG/ H. GURU/ EMERALD/ ANERGY.
Supply and fix in butter fly valve 150 mm complete all as specified and directed . Make-ADVANCE/ AUDCO/LEADER /CASTLE.
Supply & fix in replacement butter fly valve 125 mm complete all as specified and directed . Make-ADVANCE/ AUDCO/LEADER /CASTLE.
Supply & fix in replacement strip heater 2 KW for humidity control system complete all as specified and directed . Make-RAYCOLD/ DASSPASS/HONEYBEE.
Supply & fix in replacement over load relay ML type 9-15 amp Make-L&T/ ABB/ SIEMENS /SCHNEIDER.
Supply & fix in replacement contactor ML 1.5, 3 pole, 440 volts 50 Hz complete all as specified and directed . Make-L&T/ABB/Legrand.
Supply & fix in replacement contactor MNX 25 with 1NO+ 1NC , 3 pole, 440 volts 50 Hz complete all as specified and directed . Make-L&T/ABB/Legrand.
Supply only water tray of FCU made out of GI sheet, 20 gauge with insulation of size 48"x6"x2".
Supply only water tray of FCU unit made out of GI sheet, 20 gauge with insulation of size 39"x6"x2".
Supply only water tray of FCU unit made out of GI sheet, 20 gauge with insulation of size 13"x9'x2" Note :-Fixing/filling/laying shall be catered for under sch 'A' item No 2 No extra fixing/filling charges shall be paid separately.
Supply and fix fan blade assembly complete for cooling tower motor of capacity 7.5 HP including making tin shed for protection of motor complete all as specified and directed.
Supply and fix in replacement MCCB three pole (3 pole) 415 Volts grade 250 amps rating 35 KA rupturing capacity and both thermal and magnetic adjustable type complete all as specified and directed. Make- L&T/ Legrand /CG/C&S/Indoasian.
Supply only LED indicator bulb(red/green )colour of suitable size as directed. L&T/ Havells/CG.
Supply and fix in replacement MS ERW pipe of size 125 mm complete with flange, bend whichever required for fixing complete in all respect as directed by Engr-in-charge including welding work as required for . Make- JINDAL PIPES/ TATA/ BST/ PRAKASH TUBES/ OSWAL.
Supply and fix in replacement of MS pipe of size 100 mm complete with flange, bend whichever required for fixing complete in all respect including welding work as required on site as directed by Engr-in-charge. Make- JINDAL PIPES/ TATA/ BST/ PRAKASH TUBES/ OSWAL.
S&F in repair thermometer of suitable size and capacity to the chiller pipe line complete all as directed. Make-FIEBIG/ H. GURU/ EMERALD/ ANERGY.
S&F in replacement water flow switch of size 25 mm including nipple and socket complete all as specified and directed .
Supply and laying in replacement wall and floor in cable trays cable PVC control cable LT 1100 volt grade with copper conductor of size 1.5 sq. mm, 8 core complete all as specified and directed .
S&F in replacement cooling tower fins suitable for 200 TR capacity vertical counter flow complete all as specified and directed .
S&F in replacement Y-strainer of size 150 mm complete all as directed. Make:- Emerald/ Rapid cool/ Leader
S&F gun metal gate valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed of size 25 mm bore. Make:- Kirloskar/Zoloto/ Leader/ L&T(Audco)
S&F gun metal gate valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed of size 50 mm bore. Make:- Kirloskar/Zoloto/ Leader/ L&T(Audco)
Comprehensive and preventive maintenance of for 03 Nos screw type chilling plant each of 90 TR capacity Model ERTWA-211 having semi hermetic sealed compressor, shell and tube type condenser with micro processor in including material and replacement of all parts pertains to above model chiller, the contractor will ensure that M/S Trane is liable to give per month preventative maintenance visits and also on call on requirement basis as and when required.
NOTE : Descaling with chemical overhauling of condensing pumps & replacement of siphon with gauge of AHU
All the parts pertaining to 3x90 TR chillers model ERTWA-211 Make-Trane should be supplied and replaced by M/S Trane. The cost of parts shall deemed to be included in quoted rates. No extra payment shall be made on this account.
Contractor is to act promptly on call and any complaint shall be attended with in-02 (Two) hours as the area is very sensitive and delay is not acceptable.
The contractor will maintain the temp & humidity as under :- Inside condition Library room, dining hall Other area and lecture room DB Temp 72º F +4º F (22º C + 2º C) 75º F + 4º F(24º C ± 2º C) RH 55% ± 5% 55% ± 5%
Descaling of condensers shall be carried out by contractor through M/s Trane before on set of summer season.
T&P required for comprehensive & preventive maintenance shall be provided by the M/S Trane it self.
Comprehensive & preventive maintenance shall be carried out at site NDC irrespective of distance.
Spectro chemical oil analysis and oil replacement shall be carried out by contractor through M/S Trane in the beginning of the contract and after every year.
In case need arises to the change the compressor as a whole due to any defect M/s Trane is to inform the department well in time to avoid breakdown.
The contractor to ensure the parameters of different component of central AC plant on a checklist at fortnight basis with suitable instrument
(i) Condenser (a) Water temperature IN - 32.2⁰C (b) Water temperature OUT - 36.4⁰C (c) Temperature rise - 4.2⁰C (d) Maximum permissible pressure drop 10m of water head
(ii) Chiller (a) Water temperature IN - 12.2⁰C (b) Water temperature OUT - 6.67⁰C (c) Temperature rise - 5.5⁰C (d) Maximum permissible pressure drop 10m of water head
(iii) Piping (a) Maximum flow velocity 2.5m/s
(iii) AHU (a) Max face velocity across cooling coil - 155 m/min (b) Max outlet air velocity - 610m/min (c) Max velocity across filters- (i) Micro Vee filters - 155m/min (ii) Ducting for air-conditioning Main Duct Branch Duct Max flow velocity 400 m/min 250m/min (iii) Max velocity of air at supply of air diffusers - 150m/min
NOTE : Instruments needed for all type of testing will be supplied by the contractor and rate for the same to be included in the quoted rate.
Labour for checking and attending complaints of ACs, water coolers, Refrigerators etc of any capacity, rectification of minor defects and make the equipment fictional complete all as directed.(any parts required for replacement shall be measured and paid for separately under relevant item of BOQ/Sch 'A' as "Supply only") .
Servicing of Window/split type AC 1.5/2/3 Ton capacity of any make / model by taking out the AC, Cleaning of evaporating coil, condensing coil with water & brush to remove dust including cleaning of filter, greasing oiling of fan motor and checking of electric circuit for smooth functioning of AC (unserviceable spares required to be replaced shall be measured & paid for "Supply only" separately under respective items.
Supply only Running capacitor 36 mfd 230 volt suitable for AC 1.5 Ton. Make : Usha/Epcap/Tesla.
Supply only Running capacitor 45 mfd 230 volt suitable for AC 2 Ton. Make : Usha/Epcap/Tesla.
Supply only Running capacitor combination 50 mfd + 6 mfd 230 Volt for AC 2 Ton. Make : Usha/Epcap/Tesla.
Supply only Running capacitor 80-100 mfd 230 volt. Make : Usha/Epcap/Tesla.
Supply only Running capacitor 4/6 mfd 230 volt Make : Usha/Epcap/Tesla.
Gas filling R-22 in existing Split / window AC for 1.5/2/3 Ton capacity complete all as specified.
Supply only starting relay suitable for 1.5Ton capacity AC Make : Renutrol/Classic/Indfos.
Supply only starting relay suitable for 2 Ton capacity AC Make : Renutrol/Classic/Indfos.
All as per item No 46 but for 3 Ton capacity.
Supply only over load protector suitable for 1.5/2/3 Ton capacity AC Make : Renutrol/Classic/Hitech.
Supply only thermostat switch suitable for 1.5/2/3 Ton capacity AC Make : Pacific/renutrol/Indfos.
Supply only new compressor 1.5 Ton capacity reciprocating type Make : Kirloskar/Carrier/Tecumseh / existing make (other unserviceable spares required to replace with AC compressor shall be measured & paid for separate under respective items).
All as per item No 50.00 here-in-before but 2/3 Ton capacity.
Supply & fixing in repair 'R' type compressor capacity 1.5 Ton Make : Carrier/Kirloskar/Tecumseh ( 'R' type means the compressor repaired/reconditioned by the manufacturer or got repaired from authorised dealer of the manufacturer).
All as per item No 52.00 here-in-before AC 3 Ton capacity.
Supply & fixing in repair wiring kit suitable for 1.5/2/3 Ton capacity AC complete all as specified & directed by Engineer-in-charge.
Supply and fixing in repair air filter synthetic/ nylon as per existing size and shape suitable for 1.5/2/3 Ton capacity window type ACs .
All as per item No 55.00 here-in-before but for 1.5/2/3 Ton capacity for Split type ACs.
Supply and fixing new fan motor 1/4,1/5 HP single/double shaft as per existing model suitable for any make ACs as per requirement.
All as per item No 57.00 here-in-before but for air blower of Split ACs of 1.5/2/3 Ton capacity of make : LG/Career/Volts.
Supply and fixing 1.5 TR capacity window type AC kit including condensing coil, evaporating coil, front grill, blower motor, blower and fan, chasis base plate complete except compressor. Make- Blue star/Voltas/Carrier.
Supply & fixing in repair condenser fan blade made out of aluminium/plastic suitable for 3 Ton capacity window type AC. Make- Blue star/Voltas/Carrier.
All as per item No 60.00 here-in-before but for Split ACs of 1.5/2/3 Ton capacity.
Supply & fixing in repair evaporating air blower made out of aluminium/plastic suitable for 2 Ton capacity for window type AC all as directed by Engineer-in-charge.
All as per item No 62.00 here-in-before but for air blower of Split ACs of 1.5/2/3 Ton capacity.
Supply and Fixing in repair synthetic rubber tube insulation of thickness 9 mm & Internal diameter - 6.0 mm (1/4")for refrigerant copper piping of split AC units including suitable PVC tape . Make Supreme/Gulf-o-flex/Superlon.
All as per item No 64.00 here-in-before but internal dia 9 mm (3/8") -do-
All as per item No 64.00 here-in-before but internal dia13 mm (1/2")-do-
S&F copper tubing heavy duty inner dia 6 mm (1/4") for refrigerant for ACs.
S&F copper tubing heavy duty inner dia 9mm (3/8") for refrigerant for ACs.
S&F copper tubing heavy duty inner dia 13mm (1/2") for refrigerant for ACs.
S&F condensing coil suitable for 2/3 Ton split/window type ACs as per existing size/shape.
Supply and fix brass ball valve of size 20x5/8 mm.
Supply and fix brass ball valve with strainer of size 20x5/8 mm.
NOTE : 1 The contractor should detail minimum one AC mechanic & one helper to attend complaints in NDC areas. 2. The complaint should be attended on same day. 3. If the complaint not attended/not completed on same day recovery will be done as follows. a) for first day Rs 200/- b) For second day Rs 300/- c) For next every day Rs 500/-
S&F Compressor Oil filter size 207 to 212 with existing suitable size for chiller unit of AC Plant
Supply and fix fan belt suitable for air handling unit all as specified.
Servicing of Package type AC 8.5 Ton capacity of any make / model by taking out the AC, Cleaning of evaporating coil, condensing coil with water & brush to remove dust including cleaning of filter, greasing oiling of fan motor and checking of gas leakage in gas pipe line & record the temp in register of library etc complete all as specified.
Supply and fix ductable 8.5 TR scroll expansion valve suitable for 8.5 TR ductable unit complete with connected accessories all as specified.
Servicing & maintenance to 285 KW Hot water unit of 3X90 TR AC plant including replacement 4 Nos of 17 KW cap of heater wherever required, removing the carbon/corrosion, cleaning the carbon brushes including minor spares to make the entire unit serviceable and replace of copper bushes, lugs, Ametre & Volt metre & testing up of proper out put of wattage each heater complete all as directed.
Supply & charging R-410A suitable for 1.5/2/3 ton cap complete all as specified
M&L for 3x90 TR Central AC Plant to check performance/efficiency with thoroughly testing of chiller unit to FCUs and to check air leakage in all AHU ducts and also to record the temperature , RH , WB, DB in entire area lecture hall, Officers Mess, library, AHU , plant and offices complete in all respect all as specified & directed by Engr-in-Charge.
(a) All the parameters given above, record should be submitted by the contractor within first month of the contract. (b) Removal o insulation of chiller unit and flow measurement by ultrasonic flow meter in chiller pipe line and measurement of electrical parameter like voltage Amp etc by power analyser. (c) Reinsulating of removed insulation areas with insulation patches of all chiller units. (d) Submit the actual efficiency by calculating 3 mean value/average for chiller unit of Central AC plant.
M&L for laying in replacement of XLPE PVC sheathed armoured copper cable 16 sqmm 3.5 core complete all as specified and as directed by Engr-in-Charge. Make-Gloster, Havells, polycab
M&L for laying in replacement of copper armoured cable 1 sqmm 6 core complete all as specified and as directed by Engr-in-Charge. Make-Gloster, Havells, polycab
S&F in replacement changeover open execution type along with handle complete capacity 630 A, FN 630 TPN . Make-L&T cat Part SK95521/ Havells
M&L in replacement Single phase preventer with Auto switch. Make- Bentex / Minilec
M&L for fixing in replacement star delta Electronic Timers Type ST 100 [9107] 0-30 secs. Make- L&T cat part No- ST80328OOOO
M&L for supply, installation and testing for Maintenance free Grounding (earthing) system complete buried directly in ground vertically (Earth pit not less than 10 feet below ground level) by making bore hole of 100 mm dia inserting 01 no- 17 mm dia molecular copper bonded high tensile low carbon steel circular earth electrode of 3 mtr length with average copper thickness of 100 microns along with Akaltech Environmental friendly grounding enhancing compound and heavy duty (HDPE) PVC pipe cap all in below the ground level and connected to copper earth strip 25x 3 mm electrode by means of nuts and bolts/ brazing etc including protection pipe of GI 15 mm bore med grade upto 7.5 meter length and connection of earth/neutral lead to main LT panel/ motor and pump. Complete all as specified and directed .
M&L for fixing of Copper Strip 20x3 mm on wall / in floor by brazing of all joints and final connection to end point equipments using GI nut bolts. Complete all as specified and directed by Engr-in-Charge
M&L for opening of pump capacity 10 KW connections all type electrical or mechanical and transportation to workshop replacement of bearing complete all as specified and as directed. Complete all as specified and as directed by Engr-in-Charge
M&L for opening of pump capacity 10 KW connections all type electrical or mechanical and transportation to workshop and replacement of gun metal impeller along with shaft of MS and transporting back to site and erecting motor and pump in alignment along with replacement of coupling complete all as specified and as directed. Complete all as specified and as directed by Engr-in-Charge
M&L for replacement of HRC fuse, DIN type 125 A complete with new one along with connectors complete all as specified and as directed by Engr-in-Charge. Make- L&T SF94230, Schneider, Legrand, havells
M&L for fixing of motorised butterfly in replacement of dia 125 mm along with actuator , pcb complete suitable for single phase supply 220 V doing electric connections along with necessary alteration in existing pipelines, along with necessary welding cum joining work complete all as specified and as directed .Make-Universal Switchgears/ Zoloto
M&L for fixing of motorised butterfly in replacement of dia 65 mm along with actuator , pcb complete suitable for single phase supply 220 V doing electric connections along with necessary alteration in existing pipelines, along with necessary welding cum joining work complete all as specified and as directed . Make-Universal Switchgears/ Zoloto
M&L in replacement contactor 3 P, MN 110 as per site, complete all as specified and directed . Make- L&T/ Schneider/ Havells
M&L in replacement step type thermostat as per existing capacity suitable for hot water generator installed at 3x90 TR AC plant complete all as specified and s directed by engr-in-Charge
Leo Air and Power Solution pvt Ltd.
SNOWY ENGINEERING INC
V S BUILDER
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .