| 1 | L1₹1.8 LAccepted-AOC 12 HAJI MD MOHASIN SQUARE KOL 700016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | L1 | Accepted-AOC L1 BIDDER | |
| 2 | L2₹1.9 L+₹2,200 (1.20%)Rejected-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L2 | Rejected-Finance HIGHER | |
| 3 | L3₹2.2 L+₹31,850 (17.4%)Rejected-Finance 86 TOLLYGUNGE CIRCULAR ROAD KOLKATA WEST BENGAL 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | L3 | Rejected-Finance HIGHER |
Tender Value
Refer Docs
EMD Value
₹4,000
Closing Date
5 Sept 2022, 3:00 pmClosed
EE I CKHED
P 12 C I T Road 1st floor Kolkata 700014
Supply Installation Testing and commissioning of Air Conditioning Arrangement for CBNAAT lab at 3rd Floor of Academic Building Department of Microbiology of Calcutta National Medical College Kolkata
2022_WBPWD_394527_1
WBPWD/EE-I/CKHED/NIT-12/22-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
NMCH
AS PER NIT
4 documents required · 4 mandatory
₹4,000
P 12 C I T Road 1st floor Kolkata 700014
2 Dec 2022
10 Aug 2022
7 Sept 2022
10 Aug 2022
5 Sept 2022
18 Aug 2022
18 Aug 2022
Amount
Supply 2TR capacity concealed type Split Air Conditioner of rated cooling capacity of 24000 BTU/hr. with 1 Nos. rotary compressor, refrigerant R-410A, 1 nos. IDU of rated power supply-230V-1ph-50Hz. , 1no. ODU of rated power supply-230V-1ph-50Hz. Air-flow/per IDU:- 650CFM. ( Make: Hitachi//Diakin/Ogeneral)
Installation, testing and Commissioning Charges incl. refrigerant R-410A for 2 TR concealed type Split Air Conditioner
Copper Refrigeration pipe line for liquid and suction line with fittings, elbows, bends, supports & brackets (Make-Ryoku/Totaline/Jobu)
a) Liquid Line (1/4" OD with 0.6 mm thick)
b) Suction Line (5/8" OD with 0.7mm thick)
Supply & Fixing Pipe Insulation in liquid & suction line with 9mm nitrile rubber tube (Accoflex)
a) Liquid Line (1/4" OD with 0.6 mm thick)
b) Suction Line (5/8" OD with 0.7mm thick)
Supply & Fixing of retadrant nonporus double layer Flexible Connection ( CANVAS ) between each Indoor Unit & Duct and for concealed split AC as per Direction of E.I.C .
4 CORE X 2.5 Sq mm Armoured Cable for ODU to IDU of 8.5 Tr Ductable Split Unit as per Direction of E.I.C. (Make: Gloster / Havells/ Ploycab/ Finolex)
Supplying, fabrication & fixing M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) for making platform for installation of outdoor unit (2 Nos 2.0TR) Concealed split AC incl. drilling 4 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 50 mm x50mm x 6 mm in each platform. Area of the platform is 3.5Mtr. x 1.2Mtr. or as per Machine configuration & load with adequate service access as per direction of EIC . Diagonal 2 nos Supporting (One Side in Wall and other side should be welded in platform of 50X50X6 angle Should be done Outdoor Size:792 x 600 x 299 :W*D*H. As the platform fixed in 3rd Floor ,So safety barricade of should be constructed by 30X30X5 angle. Platform should fixed in out side of 3rd Floor.Structure should be painted by red oxide and enamel paint.
Necessary Cutting of MS iron Grill of Window and making necessary arrangement for going to the platroom from room by welding and necessary cutting of grill and fixing hinged and arrangement for lock and key function and supply of 7 lever lock with 3 nos key.
Supply and fixing of 2 nos MS ladder of height of 4 feet (consist of 4ft length of 2 nos 40 X 40 X6 angle) and width of 1 ft for climbing up/down to the platform.Structure should be painted by red oxide and enamel paint.
Supply and fixing of horizonal support for Indoor unit by MS Angle of Size of 50X50X6 mm and length of 3.5 ft (2 nos for each IDU) .One side of angle grouted in wall.Angle should be painted by red oxide and enamel paint.
Supply and fixing of Al powder coated continuous Grill (Make- Premier) (Extra 2 Nos Grill Fixing in exiting Ac of Serology and virology).
Supply & laying HDPE Drain Pipe: 40mm dia by necessary fixing arrangement like clamp and MS saddle .From 3rd Floor to Ground Floor . Another pipeline should be fixed from 4th Floor to ground floor for exiting AC of 4th Floor .
Charges for scaffolding arrangement incl. lifting for outdoor & indoor units
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
SKY DECORATIONS PRIVATE LIMITED
Lyric International
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .