EXECUTIVE ENGINEER (EM) WS SOUTH-I
GREATER KAILASH, PART-I, NEW DELHI
Replacement of old LT panel board by cubical panel board fan dewatering and vacuum pump set ( A- Pump House) at Deer Park BPS
2021_DJB_201387_3
NITNo.18/EE(EM)WS S-I/(20-21)
Open Tender
Electrical Work/ Equipment
Works
30 days
EXECUTIVE ENGINEER (EM) WS SOUTH-I
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Delhi Jal Board
Exempted
19 Mar 2021
11 Mar 2021
16 Mar 2021
11 Mar 2021
16 Mar 2021
11 Mar 2021
Dismantling of old panel structure including removing of cable etc & shifting the same from site in store.
LT Distribution panel sheet steel enclosure made out of 2mm CRCA sheet totally enclosed, powder coated free standing, floor mounted type, dust& vermin proof, outward opening, lockable doors having hidden hinges and a bolted back cover both using non-deteriorating neoprene rubber gaskets to provide IP protection .The each part of the fabricated panel will be strictly subjected to seven tank treatment. The various components, assemblies and sub equipments of the panel will be as per standard given in relevant IS. The bus bar of the panel will be shaped out of high conductivity, electrolytic conductor and shall be liberal sized in aluminum. The control wiring of the panel will be done with PVC flexible copper wires of 1.5mm cross section. Each wire will be terminating with a ferule crimped to the wire, size 1200MMx1000x400mm. Having following components of approved make.
MCCB 415V, FP 3phase 50Hz,100Amp with handle & Spreader - Make L&T/Siemens
MCCB 415V, TP 3phase 50Hz,25Amp - Make L&T
MCB Single pole 6-32Amp. Make L&T/Havells
MCB Triple pole 32Amp. Make L&T/Havells
Power capacitors 415V unit of 7Kvar Make: Epcos
Over load relay 4.5-9 AmpMake: L&T/siemens
Digial Amp. Meter Make AE/L&T
Digital Volt Meter Make AE/L&T
Motor protection Relay Make: L&T/Siemens
Power contactor 220V 3phase18Amp. Make L&T/siemens
Indicating lights LED type RYB & On/OFF Make : L&T /Havells/SG/BCH
Push Button ON/OFF Make: FTC/SG/BCH
Current Transformer100/5 Make: Saviour/AE /Advance
Current Transformer30/5 Make: Saviour/AE /Advance
Earthing of the complete panel with GI strip & hard ware as required
Fitting of the above components in panel enclosure with terminal blocks, channels, ferrules, thimble, support insulator on bus bar, required hard wares complete in all respect.
Loading ,unloading by heavy labor and cartage up to site
Installation of the panel at site, connection of bus bars ,links, bends, re-dressing of existing cable at site ,termination of cable both incoming & out going side through cable gland & thimble.
Testing & commissioning of panel & allied accessories as per required parameters with relevant IS .testing of the panel prior to switching on as follow Continuity and earth testing, Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth. Testing on load with engineer in charge.
Goodwill Enterprises
Premier Engineering Company
arun engineers and contractors
paramount systems
MITTAL TRADING COMPANY
HYDROCON ENGINEERS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .