Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.5 LAccepted-AOC GANDHI PARK ROAD TINSUKIA ASSAM PIN 786125 | TINSUKIA | ASSAM | 786125 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹39.2 L+₹1.3 L (3.31%)Rejected-Finance | L2 | Rejected-Finance Higher bid value | |
| 3 | L3₹39.3 L+₹1.4 L (3.64%)Rejected-Finance | L3 | Rejected-Finance Higher bid value | |
| 4 | L4₹39.5 L+₹1.5 L (4.01%)Rejected-Finance | L4 | Rejected-Finance Higher bid value | |
| 5 | L5₹40.0 L+₹2.1 L (5.53%)Rejected-Finance | L5 | Rejected-Finance Higher bid value |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
3 Oct 2022, 6:00 pmClosed
GE DINJAN
GE DINJAN, PANITOLA (PO), DIBRUGARH (DIST), ASSAM
SPECIAL REPAIR AND REPLACEMENT OF LT DISTRIBUTION PANELS AND PROVN OF HIGH MAST LIGHT AND CERTAIN MINOR WORKS AT OUTPOCKETS UNDER GE DINJAN
2022_MES_551643_1
C/8472/E8
Open Tender
Civil Works - Others
Item Rate
180 days
DINJAN MIL STN
AS PER TENDER DOCUMENT
10 documents required · 10 mandatory
₹500
GE DINJAN
₹70,000
Yes
22 Nov 2022
13 Sept 2022
6 Oct 2022
13 Sept 2022
3 Oct 2022
26 Sept 2022
Amount
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m deep for foundation/cable trench, not exceeding 10 Sqm on plan and getting out in soft/loose soil complete all as specified and as directed.
Excavation in trenches not exceeding 1.5m wide and exceeding 1.5m but not exceeding 3m in deep for foundation/cable trench, not exceeding 10 Sqm on plan and getting out in soft/loose soil complete all as specified and as directed.
Returning filling including spreading, levelling and well ramming in layers not exceeding 25cm thick in soil complete all as specified and as directed.
Removal of surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
M&L for sand cushioning (dry) in trenches for protection of UG cables (below, above and around the UG cable laid in trenches) of 23cm spread thick ness and consolidated (punned) upto 18cm thickness, complete all as specified and as directed. Note : For the purpose of payment, punned thick-ness of sand cushioning only shall be measured and paid for.
S&F for sub-class 'B' brick, well burnt, laid breadth-wise along the axis of cable laid in trenches over sand cushion laid for UG Cable protection complete all as specified and as directed.
M&L for hardcore of gauge not exceeding 63 mm of broken bricks, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and as directed.
M&L for plain cement concrete (1:3:6) type C-2 (using 40 mm graded stone aggregate) as in foundation, filling, sub base of floors and mass concrete, etc complete all as specified and as directed.
M&L for cement concrete (1:3:6) type C-1 (using 20 mm graded stone aggregate) as in pole foundation and coping including necessary form work for fair finish surfaces complete all as specified and as directed.
M&L for 150 mm thick, plain cement concrete (1:2:4) type B- 2 (using 40mm graded aggregate) for approach road etc complete all as specified and as directed.
M&L for non-skid coloured ceramic tiles 7 to 8 mm thick (square/ rectangular) area of each tile exceeding 0.11 Sqm but not exceeding 0.18 Sqm, in floors etc. set and jointed in neat cement slurry and pointed in white or coloured cement to match over 15 mm thick screed bed or bedding layer of cement mortar(1:6) for laying floor finishes complete all as specified and as directed.
M&L for brick work with sub class 'B' bricks, straight or curved on plan exceeding 6 m mean radius, built in cement mortar (1:6) using old size bricks as in manholes, etc complete all as specified and as directed.
M&L for preparing newly plastered surfaces of walls, etc and applying three coats of white wash complete all as specified and as directed.
Supply & installation testing and commissioning of symmetric type Galvanized steel high mast lighting system of 16 meter in length in two section, 3 mm & 4 mm section thickness, top dia 150 mm, bottom dia 360 mm, with AISI 3161 steel wire rope 7/19, 6 mm dia system 2 for wich and 3 for lantern carriage, including LED flood light 08 Nos 350 Watts, timer pannel, complete all as specified and as directed including following :- (a) Sustain upto wind speed of 180 Kmph (b) Non Flame Proof integral Motor. (c) Movable lantern carriage. (d) Double drum Winch. (e) 6 mm 316 Grade S S Hoisting Ropes of 7/19 construction. (f) Trailing Cable –1 per mast (5 Core 2.5 Sq mm) (g) Lightning Finial , Anchor Plate & Template. (h) LED Aviation light. Model: GLN 703 (i) 350W LED Flood light 8nos Model: CFS-501-350-57-60D-SL-GL-NGG (j) Accessories like Plug and Socket, GI Nut bolt with double washer,wiring cable for fixture, flexible conduit, copper lug, PVC tape, Cable tie etc (k) Foundation Bolt & Nuts T & P for fixing with its allied accessories as per OEM. System is suitable for loading 08 nos 350 w LED lights (l) Installation, Testing & Commissioning, Casting of foundation for High Mast & Panel @10T/sqm soil bearing as per OEM. (m) Earthing for High Mast & Panel, Power Supply up to the Panel & Cable laying, Providing Power Cable from High Mast to Panel. Note: Installation should be complete in presence of OEM Rep Make & Model HM-16A-LM-ACC of Crompton or equivalent in Phillips or Bajaj
M&L for 40 mm dia steel tubes (light grade) galvanised with fittings laid in trenches / wall for protection of underground cable when crossing the road /fixing on wall complete all as specified and directed.
S&F for MCCB, AC, 415 Volts, 63 Amps, breaking capacity 16 KA, 4 Pole, with fixed thermal & fixed magnetic setting, complete fixed with LT panel board complete all as specified and as directed. Make : Havells/Legrand/L&T/ABB.
S&F for bus bar panel out door type for cable of size 25 sqmm 4 core with option of MCCB 25 Amps capacity protection of suitable size complete all as specified and as directed.
Taking out/down old/unserviceable under ground LT cables of any size and connections including pipes etc from trenches/walls/poles of any cross sectional area and keeping serviceable materials in safe custody for reuse and unserviceable materials removing from site complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items of this schedule. (2) Excvation and earth work shall be measured and paid seperately.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated, armoured, 2 core, nominal cross sectional area of main conductor 16 Sqmm, stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items of this schedule. (2) Excvation and earth work shall be measured and paid seperately.
Supply, laying, jointing, commissioning and testing cross-linked polyethylene (XLPE) insulated, armoured cable for working voltage of 1100 Volts, PVC insulated, armoured, 3 core with reduced neutral conductor 3.5 core, nominal cross sectional area of main conductor 50 Sqmm, stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI Pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items of this schedule. (2) Excvation and earth work shall be measured and paid seperately.
Supply, laying, jointing, commissioning and testing cross-linked polyethylene (XLPE) insulated, armoured cable for working voltage of 1100 Volts, PVC insulated, armoured, 3 core with reduced neutral conductor (3 1/2 Core), nominal cross sectional area of main conductor 70 Sqmm, stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI Pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items of this schedule. (2) Excvation and earth work shall be measured and paid seperately.
Supply, laying, jointing, commissioning and testing cross-linked polyethylene (XLPE) insulated, armoured cable for working voltage of 1100 Volts, PVC insulated, armoured, 3 core with reduced neutral conductor (3 1/2 Core), nominal cross sectional area of main conductor 95 Sqmm, stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI Pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items of this schedule. (2) Excvation and earth work shall be measured and paid seperately.
Supply, laying, jointing, commissioning and testing cross-linked polyethylene (XLPE) insulated, armoured cable for working voltage of 1100 Volts, PVC insulated, armoured, 3 core with reduced neutral conductor (3 1/2 Core), nominal cross sectional area of main conductor 185 Sqmm, stranded aluminium conductor, ISI marked as per IS-7098 (Part-I) 1988 including cable glands, lugs etc to suit the cable size and to be laid in trenches, under floors, through GI Pipe complete all as specified and as directed. Note : (1) Pipes shall be measured and paid separately under relevant items of this schedule. (2) Excvation and earth work shall be measured and paid seperately.
M&L for earthing complete with GI earth plate electrode of size 600x600x6 mm thick buried directly in ground with earth pit not less than 2.25 meter deep below ground level with top edge of plate not less than 1.5 meter below normal ground level connected to GI earth strip of size 32 x 6 mm earth lead by means of nuts, bolts, check nuts, washers of galvanised iron as steel, protected by galvanized iron pipe 40mm bore (Medium grade) all as directed including cement concrete (1:3:6) type C-1 earth pit with precast RCC (1:1.5:3) type A-1 cover slab of size 42x42x10cm thick, reinforced with 8mm dia TMT bars @ 15 cm c/c both ways with 10mm dia mild steel round bar of 30 cm long, bent to shape as lifting handle, funnel, wire mesh, 20 mm bore galvanized iron pipe (medium grade) for watering, charcoal or coke and salt in alternate layers with necessary earth work in soft/loose soil complete all as shown in electrical plate No 3 of SSR Part I including testing on completion all complete as specified and directed after taking down old earthing.( GI strip upto 7.5m including testing consider in this item).
M&L for earthing complete with GI earth plate electrode 600mm x 600mm x 6 mm thick burried directly in ground vertically to a depth not less than 2.25m below ground level with the top edge of earth plate at depth not less than 1.5m below ground level connected to galvanised earth lead wire 4.0 mm dia by means of bolts, nuts, check nuts and washers protected by 15mm bore light grade GI pipe, funnel with 20mm bore GI medium grade pipe for watering, wire mesh, including concrete pit in PCC (1:3:6) type C-1, pre-cast RCC 1:2:4 type B-1 cover slab of size 350x350x50mm reinforced with 8mm dia TMT steel bars @ 15cm centre to centre in both direction and 10mm dia MS handle of suitable size, charcoal or coke and salt in alternative layers, necessary earth work in soft/loose soil all as shown in Electrical Plate No 3 of MES Schedule Part I and testing the base in which pit cover rests made up of MS angle iron (Frame) complete as specified and as directed.
M&L in repairs MCCBs of any descriptions from LT panel board after carefully disconnecting the electric connection and S&F new MCCB, 4 pole, AC, 415 V with fixed thermal & fixed magnetic setting, 400 Amps of breaking capacity 25 KA complete all as specified and as directed. Make : Cat No TABBASIX400C4P of HPL or Havells/Legrand/HPL/L&T.
M&L in repairs MCCBs of any descriptions from LT panel board after carefully disconnecting the electric connection and S&F new MCCB, 4 pole, AC, 415 V with fixed thermal & fixed magnetic setting, 250 Amps of breaking capacity 25 KA complete all as specified and as directed. Make : Cat No TABBASIX2250C4P of HPL or Havells/Legrand/HPL/L&T.
M&L in repairs MCCBs of any descriptions from LT panel board after carefully disconnecting the electric connection and S&F new MCCB, 4 pole, AC, 415 V with fixed thermal & fixed magnetic setting, 200 Amps of breaking capacity 25 KA complete all as specified and as directed. Make : Cat No TABBASIX2200C4P of HPL or Havells/Legrand/HPL/L&T.
M&L in repairs MCCBs of any descriptions from LT panel board after carefully disconnecting the electric connection and S&F new MCCB, 4 pole, AC, 415 V with fixed thermal & fixed magnetic setting, 160 Amps of breaking capacity 36 KA complete all as specified and as directed. Make : Cat No TABBASIX1160C4P of HPL or Havells/Legrand/HPL/L&T.
M&L in repairs MCCBs of any descriptions from LT panel board after carefully disconnecting the electric connection and S&F new MCCB, 4 pole, AC, 415 V with fixed thermal & fixed magnetic setting, 125 Amps of breaking capacity 25 KA complete all as specified and as directed. Make : Cat No TABBASIX1125C4P of HPL or Havells/Legrand/HPL/L&T.
M&L in repairs MCCBs of any descriptions from LT panel board after carefully disconnecting the electric connection and S&F new MCCB, 4 pole, AC, 415 V with fixed thermal & fixed magnetic setting, 100 Amps of breaking capacity 16 KA complete all as specified and as directed. Make : Cat No TABBASIX1100C4P of HPL or Havells/Legrand/HPL/L&T.
M&L in repairs MCCBs of any descriptions from LT panel board after carefully disconnecting the electric connection and S&F new MCCB, 4 pole, AC, 415 V with fixed thermal & fixed magnetic setting, 63 Amps of breaking capacity 16 KA complete all as specified and as directed. Make : Cat No TABBASIX1063C4P of HPL or Havells/Legrand/HPL/L&T.
S&F for pole mounted digital timer panel inbuilt short circuit protection with contactor of 32 Amp TP and MCB 40 Amp TPN suitable for three phase including clamping arrangement and commissioning complete all as specified and as directed.
S&F for pole mounted digital timer panel inbuilt short circuit protection with contactor of 32 Amp TP and MCB 40 Amp SPN suitable for single phase including clamping arrangement and commissioning complete all as specified and as directed.
M&L for danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for LT, 20 x 15 cm size complete all as specified and as directed.
M&L for cleaning of electrical panel from inside and out side and spray painting only external surfaces of dimension approx 1.8 m x 1.4 m x 0.6 m to 1.0m x 0.9m x 0.6 m without taking down pannel accessories one and apply two coat of synthetic enamel paint over a coat of red oxide primer on steel surfaces complete including preparation of old surfaces of steel surfaces by scrapping, rubbing all as specified and as directed. Note: Panel not give shutdown for external painting bidder provide necessery safety equipment and price deemed to included into unit quoted rate.
M&L for panel reparing by welding/brazing etc making door to opening properly for any existing electrical panal at outpocket area complete all as specified and as directed.
S&F in repair electric panel door lock of same type as per existing one with key complete all as specified and as directed.
S&F in repair of PVC insulated aluminium bus bar into electric panel as per existing size and hole complete all as specified and as directed.
S&F for synthetic rubber insulated mats, (IS 5424) suitable for electrical shock safety for voltage upto 11 kv of sizes 2m x 1m and thickness not less than 12 mm complete all as specified and as directed.
S&F for factory made triple pole and neutral board distribution (DB) double door, in sheet metal enclosure, 4 way, 440 Volt, 200 Amps, with common bus bar at incoming end complete all as specified and as directed.
S&F for MCB, SPN, 6 to 32 Amps, 240 Volts, 'C' Series, breaking capacity 10KA complete all as specified and as directed.
S&F for MCB, single pole, 6 to 32 Amps, 240 Volts, 'C' Series, breaking capacity 10KA complete all as specified and as directed.
S&F for MCB, TPN, 6 to 32 Amps, 240 Volts, 'C' Series, breaking capacity 10KA complete all as specified and as directed.
M&L for sub main wiring with two run of 4 Sqmm (Nominal area) single core cable PVC insulated, multistranded, unsheathed, copper conductor cables (FRLSH), 1100 Volts grade drawn through PVC casing-caping/conduit of suitable size, fixed to wall/ceiling etc including one run of 4 Sqmm (nominal area) single core, PVC insulated, multistranded, unsheathed, copper conductor (FRLSH) as earth wire and duly connected to common earth point complete all as specified and as directed. Note : (a) PVC casing-caping/conduit, two run wiring cables and one run of earth wire will be measured as one length (b) All incoming and outgoing cable shall be connected by using proper lugs & sockets.
M&L for concealed sub main wiring with two run of 2.5 Sqmm (nominal area) single core cable PVC insulated, multistranded, unsheathed, copper conductor cables (FRLSH), 1100 Volts grade drawn through PVC conduit of suitable size, fixed to wall/ceiling etc including one run of 2.5 Sqmm (nominal area) single core, PVC insulated, multistranded, unsheathed, copper conductor (FRLSH) as earth wire and duly connected to common earth point complete all as specified and as directed. Note : (a) PVC casing-caping/conduit, two run wiring cables and one run of earth wire will be measured as one length (b) All incoming and outgoing cable shall be connected by using proper lugs & sockets.
S&F for switch socket combination, 2 in 1, 5/16 Amps, 240 volts, bearing ISI marked flush type complete all as specified and as directed.
M/s GANDHESWAR PHUKAN
NChetia and Sons Trading
M/S AUTOMOTIVE WORLD
M/S K S Enterprise
STANDARD ELECTRIC WINDERS
FREEZCON
M/s. R. K. Trading Company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .