Division 1st Floor Block no.35 Kasumpati Shimla
Construction of State Forensic Science Laboratory Building at Junga Distt Shimla HP(SH Providing Addressable Fire Alarm System at Risk Cost of Ms Yogesh Enterprises Delhi
2022_BSNL_117659_1
01/2022-23/SHIMLA/SHIMLA DIVISION
Open Tender
Electrical Works
Item Rate
20 days
FSL Junga Shimla
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
AO EF CGMT SHIMLA
₹30,752
Yes
7 Jul 2022
31 May 2022
22 Jun 2022
31 May 2022
20 Jun 2022
31 May 2022
Amount
Addressable Fire Alarm System
Supply, installation, testing & commissioning of 2 loop UL Listed/FM approved Addressable Fire alarm control panel shell be networkable & expandable 32 loops. The panel shall have 240AC power supply,automatic battery charger,24V SMF battreies suffcient for 24 hour in standby and 15 minutes in alarm degrade mode opreation.UL Listed 12 Amps inbuilt power supply with 70AH capacity battery charger UL Listed Lead Acid battery charging capacity for second dry power supply including carriage of maerial in all lead and lift.(Make: SIEMENS/ANSUL/NOTIFIRE)NFS 3030+DVC or similliar superior Make)
Supply ,Installation ,Testing & commissioning of UL listedactive Repeater panel withback lit LCD 160 display to aprovide event information and LED display for status indication of Repeater panel including carriage of material. ( Make SIEMENS/ANSUL/NOTIFIREor similliar superior Make)
supply, Installation,Testing & commissioning of UL Listed Intelligent Addressable Multi application multicrteria detector with responsiveness of photoelectric,thremal technology and false alarm resistance along with base. The detector shall have Tri color LED for normal, fault 5 Alarm condition, The detector shall have infrared Light Emitting Diode &photo sensing diode. The detector shall have facilty to mount in different comprehensive environment like Hostile envirpnment,Parking garage, HVAC Ducts, Precious storage, Transformer rooms requried including carriage of matrial.FAPT 851 (SIEMENS/ANSUL/NOTIFIREor similliar superior Make)
supply,Installation. Testing& commissioning of UL Listed Intelligent Analog Addressable ype Rate/Fixed Heat Detector with inbuilt turbo Islater complete with LED,addressing done by the FACP, complete with Mounting Base as requried and approved including carriage of material.(Make SIEMENS/ANSUL/NOTIFIRE)
supply,Installation,testing &comissioning of UL listed Intelligent addressable Manul Call Point-Pull Station polarity insensitive technology complete as per sample approved and specification including carriage of materal.(SIEMENS/ANSUL/NOTIFIRE)
supply, Installation,Testing & commissioning of UL Listed Multi Tone Hooter suitable for alarm siren. It shall meet the audibilty requirement for smoke alarms as approved and specified in UL Listed Single and Multiple Station smoke Alarms including carriage of material. ( SIEMENS/ANSUL/NOTIFIRE or similliar superior Make)
Supply ,Installation ,Testing & commissioning of UL listed addressable Control Cum Moniter Module (Independent Single Input &Single Output) polarity insensitive technology, in complete as per sample and specification approved for AHUs, Hooter,Flow switch,inculding carriage of materialin all lead and lift. Make (SIEMEN/ANSUL/NOTIFIREor similliar superior Make)
Supply,Installation,Testing & commissioning of UL listed Fault Isolaters complete as per sample and secification approved. The fault isolater shall not occupy any address point in thje loop. (Make SIEMENS/ANSUL/Sinteso)
Supply, Insttallation, Testing & Commissioning of 480 W booster amplifire, Battery Voltage -24Vdc (max 10% devation), Frequency response -60Hz to 15 KHz (+1/-3db) Distoration ( at rated out power ar 1 Khz) make Boseh/JBL/Tannoy or similliar superior Make
supply, Installation,Testing & commissioning of UL Listed Celling mounting Speaker suitable for alarm siren. It shall meet the audibilty requirement for smoke alarms as approved and specified in UL Listed Single and Multiple Station smoke Alarms including carriage of material. ( SIEMENS/ANSUL/NOTIFIRE or similliar superior Make)
Supply ,Installation, Testing & commissioning of Celling/wall mounted speaker withoperations from 3to 6 watts as per complete including carriage of material .(AURAL/FGE/SIEMENSor similliar superior Make)
Supply &Fixing of Energy saving display Laser type EXIT sign board Glass type specilly designed for classic decore with excellent quality high efficiency and long life for single/both side display, well ventilated, powder coated having nominal size LED lamp,battery backup 6 hour tobe installed on wall/celling etc.(MAKe FGE/AGNIor similliar superior Make)
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2x1.5. Sq.mm.
4x1.5. Sq. mm.
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
IMPORTANT NOTE :- (1.) The detailed drawing shall be got approved by the Engineer-in-Charge of the work before execution of the work/installation at site.
(2) In case of ambiguity, between schedule and specifications, schedule shall prevail. If there is ambiguity between “schedule and specification” verses IS / BS standards, “schedule and specification” shall prevail.
(3) Quoted Rates shall be inclusive of 100% GST. However, after issue of detailed guidelines / rules, if a portion of GST on Reverse Charge Basis is to be paid by department (BSNL), the same shall be recovered from the bill of the contractor.
R.D. ENGINEER AND CONSULTANT
Galaxy Associates
Modern Agencies
Secom Systems Pvt Ltd.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .