Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.3 LAccepted-Finance | L1 | Accepted-Finance 1st Lowest | |
| 2 | L2₹31.0 L+₹64,320 (2.12%)Accepted-Finance 69 VALLUVAR ROAD ARUMBAKKAM CHENNAI TAMIL NADU 600106 | CHENNAI | TAMIL NADU | 600106 | L2 | Accepted-Finance 2nd Lowest |
Tender Value
₹31.1 L
EMD Value
₹62,102
Closing Date
9 Dec 2022, 10:00 amClosed
EE WSD APWD
EE WSD APWD Port Blair
Up Gradation of Online UPS System dedicated for network equipment, Server and Desktop PC of Section and Data-center of Directorate of Shipping Services Office at Port Blair
2022_APWD_8244_1
207/NIT/WSD/2022-23
Open Tender
Miscellaneous Works
Works
45 days
Port Blair
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹62,102
28 Dec 2022
25 Nov 2022
9 Dec 2022
25 Nov 2022
9 Dec 2022
1 Dec 2022
25 Nov 2022 - 9 Dec 2022
Amount
Supplying, Installation, Testing and Commissioning of 2 X 30 KVA, 3-Phase + Neutal input and pure sine wave Three phase output (415 V AC, 50 Hz) double conversion UPS systems fully microprocessor based connected in parallel redundant load sharing mode, along with MS rack for housing the batteries with PMMA Sheets for protecting the Battery from Earth fault along with interconnection cable with PRS kit. It shall provide Zero transmission time from AC to battery mode and Inverter to bypass mode with complete accessories etc., as required, including interconnections and as per the direction on Engineer In - Charge. (Make : Numeric/Microtek/Emerson or any Global Brand).
The system consists of the following major components i) Solid state static PWM converters utilizing IGBT. ii) Solid state static PWM Inverters utilizing IGBT iii) Converter input, bypass input and system battery breaker/ contactor, inverter out put breaker/ contactor and static bypass switch with primary contactor, converter input and system input fuses etc. iv) Maintenance bypass utilizing wrap around contactor and compatible for Generator. v) The Multiple protections such as overload, short circuit, over temperature, Battery under voltage and over charge. vi). Smart LCD Alpha - Numeric display for real time monitoring. vii). Communication with computer can be realized by RS - 232 with corresponding monitoring software.
Supplying, Installation, Testing and Commissioning of Sealed high rate discharge maintenance free (12V/200AH/32 Nos. X 2) EXIDE/QUANTA Valve Regulated Lead Acid Battery bank (VRLA) /SMF or equivalent for minimum 02 Hours back up time including Inter Connecting Uninyvin Cables.
Supplying, Installation, Testing and Commissioning of 2 X 10 KVA, 3-Phase + Neutal input and pure sine wave single phase output (230 V AC, 50 Hz) double conversion UPS systems fully microprocessor based connected in parallel redundant load sharing mode with inbuilt isolation transformer at inverter side of UPS for providing uninterruptible power supply along with MS rack for housing the batteries with PMMA Sheets for protecting the Battery from Earth fault along with interconnection cable with PRS kit. It shall provide Zero transmission time from AC to battery mode and Inverter to bypass mode with complete accessories etc., as required, including interconnections and as per the direction on Engineer In - Charge. (Make : Numeric/Microtek/Emerson or any Global Brand)
The system consists of the following major components i) Solid state static PWM converters utilizing IGBT. ii) Solid state static PWM Inverters utilizing IGBT iii) Converter input, bypass input and system battery breaker/ contactor, inverter out put breaker/ contactor and static bypass switch with primary contactor, converter input and system input fuses etc. iv) Maintenance bypass utilizing wrap around contactor and compatible for Generator. v) The Multiple protections such as overload, short circuit, over temperature, Battery under voltage and over charge. vi). Smart LCD Alpha - Numeric display for real time monitoring. vii). Communication with computer can be realized by RS - 232 with corresponding monitoring software.
Supplying, Installation, Testing and Commissioning of Sealed high rate discharge maintenance free (12V/100AH/24Nos. X 2) EXIDE/QUANTA Valve Regulated Lead Acid Battery bank (VRLA) /SMF or equivalent for minimum 02 Hours back up time including Inter Connecting Uninyvin Cables.
Supplying of 95 Sq.mm, 3.5 - Core of PVC insulated and PVC Sheathed/ XLPE Armoured 1.1 KV grade Aluminium conductor cable conforming to IS:7908 (Part - I ) 1988.
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
a). Above 35 sq. mm and upto 95 sq. mm (clamped with 25 X 3 mm MS flat clamp)
Supplying and fixing 8 way (4 + 24), Double door, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of single poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.
MRV INFOTECH INDIA PVT LTD
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .