| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹2.6 L
EMD Value
₹5,130
Closing Date
17 Feb 2025, 11:00 amClosed
Executive Engineer MHD SKIMS/JVC
SKIMS Soura
Repairs to false ceiling of new Emergency OT and providing of duct and allied works for make shift arrangement of HVAC in Main Hospital Skims ,Soura Srinagar
2025_PWDJK_271830_2
MHD/SKIMS/JVC/71 0F 2024 DATED.05.02.2025
Open Tender
Machineries/ Mechanical Engg Items
Item Rate
10 days
SKIMS Soura
Please refer Tender documents.
11 documents required · 11 mandatory
₹500
Executive Engineer MHD SKIMS/JVC
₹5,130
Yes
25 Feb 2025
6 Feb 2025
17 Feb 2025
6 Feb 2025
17 Feb 2025
6 Feb 2025
Amount
Repairs to damaged concealed T grid of false ceiling in new Emergency OT by way of providing and fitting of new T grid ceiling channels of galvanised Steel/SS of 0.3 mm thickness . Job also includes providing, fitting of fastners, fixtures, hooks, nut and bolt along with grouting of fasteners, G.I wire for tying of Grid etc.
Supply, installation, testing and commissioning of 24 swg sheet metal ducts fabricated from galvanised steel sheets (GI) complete with all accessories, straight & smooth finished G.I flanges with air tight joints for connecting of the ducts, all 90º elbow must be provided with double radius turning vanes, all rectangular duct taps should be made with shoe (45º) fittings i/c supports for hanging of ducts.The job also includes supply and fixing of external thermal insulation of 19 mm thick nitrile rubber on the duct before applying thin film of adhesive on the back of the insulating material sheet and then on the metal surface and sealing of joints with 75 mm wide aluminium tape and piercing of walls through which supply/return duct to be laid.
Shifting Cleaning, Testing of existing Old Air Handling Unit by using skilled manpower, tools and tackles, chain pulley block & safety items etc. The old AHU shall be shifted to the place identified by site Engineer. The job includes cleaning of surfaces and places by using shifting trolley.
Providing and fitting of Air fine filter of size 610x610x150 mm with aluminum die cast powder coated heavy duty hinges & nylon handles to be mounted directly on face of the AHU (return air side).
"Providing, welding, Chamfering and fitting of M.S. “C” class conforming to IS -1239 Pipe 40mm Dia. Confirming IS specifications of the following size with allied jobs.The job includes cutting, welding ,fins hing, cleaning, providing of gaskets,nuts,bolts, cleaning of site ,excavation ,back filling,dumoing of waste eath /matrerial etc
Providing and fitting butterfly valve (cast iron body) 40 mm dia. The job includes, cleaning of ends ,cutting, welding,threading , finishing etc. Product description: Cast Iron IS1865,Wafer type (Lever Operated) Pressure/class /Rating :PN-16 Type of seat:Nitrile/EPDM lining Type of disc:SS
Providing and fitting fitting of M.S. Bend class “C” ERW 40 mm size: The job also includes cutting, fabricating, welding , finsihing and of necessary items including gaskets,nuts,bolts,threads etc
Providing, welding and fitting of M.S. Slipon flanges 40 mm size of suitable thickness of reputed make including nuts, bolts, gaskets and other jobs as per requirements at site of work: ANSI-16.5(SORF) 150#
Providing and fitting of Digital Temperature Controller of assorted range with Sensor Probe along with 3 core copper sensor Control Cable 1metre for digital controller. Control Action: TP/ On-Off (Factory Set) Power Supply: 230V AC ±10%, 50 Hz Output: 1 Relay 1 c/o, 5A. 230V AC
Brazing of Heating coils of Air Handling Units of Central heating system to arrest water leakage including hydraulic test. Job includes disconnecting input/output connection and extracting coil and refitting back after arresting leakage etc. The job includes joining of 2 or more metals by way of filling of filler. The job includes cleaning the surfaces and testing the finished product for any leakages. The tools and tackles and man-power required for the job and any other consumable (Nut bolts, gaskets etc ) shall be provided by the contractor.
Brazing of Heating coils of Air Handling Units of Central heating system to arrest water leakage including hydraulic test. Job includes disconnecting input/output connection and extracting coil and refitting back after arresting leakage etc. The job includes joining of 2 or more metals by way of filling of filler. The job includes cleaning the surfaces and testing the finished product for any leakages. The tools and tackles and man-power required for the job and any other consumable (Nut bolts, gaskets etc ) shall be provided by the contractor.
Providing and fixing of PVC insulated 4 sq mm Three core multistranded / unsheathed heat resistant / fire resistant Copper Conductors.
Providing and fitting of negative sequence voltage sensing single phasing preventer to the starters suitable from 3 h.p. to 20 h.p. motor, L&T/Minilac make , including providing and fitting of auxiliary/control wiring, nuts, bolts, screws, etc. alongwith testing and successful commissioning and also dismounting of existing burnt out single phasing preventer.
Providing , fixing and commisioning of 30 amp 4 pole MCB. The job includes, making of all incoming and outgoing connection, providing thimbles of respective amperage
M/S KHAN ELECTRICALS and MECHANICALS WORKS (BID ID -2332349)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .