Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 CrAdmitted-Finance | ₹1.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.2 Cr+₹6.5 L (5.51%)Admitted-Finance ACHNAMBAL ZAFFRON COLONY PANTHACHOWK SRINAGAR J K INDIA 191101 | SRINAGAR | JAMMU AND KASHMIR | 191101 | ₹1.2 Cr+₹6.5 L (5.51%) | L2 | Admitted-Finance |
| 3 | L3₹1.3 Cr+₹16.4 L (13.9%)Admitted-Finance I 910 JAHANGIR PURI NEAR BY ANAND MAYA HOSPITAL NORTH WEST DELHI DELHI 110033 UDYAM DL 06 0040830 | NORTH DELHI | DELHI | 110033 | ₹1.3 Cr+₹16.4 L (13.9%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | M/s NORTHERN ELECTRICALS L1 | Ess Bee Electricals L2 | SATISH & CO L3 |
|---|---|---|---|---|---|---|
| 1.00 | Loading of 33/11kV, 10MVA Power Transformer, Oil Filled with OLTC , LV box and all accessories including HT and LT Terminal connections on to the Vehicle/Platform at Divisional Stores, carriage & unloading at the site of installation (Panthachowk) & subsequent Loading on to the Transformer Bed | 1 | Job | 65,000 ₹65,000 | 55,000 ₹55,000 | 50,000 ₹50,000 Lowest |
| 2.00 | Installation, Testing & Commissioning of 33/11kV, 10MVA, ONAN, Copper wound, Out-door Type, Conventional Power Transformer, Oil Filled with OLTC , LV box and all accessories including HT and LT Terminal connections (complete job) | 1 | Job | 1,05,000 ₹1,05,000 | 55,000 ₹55,000 Lowest | 1,50,000 ₹1,50,000 |
| 3.00 | Supply, Laying, Testing & Commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards | 240 | Mtr | 1,500 ₹3,60,000 | 1,250 ₹3,00,000 | 600 ₹1,44,000 Lowest |
| 4.00 | Supply, Laying, Testing & Commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards | 420 | Mtr | 700 ₹2,94,000 | 450 ₹1,89,000 | 350 ₹1,47,000 Lowest |
| 5.00 | Supply, Laying, Testing & Commissioning of 4 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards | 300 | Mtr | 450 ₹1,35,000 | 310 ₹93,000 | 250 ₹75,000 Lowest |
| 6.00 | Supply, Laying, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards | 360 | Mtr | 310 ₹1,11,600 | 170 ₹61,200 Lowest | 180 ₹64,800 |
| 7.00 | Providing and fixing of Lugs, Ferrules etc. (complete job) | 2 | Item | 6,500 ₹13,000 | 6,000 ₹12,000 | 5,000 ₹10,000 Lowest |
| 8.00 | Supply, Installation, Testing & Commissioning of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) with clamps as per relevant Standards | 2 | No | 4,80,000 ₹9,60,000 | 4,10,000 ₹8,20,000 | 3,25,000 ₹6,50,000 Lowest |
| 9.00 | Supply, Installation, Testing & Commissioning of 33kV C&R Panel along with O/C, E/F relays, mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps with RS-485 port, DLMS Compliant with RS-485 port | 2 | No | 3,90,000 ₹7,80,000 | 2,85,000 ₹5,70,000 | 2,75,000 ₹5,50,000 Lowest |
| 10.00 | Supply, Installation, Testing & Commissioning of 33 kV Isolator with Earthing Blade (36kV, 1250A, Outdoor, 3 poles, 25 kA) with clamps as per relevant Standards | 2 | Set | 80,000 ₹1,60,000 | 67,000 ₹1,34,000 Lowest | 69,000 ₹1,38,000 |
Tender Value
Refer Docs
EMD Value
₹3 L
Closing Date
27 Dec 2023, 3:00 pmClosed
Executive Engineer STD-1 Bemina Srinagar
PDD Complex Bemina Srinagar 190018
ITC of 10 MVA Power Transformer and SITC of 33 kV Electrical Equipment viz 11kV panels, 11kV outgoing pole structure, auxiliary transformer and other allied works For Construction of 33/11KV, 10 MVA Receiving Station for e-Charging Station
2023_PDD_237187_1
e-NIT No. STD I / 19 of 2023-24 dated 16.11.2023
Open Tender
Electrical Works
Item Rate
90 days
Panthachowk
Please refer Tender documents.
5 documents required · 5 mandatory
₹3,000
Executive Engineer STD-1 Bemina Srinagar
₹3 L
18 Jan 2024
17 Nov 2023
29 Dec 2023
20 Nov 2023
27 Dec 2023
22 Nov 2023
20 Nov 2023 - 21 Nov 2023
Amount
Loading of 33/11kV, 10MVA Power Transformer, Oil Filled with OLTC , LV box and all accessories including HT and LT Terminal connections on to the Vehicle/Platform at Divisional Stores, carriage & unloading at the site of installation (Panthachowk) & subsequent Loading on to the Transformer Bed
Installation, Testing & Commissioning of 33/11kV, 10MVA, ONAN, Copper wound, Out-door Type, Conventional Power Transformer, Oil Filled with OLTC , LV box and all accessories including HT and LT Terminal connections (complete job)
Supply, Laying, Testing & Commissioning of 12 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards
Supply, Laying, Testing & Commissioning of 6 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards
Supply, Laying, Testing & Commissioning of 4 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards
Supply, Laying, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI,FRLS as per relevant Standards
Providing and fixing of Lugs, Ferrules etc. (complete job)
Supply, Installation, Testing & Commissioning of 33 kV Vacuum Circuit Breaker (36 kV, 1250A, 26.2 kA, Outdoor Type) with clamps as per relevant Standards
Supply, Installation, Testing & Commissioning of 33kV C&R Panel along with O/C, E/F relays, mimic diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps with RS-485 port, DLMS Compliant with RS-485 port
Supply, Installation, Testing & Commissioning of 33 kV Isolator with Earthing Blade (36kV, 1250A, Outdoor, 3 poles, 25 kA) with clamps as per relevant Standards
Supply, Installation, Testing & Commissioning of 33 kV Isolator without Earthing Blade (36kV,1250A, Outdoor, 3 poles, 25 kA) with clamps as per relevant Standards
Supply, Installation, Testing & Commissioning of 33 kV Current Transformer (33 kV, 1Φ, Multi Ratio Multi Core, Outdoor) (1 No. per Φ) with clamps as per relevant Standards
Supply, Installation, Testing & Commissioning of 33 kV Voltage Transformer (33 kV/110 V, 1Φ, Multi-Core, Outdoor), (1No. per Φ) with clamps as per relevant Standards
Supply, Installation, Testing & Commissioning of 33 kV Lightening Arrestors (30 kV, 10kA, Station class, ZnO, Polymer) gap less with clamps as per relevant Standards
Supply, Installation, Testing & Commissioning of 33 kV 10KN Polymer Post Insulator 36kV,170kV Impulse, creepage distance 1224m with clamps as per relevant Standards
Supply& Erection of 11Mtr long Steel Tubular Poles ST-410 SP56 complete along with pit excavation and 1/6 th of pole embedded in soil as per relevant REC standards.
Providing and laying of Cement bottoming 1:2:4 mix as per Standards 0.6 cum/pole
Providing and fixing of Earthing Complete of 11 Mtr long Steel Tubular Poles by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip as per relevant REC standards
Providing and painting of 11 mt S.T Poles with single coat of Red Oxide and two coats of Aluminium Paint as per relevant standards
Providing and fixing of G.I Pipe of Dia 150mm, 5.9 mm Thick 3m long with G.I Base Plate 8mm Thick
Providing and fixing of Galvanised Steel Structures
Providing and fixing of Galvanised Nuts & Bolts
Supply, laying, Stringing and binding of 0.2 ACSR Conductor with jumpering at tension points as per relevant standards.
Providing and fixing of T Clamps
Providing and fixing of 11 kV Single Tension Fittings
Supply, Installation, Testing & Commissioning of Polymeric composite Disc Insulator (with fittings) 36KV, Lightening Impulse 170kV Positive and 180kV Negative, creepage distance 900mm,min failing load 70kN
Supply, Installation, Testing & Commissioning of 11 kV VCB Panel Board (12 kV, 1250A, 25 kA, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port for 10MVA (1+4) as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 11kV, Gapless Surge Arrestor,9 KV ,10 KA ,LA with Polymer housing, Stn. Type (4/5/6 Sets) as per relevant REC Standards
Supply, Laying, Testing & Commissioning of 11 kV 1- Core XLPE 630 mm² armoured, FRLS as per relevant REC Standards
Supply, Laying, Testing & Commissioning of 11 kV 3- Core XLPE 185mm² armoured, FRLS as per relevant REC Standards
Supply, Laying, Testing & Commissioning of 11 kV 3- Core XLPE 120mm² armoured, FRLS as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 11 kV Indoor Heat Shrinkable Cable Termination Kits (Single Core) as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 11 kV Outdoor Heat Shrinkable Cable Termination Kits (Single Core) as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 11 kV Indoor Heat Shrinkable Cable Termination Kits ( Three Core) as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 11 kV Outdoor Heat Shrinkable Cable Termination Kits (Three Core) as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 11 kV Isolator, double break,3-pole, 630 Amp, horizontal mounting Type, with Earth Switch as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 9 Mtr. Long Pole(ST-410 SP33) as per relevant REC Standards
Supply, Installation, Testing & Commissioning of 33kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp as per relevant REC Standards
Providing & Fixing of Galvanised iron of sorts as per relevant Standards.
Supply, Installation, Testing & Commissioning of 100 kVA, 11/0.433KV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-2, (Aluminium wound) as per relevant Standards.
Supply, Laying, Testing & Commissioning of 120 mm² XLPE LT Cable 4 Core, armoured, FRLS as per relevant REC Standards.
Providing and laying of Cement bottoming 1:2:4 mix as per REC standards (0.5cum per pole)
Providing & Fixing of Earthing of 100KVA substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mm x10 mm & 50 mm x 6 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover as per relevant Standards.
Supply, Installation, Testing & Commissioning of MCCB-200Amps, 36kA,4P with weather proof chamber with inbuilt bus bars along with cable glands and clamps as per relevant REC Standards
Providing & Fixing of Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5mtr long through GI strip 25x3 mm as per relevant Standards
Supply, Installation, Testing & Commissioning of a) Battery Bank 30 V,100 AH , of 15 No. cells of 2 V each, sealed Maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant (as per relevant Standards) b) 30V,100 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply ( as per relevant Standards)
Supply, Installation, Testing & Commissioning of Distribution Panel (30 V, DC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43 for 2 No battery incoming supply with 2 No 63 Amps DP MCBs for incoming supply Double busbar of adequate size, 12 No DP DC MCB (0-32A) including indication lamps and cables and other accessories as per relevant Standards
Supply, Installation, Testing & Commissioning of Distribution Panel (415 V, AC) made of CRCA thickness not less than 2mm. Powder Coated, degree of protection IP43. 200 Amps Switch Fuse disconnector for incoming supply and 5 No TPN MCB's (16-125 Amps ) and 5 No DP MCBs (0-32A), rectangular busbar suitable for 200 Amps continuous Supply including indication lamps and cables and other accessories as per relevant Standards
Providing of & Fixing of Telecommunication Facilities as per relevant Standards
Supply of Rubber Mat 1mx2m 19mm thick as per relevant Standards
Supply & Fixing of Fire Extingiusher Co₂ Type of 4.5 kg capacity for control room as per relevant Standards
Supply & Fixing of 3 Sand Bucket Fire Extingiusher as per relevant Standards
Supply of Safety Helmet as per relevant Standards
Supply of Rubber Gloves for 33 kV level as per relevant Standards
Supply of Rubber Gloves for 11kV level as per relevant Standards
Supply of Safety Belt as per relevant Standards
Supply of Safety Shoes ( Ankle boot) as per relevant Standards
Supply of Earthing rod 5m long with 25 Sqmm cable 12 m as per relevant Standards
Supply of HV Detectors all voltages as per relevant Standards
Supply of Al Ladder 2x20' 3mm thick ( extendable with rope & pulley arrangement) as per relevant Standards
Supply, Laying, Testing & Commissioning of 33 kV,1 core(4 runs) 185sq.mm, Al conductor,XLPE, insulated, armoured cable (from the RMU to Recieving Substation)
SITC of 33kV RING MAIN UNIT( 3 Way Type Two Isolators & one circuit Breaker): Out-door type RMU,SF6 Insulated, extensible type, at 33kV system volatge and breaking capacity 25kA for one second,with SF6 circuit breaker / VCB self powered with O/C + E/F Relay system comprising of a) 33kV, 630 Amp. motorized Isolators including earthing switches with making capacity 62.5kA, having mechanical ON/OFF b) 33kV, 200Amp motorized, spring operated, Circuit Breakers (CB) with earthing switches c) Cu Bus - Bar of 630 Amp. rating d) One (1) No. Numerical Aux. self powered relay having non-directional 0/C and E/F protection (for each Circuit Breaker feeder). Relay should have minimum 7-DI & 8- DO. The relay shall also interface via an RS 232/485 port in order to send, as a minimum, real-time readings using the MODBUS protocol. e) Incoming Isolators shall have FPI with electrical reset contact / facility. f) All necessary potential-free contacts for indications relevant to RMU monitoring and control. g) Capacitor Voltage Dividers serving live-line cable indicators in each Breaker & Isolator.
Supply, Installation, Testing & Commissioning of 33 kV Single core indoor terminating kit to be used with cables - 185 sq.mm.
Supply, Installation, Testing & Commissioning of 33 kV Single core outdoor terminating kit to be used with cables - 185 sq.mm.
Supply & Fixing of Cable Route Markers.
Excavation in any type of soil including hard laterite soil.
Refilling of excavated soil
Supply of Sand for cushioning of the cables in the trench.
Supply & Fixing of Cement Tiles of size 300mm length x250mm width x 37mm thick as a protective cover for underground cables.
Supply & Fixing of Earthing of RMU --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 75 mmx10 mm & 50 mmx6 mm for connection of rmu body as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 20 mm nominal size for foundations)
Supply & Fixing of Centering and shuttering including struttings, propping etc and removal of formwork.
15 mm cement plaster 1:4 (1 - cement: 4 -fine sand) for foundations.
Constructing masonry chamber (600x600x900)mm .inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse s&) including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover & frame to be not less than 38 kg (weight of cover 23kg & weight of frame 15 kg) & RCC top slab 1:2:4 mix (1 cemenf :2 coarse s& : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine s& : 10 graded stone aggregate 40 mm nominal size) & inside plastering with cement mortar 1:3 (1 cement : 3 coarse s&) 12 mm thick, finished with a floating coat of neat cement complete as per st&ard design with common burnt clay F.P.S. (non modular ) bricks of class designation 7.5
Providing & Fixing of Wire mesh boundary fencing around the RMU
Ess Bee Electricals
SATISH & CO
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .