Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹16.9 L
Closing Date
18 Sept 2026, 3:00 pm7d left
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
Provision of RDSO approved aspiration type fire alarm system ( AFDAS) at relay room at various LC Gates & IB Goomty of Danapur Division.
DNRSnTSig2026-15~ECR
DNRSnTSig2026-15
Open
Works - General
12 Months
Patna, Bihar
₹0
₹16.9 L
27 Aug 2026
27 Aug 2026
4 Sept 2026
17 items across 1 schedule · ₹8,47,46,235 total
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| 1 | "Supply, Installation, Testing & Commissioning of Networkable Single loop addressable Fire alarm Control panel expandable upto 2 loops & interface with GSM/LTE module working as per RDSO/SPN/217/2025 ver-3.1or latest.The control panel shall be networkable to Zonal /Divisional Headquarters preferably over TCP lP/OFC media converter and shall have clock synchronization facility. This schedule includes supply of TCP IP converter/ Networking card/OFC media converter. The control panel shall have provision of Graphical software to enable remote monitoring of entire fire detection and alarm system of a station from Head Quarters. The control panel shall be designed to work on power supply of 110V/230V AC as well as on DC battery backup of adequate capacity to work upto 24 hrs. Backup. The Power supplies like batteries and chargers shall be supplied by the contractor. The Control Panel shall have means for the user to visualize and interact with the complete Automatic Fire Detection and Alarm System layout through a user- friendly software executable on a standard Windows based Personal Computer. It shall be possible to download data and extend alarms from Control Panel through suitable ports like RS485/RS232/USB/TCP/IP into a PC/Laptop available with SSE at the installation and remote location (Divisional Control room) operating on Windows platform. The software for downloading and analysing fault data shall be provided & shall be compatible with the latest windows operating system. Detection, actuation, and control system shall have provision for automatic as well as manual operation. The control panel should have provision to connect a GSM/LTE module duly providing compatible SIM with SMS facility on minimum of 5 numbers (users).Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO " | Set | 70.00 | 1,38,058 | 96,64,060 |
| 2 | "Supply, Installation, testing and commissioning of laser or high power LED based Aspiration detection unit for AC room with programmable 4 stage alarm generation and with 4 addressable modules. It should have auto cleaning facility in optical chamber, electronic discrimination of particle size or other listed methods or combination thereof. The aspiration system shall also include external power supply unit with battery backup as per OEM. The aspiration type smoke detector should be UL/LPCB/Vds/ FM listed/approved and shall comply tospecification Nos. RDSO/SPN/217/2025ver- 3.1 or latest.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO" | Set | 70.00 | 3,28,469 | 2,29,92,830 |
| 3 | Supply, installation testing & commissioning of Heat and smoke multi sensor with inbuilt fault isolator (open/short circuit in loop) as per specification Nos. RDSO/SPN/217/2025 ver- 3.1 or latest and required to be provided at suitable locations inside the diesel generator room, battery room, ASM room, power equipment room, B96 non air conditioned RR, CCTV control & equipment rooms, way side OFC room and other S&T service rooms as directed by the Railway site Engineer. The location of fixing is to be meticulously decided so that full advantage of the system is achieved.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Numbers | 1070.00 | 4,024 | 43,05,680 |
| 4 | Supply, Installation, Testing & commissioning of Audio Visual alarm (Hooter and strobe) controlled through addressable control model. It shall be preferably flashing type Red/White colour. It shall be preferably with Piezoelectric type sounder. The sound level shall be preferably adjustable type up to 90 dB at a distance of 1Mtr as per specification No. RDSO/SPN/217/2025 ver- 3.1 or latest.Note: Spares cost are also included & to be supplied as per RDSO para Nos. 4.15 or latest Inspection-Supply RDSO | Numbers | 70.00 | 8,398 | 5,87,860 |
| 5 | Supply, Installation and Testing, commissioning of Addressable and resettable Manual call point with inbuilt fault isolator (open/short circuit in loop) status LED for alarming & standby mode as per specification Nos. RDSO/SPN/217/2025ver- 3.1 or latest.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Numbers | 70.00 | 5,145 | 3,60,150 |
| 6 | Supply, Installation, Testing and Commissioning of UL/FM/Vds/LPCB approved/listed resettable UV/IR Type flame detector for diesel oil storage room with required module to communicate on main fire alarm panel. Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Numbers | 70.00 | 61,325 | 42,92,750 |
| 7 | Supply, Installation, Testing and Commissioning of resettable Probe type bimetallic Heat and all other accessories for diesel generator encloser as per RDSO Specification Nos. RDSO/SPN/217/2025 ver- 3.1 or latest.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Numbers | 70.00 | 6,672 | 4,67,040 |
| 8 | Supply, installation, testing & communication of Linear Heat Sensing (LHS)/Linear Heat Detection (LHD) Interface module with all accessories for integration with main line fire alarm control panel as per RDSO specification Nos. RDSO/SPN/217/2025ver- 3.1 or latest. It should be UL/FM/Vds/LPCB approved/listed.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Numbers | 70.00 | 92,882 | 65,01,740 |
| 9 | Supply, Installation Testing and commissioning of Analogue type Linear Heat Sensing cable/Linear Heat Detector hollow metallic pneumatic tube type with required module to be integrated on main Fire Alarm Panel as per specification Nos. RDSO/SPN/217/2025ver- 3.1 or latest. It shall be laid in all cables tray located in power equipment room, relay room & telecom room and should be UL/FM/Vds/LPCB approved/listed. Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Metre | 1070.00 | 533 | 5,70,310 |
| 10 | Supply, Installation, Testing, Commissioning of Auto Telephone Dialler (GSM) Module to send the prerecorded message, fire and fault massage, to multiple mobile numbers, programmed earlier, complying to the RDSO/SPN/217/2025ver- 3.1or latest. Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Numbers | 70.00 | 10,548 | 7,38,360 |
| 11 | Supply of Power supply System 24 V/2 Amp or other rating as per OEM with built in Charger with battery backup as per specification Nos. RDSO/SPN/217/2025ver- 3.1or latest.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest.Inspection-Supply RDSO | Set | 70.00 | 34,480 | 24,13,600 |
| 12 | Supply, Installation Testing and commissioning of FRLS/Fire Survival Circuit Integrity Cables of size 2C X1.5 Sq. mm with all accessories certified by UL/FM/Vdc/LPCB/ BRE global or any recognised Lab by GOI for connection of Fire Alarm devices specification Nos. RDSO/SPN/217/2025ver- 3.1or latest.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Metre | 1885.00 | 169 | 3,18,565 |
| 13 | Supply, Installation, Testing & Commissioning of UL/LPCB/Vdc listed/approved Pipe made of CPVC with suitable diameter & pipe accessories (couplings, unions, elbows, tees, end caps, capillary tubes, sampling ports, mounting brackets etc.) as per requirement for the Aspiration detection shall comply to RDSO/SPN/217/2025ver 3.1or latest.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO | Metre | 1450.00 | 1,018 | 14,76,100 |
| 14 | Supply, Installation, Testing and Commissioning of Addressable Multi detector combination of heat cum smoke, with isolator base binary coded address setting. Dual LED's for 360 degress visibility.Sleek low-profile housing design. Regular 100mm base. IP Rating : IP -42. Approval: UL listed, (As per RDSO Specification No.RDSO/ SPN/ 217/ 2021 ver 3.0 or latest Inspection-Supply RDSO | Numbers | 290.00 | 6,142 | 17,81,180 |
| 15 | Supply of CO2 Fire extinguisher 4.5 kg capacity confirming to IS 15683: 2018 or latest with ISI mark provided with all fittings and accessories. Inspection-Consignee | Numbers | 320.00 | 5,281 | 16,89,920 |
| 16 | Supply of Fire ball as per specification (i) To be used for extinguishing fire with very less time of 3-5 Sec, (ii) Shelf life- Minimum 05. Yrs., Item Weight: 1.3 Kg (Min) (iii) It should have a stand for keeping it.Warrantee/Guarantee: As per OEM,(V) GC/TC to be submitted along with the materials. Make: AFO, Elide fire or better. Inspection- Consisgnee | Numbers | 250.00 | 1,233.2 | 3,08,300 |
| 17 | "Supply, installation, configuring, testing and commissioning of remote monitoring software (GUI) along with license for Min. 20 addressing control panels as per RDSO/SPN/217/2025ver- 3.1or latest. This includes necessary gateway card and network interface card for the system fully functional as desired by railways.Note: Spare cost is also included & to be supplied as per RDSO para Nos. 4.15 or latest. Inspection-Supply RDSO" | Numbers | 70.00 | 3,75,397 | 2,62,77,790 |
| Schedule total | ₹8,47,46,235 | ||||
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC_April-2022_2022__GCC-2022_POLICY_27.04.22.pdf
ATTACHMENT
DocSig2026-15.pdf
ATTACHMENT
ECRJPOregardingprocedureforundertakingearthworkdiggingworktrenchingworkinthevivinityofsignallingtelecomandelectricalcables.pdf
ATTACHMENT
ACSGCC20221to11.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .