| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.5 LAccepted-AOC PLOT NO 14 SHIV COLONY KATI GHATI RAJGARH ROAD ALWER RAJ | ALWAR | ALWAR | RAJASTHAN | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹37.0 L+₹2.7 L (7.75%)Rejected-Finance 40 VISHNU VIHAR KHERAI SHAMSHABAD ROAD KHERAI AGRA UTTAR PRADESH 282001 | AGRA | UTTAR PRADESH | 282001 | L2 | Rejected-Finance Not Lowest Bidder | |
| 3 | L3₹39.1 L+₹4.8 L (13.9%)Rejected-Finance | L3 | Rejected-Finance Not Lowest Bidder | |
| 4 | L4₹39.2 L+₹4.9 L (14.3%)Rejected-Finance | L4 | Rejected-Finance Not Lowest Bidder | |
| 5 | L5₹54.9 L+₹20.6 L (60.1%)Rejected-Finance 61 ABHAY GARH SCHEME AIR FORCE JODHPUR 342001 RAJ | JODHPUR | JODHPUR | RAJASTHAN | 342001 | L5 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
22 Mar 2023, 6:00 pmClosed
GE (AF) Jaisalmer
GE (AF) Jaisalmer
REPAIR /MAINT OF LT PANEL , SERVICE CABLE AND MAIN DBS OF BPS INCLUDING LIGHT FITTING AND REPAIR/MAINT OF DG SETS , CONTROL CABLE , LT CABLES AND OTHER CONNECTED WORK AT CERTAIN UNIT AND DOMESTIC AREA AT AF STN JAISALMER
2023_MES_582186_1
8885/GE/E8
Open Tender
Miscellaneous Works
Item Rate
270 days
GE (AF) Jaisalmer
As per tender documetns
7 documents required · 7 mandatory
₹500
Yes
GE (AF) Jaisalmer
₹80,000
Yes
21 Apr 2023
21 Feb 2023
24 Mar 2023
21 Feb 2023
22 Mar 2023
8 Mar 2023
22 Feb 2023 - 25 Feb 2023
Amount
Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in any type of soil complete all as specified and as directed .
Sand cushioning and cover (using local tibba sand), 80 mm thick before laying of cable and 150 mm thick after the cable is laid, complete all as specified and as directed by Engineer-in-Charge. (Note : 1. Approved local tibba dry sand after removal of vegetations, grass and other deleterious substances shall be used for sand cushioning and cover).
Jodhpur stone rough dressed slab, 40 mm to 50 mm thick, 25 cm to 35 cm wide of not less than 60 cm long dry abuttting each other for protection to under groung cable , complete all as specified and as directed .
Removing surplus soil to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and as directed .
Returning, filling in any type of soil including spreading, leveling, watering and well ramming in layers each n.exc 25cm complete all as specified and as directed .
Supply, laying, jointing and testing XLPE insulated screened PVC bedded, armoured, heavy duty underground electric cable with stranded aluminium conductor 1100 volts grade cross sectional area 10 sq mm 2 core confirming to IS-7098 (Part-I-1988) laid in trenches, along poles through pipes etc. including taking out old unservicable cable complete all as specified. Notes :- (i) Sand cushioning, cable protection, GI pipe and excavation & earth work shall be measured & paid for separately (ii) Road cutting/ floor cutting/ cutting holes etc in walls required for laying/ fixing of cable etc shall be made good as per existing. Nothing extra shall be admissible on this account. Quoted rates shall be inclusive of the above provisions.
All as per SI No 6.00 here-in-before but 10 Sqmm 4 core
All as per SI No 6.00 here-in-before but 16 Sqmm 4 core
All as per SI No 6.00 here-in-before but 25 Sqmm 4 core
All as per SI No 6.00 here-in-before but 35 Sqmm 3.5 core
All as per SI No 6.00 here-in-before but 50 Sqmm 3.5 core
40 mm bore GI tube, light grade galvanised with clamp of 25 x3 flat iron for protection of cable , with all fitting lead in trenches /under road / with wall /in wall /pole /under floor where required complete all as specified and as directed.
50 mm bore GI tube, light grade galvanised with clamp of 25 x3 flat iron for protection of cable , with all fitting lead in trenches /under road / with wall /in wall /pole /under floor where required complete all as specified and as directed.
Drilling (Horizontally) of holes under road width 110 mm dia , pavement , hard standing by trench less technology ( manually ) with out disturbing the top surface of road (maximum 10 mtr wide) for laying of cable/ GI pipes complete all as specified and as directed .
Energy efficient LED Post top light fittings made in die cast aluminium bottom and spun aluminium to reflector with decorative clear acylic diffuser and IP65 protection, with higher efficiency lighting of capacity not less than 25 Watt, range 140-280 volts with surge protection inbuilt in driver for maximised protections, driver should be potted type for viberation proof performance in & includings making electrical connections and taking down of old fittings of any type and size, mountiung arrangements, complete all as directed .
LED flood lights not less than 120 watts, nominal voltage 240 volts, 50 Hz, high efficiency long life LED module with SMD LED package mounted on MCPCB, lumen efficacy of LED shall not be less than 120 lumen/W, Colour temp (CCT) -5700K and viewing angle of 120 degree to ensure better uniformity, epoxy powder coated pressure die cast aluminium housing elegantly designed heat sink for efficient thermal management, high quality toughened glass IK 07 fixed to housing, having electronic driver, integral, isolated electronic driver with lower THD, output open/short circuit protection, over voltage protection, surge voltage protection with external SPD not less than 10 KV and other safety test as per IS 15885 Part-2/Sec 13, having adjustable MS cradle of thickness 5mm provided in and including taking down of existing lights of any type complete all as specified and directed,
LED bollard light decorative type with reflector not less than 10 watt , IP65 rated Inverted Pyramid Tripod type LED Bollard with soft 360 deg light distribution having fixing arrangements at bottom with necessary nuts, bolts, washers complete in and including taking down of old unserviceable lights complete all as specified and directed.
Energy efficient LED street light fittings of 60 Watt, pressure die cast alluminium housing with prismatic poloycarbonate modular secondary lens optics, IP-66 degree of protection,140-280 volts fittings should be provided 5 KV surge protection external and apart from this surge, arrestor driver should have additional 4 KV surge protector inbuilt in driver for maximised protections, should have lumens output of 100 lumens watt minium protections facility in drivers, driver should be potted type for viberation proof performance & includings making electrical connections and taking down of old unserviceable lights of any type all as directed.
Plain cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate) as in lintel, cill, bed block coping ,bed plate, bond stone etc including weathering slightly rounded or chamfered angles and throating and necessary form work in and including dismantling of existing PCC complete all as specified and directed .
Supply, fixing and connecting elastomer insulated, flat,sheathed, multicore, industrial flexible cable with bright annealed copper conductor, 1100 volts grade cable of size1.5 sqmm, 3 core, confirming to IS 694-1990 including taking down of old unserviceable connection wire complete all as specified and directed.
Supply and fixing service cable 10 sqmm, twin core, 1100 volts grade heavy duty cable PVC stranded insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire including taking down of old service wire complete all as specified and directed.
Supply and fixing 6 sqmm , twin core, 1100 volts grade heavy duty cable PVC insulated stranded aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, including taking down of old service wire complete all as specified and directed.
Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections conforming to Fe-290 Gde E-165 including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and also including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces, supply and fixed in repairs, complete all as specified and as directed by Engineer-in-Charge. Notes :- (i) Sizes & types of members and shape of the cross arms etc shall be as required at site all as directed . (ii) Un-exposed steel surfaces shall be given one coat of red-oxide zinc chromate primer only.
Design, supply, erection, testing and commissioning of outdoor type LT Bus Bar Chamber box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type Aluminium bus bars (32mm x 5mm) for looping & branch connection system .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947 in and including providing of one No MCCB of 160 Amps, 4 Pole, 25 KA, 50 Hz 415 Volts .The bus bar chamber shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. The bus bar chamber shall be provided with ventilation facility in the form of louvers for better heat dissipation in and including dismantling/taking down of old unserviceable complete. Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5 deep below normal ground level and connected to and including galvanized earth lead wire 4mm dia upto 7.5 metre by means of GI nuts, bolt, check nuts, washers thimbles, etc as shown in electrical plate No 03 SSR Part I and connection to main switch board or panel and testing on completion including excavation and earth work in any type to soil, returning fitting in and removal of surface spoil to a distance not exc 50 metre, PCC chamber (1:3:6) type C-2, charcoal and salt mixed layer 15cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe light grade 20mm bore for watering and 15mm bore meter long GI pipe light grade for earth wire protection fixed with poles with two clamps, made from MS flat 25mm x 3mm, bolts, nuts and washers 75mm thick RCC cover 1:2:4 type B-1 shall be provided on CI frame etc complete all as specified. Note - (i) PCC chamber shall be constructed at least 1.5m away from the earth electrode. The pipe for watering shall be provided in slanting manner.including the cost of 7.50m GI pipe for protection of earth wire/strip .(ii) Quoted amount deemed to include the cost of excavation /earthwork , PCC pit , funnel , cover GI medium grade protectiom pipe.
Supply installation , commissioning and testing in replacement of tripode ring earthing system to construct earthing of resistance not more than 01 ohm mainly consisting of 250 micron copper bonded high tensile low carbon steel rod earth electrode of minimum 3.0 m length , 17 mm dia with copper strip of size 20 x 3.15mm for inter connection to earth electrode and for connected to equipment as per required length, with set of steel nut and bolts, earth enhancement material of mainly consisting of Jamfill compound 50 kg (25 x 2 bags in each pit) jam fill to provide maximum contact between the electrode and jam fill compound. Back fill compound. Jam fill compound shall be eco friendly having RDSO certification, Earthing shall be maintenance free and does not require regular manual addition of water and PCC (1:3:6) type C1 (using 20 mm graded stone aggregate) earth chamber and Earth Pit cover 300 x 300mm . Note: Copper strip of size 20 x 3.15mm required to connect the electrode shall be passed through GI pipe of suitable size . Note :- (i) Quoted rate deemed to include the cost of excavation and earth work, PCC pit, funnel and cover etc.(ii) copper strip beyond earth test point shall be mearued and paid seperately .
Change over switch 250 Amps ON load in sheet enclosure four pole to be fixed on wall with FI 32X6mm, nuts, bolts, washers etc. fixed in repair complete with all electric connection complete all as specified and directed.
Sub main wiring with 2 run of single core 4.0 Sqmm multi-stranded copper conductor 1100 volts grade heavy duty FRLS-H PVC insulated unsheathed cable drawn through and including PVC conduit medium grade of suitable size conduit in concealed wiring including 4.0 Sqmm PVC insulated unsheathed single core copper conductor earth wire including taking down old unserviceable submain wiring complete all as specified. Note : Two run of 4.00 sqmm cable and one run of 4.00 sqmm cable as earth wire continuity conductor and PVC conduit shall be measured & paid as one unit.
Sub main wiring with 2 run of single core 6.0 Sqmm multi-stranded copper conductor 1100 volts grade heavy duty FRLS-H PVC insulated unsheathed cable drawn through and including PVC conduit medium grade of suitable size conduit in concealed wiring including 6.0 Sqmm PVC insulated unsheathed single core copper conductor earth wire including taking down old unserviceable submain wiring complete all as specified. Note : Two run of 6.00 sqmm cable and one run of 6.00 sqmm cable as earth wire continuity conductor and PVC l conduit shall be measured & paid as one unit.
Single pole and neutral enclosure with a two pin and earth plug and socket , 20 Amps 230 Volts with & including one MCB SP ‘C’ Curve 10 kA 20 Amps fixed in repair complete all as specified and directed
Battery,12 V 150 AH, 25 plates including testing for its proper functioning fixed in repair complete all as specified and directed . Make Exide/Amron. Note :- Battery shall be original make accepted No substitute of battery.
Aviation obstraction lights not less than 10 watt, 230 volts, 50 Hz comprising of aluminium housing with Polycarbonate enclosure, suitable for outdoor application fixed in repair complete all as specified and directed.
Sheet metal enclosure powder coated single phase DB SPN 8 ways and neutral 240 Volts, AC supply, 50 Hz, with 200 Amps rated bus bar Double Door (IP-43 IK 09 with metal door) suitable for fixing of MCBs including fixing of lugs in main incomming and outgoing line and fixing of cable glands of suitable size including grouting flush in the wall by means of nuts, bolts, angle iron and making good disturbed surfaces including taking down old unserviceable DB complete all as specified and directed.
Sheet metal enclosure powder coated single phase DB SPN 12 ways and neutral 240 Volts, AC supply, 50 Hz, with 200 Amps rated bus bar Double Door (IP-43 IK 09 with metal door) suitable for fixing of MCBs including fixing of lugs in main incomming and outgoing line and fixing of cable glands of suitable size including grouting flush in the wall by means of nuts, bolts, angle iron and making good disturbed surfaces including taking down old unserviceable DB complete all as specified and directed.
Sheet metal enclosure flush mounting factory made for TPN DB 4 way, 415 Volt, AC 50 Hz Double door, IP-43 protection, IK-09 built in bus bar complete with siitable for incomming MCB and outgoing MCBs and fixed in recess on wall including taking down old unserviceable DB complete all as specified and directed.
Supply and fixing flush mounting factory made sheet metal enclosure for VTPN DB 4 way, 415 Volt, Double door, IP-43 protection, IK-09, No. of modules (8+20) with metal door with 200 Amps copper bus bar, with neutral bar, earth bar and cables ties for cable management fully insulated bus bar suitable for incoming MCCB and outgoing MCBs and fixed in recess in brick masonary wall including taking down old unserviceable DB complete all as specified and directed.
MCB, Single Pole, 5 to 32 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 240 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles including taking down old unserviceable MCB complete all as specified and directed.
MCB, Single Pole and netural , 32 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 240 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles including taking down old unserviceable MCB complete all as specified and directed.
MCB, Single Pole and netural, 40 to 63 Amps rating, with over load and short circuit protection 'C' curve and rupturing capacity 10 kA, 240 Volt grade, AC supply, 50 Hz and making connections using suitable size copper lugs/thimbles including taking down old unserviceable MCB complete all as specified and directed.
MCB, TPN/FP , 40 to 100 Amps rating, with over load and short circuit protection 'B' curve and rupturing capacity 10 kA, 415 Volt grade, AC supply, and making connections using suitable size copper lugs/thimbles including taking down old unserviceable MCB complete all as specified and directed.
MCCB, 4 Pole, 100 Amps rating, rupturing capacity 16 kA, 415 Volt grade, AC supply, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
Taking down of existing u/s street light of any type/ Bollard light/Perimeter light /high mast light and building security lights of any type any make from pole , hangers, buildings/Highmast poles at any height etc any type complete after removing from existing mounting arrangements/ street light bracket etc and re-fixing the same after necessary repair / replacement of unserviceable light with new fittings /component etc complete all as specified and directed by Engineer-in-Charge. Note:- (i) Replacement and fixing of unserviceable component etc required will be measured & paid separately under relivent items as supply only. (ii) Fitting shall be connected with existing electric wire / cable, in case of existing wire / cable found unserviceable same shall be measured and paid in relevent items as supply only. (iii) Any type of Ladder required for dismantling of light from pole/ from hanger/high mast pole shall be arranged by the contractor.
Supply only electronic driver suitable for LED street lights of capacity 25 to 45 watt as per existing complete all as specified & directed.
Supply only electronic driver suitable for LED flood lights of capacity 60 to 90 watt as per existing complete all as specified & directed.
Supply only electronic driver suitable for LED flood lights of capacity 120 watt to 150 watts as per existing complete all as specified & directed.
Supply only surge protection device 10 KV, suitable for LED street lights of capacity 45 watt to 250 watts, single phase, 230 volts, 50 hz complete all as specified and directed
Painting to steel tubular pole 9 to 11 mtr long /Rail Pole of Lightening conductor or LT over head line or street light poles and all MS clamps, cross arm work on poles with one coat of superior aluminium paint including necessary preparation of surfaces by scrubbing of old paint and including painting of alternate strip with white and Blue synthetic enamelled paint strip 05 Nos each of 30 cm height up to 1.5mtr above PCC benching/coping including writing of Pole Number as per existing or new as directed at site complete all as specified and directed .
Preperation of surface of RCC LT/HT poles and painting with one coat synthetic enamel paint upto 1.5m height in blue and white colour alternate strips each of 30cm wide all as specified and directed .
Routine and periodical cleaning the inside area of 11 KV Sub Stations including cutting and removal/uprouting of unwanted grass/bushes, small trees near all around sub station and pump houses complex complete including surface dressing and leveling by surface excavation wherever as required complete all as specified and directed .
Scrubbing of existing paints of existing LT panel board where rusted, LT feeder Pillar boxes, LT bus bar chamber paints of any specification and removing old paints and preparation of surfaces for painting complete and M&L for painting of LT Panels, LT Feeder pillar boxes, LT bus bar chambers internaly and externaly with two coats of Ist quality smoke grey paint over a coat of red oxide primer to achieve fine finishing complete all as specified and directed .
Dismantling of old unserviceable doors, back sheets, side sheet of LT panels, bus bar chamber or feeder pillar box installed at various places by cutting/descrewing after making the system disconnected from Elect supply and M&L for fabrication of doors/frames/ partition, bottom sheet by bending hot or cold, making holes, notching, welding of MS black sheet for LT panel board, bus bar chamber, feeder pillar box made out of 2 mm thick mild steel sheet including providing hinges for opening or closing of door, making handles, locking arrangement and painting of sheet both side with superior quality smoke grey paint after applying a coat of red oxide primer and matching with the existing ( Complete LT panel/ Bus bar chamber shall be painted ) complete all as specified and directed by the Engr - in-charge at site. Note : 1. The cost of disconnecting of LT cable and earth strip and reconnecting the same after repair work shall be deemed to be inclusive in the unit quoted rates. 2 Painting of complete LT Pannel/Bus bar chamber shall be carried out , nothing shall be payable extra in this regard.
Taking down of existing LT cables connected to street light junction box and reconnecting the same after providing of new aluminium cable lugs as per existing with lugs/Thimbles, providing of new cable connector in existing street light junction box, replacement of existing clamp of size 25x3 mm with suitable size nuts and bolts as per site requirement and fixing of LT cables of size upto 70 Sqm mm properly along the poles/walls by providing of suitable size clamps or passing through GI Pipe of suitable size, taking up of cable from loop if required by breaking of existing PCC complete all as specified and directed at site. Note:- GI pipe and PCC for coping shall be measured and paid seperatly under relevent item of BOQ.
Street/security light bracket made out of 40 mm dia galvanized steel tubing medium grade 1.5 m long including bending if required as directed ,02 nos clamps made out of MS flat iron 40X6mm of suitable size fixed with bolts, nuts and washer including drilling holes and grouting with the same for fixing bolts including taking down existing complete all as specified and directed .(Rates quoted by the contractor shall deemed to include for nut and bolts).
Attending major breakdowns by providing 01 line man, one helper and one Camper Vehicle in serviceable condition on LT/HT lines, LT/HT cables, LT Panels, DBs, VCBs, RMUs, four pole, two pole, transformers etc including clearing of lines, trimming of tree branches, replacement of insulators/conducotrs/ cross arms & removal of tree branches from LT/HT lines and laying of temporary cables etc complete all as directed at site by Engr-in-charge. Note:- 1 Items used will be measured & paid seperately under relevent item of sch A. Contractor has to arrange suitable vehicle with manpower as above and T&P on short notice as & when required on the direction of Engineer in charge. The contractor will immediately depute complete set of arrangements as above on receipt of information to attending the electric breakdown, failing which the penalty at the rate of Rs 2000.00 per complaint.will be recovered from the contractor dues.
Maintenance and serviceing of DG Set of capacity 7.5 KVA to 75 KVA complete including draining out of diesel from tank, cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the chamber, cleaning the chamber thoroughly and refilling the same with new engine oil to required level, replacing the fuel filter, lubricating oil filter, check & clean air cleaner, change air cleaner elements, check coolant level & make up the same, drain the Fuel filter & water separator, filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replace the unserviceable brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, changing of V-belts, changing rubber hoses and clips of air cleaner, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load & record shall be made in respect of RPM, oil pressure, oil temperature, coolant temperature, voltage, frequency, load current, battery charging, fuel consumption etc. complete all as specified and directed .
Maintenance and serviceing of DG Set of capacity 80 KVA to 160 KVA complete including draining out of diesel from tank, cleaning the tank thoroughly and refilling the drained out diesel, draining out engine oil from the chamber, cleaning the chamber thoroughly and refilling the same with new engine oil to required level, replacing the fuel filter, lubricating oil filter, check & clean air cleaner, change air cleaner elements, check coolant level & make up the same, drain the Fuel filter & water separator, filling the starting batteries with electrolyte/distilled water to maintain the required specific gravity, replace the unserviceable brass connectors for batteries, cleaning of battery terminals & applying petroleum jelly to battery terminal posts & brass connectors, changing of V-belts, changing hoses and clips of air cleaner, checking of exhaust leakage, governor, breathers etc, adjust/set the same for proper functioning of DG Set, checking of fuel, oil and water/coolant level etc, adjusting and keeping the fan belts to the desired tension, tightening all the bolts and nuts to the required torque etc, cleaning the DG Set with accessories as prescribed by the manufacturer and test for satisfactory running of DG set for two hour at connected load & record shall be made in respect of RPM, oil pressure, oil temperature, coolant temperature, voltage, frequency, load current, battery charging, fuel consumption etc. complete all as specifed and directed.
Supply only in repair the following items from 7.5 KVA to 160 KVA
Control Safety (Water),
Control Safety (Lub Oil) ,
Gauge Water Temp.(54'),
Gauge Low Temp.(96'),
Gauge Lub Oil Pressure,
Techohourmeter,
Battery,12 V 180 AH including testing for its proper functioning fixed as in repair complete all as specified and directed. . Make Exide/Amron. Note :- Battery shall be of original make accepted No substitute of battery.
Battery,12 V , 80 AH, 25 plates including testing for its proper functioning fixed in repair complete all as specified and directed . Make Exide/Amron. Note :- Battery shall be original make accepted No substitute of battery.
Supply and filling in sump / topping up engine oil, multi grade 20w / 40 in engine or relpacement of engine oil complete all as specified and directed . .Make :- Indian oil / Hindusthan petrolium / Castrol / Pried /Servo
Battery link lead made out with 25 sqmm copper conductor PVC insulated with bettry terminal of +/- terminal 0.3 mtr long complete all as specified and directed .
Battery link lead made out with 25 sqmm copper conductor PVC insulated with Bty terminal of +/- terminal 1.50mtr long complete all as specified and directed .
AVR card suitable for 7.5 KVA to 75 KVA DG Set as per existing fixed as in repair complete all as specified and directed .
AVR card suitable for 83 KVA to 160 KVA DG Set as per existing fixed as in repair complete all as specified and directed .
Controller suitable for 60 KVA to 83 KVA DG set, CPCB -I, silent type as per existing complete all as specified and directed
Controller suitable for 250 KVA to 500 KVA DG set, CPCB -I/CPCB-II, silent type as per existing complete all as specified and directed
Self starter of cpacity 12/24 volts from engine and shifting to civil workshop for repair/overhauling of the self starter by rewinding of one field coil, repair and rewinding of armature and fixing it to the existing place after repairing including taking down complete all as specified and directed .
Contactor 3 pole 32-55 Amps, 415 Volts, conforms to IS/IEC 60947-4-1 & IEC 60947-4-1 in and including providing auxilary conactors NO/NC complete all as specified and directed.
Contactor 3 pole 80-85 Amps, 415 Volts, conforms to IS/IEC 60947-4-1 & IEC 60947-4-1 in and including providing auxilary conactors NO/NC complete all as specified and directed .
Contactor 3 pole 160 Amps, 415 Volts, conforms to IS/IEC 60947-4-1 & IEC 60947-4-1 in and including providing auxilary conactors NO/NC complete all as specified and directed.
Contactor 3 pole 250 Amps, 415 Volts, conforms to IS/IEC 60947-4-1 & IEC 60947-4-1 in and including providing auxilary conactors NO/NC complete all as specified and directed
Contactor 3 pole 400 Amps, 415 Volts, conforms to IS/IEC 60947-4-1 & IEC 60947-4-1 in and including providing auxilary conactors NO/NC complete all as specified and directed
MCCB, 4 Pole, 400 Amps rating, rupturing capacity 36 kA, 415 Volt grade, AC supply, 50 Hz, thermal Magnetic protection unit and making connections using suitable size copper lugs/thimbles and crimping tool, including disconnecting & taking down old unserviceable MCCB, complete all as specified & directed.
Connecting and testing ACB 4 Pole, 415 V, Manual Drawout type with microprocessor release of capacity 800 Amps, 50 KA complete of existing make of Havells in and including taking down of existing unserviceable ACB all as specified and directed.
Excavation in trenches, n exc 1.5m wide and n exc 1.5m in depth , for foundation, etc or for shafts, wells, cesspits, manholes, pier holes, laying of cables etc. n exc 10sqm on plan and n exc 1.5m in depth and getting out in hard/disintegrated soil/rock complete all as specified and as directed .
Supply and fix junction box made out of polycarbonate with IP 55/IP 65 protection of size not less than 200 x 160 x 98 mm , 5 way having terminals for termination of cable with necessary nuts and bolts including -02 Nos polycarbonate cable gland, 01 Nos DIN rail for mounting of MCB and 01 No, MCB SP, 10 KA, 6 Amps in and including fixing clamp of FI 25 x 3mm with necessary nuts and bolts in and including taking down of old junction box of any type and size complete all as specified and directed.
20mm outer dia, 3- layer PP-R Polypropylene random copolymer) concealed pipes SDR 7.4 (PN16) UV stabilized and antimicrobial fusion welded having thermal stability for hot & cold water supply all PP-R plain & brass threaded olypropylene random fittings fixed with the pole by providing FI clamps, nuts and bolts of size 25x25x3mm with nuts & bolts for protection of connecting wires, connection from junction box to light fittings, fixed as in repair complete all as specified and directed.
S.D. And Company
M/S SHREE AAINATH ENTERPRISES
prem enterprises
SANJOLI CONSTRUCTION COMPANY
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .