GM(EnM), Dudhichua Area
PO-Khadia, Disstt.- Sonebhadra, U.P., Pin- 231222
Erection of New HT OHL from F substation to central pump house at coal section of Dudhichua Project for supplying uninterrupted power to pumps during Monsoon period
2025_NCL_326943_1
DCH/EnM/Tender/FLD/24-25/64
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
Dudhichua NCL
Please refer tender documents
4 documents required · 4 mandatory
₹39,100
15 Feb 2025
27 Jan 2025
7 Feb 2025
27 Jan 2025
6 Feb 2025
28 Jan 2025
27 Jan 2025 - 30 Jan 2025
Amount
PART-A (Supply):
Supply of 7/14 SGW GI wire for Guarding and earthing
Supply of 10 SWG GI wire for latching in shape of Guarding
PART-B (Erection):
Erection of 11/13 mtr long of MS tubular pole in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling and secured with holding clamps, bolts, nuts , barbed wire etc. as required.
Erection of all aluminium conductor of 7/3.40 to 7/4.00mm diameter and above including binding etc. as required.
Supply and Erection of galvanised stay set for 11 KV overhead line complete with 19/20 mm dia X 1.8 meters long stay rod, anchor plate of size 45cmx45cmx7.5mm thick turn buckle (20mmx600mm) 7/4.00 mm dia, G.I stay wire and 11kv strain insulator etc in cement concrete 1:3:6 (1 cement: 3 coarse sand: 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required
Laying stringing of 7/14 S.W.G. G. I. earth with 10 SWG guarding wire in shape of guarding wherever is required
Supply and Erection of 11kv disc insulator for 11KV overhead lines with galvanised insulator hardware fitting, ball and socket type compelete with galvanised strain clamp,bolt ,nut,washers etc. as required
Supply and Erection of 11kv pin insulator compelete with large steel head G.I.pin nuts washers etc. as required
Erection of double pole 3 wire cross arm for 11kv overhead line etc. as required
Erection of pole top/straight two wire/V shape two wire angle iron/channel iron cross iron arm on wood/RCC/PCC/steel tublar/rail pole etc. as required
Earthing with GI pipe 4.5meter long 40mm dia including accessories and providing masonary enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/coke and salt as required.
Laying and fixing of one of PVC inculated and PVC sheathed /XLPE power cable of 11KV grade of upto 120sqmm direct in ground including excavation, sand cushioning , protective covering and refelling the trench as required.
Supply and fixing of light class GI pipe of 80mm dia (normal) 3 meter length along the pole for protection of underground cable as required
Providing and fixing of HT danger notice plate of 250mm X 200mm made of mild steel, at least 2mm thick and vitreous enameled white on both sides and with inscription in single red color on front side as required.
Total impact of GST for the purpose of CTC
M/S. AMAN ASSOCIATES (BID ID -1124954)
M/s HARIHAR SINGH ELECTRICALS (BID ID -1125158)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .