Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹1.1 L+₹3,640 (3.30%)Rejected-Finance | L2 | Rejected-Finance 1ST. LOWEST | |
| 3 | L3₹1.1 L+₹3,880 (3.52%)Rejected-Finance | L3 | Rejected-Finance 2ND. LOWEST |
Tender Value
Refer Docs
EMD Value
₹2,600
Closing Date
30 Jun 2023, 5:00 pmClosed
AE AHESD
West Bengal Legislative Assembly South Annex Building Gr Floor Kolkata 700 001
Installation of new Air conditioner machine in the chamber of Secretary at Assembly House Kolkata
2023_WBPWD_543850_1
eNIQ No. - 04 /WBPWD/AE/AHESD of 2023-24
Open Tender
ELECTRICAL WORKS ORG
Item Rate
7 days
Assembly House
Please refer Tender documents.
6 documents required · 6 mandatory
₹2,600
8 May 2025
23 Jun 2023
3 Jul 2023
23 Jun 2023
30 Jun 2023
24 Jun 2023
Amount
Supply and delivery of Split type 1.5 or higher ton capacity Air conditioner of BEE 3 Star rating (Minimum), with Super Tropical - Return Cooled Rotary Compressor, 18000 Btu/h (minium), Indoor units PCB. covering by metal sheet, Indoor unit Refrigerant R-32/410A, Multi port Refrigerant inject coil, outdoor & indoor unit coil must be made by copper tubes. [Make Daikin/Hitachi/Mitsubishi Heavy)
Supply, installation, testing and commissioning incl. vaccumiazation and nitrogen testing as required of following nominal sizes of soft/hard drawn copper refrigent piping for above ac complete with fitting with suitable adjustable ring type hanger supports, jointing/brazing incl. accessories insulated with XPLE class-O tubular insulation with / class O closed cell elastromatric nitrile rubber tubular sleeves section of specified thickness as given below for suction and liquid line all accessories as per specification etc as required. (Make: Ryoku/Totaline/Jobu/Godrej)
12.7mm (1/2") OD (with 13mm insulation) or suitable size as per manufacturer advice.
6.35mm (1/4") OD (with 13mm insulation) or suitable size as per manufacturer advice.
Supplying & drawing of 3 core x 2.5 sq.mm. PVC insulated copper cable for interconnecting the indoor & outdoor unit.
Supplying, fitting & fixing of 5/8 th. Inch dia PVC drain pipe for condensed water as per direction of EIC.
Installation the outdoor & indoor unit, after making holes in wall by expert labour, also mending good after complete the work, Connecting the pipe line testing the leack by gas pressure (minimum 400 PSI ) and vacuuming the unit properly (Minimum -30 PSI), hold the vacuum up to 48 hours, after release the gas testing the Split type Room Air conditioner with supply & fitting adjustable powder coated painted heavy duty iron bracket.
aswirbad infra co
SUPER COOLING AGENCY
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .