Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.9 LAccepted-AOC | L1 | Accepted-AOC Being lowest bidder for the work | |
| 2 | L2₹31.0 L+₹1.1 L (3.52%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹31.5 L+₹1.6 L (5.21%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
31 Aug 2021, 6:00 pmClosed
Commander Works Engineer Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
REPAIR AND MAINTENANCE OF TRANSFORMERS AND ALLIED WORKS UNDER AGE E/M BAIRAGARH UNDER GE BHOPAL
2021_MES_463064_1
83669/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bhopal
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹500
GE Bhopal
₹70,000
Yes
10 Sept 2021
5 Aug 2021
2 Sept 2021
5 Aug 2021
31 Aug 2021
19 Aug 2021
Amount
Dehydration and filtration of existing transformer oil of transformer at different location with filtration machine and heating system to get the minimum di-electric strength of oil 60 kV minimum without disturbing the power supply system and refilling/ topping up /replacement of unserviceable transformer oil complete all as specified and as directed.( Note: Transformer oil required extra for filling/topping up shall be measured and paid separately under the relevant items of this schedule).
Supply, filling and topping up new transformer oil of dielectric strength not be less than 60 kV and conforming to IS 335: 1993 complete all as specified and as directed.
Dismantling existing HT bushing with copper stud including disconnection of electrical connection and replacement of porcelain bushing vitreous, brown colour, 33 kV grade along with a set of oil seals & copper alloy stud, nuts, washers etc. of suitable size for primary side (HT side) of outdoor type 33 kV for distribution transformer of capacity upto 500 kVA of 33 kV/ 433 kV of any make complete all as specified and as directed.
S & F in repairs 25 mm dia gunmetal drain valve of transformer as per existing one along with brass/ gun metal dummy cap complete all as specified and as directed.
S & F in repairs 50 mm dia gunmetal drain valve of transformer as per existing one along with brass/ gun metal dummy cap complete all as specified and as directed.
M & L for replacement of silica gel, indicating type, 4 to 6 mm standard size of the particle, blue colour for transformer of any capacity.
S & F in repairs silica gel breather including silica gel, indicating type, 4 to 6 mm standard size of the particle, blue colour for transformer of capacity upto and including 500 kVA complete all as specified and as directed.
Disconnecting, taking down power transformer outdoor type 33 kV /433 V having capacity upto 315 kVA, transportation to the workshop for repairs including opening of transformers cover, draining of oil, de-tanking of core and coil assembly, cleaning, washing of dust and dirt from all parts including core, tank and cooling tubes radiators etc., joint inspection for estimate, replacement of defective parts, assembly, stage inspection, re-tanking, oil filtration/ dehydration, fill dehydrated oil and fresh oil and testing the repaired transformers for all the routine tests as per IS 2026 (Part 1): 2011 with latest amendments. Note: - (a) Transformer oil shall be drained out by the contractor in suitable capacity mild steel drums to be arranged by the contractor. The said drained out transformer oil shall be refilled in the transformer duly dehydrated after repair and the cost thereof shall be included in unit rate quoted against the respective item of this schedule and paid separately. (b) Rewinding of both HT & LT coil shall be measured and paid for separately under respective item of this schedule. (c) Transportation charges for transportation of transformer from site to workshop and after repair, workshop to site shall be borne by the contractor and cost thereof shall be deemed to be included in the unit rate quoted for this item. (d) The spare parts excluding nuts, bolts, washer shall be measured and paid for separately (e) The said transformer shall be repaired in reputed workshop as decided by the GE. (f) Testing of transformer after repair shall be carried out as per IS 2026 (Part 1): 2011 and the cost of testing shall be deemed to be included in unit rate quoted against this item. (g) The IR value of the dried winding before inserting the core in the shell shall be measured and recorded.
M & L for rewinding of coils on primary side of transformer of any capacity using proper size, double paper covering, ordinary copper winding wires conforming to IS 7404 (Part-1): 1991 as per existing size, turns and insulation class including connecting minor insulation materials suitable for 33 kV/ 433 V transformer complete all as specified and as directed. (Note: - Weight of only winding wire shall measured for payment purpose.)
M & L for rewinding of coils on secondary side of transformer of any capacity using proper size, double paper covering, ordinary copper winding wires conforming to IS 7404 (Part-1): 1991 as per existing size, turns and insulation class including connecting minor insulation materials suitable for 33 kV/ 433 V transformer complete all as specified and as directed. (Note: - Weight of only winding wire shall measured for payment purpose.)
M & L for tap changer off load type suitable for transformer of capacity 250 kVA to 500 kVA complete all as specified and as directed.
Supply only porcelain bushing vitreous, brown colour, 33 kV grade along with a set of oil seals & copper alloy stud, nuts, washers etc. of suitable size for primary side (HT side) of outdoor type 33 kV for 500 kVA distribution transformer of 33 kV/ 433 kV of any make
Supply only porcelain bushing vitreous, brown colour, 433 V grade along with a set of oil seals & copper alloy stud, nuts, washers etc. of suitable size for primary side (LT side) of outdoor type 433 V for 500 kVA distribution transformer of 33 kV/ 433 kV of any make
M & L for spray painting of transformers (any type power or distribution)) of capacity upto and including 250 kVA ( in situ ) outdoor type, installed and located at different sites in scattered area under the GE including the following: - (a) preparation of old surfaces by cleaning, scrapping, rubbing/ polishing etc. complete. (b) Spray painting with two coats of synthetic enamel paint of approved make / quality all as directed at site. (c) Writing the SM MES No of transformer on MS body of transformer all as directed .
M & L for spray painting of transformers (any type power or distribution)) of capacity above 300 kVA and upto and including 500 kVA ( in situ ) outdoor type, installed and located at different sites in scattered area under the GE including the following: - (a) preparation of old surfaces by cleaning, scrapping, rubbing/ polishing etc. complete. (b) Spray painting with two coats of synthetic enamel paint of approved make / quality all as directed at site. (c) Writing the SM MES No of transformer on MS body of transformer all as directed.
M & L in repairs for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT, 250 mm X 200 mm complete all as specified and as directed.
Supply and erection in repairs of three piece metal oxide lightning arrestor suitable for 33 kV continuous operating voltage (3 phase) with rated voltage 36 kV (rms) with nominal discharge current rating of 2.5 kA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete as specified and as directed.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. or carrying to MES store (spare/components for replacement to be provided free by department)
Supply and replace drop out fuse assembly, triple pole mounted on polymer HT insulator 6 Nos and mild steel galvanised steel frame rating upto 200 Amp, 33 kV complete with drop out fuse and electrical connections, jumpering by ACSR conductor and connectors complete all as specified and directed.
Supply and replace for 33 kV Drop out fuse assembly, double stack channel type , triple pole mounted on porcelain HT insulator 6 Nos and mild steel galvanised steel frame rating upto 200 Amp, 33 kV complete with DO fuse and electrical connections, jumpering by ACSR conductor and connectors complete all as specified and directed.
S & F gang operated air break switch, three poles, outdoor type, nominal system voltage 33 kV, rated voltage 36 kV, rated normal current 400 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 70 kV (rms) (ii) across the isolating distance 80 kV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 170 kV (Peak) (ii) across the isolating distance 195 kV (Peak), Rated short-time withstand current 20 kA for 3 seconds, rated peak withstand current 50 kA for climatic conditions at the site, mechanically operated mounted on polymer insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed.
M & L for taking out and repairing/overhauling of air break gang operated switch with DO fuse unit 200 Amp/400 Amp capacity triple pole, mechanically operated mounted on insulators and steel frame installed vertically / horizontally ,replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothing and polishing of electric contacts with providing conducting jelly of contacts refixed the same after repair complete including new nut, bolts and washer etc all as specified and directed. (Note: - The quoted rate by contractor shall include the fixing of the old parts and the new parts. The new parts shall be measured and paid for separately under the relevant items.)
Supply only male contact/ moving contact blade
Supply only female contact fix contact jaw
Supply only tinned flexible copper jumper 200 Amp
Supply only mild steel jumper carrier
Supply only back contractor plate
Dismantling insulators any type, any size complete all as specified and as directed.
S & F porcelain pin insulator, Type B, Nominal System voltage 33 kV, highest system voltage 36 kV, visible discharge test voltage 27 kV, wet power frequency withstand voltage 75 kV, power frequency puncture withheld voltage 180 kV, impulse withstand voltage 170 kV, minimum total creepage distance 580 mm, minimum failing load 10 kN, of suitable size with galvanised steel insulator pin, nut, washers complete all as specified and as directed.
S & F porcelain disc insulator, ball and socket type, Type B, Nominal System voltage 33 kV, highest system voltage 36 kV, visible discharge test voltage 27 kV, wet power frequency withstand voltage 75 kV, impulse withstand voltage 170 kV, minimum total creepage distance 580 mm, minimum failing load 70 kN, of suitable size with galvanised steel stud pin, nut, washers complete all as specified and as directed.
S & F polymeric composite disc insulator, ball and socket type, Type B, Nominal System voltage 33 kV, highest system voltage 36 kV, visible discharge test voltage 27 kV, wet power frequency withstand voltage 75 kV, impulse withstand voltage 170 kV, minimum total creepage distance 580 mm, minimum failing load 70 kN, of suitable size with galvanised steel stud pin, nut, washers complete all as specified and as directed.
S & F polymer pin insulator, Type B, Nominal System voltage 33 kV, highest system voltage 36 kV, visible discharge test voltage 27 kV, wet power frequency withstand voltage 75 kV, power frequency puncture withheld voltage 180 kV, impulse withstand voltage 170 kV, minimum total creepage distance 580 mm, minimum failing load 10 kN, of suitable size with galvanised steel insulator pin, nut, washers complete all as specified and as directed.
Dismantling cross-arms of mild steel channel or angle sections etc. complete and setting aside for re-use or removing to store or for schedule of credit
Fixing only cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
S & F in repairs earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32 mm X 6 mm galvanised mild steel strip complete all as specified and as directed.
M & L for earthing complete with copper plate earth electrode 600 mm X 600 mm X 3.15 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm copper strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
S & F in repairs earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 32 mm X 6 mm copper strip complete all as specified and as directed.
M & L for preparing and painting on steel tubular swaged pole 410 SP-55 (11.00 metre long) including cross arms, GI brackets with two coats of aluminium paint over a coat of aluminium red oxide primer on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
M & L for preparing and painting on steel tubular swaged pole 410 SP-31 (9.00 metre long) including cross arms, GI brackets with two coats of aluminium paint over a coat of aluminium red oxide primer on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
M & L for preparing and painting on cross arms, GI brackets of steel tubular swaged pole of any height with two coats of aluminium paint over a coat of aluminium red oxide primer on exposed portion complete all as specified and as directed.
M & L for loose filling with broken stone or boulder aggregates of gauge 80 to 150 mm in soakage pits, soakage wells, on open space complete all as specified and as directed.
M & L for loose filling with broken stone or boulder aggregates of gauge 40 to 80 mm in soakage pits, soakage wells, on open space etc. complete all as specified and as directed.
Surface dressing of installation/sub station area by removing of grass, creepers, etc. from the roof of the building, in fencing and surrounding area of installation building complete all as specified and directed.
M & L for trimming of branches of trees touching HT/LT Electric over head line and making clear about 3 m in radius and carrying and disposal where directed not exceeding 50 m complete all as directed. Note :- Vehicle and othe T&P shall be arranged by the contractor at own cost.
Dismantling steel poles/ struts, any size, transporting to store and stacking or for schedule of credit
M & L for steel tubular swaged pole 410 SP-55 (11.0 metre long) including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed.
M & L for steel tubular swaged pole 410 SP-31 (9.0 metre long) including CI base plate, finial taper plug, bolts, nuts & screws as per IS 2713 Part -I & II including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer on exposed portion and making strips of width 30 cm upto 1.5 m from the ground level in black and white shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer and two coats of anticorrosive paint over a coat of red oxide primer to embedded portion of pole including making good to match existing area complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
M & L for laying of bricks locally available sub class 'B' bricks, non-modular sizes as per IS 1077: 1992 for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and directed by Engineer- in-charge.
S & F in repairs batteries 12 V, 100 AH, lead acid, maintenance free with 36 months warranty complete all as specified and as directed.
Restringing only ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag complete all as specified and as directed.
Restringing only galvanised iron wire of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag complete all as specified and as directed.
Dismantling ACSR or AAC conductors removing to store or taken on schedule of credit complete all as specified and as directed.
Supply, fixing and stringing ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag complete all as specified and as directed.
S & F earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 4 mm dia galvanised mild steel wire complete all as specified and as directed.
M & L for cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 mm or 4 mm dia complete all as specified and as directed.
M & L in repair for disconnecting and taking out worn out jumpers of HT / LT overhead line at cut point/ at two pole/ four pole structure of any size any length as per existing after removing binding wire connector of AB switch/DO fuse unit, replacement of old jumper with the new ACSR conductor (Mink/ Dog conductor as directed by Engineer-in-Charge) Jumpers Including PVC sleeve in colour coding R/Y/B of same size and length including new binding wire connectors suitable for AB switch/DO fuse unit, with providing conducting jelly complete all as specified and as directed. (Note: -Each Jumper to be measured separately)
Taking down main switch/MCB/MCCB/MCB DB/ MCCB DB/ sheet metal enclosure by disconnecting the electric supply including MCB/MCCB/Cut out etc. any type and size complete all as specified and as directed.
S & F MCCB rated current(In): 630A, ultimate short circuit breaking capacity (Icu): 50 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply complete all as specified and as directed.
S & F MCCB rated current(In): 400A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply complete all as specified and as directed.
S & F MCCB rated current(In): 250A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply complete all as specified and as directed.
S & F MCCB rated current(In): 200A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, four pole, suitable for 415 V, 50 Hz AC supply complete all as specified and as directed.
S & F MCCB rated current(In): 200A, ultimate short circuit breaking capacity (Icu): 36 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply complete all as specified and as directed.
S & F MCCB rated current(In): 160A, ultimate short circuit breaking capacity (Icu): 25 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply complete all as specified and as directed.
S & F MCCB rated current(In): 100A, ultimate short circuit breaking capacity (Icu): 25 kA, service short-circuit breaking capacity (Ics): 100% of Icu, impulse withstand voltage (Uimp): 8 kV, insulation voltage (Ui): 690 V, utilization category: A, pollution degree 3, degree of protection: IP40, adjustable thermal (80% to 100%) and adjustable magnetic (5-10 times) setting, three pole, suitable for 415 V, 50 Hz AC supply complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 25 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 35 sqm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 50 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 70 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 120 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 150 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 185 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 240 sqmm complete all as specified and as directed.
S & F cable jointing kit for 1100 V (Earthed) grade cable for straight through heat shrink type joint, indoor/ outdoor type complete with jointing material and accessories suitable for 3 core with reduced neutral conductors (3½ core) XLPE armoured aluminium conductor cable of size 300 sqmm complete all as specified and as directed.
S & F composite spacer for maintaining the specified spacing between the conductors for 415 V/ 240 V overhead line for single phase 2 wire system, made of poly propylene in a single mould except clamping pieces, 25 mm width X 12 mm depth, projected 30 mm beyond the external conductor on both sides complete all as specified and as directed.
S & F composite spacer for maintaining the specified spacing between the conductors for 415 V/ 240 V overhead line for single phase 3 wire system, made of poly propylene in a single mould except clamping pieces, 25 mm width X 12 mm depth, projected 30 mm beyond the external conductor on both sides complete all as specified and as directed.
S & F composite spacer for maintaining the specified spacing between the conductors for 415 V/ 240 V overhead line for three phase 4 wire system, made of poly propylene in a single mould except clamping pieces, 25 mm width X 12 mm depth, projected 30 mm beyond the external conductor on both sides complete all as specified and as directed.
S & F composite spacer for maintaining the specified spacing between the conductors for 415 V/ 240 V overhead line for four phase 4 wire system, made of poly propylene in a single mould except clamping pieces, 25 mm width X 12 mm depth, projected 30 mm beyond the external conductor on both sides complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 10 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 2 core, nominal cross sectional area of main conductor 10 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 16 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 4 core, nominal cross sectional area of main conductor 16 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 25 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 25 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 35 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 35 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 50 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 50 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 70 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 70 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 95 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 95 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 120 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 120 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 1100 V, nominal cross sectional area of main conductor 150 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Supply, laying, jointing, testing and commissioning cross-linked polyethylene (XLPE) insulated cable for working voltages of 1100 V, PVC sheathed, armoured, 3 core with reduced neutral conductors (3½ core), nominal cross sectional area of main conductor 150 sqmm, stranded aluminium conductor, ISI marked as per IS 7098(Part-I): 1988 including cable glands, lugs etc. to suit the cable size and to be laid in trenches, fixed along pole, under floors, through GI pipe laid under floors/roads, through concealed GI pipe along wall etc. complete all as specified and as directed.
Supplying & laying including taking town in trenches, in road cutting and along pole 40 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 50 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying including taking down in trenches, in road cutting and along pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-16 as per IS 8309: 1993 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-25 as per IS 8309: 1993 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-50 as per IS 8309: 1993 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-70 as per IS 8309: 1993 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-95 as per IS 8309: 1993 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-120 as per IS 8309: 1993 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-150 as per IS 8309: 1993 complete all as specified and as directed.
S & F compression type aluminium tubular terminal ends for crimping to aluminium conductors for XLPE cable of designation CAAX-240 as per IS 8309: 1993 complete all as specified and as directed.
Supply only pressure sensitive adhesive plasticized PVC tapes with non-thermosetting adhesive, designation F-PVC/90/0/Tp, general purpose application for electrical insulation, plasticized polyvinylchloride backing material, thickness 0.125 mm, width 25 mm, length 20 metre all as per o IS 7809 (Part 3/section 1): 1986
Supply only copper fuse wire of different capacity (10 to 50 Amps)
S & F in repairs glow sign board made of retro reflective Type IV high intensity prismatic grade sheeting in twin colours conforming to IRC 67- 2012, digitally colour printed in 3D font as directed to be fixed on mild steel pipe and angle iron frame complete all as specified and as directed. Note: Angle iron and mild steel shall be measured and paid separately.)
S & F nominal 3.0 mm + 10% thick insulating mats made of elastomer conforming to IS-15652: 2006 and meeting the requirement of IS- 5216 (Part -1 & 2) IS 8437, IEC-479 Pub -1 along with suitable adhesive/ homebound, PV resin water proofing compound and sealing material as per recommendation of Annex 'A’, Clause- 'C’ of IS- 15652 and suitable for class - C upto 33 kV complete all as specified and as directed.
M & L for 50 mm nominal bore, medium grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 to support signboard, poster, etc., welded suitably as per IS 5206: 1983 including necessary nuts, bolts etc. complete all as specified and directed by Engineer-in-charge.
M/S RAKESH TRADERS
PRADEEP SISODIYA
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .