Tender Value
₹55.8 Cr
EMD Value
₹55.9 L
Closing Date
15 Jun 2026, 5:30 pm
Karnataka Power Transmission Corporation Limited
1Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District,2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District,3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District,on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Dismantling and Civil Works) of all Materials/Equipments, Testing and Commissioning.
303851
KPTCL/2026-27/SS/WORK_INDENT3786
Open
Sub-Station
KPTCL CEE Corporate Office Tendering and Procurement Bengaluru
4 documents required · 4 mandatory
Documentary proof for Clause No. 3.2(b)(i) (GIS Sub station) of ITT such as P.O, LOI/LOA, DWA, Work done Certificates, Performance Certificates issued by the end users not below the rank of Executive/Divisional Engineer.
Documentary proof for Clause No. 3.2(b)(ii) (UG cable laying) of ITT such as P.O, LOI/LOA, DWA, Work done Certificates, Performance Certificates issued by the end users not below the rank of Executive/Divisional Engineer
Partner of the consortium who does not meet stipulated QR at 3.2 b(i) & 3.2 b(ii), such partner shall have minimum 3 years of experience in execution of electrical works as on the date of bid submission. Such partner shall upload the work award copies and performance certificates issued by the Government authorities/Power Utilities (end user) in support of the same
3.2 (d) A (1) (a) of ITT: Order completion certificate, P.O. copies, LOA/DWA, Performance Certificates by Indian Govt. Power Utilities not below the rank of Executive/Divisional Engineer-GIS manufactutrer-1 & 2
3.2 (d) A (1) (b) of ITT: Order completion certificate, P.O. copies, LOA/DWA, Performance Certificates by Indian Govt. Power Utilities not below the rank of Executive/Divisional Engineer (quality and the performance of GIS modules were satisfactory and no claims are pending against the Bidder) -GIS manufactutrer-1 & 2
Clause no. 3.2 (d) A (2) (a) of ITT :Documentary Proof for Order completion certificate, P.O. copies, LOA/DWA, Performance Certificates by end users (Indian Government Power Utilities) not below the rank of Executive/Divisional Engineer -Cable manufacturer-1 & 2
Clause no. 3.2 (d) A (2) (b) of ITT: Documentary Proof for Order completion certificate, P.O. copies, LOA/DWA, Performance Certificates by end users (Indian Government Power Utilities) not below the rank of Executive/Divisional Engineer-Cable manufacturer-1&2
3.2 (d) B (2) (a) of ITT: P.O. copies or LOA/DWA & Performance certificates by end user (Utilities) not below the rank of Executive/Divisional Engineer-Cable accessories manufacturer-1&2
Cl.No.3.2(d)(A) (3) (a) of ITT: Necessary documentary evidence if Power transformer manufacturer participates as a Bidder.
Cl.No.3.2(d)(A)(3)(b) of ITT :Necessary documentary proof such as P.O. copies, LOA/DWA, Performance Certificates issued by the end users (Indian Government Power Utilities) not below the rank of Executive/ Divisional Engineer, should be uploaded along with the offer
Cl.No.3.2(d)(A)(3)(b) of ITT :Necessary documentary proof such as P.O. copies, LOA/DWA, Performance Certificates issued by the end users (Indian Government Power Utilities) not below the rank of Executive/ Divisional Engineer, should be uploaded along with the offer.
shall upload Lead Bidder : Audited financial statements including Balance sheets, Profit and Loss statements, Turnover Certificate in the prescribed format (Annexure-XX), Auditors Reports of the last five years preceding the date of bid submission as per cl. no. 3.2 (a) of ITT
shall upload Consortium member(In case of Consortium) :Audited financial statements including Balance sheets, Profit and Loss statements, Turnover Certificate in the prescribed format (Annexure-XX), Auditors Reports of the last five years preceding the date of bid submission as per cl. no. 3.2 (a) of ITT
shall upload Lead Bidder : Certificate from Chartered Accountants for split details of financial Turnover and GST in the prescribed format (Annexure-XX) of Lead Bidder.
shall upload Consortium partner (In case of Consortium) : Certificate from Chartered Accountants for split details of financial Turnover and GST in the prescribed format (Annexure-XX) of Consortium partner
Clause No: 3.6 of ITT: Lead Bidder : Assessed available tender capacity such as, i)existing commitments and ongoing works statement & countersigned by Employer in charge, not below EE or equivalent OR certified by CA/Cost Auditor & PO/Work Award copies ii) Self declaration iii) Certificate from CA for split details of Ex-works values and GST of Contract values of the works in the prescribed format as at Clause No. 1.5 of Section-3: Qualification Information
Clause No: 3.6 of ITT: Consortium member(In case of Consortium): Assessed available tender capacity such as, i)existing commitments and ongoing works statement & countersigned by Employer in charge, not below EE or equivalent OR certified by CA/Cost Auditor & PO/Work Award copies ii) Self declaration iii) Certificate from CA for split details of Ex-works values and GST of Contract values of the works in the prescribed format as at Clause No. 1.5 of Section-3: Qualification Information
Clause no.3.3 (b) of ITT (Liquid Assets and /or availability of credit facilities): Lead Bidder : Banker Certificate duly signed by authorized person in the prescribed format as at Annexure XVIII of Section-4
Clause no.3.3 (b) of ITT (Liquid Assets and /or availability of credit facilities): Consortium partner(in case of Consortium) : Banker Certificate duly signed by authorized person in the prescribed format as at Annexure XVIII of Section-4
Cl.No.3.2(d)(A) (3)(d) of ITT : Type test reports for Power transformer
Cl.No.3.2(d)(A)(3) (e) of ITT : Temperature rise Test report for Power transformer
Cl.No.3.2(d)(A) (3)(f) of ITT- Dynamic Short Circuit test reports for Power transformer
Undertaking-1 wrt to Type test reports & Dynamic Short Circuit test reports if Power transformer manufacturer participates as a Bidder.
Consortium Agreement
Power of Attorney in favour of all the persons signing the documents, Power of Attorney for Consortium, combined power of attorney signed by the signatories of all the members of consortium as an evidence of authorization for nominating leader (Prime Bidder) of consortium.
Valid Super Grade Electrical Contractors License of both Lead Bidder & Consortium partner (in case of Consortium) issued by the Govt. of Karnataka OR valid Form J-1 Verification Letter issued by Chief Electrical Inspectorate, Govt. of Karnataka to Other State Electrical Contractor License Holder for the highest system voltage specified in the tendered work
Certificate of Incorporation of the Individual/Consortium or any relevant document in respect of Partnership/Proprietorship firms as per the tender document
Lead Bidder and Consortium Partner(in case of Consortium) should have valid GST registration with GSTIN number PAN Card and ISO Certificates.Note The successful Bidder and his consortium partner who have GST registration in other States should have GST registration in the State of Karnataka mandatorily at the time of execution of the Contract Agreement.
No Deviation Certificate
Letter of Undertaking as in Annexure
Qualification and experience of key Personnel proposed for carrying out the Work
Description of the Tools & Plant available with them for execution of the Work
undertaking to source the supply of equipment/material from KPTCL approved Vendors only as per the QR for Vendor registration, available in the KPTCL website i.e., https://kptcl.karnataka.gov.in, Link Tender and Procurement - application for Vendor registration etc.
undertaking to source the supply of equipment/material from Vendors who meet the eligibility clauses regarding restriction on procurement from a country which shares land border with India as specified in Annexure- XVII.
Details of Works on hand and Ongoing contractual commitments
Copies of original documents defining the Constitution or Legal Status, place of Registration and Principal place of Business of the Bidder (Lead Bidder & Consortium Partner) , written Power of Attorney to the Signatory of the Bid to commit the Bidder (Lead Bidder & Consortium Partner) to the Contract along with the resolution passed in this regard by the Board of Directors all the Partners of the Firm.
Tenderer shall upload declarations for Deviations, if any as per Schedule-5 and Schedule-6 of the Techno Commercial sheets
Techno Commercial sheets duly filled
Clause No. 3.6 Note (ii) of ITT: Lead Bidder : self-declaration stating that the information with regard to assessed available tender capacity (Works on Hand) furnished are correct.
Clause No. 3.6 Note (ii) of ITT : Consortium partner(in case of Consortium) self-declaration stating that the information with regard to assessed available tender capacity (Works on Hand) furnished are correct.
Scanned copy of the Bank Guarantee/ Insurance Surety Bond towards EMD as per 13.1 of ITT
Self-declarations of Lead Bidder & Consortium partner (In case of Consortium) in respect of Litigation, dis-qualification due to non-performance, Risk & cost clause and Restriction on border sharing as specified in Annexure- XVI& Annexure-XVII as per Clause No.2.4 of ITT
Self-declarations (Technical Snag) -GIS manufacturer 1&2 - cl .no. 2.4 (d) of ITT
Self-declarations (Technical Snag) -Cable manufacturer-1&2 - cl. no.2.4 (d) of ITT
3.2 (d) A (1) (d) of ITT: GIS Manufacturer-1 - Type tests reports
3.2 (d) A (1) (d) of ITT :GIS Manufacturer-2-Type tests reports
3.2 (d) A (1) (d) of ITT Note-4 of ITT:If Type test reports of Parent company/ collaborator - letter - legally endorse guarantee by Parent company/ Collaborator
Cl.No.3.2(d)(A)(2) (c) of ITT : Cable Manufacturer-1-Type tests reports
Cl.No.3.2(d)A(2) (c) of ITT:Cable Manufacturer-2 - Type tests reports
Cl.No.3.2(d)A(2) (c) Note-ii of ITT: Undertaking-2 Joint Deed of undertaking with Cable manufacturer-1&2
Cl.No.3.2(d)A(2) (c) Note-ii of ITT:Undertaking-2A-- Joint Deed of undertaking with Cable accessories manufacturer-1&2
Cl.No.3.2(d)A(2) (c) Note-iv of ITT: Undertaking-4 (Range of Type approval - Cable)
Cl.No.3.2(d)A(2) (c) Note of ITT:Undertaking-2B (Special tests on the Cable of same Voltage class, design & cross section)
3.2 (d) A (2) (c)-Note-v of ITT: Undertaking-5 (Type tests on UG Cable & its accessories)
Cl.no.3.2 (d) B(2) (b) of ITT:Cable joints & terminations Manufacturer-1 - Type test reports
Cl.no.3.2 (d) B(2) (b) of ITT:Cable joints & terminations Manufacturer-2 - Type test reports
Cl.no.3.2 (d) B(2) (b) Note-a) of ITT:Undertaking-3 (propose manufacturers- GIS, EHV Underground cables and cable accessories i.e., Joints & Terminations)
Undertaking-6 : Joint Deed of undertaking for GIS equipments manufacturer-1&2
Undertaking-7
Information on litigations in which the Tenderer is involved as per prescribed format as at 1.12 of Qualification Information
Upload all relevant documents as per NIT, tender documents and technical specifications
₹7,500
₹55.9 L
4 Jun 2026
4 Jun 2026
15 Jun 2026
15 Jun 2026
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNO - COMMERCIAL SHEETS
NOTE* For detailed scope of the work please refer Bid Documents.
BIDDERS TO READ CAREFULLY
THE FOLLOWING DOCUMENTS [DULY SIGNED BY AUTHORISED PERSON, WHEREVER NECESSARY] ARE TO BE UPLOADED AND BANK GUARANTEE/INSURANCE SURETY BOND TOWARDS EMD OVER AND ABOVE RS.1.00LAKH AS PER ANNEXURE-II OF THE BID DOCUMENT SHALL BE SENT IN ORIGINAL TO CHIEF ENGINEER ELECTY., (T&P), KPTCL, BENGALURU SO AS TO REACH THIS OFFICE AFTER THE LAST DATE OF SUBMISSION OF BID AND ON OR BEFORE THE DATE & TIME NOTIFIED FOR OPENING OF TECHNO COMMERCIAL BIDS, FAILING WHICH THE BID WILL NOT BE OPENED. 1) NO DEVIATION CERTIFICATE (SCHEDULE-16). 2) EMD/BID SECURITY AS DETAILED IN CLAUSE NO. 13 of ITT. 3) BANK GUARANTEE issued either by a Nationalized/Scheduled Bank OR INSURANCE SURETY BOND issued by Insurance Company authorized by Insurance Regulatory and Development Authority of India (IRDAI) TOWARDS BALANCE EMD/BID SECURITY. (For the balance EMD above Rs. 1.00Lakhs) (SCHEDULE-17) - as detailed in Clause No. 13 of ITT-The Bidder shall scan the Bank Guarantee/INSURANCE SURETY BOND towards EMD and upload the same in the prescribed format in the slot specified for “EMD and Tender Fee Payments” in the e-procurement portal to enable the owner for verification of EMD BG/ISB at the time of opening of Techno Commercial Bid, failing which the offer will be rejected. 4) LETTER OF UNDERTAKING (SCHEDULE-18). 5) CONSORTIUM AGREEMENT (IF APPLICABLE-SCHEDULE-19) 6) POWER OF ATTORNEY (SCHEDULE- 20). 7) ANY OTHER AGREEMENTS /UNDERTAKINGS/SELF DECLARATIONS SPECIFIED IN THE TENDER.
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
BID PROPOSAL SHEET
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. :
Bid Proposal Reference :
Person to be contacted :
E-Mail Address:
The Chief Engineer, Electricity,
Tendering & Procurement, KPTCL,
Indhana Bhavana, Bangalore - 560 009.
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
a) * We have submitted bid as individual Bidder. (Indicate Name of the Individual Bidder)
b) * We have submitted bid in Consortium with the following Bidders. (Key in Consortium)
Name of the Consortium Partner Scope / Participation of each Consortium Partner
(* Fill-up whichever is applicable)
1 We, the undersigned Bidder, having read and examined in detail the specifications and all the Bidding documents of the said work and hereby propose to design, manufacture/fabricate, shop test, supply on FOR site basis, and carry out the erection, testing and commissioning including civil, structural and architectural works for
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
2 PRICES AND VALIDITY :
2.1 We declare that the Prices stated in our Proposal are in accordance with subject Bid Documents (including Clause No.40 of "Conditions of Contract (CC)" & Clause No.12 of Instruction to Tenderers (ITT) of Bid Documents. We further declare that all Ex-works price/CIF components of Spares, Maintenance and Testing Equipments and other charges viz., Freight and Insurance, Type Test charges and other charges stated in our proposal shall be as per the Tender conditions. All the Price and other terms and conditions of this Proposal are valid during the Performance of the Contract.
2.2 All Duties, such as Custom Duties on imports, Levies, Surcharge/Cess etc., if any applicable on the transaction excluding GST are included in the Bid Price and shall be to Our account and the Owner is not having any liability whatsoever on this account, whatever may be the contrary elsewhere in the Bid documents. However the component of Duties included in the Bid Price are separately indicated in Schedule - 2 for TDS purpose. We further confirm that our Bid Prices as quoted in Schedule-I, include all import Duties and levies including Licence fees lawfully payable by us on imported items and all other Duties and Levies applicable on Bought-out Components, Materials, Equipment and other items and confirm that any such Duties and Levies additionally payable shall be to our account. We further confirm that, no Sales Tax in any form shall be payable by Owner either for Bought-out items which are despatched by our Sub-Suppliers directly to the Project Site or for items Supplied directly by us. We confirm that, the Prices quoted by us are excluding GST.
2.3 We declare that we have noted and considered Clause No.39 of Conditions of Contract (CC ), Clause No. 11.11 of Instruction to Tenderers(ITT) of Bid Documents regarding Taxes and Duties and quoted our Prices accordingly. We further agree for TDS as per Statutory stipulations.
2.4 The Bid Prices, the Price components of the various items in our Scope of Supply, Erection including Testing & Commisisoning, Civil and Mandatory spares is quoted in Percentage rate Financial Bid in KPP Portal for this proposal..
3 CONSTRUCTION OF THE CONTRACT : We, declare that we are making the Offer on the basis of Single Contract for the entire Scope of the Package in accordance with Clause No.26.2 of Instruction to Tenderers (ITT) of Bid Document.
4 We having studied Clause No.39 of Conditions of Contract (CC ), Clause No. 11.11 of Instruction to Tenderers(ITT) of Bid Documents , relating to Tax and we hereby, declare that if any income-tax, surcharge on income tax or any other corporate tax is attracted under the law, we agree to pay the same.
5 Bid Security/ EMD : We have enclosed a Bid Security through e-Payment mode for a sum of Rs.1.00Lakhs and remaining amount of Rs..........Lakhs ( above Rs.1.00 Lakhs) in the form of Insurance Surety Bond (ISB) issued by Insurance Company authorized by Insurance Regulatory and Development Authority of India (IRDAI) OR in the form of Bank Guarantee in original valid for a period of 225 days from last date of bid submission and liable to be forfeited in accordance with Bid Documents. (Mode of Payment towards EMD is as detailed in CLAUSE NO. 13 of ITT & Clause No. 5 of NIT)
We have also ensured that the above Bid Guarantee furnished by us is in line with the Bid Documents and complete in respect of following :
1. Value of Non judicial Stamp Paper purchased in the name of executing Bank is as per Stamp Act.
2. Power of Attorney Number and Date as well as Signature and Full Name and Designation of Executant along with Bank's Stamp are there.
3. Signature, Full Name, Designation and address of Witness are there.
4. Completed Mailing address of the Head Office of the Bank is indicated.
6.1 We declare that the Works shall be performed strictly in accordance with the Specifications and Documents except for the variations and Deviations, all of which have been detailed out exhaustively in the following Schedules, irrespective of whatever has been stated to the contrary anywhere else in our Proposal.
a Commercial Deviations Schedule Schedule - 5
b Technical Deviations Schedule Schedule - 6
6.2 We further confirm that Specified Stipulation of following Clauses are acceptable to us and No Deviation / Exceptions are taken on any account whatsoever in the following Clauses.
a. Terms of payment Clause No. 37 of Section-5,Conditions of Contract (CC) and Clause No.8 of Special Conditions of Contrac (SCC)
b. EMD/Bid Security Clause No. 6, Section :1, Invitation for Tenders (IFT) and Clause No. 13, Section :2, Instruction to Tenderer (ITT)
c. Contract Performance Guarantee Clause No. 29 of Section:2, Instruction to Tenderers (ITT).
d. Penalty for delay Clause No. 41 of Section-5 : Conditions of Contract (CC).
e. Price Basis/ Price adjustment Clause No. 40 of Section-5 :Conditions of Contract (CC).
f. Defects Liability Period/Guarantee Clause No. 10 of Section-5 Special Conditions of Contract (SCC)
g. Work Schedule Clause No.17 of Section:5 Conditions of Contract (CC)
h. Taxes and Duties Clause No. 11.11 of Section-2: Instruction to Tenderers (ITT).
Further, we agree that additional conditions, if any, found in the Proposal Documents other than those stated in Deviation Schedules, save that pertaining to any rebates offered, shall not be given effect to.
7 PERFORMANCE GUARANTEE ; We declare that the ratings and performance figures of the equipment to be supplied and erected by us are guaranteed. The Guaranteed particulas of different equiment in our Scope are enclosed in Data Requirement Sheets.
8 BID PRICING : We further, declare that the Prices stated in our Proposal are in accordance with your ITT & SCC & all other relevant clauses of Bid Documents.
9 PRICE ADJUSTMENT : We declare that the Prices quoted by us are in accordance Clause No. 40 of Section-5 :Conditions of Contract (CC)
10 SPECIAL TOOLS AND TACKLES : We have given a list of Special Tools and Tackles in Schedule - 7 and Prices thereof are included in our lumpsum Bid Price. We further agree that any items of Special Tools and Tackles, though not included in the aforesaid list, but required for effective Erection, Testing, Commissioning & Operation of the Equipments of Substations & Transmission lines shall also be furnished by us, at no extra cost to you.
11 ADDITIONAL INFORMATION : In addition to the information called for in these Proposal Sheets, we have included with this Proposal, additional information as listed in Schedule - 8. We further confirm that such additional information does not imply any additional deviation beyond those covered in Schedule - 5 & 6 and in case of any contraction between these additional information and other provisions of Bid, the later will prevail.
12 QUALIFICATION DATA : We confirm having submitted the Qualification Data, as required by you in your Bid Documents in e-Procurement Portal along with this Proposal. Further we have filled in the information for Qualification Requirements in Schedule 9. In case you require any further information in this regard, We agree to furnish the same in time.
13 WORK SCHEDULE : If this Proposal is accepted by you, we agree to submit Engineering Data, Provide Services and complete the entire Work from time to time, in accordance with Schedules indicated in the Proposal. We fully understand that the Time Schedule stipulated in this Proposal is the essence of the Contract, if awarded. The completion schedule of the various Major Key Phases of the Work is indicated in Schedule - 11.
14 CONTRACT PERFORMANCE GUARANTEE ; We further agree that if our Proposal is accepted, we shall provide an irrecoverable Contract Performance Guarantee, of value equivalent to Five percent (5%) of the Amount Put to Tender (Excluding GST) plus additional security for unbalanced tenders in accordance with Clause 29 of Instructions To Tenderers (ITT) of the tender valid up to the end of ninety (90) days after the end of the Contract Guarantee Period mandatorily in the form of Insurance Surety Bonds (ISBs) issued by Insurance Company authorized by Insurance Regulatory and Development Authority of India (IRDAI) (OR) in the form of electronic Bank Guarantee (e-BG) from the Banks which are integrated with NeSL in the form attached as Annexure-III (Section 4: Formats of Annexures) in your favour in accordance with Clause 25.5 of ITT and Clause 43 of the CC (Conditions of Contract), as per the format given in Section 4 and enter into a formal agreement with you within Twenty (20) days from the date of issue of Letter of Intent to Award the Contract.
15 We, the partners of the Consortium whose Signatures are appended below, shall be liable jointly and severally for the execution of the Contract(s), in the event of Award, in accordance with the terms of Contract(s). The Lead Partner for this Bid - M/s .................................................................................... on behalf of the Consortium, is submitting the Bid. The Power of Attorney in favour of M/s .......................................................................................is enclosed.
16 BID PRICE : We declare that our lumpsum Price for the entire scope of work specified in the specifications and documents, shall be as indicated in Schedule - 1.
17 CHECK LIST : We have included a Checklist duly filled in Schedule 22
18 We, hereby, declare that only the Persons or Firms interested in this Proposal are named herein as Principals and that no other Persons are interested in the Proposal or in the Contract to be entered into, if we are awarded the Contract, and that this proposal is made without any connection with any other Person, Firm or Party likewise submitting a Proposal and that this Proposal is in all respect for and in good faith, without collusion or fraud.
19 We declare, in case our bid is accepted, that until a formal Contract is prepared & executed, this bid together with your written letter of acceptance thereof and your notification of award /Letter of Intent to Award the Contract shall constitute a binding contract between us. We further understand that you are not bound to accept the lowest or any bid you may receive.
Thanking you, we remain,
Yours faithfully,
Place Printed Name
Business Address Country of Incorporation (State or Province to be indicated)
Name and Address Principal Officer
Karnataka Power Transmission Corporation Limited
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
FILL ONLY IN LIGHT BLUE COLOURED CELLS.
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL, 9th Floor, Indhana Bhavana, BANGALORE - 560009
We declare that in terms of Clause No. 11 of ITT, Bid documents, the following are our lumpsum price in Rupees for the entire scope of work as specified in the Specifications and Documents.( Inclusive of all Taxes (Excluding GST) & Duties).
Total Lumpsum Price : ( In Figures)
Total Lumpsum Price : ( In Figures)
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 2 (1 of 2)-SUMMARY OF PRICE COMPONENTS
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
FILL ONLY IN LIGHT BLUE COLOURED CELLS.
Summary of Price Components
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
Summary price components for identified in accompanying specifications
( Name of the Work) as per the scope identified in accompanying specifications.
Sl no Description Amount in Rs. (Fill as "YES" against the above Price columns in case Prices are indicated in the Price templates)
Establishing Sub station Construction of Transmission Lines
A Material / Equipment Price (including Packing & Forwarding charges) in the Scope of the Contractor
Ex-works including all taxes & duties [As per schedules - 3A(i) for Station & 3B(i) for Line]
ii) Freight and Insurance Charges (Not Applicable) [As per schedules - 3A(i) for Station & 3B(i) for Line]
iii) Total FOR site price (i+ii)
B Mandatory spares price (including packing & forwarding charges)
Ex-works including all taxes & duties(As per schedule - 4)
ii) Freight and Insurance Charges(Not Applicable) (As per schedule -4)
iii)Total FOR site price (i + ii)
C Supply portion total FORD price [A+B]
D Erection portion:
i) Total charges for Erection, Testing & Commissioning of all Supply items [as per schedules-3A(ii) for Station, 3B(ii) for Line]
ii) Total charges for entire civil works [ as per Schedules-3C(i) for Station and 3C(ii) for Line]
iii) Total civil works, erection, Testing and commisioning charges (i)+(ii)
E Total Bid Price = C+D(iii) In figures : Rs.
Total Bid Price in Figures : Rs.
Total Bid Price in words : Rupees
Note: The erection charges shall include the charges for taking delivery at Owner's store, unloading, handling, storage, erection, testing and commissioning of all equipments and applicable GST.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 2 ( 2 of 2 ) - TAXES (Excluding GST), DUTIES & OTHER LEVIES
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
Fill IN LIGHT BLUE COLOURED CELLS.
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
Estimates of Indian Taxes (Excluding GST), Duties and Levies included in the Total Bid Price are as follows:
SL. No. Description of Applicable Tax (Excluding GST) / Duty / Levy Establishing Sub station Construction of Transmission Lines
Rate of Tax (Excluding GST)/ Duty / Levy Amount of Taxes (Excluding GST) / Duties in Rupees Rate of Tax (Excluding GST) / Duty / Levy Amount of Taxes (Excluding GST)/ Duties in Rupees
1 Applicable taxes (Excluding GST), duties & levies prevailing as on the last date of bid submission shall be quoted
i. Supply Portion
ii. Erection Portion
iii. Civil Portion
i. Supply Portion
ii. Erection Portion
iii. Civil Portion
i. Supply Portion
ii. Erection Portion
iii. Civil Portion
6 Building and other construction workers welfare Cess for Supply, Erection and Civil Portion works
8 a. Applicable Customs Duty (*) (Bidders shall also clearly indicate the breakup of Customs duty such as BCD, Cess,etc.,)
b. If there is any existing Treaty between India and the country from where the goods required for this project are proposed to be imported, then copy of the treaty shall be uploaded.
9 Other Taxes & duties if any (Specify) **
10 Other Taxes & duties if any (Specify) **
11 Total (Sum of 1 to 10)
(*) In case of CIF portion of Supply.
** Please Specify the nature of the other Taxes (Excluding GST) along with the details in the "Rate" Column.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 2A : SCHEDULE OF DISCOUNT
SHEET FOR TECHNOCOMMERCIAL OPENING (UN - PRICED)
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
FILL ONLY IN LIGHT BLUE COLOURED CELLS.
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
We hereby offer an unconditional discount on our quoted price in Schedule 2 (1 of2) as under. Any discounts offered anywere else in Bid shall not be considered.
Sl.No Nature of Discount Establishing Sub station along with construction of associated Lines
Percentage of discount Amount (in Rs.) Remarks
I Supply Schedules
b) Freight & Insurance (Not Applicable)
II Erection Schedules
III Civil Works Schedules
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE- 2 B - STATEMENT OF COMMERCIAL TERMS AND CONDITIONS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Details of payments made in the form of Credit card/Debit card/NEFT/RTGS/OTC (over the counter) as per the tender conditions should be keyed in against column no.3 (a) . BG Amount, BG No. and date, Name and address of the bank issuing the BG, validity of the BG should be keyed in against column no. 3 (b) .
FILL ONLY IN LIGHT BLUE COLOURED CELLS.
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
STATEMENT OF COMMERCIAL TERMS AND CONDITIONS
Sl. No. Particulars Details
1 Bid proposal form Uploaded.
2 No deviation certificate Uploaded.
3. a). EMD / Bid Security Bids shall be accompanied by bid security (EMD); 1) Up to Rs.1.00Lakh The following modes of payment will be provided as a part of e-Payment services. • Credit Card/Debit Card • Net Banking • NEFT/RTGS • Over-the-Counter (OTC) • IMPS For further detail regarding mode of e-payment of EMD in e-procurement platform, contact e-procurement cell, Government of Karnataka.
b). EMD amount above Rs.1.00Lakh by Bank Guarantee/Insurance Surety Bond (ISB)
4 Validity of the Bid.
5 Qualifying Requirements.
6 Financial capability
8 Taxes & Duties.
9 Completion Schedule
10 Defects Liability Period/Guarantee
11 Payment Terms
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 3A(i) - Price Breakup for - GIS Station Supply portion
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. :
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
BIDDERS SHALL FILL ONLY IN THE LIGHT BLUE COLOURED CELLS.
Station Supply portion :
Sl No. Name of the Equipment/Materials Unit Quantity Indicate whether "Own manufactured Item" or "Bought Out Item" Indicate country of Origin
110/11kV GIS S/s at BIMS(Civil Hospital) 1No. of 110kV TB at 110kV Neharu Nagar S/s Total
SS1 POWER TRANSFORMERS: a) 20 MVA, 110/33-11kV, Delta/Star, Dyn11, 3-Ph, 50Hz, Core Type, 2 Winding Delta/Star transformer, vector group Dyn11 with OLTC ONAN/ONAF with fan control cubicle, RTCC Panel,Condition controlled maintenance free breather, first filling of Oil and 10% spare oil in non-returnable drums etc., complete with Terminal connectors suitable for Single Drake/Moose ACSR on primary side of transformer and 2 nos of copper flat for each phase from LV side of Transformer to cable at 11 kV cable terminating structure with suitable support insulator on LV side of Transformer and 2 Nos of copper flats from neutral terminal to earthmat through NCT along with necessary support pin insulators complete as per technical specifications Note: Copper Flats required for Power Transformers shall be supplied alongwith the Transformers as per Technical Specifications. No 2 2
SS2 b)Nitrogen Injection Fire Extinguishing system including Supply,Erection, Testing & Commissioning and civil engineering works as per the recommendation of the supplier of the fire Extinguishing system for Power Transformer below 100MVA as per technical specifications. No 2 2
SS3 Metal encapsulated SF6 gas insulated Switchgear 40kA rating suitable for indoor installation of modular design: A (i) 110kV Line (U.G Cable) Module with GIS surge arrestor: Each Module Comprising of the following: a) SF6 Circuit Breaker complete with operating mechanism , 1600A, 1phase/3phase - 1 No. b) Disconnector: (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 3 Nos. (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 2 Nos (iii) 3 Phase, single pole, fast acting, fault make earthing switch complete with group operated manual and motor driven operating Mechanism - 1 No c) Current Transformer : 3 core Multi Ratio, single phase current Transformer 800-400/1-1-1 A - 1Set (3Nos) d) Surge Arresters (96 kV) - 1 Set (3 Nos). e) Cable end unit (plug in type) 3 phase , single pole , plug in type cable termination - 1 Run of 630sqmm for each phase - 1 Set. f) Bus Bar-Double Bus arrangement: i) Main Bus -2500 A ii) Auxiliary Bus- 1250 A g) "Gas monitoring device, remote gas pressure transmitters ( 4-20 mA signals), barrier pressure switches, UHF sensors, etc as required. Note: The Bus and the equipments may be with single phase or 3 phase enclosure." h) Control cables/power cables/screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specifications. No 2 2
SS4 (ii) Local Control cubicle for 110kV Line (U.G Cable) Module as per specification Nos 2 2
SS5 B (i)110kV Transformer Module (For 110/11kV - 20MVA ): Each Module Comprising of the following: a) SF6 Circuit Breaker complete with operating mechanism , 1600A, 1phase/3phase - 1 No. b) Disconnector: b (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 3 Nos. b (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 3 Nos c) Current Transformer : 3 Core Multi Ratio, single phase current Transformer 200-100/1-1-1A - (1Set) 3Nos d) Bus Bar-Double Bus arrangement: (i) Main Bus - 2500 A (ii) Auxiliary Bus -1250 A e) Gas monitoring device, remote gas pressure transmitters ( 4-20 mA signals), barrier pressure switches, UHF sensors, etc as required. Note: The Bus and the equipments may be with single phase or 3 phase enclosure. f) Control cables/power cables/ screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specification as required. g) "Cable end unit (Plug in type) 3 phase, single pole, plug in type cable termination - 1 run of 630sqmm for each phase - 1 Set. Nos 2 2
SS6 (ii) Local Control cubicle for Transformer Module (For 20MVA -110kV Side) as per specification Nos 2 2
SS7 C (i) 110kV Bus Coupler Module. Each Module Comprising of the following: a) SF6 Circuit Breaker complete with operating mechanism , 1600A, 1phase/3phase - 1 No. b) Disconnector: b (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 2 Nos. b (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 2 Nos c) Current Transformer : 3 Core Multi Ratio, single phase current Transformer 800-400/1-1-1A -(1Set) 3nos. d) Bus Bar-Double Bus arrangement: (i) Main Bus 2500 A (ii) Auxiliary Bus 1600 A e) "Gas monitoring device, remote gas pressure transmitters ( 4-20 mA signals), barrier pressure switches, UHF sensors, etc as required. Note: The Bus and the equipments may be with single phase or 3 phase enclosure." f) Control cables/power cables/screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specification as required. Nos 1 1
SS8 (ii) Local Control cubicle for 110kV Bus Coupler & Bus PT Module as per specification Nos 1 1
SS9 D (i) PT Module: 110kV ( 1 for each bus) Each Module Comprising of the following: a) Disconnector: a (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 1 No. a (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 1 No. b) Potential Transformer : 3 Core , Multi Ratio , single phase potential transformer. b (i) 110kV/√3 110V/√3 - 110V/√3 - 110V/√3 - 1 Set (3 Nos). c) Bus Bar- Double Bus arrangement: i) Main Bus 2500 A ii) Auxiliary Bus 1250A d) Gas monitoring device, remote gas pressure transmitter ( 4-20 mA signals) barriers pressure switches UHF sensors etc as required. e) Control cables / power cables / screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specification as required. Nos 2 2
SS10 Bus Maintenance earth switch 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - i) - 110 kV -2Nos (1 for each bus) Nos 2 2
SS11 CIRCUIT BREAKER : SF6 Gas circuit breaker with Semi-Pneumatic/Pneumatic operated/Spring type operating mechanism, including mounting Structures arrangements with rigid, bi-metallic terminal connectors complete suitable for 50mm Al.Tube Conductor and mounting structures complete as per technical specifications. A.145kV, 3150A, 40 kA Class For 110 kV line Nos 1 1
SS12 ISOLATORS : 110KV, 1250A,40KA Class Double Break electrically cum Manually operated isolator with solid core cylindrical post insulators, terminal connectors suitable for 50mm Al.tube, marshalling box etc., complete set as per technical specifications. (for 110kV side of 220/110kV Trf.110kV Lines & B/C Bays). 1) Upright mounting type with Earth switch LPH 4600mm Nos 1 1
SS13 2) Upright mounting type without earth switch LPH 6350mm Terminal connectors for Isolators : Flexible type suitable for 50mm Al.pipe - 27 Nos Rigid type suitable for 50mm Al.tube for CTs - 03Nos Nos 1 1
SS14 Oil filled Current Transformers: 11 kV NCT's of Ratio 1200-800/1-1-1 A. (for NCT) (required for 110/11 kV Tr.) complete as per Technical specifications Note:- The Characteristic of the above CT's shall be similar to that of main CT's 11kV Switchgear. Nos 2 2
SS15 CURRENT TRANSFORMER : Current transformers including marshalling boxes, Single phase,oil filled outdoor type with rigid bimetallic terminal connectors suitable for Al.Tube/Moose/Twin Moose ACSR conductor complete as per technical specifications. i)110 kV class, 40 KA, CT of ratio 800-400/ 1-1-1A for Line Core - 1 : Accuracy class PS-Dist/Dif Core- 2 : 10 VA, Accuracy class 0.2s- Metering Core - 3 : 30 VA, Accuracy class 5P20-Back up Note: All the current transformer in each KV Class shall be of One and the same make for interchangeability and relability of performance No 3 3
SS16 SURGE ARRESTOR : (Procelain/Polymer) metal oxide, gapless type with rigid bimetallic terminal connectors suitable for Drake (BIMS S/s)/Moose/Twin Moose ACSR (Neharu Nagar S/s) as per technical specifications. i) 96kV, 10kA, Class- III,Station Medium Duty (SM) type No 6 6
SS17 ii) 96kV, 10kA, Class- III,Station Medium Duty (SM) type - for UG cable Note : Surge arrestors are with surge monitors & insulating base No 3 3
SS18 1. C&R Panel compatible to IEC 61850, communication protocol for Sub-station Automation System complete as per technical specification: a) 110kV line- Type 1L for UG cable less than 5km (Annexure RPP4 -CABLE-SAS) No 2 2
SS19 b) 110/11 kV Transformer Panel - Type 1T1 (As per Annexure RPP5-SAS) No 2 2
SS20 c) 110 kV Panel for Bus Coupler - Type 1BC (As per Annexure RPP6-SAS) No 1 1
SS21 d) 11 kV Line & Capacitor Bank - Type 11L (Annexure RPP7 - SAS) (Provision for 2 line feeders to be made in one panel) (provision for 1 line & 1 Bus coupler to be made in one panel) (Provision for 2CB to be made in one panel). No 8 8
SS22 2. Substation Automation System Complete substation Automation System including hardware and software for substation and for operation from remote control centre along with associated equipment as per Annexure-SAS of Relay & Protection Panels and Substation Automation specification along with OFC and Ethernet switches, seperate Auxiliary panel etc., Note: a) The proposed SAS shall be suitable for communicating and remotely controlled from existing Neharu Nagar. b) The Accuracy class of metering core of CT's and also trivector meter of control & relay panels shall be 0.2S class Accuracy and VT's shall be 0.2 class, instead of that specified elsewhere in the respective clauses of Technical specification of bidding documents. c) All the panels shall be of one and the same make for uniformity and interchangebility of components. d) The Electronic Trivector meters with ABT features DLMS Compliant has to be provided both on the HV side and IV side of 66/11 kV Transformers. set 1 1
SS23 3. Control and Relay panel complete : Simplex 110V DC compatible to SCADA as per technical specifications a) 110 kV Panel for UG Cable Note: 1.All the C&R panels and associated panels shall be of one and the same make for uniformity and interchangability of components. 2. The accuracy class of metering core of CTs and VTs and ETV meter of C&R Panel shall be 0.2s accuracy class irrespective of what has been indicated else where in the bid document. 3. The electronic tri-vector meter with 0.2s accuracy class with ABT & TOD features, DLMS protocol has to be provided No 1 1
Mounting Structures : Design , fabrication and supply of Galvanised Steel supporting mounting structure including Bolts & Nuts as per technical specifications: i. Current transformer for 11kV NCTs (for 110/11kV Transformer) (0.157t per Structure) (0.146t per tower for structure+ 0.011 t per tower for Bolt & Nuts) No/t 02/0.3140 02/0.3140
ii Cable Terminating structure: a) 110kV Cable Terminating structure with provision for fixing LA suitable for 630sqmm cable.(0.4473t per Structure) (0.426t per tower for structure+ 0.0213t per tower for Bolt & Nuts) No/t 06/2.6838 06/2.6838
b) 11kV Cable Terminating structure suitable for 3 X 3 runs of 1C x 1000 sqmm cable (for 110/11 kV Transformer) (0.0788t per Structure) (0.075t per tower for structure+ 0.0038t per tower for Bolt & Nuts) No/t 02/0.1575 02/0.1575
iii. Tubular type Lightning /Lighting mast.(2.812t per structure) (2.678t per tower for structure +0.134t per structure for Bolts & Nuts) No/t 01/2.8119 01/2.8119
iv) Street lighting lattice type structure along with GI pipe for fixing of LED lamp (0.182t + 5% B&N) - 8.5mtr height No/t 08/1.5288 08/1.5288
v. 110 kV Isolator Live point height 4600 mm (0.752t per Structure)(0.726 t per tower for structure+ 0.026 t per tower including Bolt &Nuts) No/t 01/0.7520 01/0.7520
vi. 110 kV Isolator Live point height 6350 mm (0.982t per Structure)(0.955 t per tower for structure+ 0.027 t per tower including Bolt &Nuts) No/t 01/0.9820 01/0.9820
vii. Current transformer 110 kV. (0.158t per Structure) (0.146 t per tower for structure+ 0.012 t per tower for Bolt & Nuts) No/t 03/0.4740 03/0.4740
viii.Combined mounting structure for 110kV cable terminating & 96kV surge arrestors (0.1575t per structure) (0.015t per tower for structure+ 0.0075t per tower for Bolt &Nuts) No/t 03/0.4725 03/0.4725
ix.Pedestal insulators for 110kV bus (0.140 t per Structure) (0.127 t per tower for structure+ 0.013t per tower for Bolt &Nuts) No/t 01/0.1400 01/0.1400
SS24 Total Weight of fabricated out of galvanised Station structures & Mounting Structures,Lighting Mast & Street Lighting Structure (excluding Bolts & Nuts) as per technical specifications t 7.1320 2.6960 9.8280
SS25 Total Weight of galvanised Bolts & Nuts of Station structures & Mounting Structures,Lighting Mast & Street Lighting Structure as per technical specifications t 0.3640 0.1245 0.4885
SS26 BUS BAR FORMATION as per technical specifications: a) Drake ACSR Mtr 50.00 20.00 70.00
SS27 b) Terminal Connectors for Twin Drake ACSR. (At Tr. LV bushing) No 6 6
SS28 c) Pad Clamps for Single Drake ACSR (for UG cable at Tr. Side). No 12 12
SS29 d) PG Clamp for Drake ACSR (for Tr. LV Bushing to cable jump). No 12 12
SS30 Rigid bus with taps & clamps as per technical specifications: (i) Aluminium Tube conforming to 6340 WP of IS-5082/1969 (BS 1600-Sch.40) of following nominal diameter a) 50 mm size Mtr 105.00 105.00
SS31 Auxilliary Transformer : 1.Supply of Station Auxiliary Transformer-copper winding with oil, cable termination type on both HT & LT outdoor type 100 kVA, 11 kV/433 V, 3 Ph, Vector group Dyn 11 off load tap changer with step voltage of 2.5% along with other accessories as per technical specification. No 2 2
SS32 2. LTAC Panel (indoor): LTAC panel (Indoor) 415 V as per technical specification, comprising of Volt meter, Ammeter, 2 I/C ACB, 800A + 2 O/G SFU, 200A + 8 O/G SFU,100A + 14 O/G SFU, 63A + 12 O/G, 32A + 1B/C SFU, 800A + 1DG change over switch 300A etc.,complete with all necessary protection as per technical specification. No 1 1
SS33 3. AC Distribution box (out door ): a) AC Distribution box (outdoor) 415 V, Single front type with 6 terminals,750x1350x300mm, one I/C of 100 A MCCB 20 KA+ 6 O/G 16A MCB +1 O/G of 100 A HRC Fuse panel complete as per technical specification. No 2 2
SS34 b) AC Distribution box (outdoor) 415 V, Single front type with 6 terminals,1200x1350x300mm, one I/C of 100 A MCCB 20 KA+ 6 O/G 16A MCB +1 O/G of 100 A HRC Fuse panel complete as per technical specification. 1 1
SS35 Power cables from Auxiliary Transformer to LTAC panel as per Technical Specifications: a) 1.1kV PVC insulated 240sqmm Al. Cable, 3.5core with glands / lugs / ferrules. (To be run from Auxillary transformer to LTAC panel) Mtr 100.00 100.00
SS36 b) 1.1kV PVC insulated 70sq.mm Al. Cable, 3.5core with glands / lugs / ferrules. Mtr 200.00 200.00
SS37 LT Power armoured UG Cable as per specification: c) 1.1 kV class 4 X 25 Sq mm L T Aluminium Cable with glands/lugs/ferrules Mtr 150.00 150.00
SS38 D.G.Set: 3 Ph, 50 Hz, 415V, 0.8 PF, 25KVA capacity including Erection as per Technical specifications set 1 1
SS39 Station Battery & Battery Charger: A) Station Battery : 220 V, 300 AH Battery set consisting of 110No. of cells per Bank (Plante/Grid/Nickel Cadmium Type) as per Technical Specifications. Set 2 2
SS40 B) Station Battery Charger : 2X220V, 300AH with 2 nos. of float and 2 nos. of float cum boost including control panels, change over arrangement etc., complete as per technical specification along with 2 separate DC Distribution Panels (Indoor) 1I/C+20 O/G SFU 60A+10 O/G SFU 30A). Set 1 1
SS41 1. 11kV Switchgear as per Technical Specification: 11kV, 25kA, Metal Clad VCB Switchgear (1600A for Incomer and 1250A for feeders), comprising of 2IC+1BC+12F+2CB+1AP (SAS Compatible) complete as per technical specification. Note : The 11kV Switchgear will be supplied by KPTCL. Set (KPTCL Supply) 1 1
SS42 Capacitor Bank : Design, Engineering, Supply, Erection (including civil works), Testing & commissioning of 6MVAR, 12.1kV capacitor Bank, with internal fuses, terminal connectors,Neutral CTs & 0.2% series reactor on neutral side with elevating/mounting structure and with 10% spare capacitors complete etc.,complete as per specification. No 2 2
SS43 1.1 KV class PVC insulated armoured copper control cables of sizes,with Lugs/Ferrules/Gland as per technical specifications: i) 19 Core 2.5 Sq.mm. km 10.00 0.20 10.20
SS44 ii) 10C x 2.5 Sq.mm km 5.00 5.00
SS45 iii) 4 Core 6.0 Sq.mm. km 10.00 0.72 10.72
SS46 iv) 4 Core 2.5 Sq.mm. km 2.00 0.60 2.60
SS47 v) 4 Core 4 Sq.mm. km 3.00 3.00
SS48 vi) 2 Core 70 Sq.mm. km 0.20 0.20
SS49 vii) 0.5 Sq.mm 1P km 4.00 4.00
SS50 viii) 2 Core 6 Sq.mm. km 0.40 0.40
SS51 ix) 2 Core 2.5 Sq.mm. km 0.20 0.20
SS52 2. 11KV U.G. Cable with the required cable terminations at both ends. a) One run of 11kV, XLPE 95 sq.mm Al., 3 core cable - (to be run for Auxiliary Transformers ). Mtr 200.00 200.00
SS53 b)11KV XLPE cable, 1000Sq. mm.Aluminium cable 3x3 Runs of 1C x 1000 Sq.mm cable from 110/11KV transformers to 11KV Switchgear. Mtr 400.00 400.00
SS54 c)11KV XLPE cable, 400Sq. mm. Aluminium cable 3 Core to be run from 11KV Switchgear to 11kV Capacitor Bank Mtr 100.00 100.00
SS55 3. Cable Termination kits suitable for following sizes as per Technical Specification. A. Indoor type: i) Heat shrinkable type Cable termination kits suitable for 3 x 95 Sq.mm XLPE cable (For Aux Transformer) Set 4 4
SS56 ii) Heat shrinkable type Cable termination kits suitable for 3 x 400 Sq.mm XLPE cable (For Capacitor Bank & Feeders) Set 4 4
SS57 iii) Heat shrinkable type Cable termination kits suitable for 1 x 1000 Sq.mm XLPE cable (For 20MVA Transformer) Set 18 18
SS58 B. Outdoor type: i)Heat shrinkable type Cable termination kits suitable for 3 x 95 Sq.mm XLPE cable (For Aux Transformer) Set 4 4
SS59 ii) Heat shrinkable type Cable termination kits suitable for 3 x 400 Sq.mm XLPE cable (For Capacitor Bank & Feeders) Set 10 10
SS60 iii) Heat shrinkable type Cable termination kits suitable for 1 x 1000 Sq.mm XLPE cable (For 20MVA Transformer) Note : The bidder shall quote unit rates for power cable, control cable and cable duct.The exact requirement of power cable, control cable and cable ducts will be finalized during execution of work by the successful bidder. No 18 18
SS61 110kV UG cable with the required cable terminations: i) 110kV (Earthed), 1C X 630 Sq mm stranded, annealed, copper conductor, compacted circular, conductor screen, cross linked polyethylene (XLPE) insulation, core screen, semi-conducting water swellable layer, lead alloy 'E' sheathed, semi-conducting bedding tapes, helically applied plain round copper wire screen, plain copper tape in open helix, water swellable tape with overall extruded high density polyethylene sheath coated with graphite/extruded semi conducting layer and anti-termite treated as per technical specification for connecting GIS modules to 110/11 kV Transformers as per specification. Mtr 300.00 300.00
SS62 ii)Pre moulded outdoor cable termination Kit suitable for 110KV,1Cx 630Sqmm copper conductor lead sheathed XLPE insulated cable as per specification (for 110/11KV Transformer) No 6 6
SS63 iii) Indoor type cable termination (plug in dry type) suitable for GIS modules confirming to IEC 62271- 209 for 110kV, 630sqmm, copper conductor,XLPE insulated cable as per technical specification. (for 110/11kV Transformer) No 6 6
SS64 iv) Three phase Link box without SVL along with sheet earthing cables etc as per specification (at GIS module end for 110KV side of 20MVA transformer). No 2 2
SS65 v) Single phase Link box with SVL at cable termination end along with sheath earthing cable etc as per the technical specification (for 110KV side for 20MVA transformer). No 6 6
SS66 Equipments for establishing SCADA Communication as per KPTCL Specification i) Multi Functional Transducer (MFT) No 1 1
SS67 ii) Opto coupler No 1 1
SS68 iii) Digital Input card (DI card) No 1 1
SS69 iv) Digital Output card (DO card) No 1 1
SS70 iv) Supply of Power/Control cables for SCADA a) Current Cables-Copper Core with c/s 4.0 sq.mm Multistrand 4 Core Mtr 30.00 30.00
SS71 b) Voltage Cables-Copper Core with c/s 2.5 sq.mm Multistrand 4 Core Mtr 40.00 40.00
SS72 c) Signal Cables-armoured Copper Core with c/s 0.5 sq.mm Multi strand 10 Core Mtr 100.00 100.00
SS73 d) Control Cables- Copper Core with c/s 1.5 sq.mm Multi strand 10 Core Mtr 100.00 100.00
SS74 e) RJ cables Note: At 110kV Nehru nagar sub-station the bays are to be integrated to existing SCADA system & data are to be made available to SLDC Bengaluru on IEC-104 protocol. Set 30.00 30.00
SS75 FIRE FIGHTING EQUIPMENTS WITH NECESSARY MOUNTING STANDS i) Mechanical Foam Type Extinguisher : a) 50 Liters No 4 4
SS76 b) 09 Liters No 4 4
SS77 ii) Water type (gas pressure type) 9 Ltr. capacity No 5 5
SS78 iii) Carbon Dioxide Type 4.5 Kgs capacity No 5 5
SS79 iv) Dry chemical powder type - 6 kgs No 5 5
SS80 v) Sand type a) G.I Buckets15 Ltr. capacity No 8 8
SS81 b) Steel stands for above to have 4 buckets to each station No 2 2
SS82 vi) Fire detection system using smoke detectors heat detectors as per specification for GIS hall and control room relay panel room, LTAC room, office room, monitoring room etc: Addressable type Set 1 1
SS83 Maintenance Tools and Plant. 1.Earth Resistance Tester No. 1 1
SS84 2. Welding machine (arc welding) 10KVA No. 1 1
SS85 3. Heavy Duty Drilling machine No. 1 1
SS86 4. Hickery Rods Nos. 4 4
SS87 5.Grounding Sticks (Note: Grounding sticks extendable upto 18 ft : 3 nos. of each 6 ft Sticks of 3 phase R, Y, B (3 nos. of 1 set) Set (3Nos/set). 4 4
SS88 6. Manila Rope 1" Mtrs 100.00 100.00
SS89 7.Manila Rope 3/4" Mtrs 100.00 100.00
SS90 8.Files of various Sizes No. 6 6
SS91 9.Portable Drilling Machine with stand (heavy duty) No. 1 1
SS92 10.Hand Drilling Machine No. 1 1
SS93 11.Safety Belts Nos. 2 2
SS94 12.Safety Helmets Nos. 2 2
SS95 13. Steel Measuring tape 30 Mtrs No. 1 1
SS96 14. Steel Measuring tape 15 Mtrs No. 1 1
SS97 Miscellaneous items: 1. Rubber mats 1000mm X 1000mm X 10mm size tested for 15KV class No 40 2 42
SS98 2. First aid box No 1 1
SS99 3. Shock treatment charts hard board laminated with colured pictures & Literatures both in kannada & English No 1 1
SS100 4. Water filter/water purifier wall mounting type (Aqua guard type) No 1 1
SS101 5. Sub-station name board duly painted No 1 1
SS102 6. Fixograph of size 1.5m x 2.5m with Engilsh/Kannda alphabets No 1 1
SS103 7. Brass cupboard lock 6 levers (best make of approved quality) 75 mm size No 5 5
SS104 8. Danger board (probhited) with support structure in front of the gate No 1 1
SS105 9. Equipments name plates & earthing name plates including fixing at outdoor yard. No 50 6 56
SS106 Furniture for Control Room Staff and Maintenance Staff: 1. Steel Almirahs 6.5 Feet No 2 2
SS107 2.Steel Almirahs 6.5 Feet with glass panel doors No 1 1
SS108 3.Officers Tables No 4 4
SS109 4.Steel Slotted Angle rack(big size) No 4 4
SS110 5.Steel Slotted Angle rack(small size) No 4 4
SS111 6.Steel dust bins No 4 4
SS112 7.Executive revolving chairs No 20 20
SS113 8.'S' Type arm chairs No 10 10
SS114 9.Steel folding chairs No 4 4
SS115 Station Yard Lighting (Out Door) (To be designed, assessed & quoted by the bidder) Supply and installation/Fixing/Provision of Outdoortype Thermoplastic Modular Panel enclosure with transparent Polycarbonate Lid, shockproof, IP65 (WeatherProof), rustproof, dustproof, waterproof, corrosion proof having internally Embedded gasket on both lid and flap suitable to fix Single Phase/Three Phase Energy Metering suitable base plate and having a provision for Fuse/ MCB cut-out with suitable transparent hinged flap opening for operating MCB along with complete tamper proof SEALING facility,Timer/sensor,Contactor etc., as per techical specification. No 1 1
SS116 PVC Insulated Copper Control Cables : 1.1 KV PVC insulated Copper Control Cable with glands/Lugs/ Ferrules etc as per technical specification. 2C x 6 sqmm km 0.96 0.96
SS117 Station Lighting/Lightning Protection : Supply of LED Street light luminaire with pressure die cast aluminium housing body for optimal thermal dissipation. Lamp compartment comprising of anti glare clear diffuser with Injection moulded polycarbonate material LED streetlight 200W Note: 1No. Lightning/Lighting Mast (LM) tubular type as proposed for lightning protection and for illumination of the station Yard. The quantity of lightning / lighting mast indicated are located such that the entire station yard with equipments is protected against lightning. However any additional lighting masts may be provided for sufficient illumination and lightning protection (DSLP)of yard, if necessary. The design of lighting outdoor & indoor is also in the scope of the bidder as specified elsewhere in the technical specification. The scope also includes supply & erection of lighting fixtures, lighting mast panels with timer, contactor, control cable, etc. Suitable 2.5M Lightning spikes shall be provided on top of GIS building for Lightning protection. The Design of lighting outdoor & Indoor in station yard and GIS buildings etc. is in the scope of bidder as specified in the technical specification. No 12 12
NOTE 1. Any clarifications / hard copy of drawings can be obtained from the office of the Chief Engineer Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore.
2. Spacers shall be provided wherever necessary and no extra charges is payable on account of the same.
3. Supply of equipment/materials and the Erection charges shall include loading and unloading.
4. Copper Flat and GI Flat required for Power Transformers (if supply is in Bidder's scope) shall be supplied alongwith the Transformers and no extra cost is payable on this account. Date
5. The Bidder shall take necessary action to ensure that all the materials supplied shall be properly housed to ensure satisfactory commissioning. Place
6. The prices for all the materials shall be quoted in the Item wise Percentage rate finanacial bid. Name
7. Released materials shall be transported to the nearest Major Works Store of KPTCL without any additional cost as per the directions of the Engineer in charge of the work. Designation
8. The Bidder shall clearly indicate whether the materials/equipments are “Own manufactured” or “Bought out item”. Name of Company
9. The Bidder shall take necessary action to ensure that all the materials supplied for subject project shall be properly housed to ensure satisfactory commissioning.
Karnataka Power Transmission Corporation Limited
SCHEDULE - 3A(ii) - Price Breakup for - Station Erection portion including Testing and Commissioning.
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. :
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
BIDDERS SHALL FILL ONLY IN THE LIGHT BLUE COLOURED CELLS.
STATION ERECTION PORTION INCLUDING TESTING & COMMISSIONING :
Sl No. Name of the Equipment/Materials Unit Quantity
110/11kV GIS S/s at BIMS(Civil Hospital) 1No. of 110kV TB at 110kV Neharu Nagar S/s Total
SE1 POWER TRANSFORMERS: a) 20 MVA, 110/33-11kV, Delta/Star, Dyn11, 3-Ph, 50Hz, Core Type, 2 Winding Delta/Star transformer, vector group Dyn11 with OLTC ONAN/ONAF with fan control cubicle, RTCC Panel,Condition controlled maintenance free breather, first filling of Oil and 10% spare oil in non-returnable drums etc., complete with Terminal connectors suitable for Single Drake/Moose ACSR on primary side of transformer and 2 nos of copper flat for each phase from LV side of Transformer to cable at 11 kV cable terminating structure with suitable support insulator on LV side of Transformer and 2 Nos of copper flats from neutral terminal to earthmat through NCT along with necessary support pin insulators complete as per technical specifications Note: Copper Flats required for Power Transformers shall be supplied alongwith the Transformers as per Technical Specifications. No 2 2
SE2 Metal encapsulated SF6 gas insulated Switchgear 40kA rating suitable for indoor installation of modular design: A (i) 110kV Line (U.G Cable) Module with GIS surge arrestor: Each Module Comprising of the following: a) SF6 Circuit Breaker complete with operating mechanism , 1600A, 1phase/3phase - 1 No. b) Disconnector: (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 3 Nos. (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 2 Nos (iii) 3 Phase, single pole, fast acting, fault make earthing switch complete with group operated manual and motor driven operating Mechanism - 1 No c) Current Transformer : 3 core Multi Ratio, single phase current Transformer 800-400/1-1-1 A - 1Set (3Nos) d) Surge Arresters (96 kV) - 1 Set (3 Nos). e) Cable end unit (plug in type) 3 phase , single pole , plug in type cable termination - 1 Run of 630sqmm for each phase - 1 Set. f) Bus Bar-Double Bus arrangement: i) Main Bus -2500 A ii) Auxiliary Bus- 1250 A g) "Gas monitoring device, remote gas pressure transmitters ( 4-20 mA signals), barrier pressure switches, UHF sensors, etc as required. Note: The Bus and the equipments may be with single phase or 3 phase enclosure." h) Control cables/power cables/screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specifications. No 2 2
SE3 B (i)110kV Transformer Module (For 110/11kV - 20MVA ): Each Module Comprising of the following: a) SF6 Circuit Breaker complete with operating mechanism , 1600A, 1phase/3phase - 1 No. b) Disconnector: b (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 3 Nos. b (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 3 Nos c) Current Transformer : 3 Core Multi Ratio, single phase current Transformer 200-100/1-1-1A - (1Set) 3Nos d) Bus Bar-Double Bus arrangement: (i) Main Bus - 2500 A (ii) Auxiliary Bus -1250 A e) Gas monitoring device, remote gas pressure transmitters ( 4-20 mA signals), barrier pressure switches, UHF sensors, etc as required. Note: The Bus and the equipments may be with single phase or 3 phase enclosure. f) Control cables/power cables/ screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specification as required. g) "Cable end unit (Plug in type) 3 phase, single pole, plug in type cable termination - 1 run of 630sqmm for each phase - 1 Set. No 2 2
SE4 C (i) 110kV Bus Coupler Module. Each Module Comprising of the following: a) SF6 Circuit Breaker complete with operating mechanism , 1600A, 1phase/3phase - 1 No. b) Disconnector: b (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 2 Nos. b (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 2 Nos c) Current Transformer : 3 Core Multi Ratio, single phase current Transformer 800-400/1-1-1A -(1Set) 3nos. d) Bus Bar-Double Bus arrangement: (i) Main Bus 2500 A (ii) Auxiliary Bus 1600 A e) "Gas monitoring device, remote gas pressure transmitters ( 4-20 mA signals), barrier pressure switches, UHF sensors, etc as required. Note: The Bus and the equipments may be with single phase or 3 phase enclosure." f) Control cables/power cables/screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specification as required. No 1 1
SE5 D (i) PT Module: 110kV ( 1 for each bus) Each Module Comprising of the following: a) Disconnector: a (i) 3 Phase, single pole, Group operated isolator switch complete with manual & motor driven operating Mechanism 1250A - 1 No. a (ii) 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - 1 No. b) Potential Transformer : 3 Core , Multi Ratio , single phase potential transformer. b (i) 110kV/√3 110V/√3 - 110V/√3 - 110V/√3 - 1 Set (3 Nos). c) Bus Bar- Double Bus arrangement: i) Main Bus 2500 A ii) Auxiliary Bus 1250A d) Gas monitoring device, remote gas pressure transmitter ( 4-20 mA signals) barriers pressure switches UHF sensors etc as required. e) Control cables / power cables / screened cables etc., (FRLS type) from GIS module to LCC panel as per technical specification as required. No 2 2
SE6 Bus Maintenance earth switch 3 Phase, single pole, Group operated Maintenance earthing switch complete with manual operating Mechanism - i) - 110 kV -2Nos (1 for each bus) No 2 2
SE7 CIRCUIT BREAKER : SF6 Gas circuit breaker with Semi-Pneumatic/Pneumatic operated/Spring type operating mechanism, including mounting Structures arrangements with rigid, bi-metallic terminal connectors complete suitable for 50mm Al.Tube Conductor and mounting structures complete as per technical specifications. A.145kV, 3150A, 40 kA Class For 110 kV line No 1 1
SE8 ISOLATORS : 110KV, 1250A,40KA Class Double Break electrically cum Manually operated isolator with solid core cylindrical post insulators, terminal connectors suitable for 50mm Al.tube, marshalling box etc., complete set as per technical specifications. (for 110kV side of 220/110kV Trf.110kV Lines & B/C Bays). 1) Upright mounting type with Earth switch LPH 4600mm No 1 1
SE9 2) Upright mounting type without earth switch LPH 6350mm Terminal connectors for Isolators : Flexible type suitable for 50mm Al.pipe - 27 Nos Rigid type suitable for 50mm Al.tube for CTs - 03Nos No 1 1
SE10 Oil filled Current Transformers: 11 kV NCT's of Ratio 1200-800/1-1-1 A. (for NCT) (required for 110/11 kV Tr.) complete as per Technical specifications Note:- The Characteristic of the above CT's shall be similar to that of main CT's 11kV Switchgear. No 2 2
SE11 CURRENT TRANSFORMER : Current transformers including marshalling boxes, Single phase,oil filled outdoor type with rigid bimetallic terminal connectors suitable for Al.Tube/Moose/Twin Moose ACSR conductor complete as per technical specifications. i)110 kV class, 40 KA, CT of ratio 800-400/ 1-1-1A for Line Core - 1 : Accuracy class PS-Dist/Dif Core- 2 : 10 VA, Accuracy class 0.2s- Metering Core - 3 : 30 VA, Accuracy class 5P20-Back up Note: All the current transformer in each KV Class shall be of One and the same make for interchangeability and relability of performance No 3 3
SE12 SURGE ARRESTOR : (Procelain/Polymer) metal oxide, gapless type with rigid bimetallic terminal connectors suitable for Drake (BIMS S/s)/Moose/Twin Moose ACSR (Neharu Nagar S/s) as per technical specifications. i) 96kV, 10kA, Class- III,Station Medium Duty (SM) type No 6 6
SE13 ii) 96kV, 10kA, Class- III,Station Medium Duty (SM) type - for UG cable Note : Surge arrestors are with surge monitors & insulating base No 3 3
SE14 1. C&R Panel compatible to IEC 61850, communication protocol for Sub-station Automation System complete as per technical specification: a) 110kV line- Type 1L for UG cable less than 5km (Annexure RPP4 -CABLE-SAS) No 2 2
SE15 b) 110/11 kV Transformer Panel - Type 1T1 (As per Annexure RPP5-SAS) No 2 2
SE16 c) 110 kV Panel for Bus Coupler - Type 1BC (As per Annexure RPP6-SAS) No 1 1
SE17 d) 11 kV Line & Capacitor Bank - Type 11L (Annexure RPP7 - SAS) (Provision for 2 line feeders to be made in one panel) (provision for 1 line & 1 Bus coupler to be made in one panel) (Provision for 2CB to be made in one panel). No 8 8
SE18 2. Control and Relay panel complete : Simplex 110V DC compatible to SCADA as per technical specifications a) 110 kV Panel for UG Cable Note: 1.All the C&R panels and associated panels shall be of one and the same make for uniformity and interchangability of components. 2. The accuracy class of metering core of CTs and VTs and ETV meter of C&R Panel shall be 0.2s accuracy class irrespective of what has been indicated else where in the bid document. 3. The electronic tri-vector meter with 0.2s accuracy class with ABT & TOD features, DLMS protocol has to be provided No 1 1
SE19 Mounting Structures : Design , fabrication and supply of Galvanised Steel supporting mounting structure including Bolts & Nuts as per technical specifications: i. Current transformer for 11kV NCTs (for 110/11kV Transformer) (0.157t per Structure) (0.146t per tower for structure+ 0.011 t per tower for Bolt & Nuts) No/t 02/0.3140 02/0.3140
ii Cable Terminating structure: a) 110kV Cable Terminating structure with provision for fixing LA suitable for 630sqmm cable.(0.4473t per Structure) (0.426t per tower for structure+ 0.0213t per tower for Bolt & Nuts) No/t 06/2.6838 06/2.6838
b) 11kV Cable Terminating structure suitable for 3 X 3 runs of 1C x 1000 sqmm cable (for 110/11 kV Transformer) (0.0788t per Structure) (0.075t per tower for structure+ 0.0038t per tower for Bolt & Nuts) No/t 02/0.1575 02/0.1575
iii. Tubular type Lightning /Lighting mast.(2.812t per structure) (2.678t per tower for structure +0.134t per structure for Bolts & Nuts) No/t 01/2.8119 01/2.8119
iv) Street lighting lattice type structure along with GI pipe for fixing of LED lamp (0.182t + 5% B&N) - 8.5mtr height No/t 08/1.5288 08/1.5288
v. 110 kV Isolator Live point height 4600 mm (0.752t per Structure)(0.726 t per tower for structure+ 0.026 t per tower including Bolt &Nuts) No/t 01/0.7520 01/0.7520
vi. 110 kV Isolator Live point height 6350 mm (0.982t per Structure)(0.955 t per tower for structure+ 0.027 t per tower including Bolt &Nuts) No/t 01/0.9820 01/0.9820
vii. Current transformer 110 kV. (0.158t per Structure) (0.146 t per tower for structure+ 0.012 t per tower for Bolt & Nuts) No/t 03/0.4740 03/0.4740
viii.Combined mounting structure for 110kV cable terminating & 96kV surge arrestors (0.1575t per structure) (0.015t per tower for structure+ 0.0075t per tower for Bolt &Nuts) No/t 03/0.4725 03/0.4725
ix.Pedestal insulators for 110kV bus (0.140 t per Structure) (0.127 t per tower for structure+ 0.013t per tower for Bolt &Nuts) No/t 01/0.1400 01/0.1400
SE19 Total Weight of Station structures and Mounting Structures,Lighting Mast & Street Lighting Structure including Bolts & nuts as per technical specifications: t 7.4960 2.8205 10.3165
SE20 Rigid bus with taps & clamps as per technical specifications: (i) Aluminium Tube conforming to 6340 WP of IS-5082/1969 (BS 1600-Sch.40) of following nominal diameter a) 50 mm size Mtr 105.00 105.00
SE21 Auxilliary Transformers : 1.Erection of Station Auxiliary Transformer-copper winding with oil, outdoor type 100 kVA, 11 kV/433 V, 3 Ph, Vector group Dyn 11 off load tap changer (with 5 taps) with step voltage of 2.5% along with DOLO/HG-fuse unit,L.T.Protection Kit,Distribution Box and other accessories as per technical specification. No 2 2
SE22 2. LTAC Panel (indoor): LTAC panel (Indoor) 415 V as per technical specification, comprising of Volt meter, Ammeter, 2 I/C ACB, 800A + 2 O/G SFU, 200A + 8 O/G SFU,100A + 14 O/G SFU, 63A + 12 O/G, 32A + 1B/C SFU, 800A + 1DG change over switch 300A etc.,complete with all necessary protection as per technical specification. No 1 1
SE23 3. AC Distribution box (out door ): a) AC Distribution box (outdoor) 415 V, Single front type with 6 terminals,750x1350x300mm, one I/C of 100 A MCCB 20 KA+ 6 O/G 16A MCB +1 O/G of 100 A HRC Fuse panel complete as per technical specification. No 2 2
SE24 b) AC Distribution box (outdoor) 415 V, Single front type with 6 terminals,1200x1350x300mm, one I/C of 100 A MCCB 20 KA+ 6 O/G 16A MCB +1 O/G of 100 A HRC Fuse panel complete as per technical specification. No 1 1
SE25 Power cables from Auxiliary Transformer to LTAC panel as per Technical Specifications: a) 1.1kV PVC insulated 240sqmm Al. Cable, 3.5core with glands / lugs / ferrules. (To be run from Auxillary transformer to LTAC panel) Mtr 100.00 100.00
SE26 b) 1.1kV PVC insulated 70sq.mm Al. Cable, 3.5core with glands / lugs / ferrules. Mtr 200.00 200.00
SE27 LT Power armoured UG Cable as per specification: c) 1.1 kV class 4 X 25 Sq mm L T Aluminium Cable with glands/lugs/ferrules Mtr 150.00 150.00
SE28 Station Battery & Battery Charger: A) Station Battery : 220 V, 300 AH Battery set consisting of 110No. of cells per Bank (Plante/Grid/Nickel Cadmium Type) as per Technical Specifications. Set 2 2
SE29 B) Station Battery Charger : 2X220V, 300AH with 2 nos. of float and 2 nos. of float cum boost including control panels, change over arrangement etc., complete as per technical specification along with 2 separate DC Distribution Panels (Indoor) 1I/C+20 O/G SFU 60A+10 O/G SFU 30A). Set 1 1
SE30 1. 11kV Switchgear as per Technical Specification: 11kV, 25kA, Metal Clad VCB Switchgear (1600A for Incomer and 1250A for feeders), comprising of 2IC+1BC+12F+2CB+1AP (SAS Compatible) complete as per technical specification. Note : The 11kV Switchgear will be supplied by KPTCL. Set 1 1
SE31 1.1 KV class PVC insulated armoured copper control cables of sizes,with Lugs/Ferrules/Gland as per technical specifications: i) 19 Core 2.5 Sq.mm. km 10.00 0.20 10.20
SE32 ii) 10C x 2.5 Sq.mm km 5.00 5.00
SE33 iii) 4 Core 6.0 Sq.mm. km 10.00 0.72 10.72
SE34 iv) 4 Core 2.5 Sq.mm. km 2.00 0.60 2.60
SE35 v) 4 Core 4 Sq.mm. km 3.00 3.00
SE36 vi) 2 Core 70 Sq.mm. km 0.20 0.20
SE37 vii) 0.5 Sq.mm 1P km 4.00 4.00
SE38 viii) 2 Core 6 Sq.mm. km 0.40 0.40
SE39 ix) 2 Core 2.5 Sq.mm. km 0.20 0.20
Laying of PVC insulated armoured Copper Control Cables 1.1kV Class of sl.no i) to ix) of total above km 34.20 2.12 36.32
SE40 2. 11KV U.G. Cable with the required cable terminations at both ends. a) One run of 11kV, XLPE 95 sq.mm Al., 3 core cable - (to be run for Auxiliary Transformers ). Mtr 200.00 200.00
SE41 b)11KV XLPE cable, 1000Sq. mm.Aluminium cable 3x3 Runs of 1C x 1000 Sq.mm cable from 110/11KV transformers to 11KV Switchgear. Mtr 400.00 400.00
SE42 c)11KV XLPE cable, 400Sq. mm. Aluminium cable 3 Core to be run from 11KV Switchgear to 11kV Capacitor Bank Mtr 100.00 100.00
Laying of 11kV Class UG Cable of sl.no a) to c) of total above Mtr 700.00 700.00
SE43 3. Cable Termination kits suitable for following sizes as per Technical Specification. A. Indoor type: i) Heat shrinkable type Cable termination kits suitable for 3 x 95 Sq.mm XLPE cable (For Aux Transformer) Set 4 4
SE44 ii) Heat shrinkable type Cable termination kits suitable for 3 x 400 Sq.mm XLPE cable (For Capacitor Bank & Feeders) Set 4 4
SE45 B. Outdoor type: iii)Heat shrinkable type Cable termination kits suitable for 3 x 95 Sq.mm XLPE cable (For Aux Transformer) Set 4 4
SE46 iv) Heat shrinkable type Cable termination kits suitable for 3 x 400 Sq.mm XLPE cable (For Capacitor Bank & Feeders) Set 10 10
Cable Termination kits of 3 x 95 Sq.mm and 3 x 400 Sq.mm XLPE cable sl.no i) to iv) of total above Set 22 22
SE47 v) A.Indoor Type : Heat shrinkable type Cable termination kits suitable for 1 x 1000 Sq.mm XLPE cable (For 20MVA Transformer) Set 18 18
SE48 vi) B Outdoor type: Heat shrinkable type Cable termination kits suitable for 1 x 1000 Sq.mm XLPE cable (For 20MVA Transformer) Note : The bidder shall quote unit rates for power cable, control cable and cable duct.The exact requirement of power cable, control cable and cable ducts will be finalized during execution of work by the successful bidder. Set 18 18
Cable Termination kits of 1 x 1000 Sq.mm XLPE cable sl.no v) to vi) of total above Set 36 36
SE49 110kV UG cable with the required cable terminations: i) 110kV (Earthed), 1C X 630 Sq mm stranded, annealed, copper conductor, compacted circular, conductor screen, cross linked polyethylene (XLPE) insulation, core screen, semi-conducting water swellable layer, lead alloy 'E' sheathed, semi-conducting bedding tapes, helically applied plain round copper wire screen, plain copper tape in open helix, water swellable tape with overall extruded high density polyethylene sheath coated with graphite/extruded semi conducting layer and anti-termite treated as per technical specification for connecting GIS modules to 110/11 kV Transformers as per specification. Mtr 300.00 300.00
SE50 ii)Pre moulded outdoor cable termination Kit suitable for 110KV,1Cx 630Sqmm copper conductor lead sheathed XLPE insulated cable as per specification (for 110/11KV Transformer) No 6 6
SE51 iii) Indoor type cable termination (plug in dry type) suitable for GIS modules confirming to IEC 60859 for 110kV, 630sqmm, copper conductor,XLPE insulated cable as per technical specification. (for 110/11kV Transformer) No 6 6
SE52 iv) Three phase cross bonding Link box without SVL including 240 Sq mm sheath bonding cable and 240/240 Sq mm co-axial cable as per technical specification suitable for 110kV, 630sqmm UG Cable. The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) (at GIS module end for 110KV side of 20MVA transformer). No 2 2
SE53 v) Single phase Link box outdoor structure mounting type, without SVL suitable for 110kV, 630sqmm UG cable including 240 Sq mm sheath bonding cable as per the technical specification (for 110KV side for 20MVA transformer). No 6 6
SE54 Equipments for establishing SCADA Communication as per KPTCL Specification i) Multi Functional Transducer (MFT) No 1 1
SE55 ii) Opto coupler No 1 1
SE56 iii) Supply of Power/Control cables for SCADA a) Current Cables-Copper Core with c/s 4.0 sq.mm Multistrand 4 Core Mtr 30.00 30.00
SE57 b) Voltage Cables-Copper Core with c/s 2.5 sq.mm Multistrand 4 Core Mtr 40.00 40.00
SE58 c) Signal Cables-armoured Copper Core with c/s 0.5 sq.mm Multi strand 10 Core Mtr 100.00 100.00
SE59 d) Control Cables- Copper Core with c/s 1.5 sq.mm Multi strand 10 Core Mtr 100.00 100.00
SE60 e) RJ cables Mtr 30.00 30.00
Laying of Power cables and Control cables for SCADA Sl.No.v) & vi) of toal above Mtr 300.00 300.00
SE61 Configuration of RTU and Engineering along with validation of data at SLDC Note: At 110kV Nehru nagar sub-station the bays are to be integrated to existing SCADA system & data are to be made available to SLDC Bengaluru on IEC-104 protocol. No 1 1
SE62 Laying of PVC Insulated Copper Control Cables for Station and Yard Lighting : 1.1 KV PVC insulated Copper Control Cable with glands/Lugs/ Ferrules etc as per technical specification. 2C x 6 sqmm km 0.96 0.96
SE63 Earth Mat formation : i.Supplying and laying MS.Flat 75 x 12mm flat welding and applying ACB paint to welded portion and covering without Sodium Bentonite Clay (SBC supplied by Corporation) as per drawing/standard (all other materials to be supplied by contractor) RMtr 975 975.00
SE64 i.Supplying and laying MS.Flat 50 x 6mm flat welding and applying ACB paint to welded portion and covering without Sodium Bentonite Clay (SBC supplied by Corporation) as per drawing/standard (all other materials to be supplied by contractor) RMtr 205.00 205.00
SE65 ii.Supplying and Erection of Grounding of Equipment with G.I.Flat 75x12mm and connecting Equipment to the earth mat/ground pit including including all connected works with all materials supplied by the contractor. RMtr 373.00 373.00
SE66 iii)Supplying and Providing 40mm dia M.S.Rod 1.075m long earthman spikes including heating, bending top 50/75mm overlap flattening and making spike edge at one end driving into the earth below the ground level and welding the rod with ground mat flat. No 58 58
SE67 iv) Providing Cast iron pipe of 100mm ID 13mm thickness, 2.75mtrs long with 2 part clamp out of G.I.Flat 50x6 mm continuously welded alround the pipe using cast iron welding electrodes as per drawing including the cost of excavationas per specification Set 21 6 27
SE68 Supplying and fixing 450mm dia x 450mm height 1.5" to 2" Hume pipe collars for earth pits. Set 21 6 27
SE69 Providing deep bore earthing : Sinking bore of 150mm clear dia using fast rig including fixing of 40mm dia MS road, including jointing the pipes as per KPTCL standards & providing sodium bentonite treatment in the annular space, including transportation of rig & other supporting vehicles, etc complete, as per the directions of engineer in charge, including cost of MS rod & sodium bentonite i. Drilling 150mm dia bore (5mtr long-2Nos) mtr 10 10.00
SE70 ii. 40mm dia MS rod Note: The BOM provided for CI pipe electrodes & 75x12mm GI flat is only for the outdoor equipments. BOM for GIS modules and hall and their earthing guidelines shall be obtained from GIS module manufacturesrs, hence quantity provided may vary as per actual field requirement. mtr 10 10.00
1. Any clarifications / hard copy of drawings can be obtained from the office of the Chief Engineer Electricity, Tendering & Procurement, 9th Floor, KPTCL, Indhnana Bhavana, Bangalore.
2. Released materials shall be transported to the nearest Major Works Store of KPTCL without any additional cost as per the directions of the Engineer in charge of the work.
3. The Erection charges shall include transportaion to site, loading and unloading.
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 4A(i) Price Break up for MANDATORY SPARES -GIS STATION SUPPLY PORTION
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. :
BIDDERS SHALL NOTE: PLEASE FILL ONLY IN THE LIGHT BLUE COLOURED CELLS.
STATION MANDATORY SPARES PORTION
Sl No Item Description Unit Quantity Indicate whether "Own manufactured Item" or "Bought Out Item"
SM1 1. For GIS common spares, maintenance and Testing Tools : 1. SF6 Gas pressure relief devices of each type Set 1
SM2 2. Pressure gauges (of each type) along with coupling device, gas pressure transmitter Set 1
SM3 3.Rubber Gaskets "O" Rings and seals for SF6 gas Set 1
SM4 4. Molecular filter for SF6 gas Set 3
SM5 5. Density Monitors for SF6 gas Nos 2
SM6 6. All types of control valves for SF6 gas Set 1
SM7 7. SF6 gas(10% of total gas requirement subject to min of 30Kgs.) L/S 1
SM8 2. CIRCUIT BREAKERS : GIS SF6 CIRCUIT BREAKER I. 110 KV, 1600A Circuit Breaker interrupting chamber complete with all necessary apparatus. Nos 1
SM9 II.Rubber Gaskets "O" Rings and seals Set 1
SM10 III. Trip coils with resistor Nos 3
SM11 IV. Closing coils with resistor Nos 3
SM12 V. Relays, Power contactors, push buttons, timers & MCB etc., Set 1
SM13 VI. Closing assembly/valve Nos 1
SM14 VII. Trip assembly / valve Nos 1
SM15 VIII. Pressure switches Set 1
SM16 IX. Auxiliary switch assembly Nos 1
SM17 X. Operation Counter Nos 1
SM18 XI. Rupture disc/diaphragm Nos 1
SM19 XII. Windoscope / Observing window Nos 1
SM20 XIII. 110KV,1600A circuit Breaker operating mechanism, complete with all necessary connecting apparatus. Nos 1
SM21 XIV. All types of coupling for SF6 gas(1 no. each type) Set 1
SM22 3. DISCONEECTORS & E/SWITCH GIS I. 110KV, 1250A disconnecting & maintenance earthing switch internal parts, complete with all necessary gaskets, mounting hardware etc., Set 1
SM23 II. Operating mechanism of 110KV, 1250A Disconnecting switch, complete with all necessary connecting apparatus. Set 1
SM24 III. 110kV, 1250A, single phase high speed fault making Earthing switch Internal parts complete with all neccesary gaskets mounting hardware etc., Set 1
SM25 IV. Operating mechanism of 110KV, 1250A, high speed fault making Earthing switch, complete with all neccesary gaskets connecting apparatus. Set 1
SM26 V. Limit switch & Aux. switches Set 1
SM27 4. CURRENT TRANSFORMER-GIS a) 110KV Complete CT (1 No of each rating) Nos 1
SM28 5. VOLTAGE TRANSFORMER-GIS a) 110KV single phase VT complete with all gaskets and mounting hardware.(1 No of each rating) Nos. 1
SM29 6. SURGE ARRESTOR-GIS a) 96 KV Complete L.A. including with Surge counter & accessories. (1 No of each) Nos. 1
SM30 7. EMERGENCY DG SETS: I.Set of filters (Lubeoil/fuel/Air ckt)- 1 set Set 1
SM31 II. Solenoid coil assembly Nos. 1
SM32 III. Self starter assembly Nos. 1
SM33 IV. Lub-oil pressure safety control Nos. 1
SM34 V. High water temp. safety control Nos. 1
SM35 VI. Diode Nos. 2
SM36 8. SPARES FOR RELAY AND PROTECTION PANELS I. Relay panel Spares 1. Numerical line Differential cum Distance relay Nos. 1
SM37 2. Numerical Transformer differential relay Nos. 1
SM38 3. Numerical Backup OCR &EFR Nos. 1
SM39 4. Trip circuit supervision relay Nos. 2
SM40 5. Self reset trip relay1 no. (each type) Nos. 1
SM41 6. Hand reset trip relay (1 no. (each type) Nos. 1
SM42 7. Timer relay (1 no. (each type) Nos. 1
SM43 8. DC supervision relays Nos. 1
SM44 9.Flag relays (1 no. (each type) Nos. 1
SM45 10.Auxiliary relays (1 no. (each type) Nos. 1
SM46 II. Mandatory spares for Sub-Station Automation system 1. Bay control unit with configuration software Set 2
SM47 2. Ethernet Switch of each type Nos. 1
SM48 3. Optical cable of longest length Nos. 1
SM49 9.Testing and Maintenance for GIS 1. SF6 Gas filling, Filtering/evacuating & storage plant Set 1
SM50 2. Portable Partial Discharge monitoring for GIS (minimum 6 channels) Nos. 1
SM51 3. SF6 gas leak Detector set 1
SM52 4. SF6 Gas Analyser Kit Nos. 1
SM53 10. MANDATORY SPARES FOR POWER TRANSFORMER : Power transformer : 1. Oil collecting bottle Nos 3
SM54 2. Terminal connector clamps a) Suitable for 110kV class bushing to suit single Drake ACSR Nos 3
SM55 b) Suitable for 11kV class bushing to suit 2 Nos. 50x6mm Copper flat Nos 3
SM56 3. Valves a) Drain valve (80mm to 200mm size) Nos 1
SM57 b) Top/Bottom Filter Valve (50mm to 100mm size) Nos 2
SM58 c)Top/Middle/Bottom Oil sampling valve with plug (15 to 25 mm) Nos 3
SM59 d)Header pipe valve Nos 1
SM60 e)Gate/Butterfly valves of various sizes ranging from 50mm to 200mm set 1
SM61 4. MOG No. 1
SM62 5. Prismatic Gauge No. 1
SM63 6. Starters, contactors, relays set 1
SM64 7. Pressure Relief Device (PRD or PRV) No. 1
SM65 8. Oil Surge relay No. 1
SM66 9. Bucholtz relay No. 1
SM67 10. Tap position Indicator No. 1
SM68 11. Fixed and moving contacts for diverter switch set 1
SM69 12. Fixed and moving contacts for selector switch set 1
SM70 13. WTI with 2 contacts, 15 meters capillary length with built in CCU RTD and external remote indicator, range 0-150 deg C with SCADA/SAS compatibility set 1
SM71 14. OTI with 2 contacts, 15 meters capillary length with built in CCU RTD and external remote indicator range 0-150 deg C with SCADA/SAS compatibility set 1
SM72 15.PT 100 sensor along with probe of suitable length set 1
Note: 1. Supply of equipment and materials shall include loading and unloading
2. Insurance cover should be taken in accordance with the provisions of the Bidding Documents.
3.The Bidder shall clearly indicate whether the materials/equipments are “Own manufactured” or “Bought out item”.) .
Karnataka Power Transmission Corporation Limited
SCHEDULE - 3BI(i) - Price Breakup for -CABLE Supply portion
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
BIDDERS SHALL FILL ONLY IN THE LIGHT BLUE COLOURED CELLS.
CABLE SUPPLY PORTION :
Sl.No Name of the Equipment/Mataerials Unit Quantity Indicate whether "Own manufactured Item" or "Bought Out Item" Indicate country of Origin
CS1 64/110 kV (Earthed), 1C X 630 Sq mm stranded, annealed, copper conductor, compacted circular, conductor screen, cross linked polyethylene (XLPE) insulation, core screen, semi-conducting water swellable layer, lead alloy 'E' sheathed, semiconducting bedding tapes, helically applied plain round copper wire screen, plain copper tape in open helix, water swellable tape with overall extruded high density polyethylene sheath coated with graphite/extruded semi conducting layer and anti-termite treated as per technical specification. mtr 7231.20
CS2 3.3KV, 1CX 240 Sq mm 31.5Ka/sec earth continuity cable (sheath bonding cable) as per technical specification including laying charges mtr 2380.40
CS3 Outdoor type cable end termination suitable for 110 kV, 1C X 630 Sq mm copper conductor lead sheathed XLPE insulated cable as per technical specification. No 3
CS4 Indoor type cable termination (plug in dry type) suitable for GIS modules confirming to IEC 62271- 209 for 110 kV, 630 Sq mm, copper conductor, XLPE insulated cable as per technical specification. No 3
CS5 Insulated shield break type Joint suitable for 110kV, 1CX 630Sq mm, copper conductor, XLPE insulated, lead sheathed cable complete with all accessories as per technical specification. No 6
CS6 Insulated shield earthing Joint/Normal Straight through Joint suitable for 110 kV, 1C X 630 Sq mm, copper conductor, XLPE insulated, lead sheathed cable complete with all accessories as per technical specification. No 6
CS7 Single phase Link box outdoor structure mounting type, without SVL suitable for 110 kV, 630 Sq mm UG cable including 240 Sq mm sheath bonding cable as per the technical specification. No 6
CS8 Three phase cross bonding Link box with SVL including 240 Sq mm sheath bonding cable and 240/240 Sq mm co-axial cable as per technical specification suitable for 110 kV , 630 Sq mm UG Cable. The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) No 2
CS9 Three phase Link box without SVL including 240 Sq mm sheath bonding cable and 240/ 240 Sq mm co-axial cable as per technical specification suitable for 110 kV ,630Sq mm UG Cable. The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) No 2
CS10 Terminal connectors to connect cable end termination to the DRAKE ACSR conductor heavy type complete.(06-Station End for TR+03-for TB N Nagar) No 9
CS11 Drake ACSR Conductor mtr 20.00
CS12 UNDERGROUND FIBRE OPTIC UNARMOURED CABLE (UG - OFC) & Accessories : 48 Fibre (DWSM) Optical Fibre Cable as per technical specification in cable trunch parallel to 110KV cable inside PLB pipes by pulling drawings etc including transportation handling cable drums,paving out cables using standard cable installation equipments and as per direction of the engineer incharge. mtr 2300.00
CS13 Polyvinyl Lubricated Bond (HDPE)pipe.OD 40mm mtr 2300.00
CS14 Straight Joint Kit for Optical Fibre Cable: 48F Kit 1
CS15 Line interface unit for optical fibre cable : 48 F No 2
CS16 Fiber to Ethernet Media Converter 10/100/1000 Mbps No 2
NOTE: 1. Any clarifications / hard copy of drawings can be obtained from the office of the Chief Engineer Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore.
2. Spacers shall be provided wherever necessary and no extra charges is payable on account of the same by KPTCL.
3. Supply of equipment/materials shall include transportation to the site, loading and unloading.
4. The bidder shall quote same rates for common materials in all the price sheets.
5. The Bidder shall take necessary action to ensure that all the materials supplied shall be properly housed to ensure satisfactory commissioning.
6. The prices for all the materials shall be quoted in the Item wise Percentage rate finanacial bid.
7. The Bidder shall clearly indicate whether the materials/equipments are “Own manufactured” or “Bought out item”.
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 3BI(ii) - Price Breakup for -CABLE Erection portion
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. :
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
BIDDERS SHALL FILL ONLY IN THE LIGHT BLUE COLOURED CELLS.
CABLE ERECTION PORTION :
Sl.No Name of the Equipment/Mataerials Unit Quantity
CE1 UG Cable Surveying: Detailed survey along the route alignment by using Modern Survey equipment like DGPS / Total stations / Digital theodolites / GPS including profiling by using computer aided techniques as detailed in the scope of work, includes the following: • Drawing the route profile including features like Roads, Railway lines, drains, park, gardens, P&T Lines, Railways crossing etc., • Preparation of cable route profile and final cable route alignment, marking lines and grades. • Leveling of the profile with reference to Survey of India bench marks (MSL). • Line Schedule along the Right of Way. • Soil resistivity along the selected route with measurement at a distance not exceeding 2 km. • Route marking along the route with GPS Co-ordinates at every 50 m duly marking road/power line/ telecommunication/ railway line crossings. • Making 150 mm dia bore holes for a depth not less than 3 m or refusal strata at every 50 m for soil classification along with GPS Co-ordinates for each bore holes and back filling of bore holes on completion of work. • Burgie details and providing GPS, Co-ordinates at every 50 m, turning points including permanent marks, like poles, telephones lines, buildings etc., • Submission of detailed consolidated final report for surveying work done appending all the reports including all relevant information collected during survey, calibration certificates of the instruments used for the work, photos/ videos taken at site and submitting soft copies of all documents and hard copy of reports in 6 sets. • The detailed report shall contain detailed Survey Report/Soil Resistivity Report/Line Schedule/Land schedule/ Geo referenced and superimposed on the line corridor. km 2.1640
CE2 Laying including Testing & Commissioning : 64/110 kV (Earthed), 1C X 630 Sq mm EHT single core XLPE copper cable in trefoil, tapping, fixing pipes for drain and gate crossing as per drawings & specification in trench pipes, ducts by pulling, drawing etc.,handling of cable drums, paving out cables using standard cable installation equipment. NOTE: The rate per m shall include laying one circuit per m each circuit consisting of 3 nos. of single core cables including transport of cable drums material equipment to site and retaining unused items to stores Ckt m 2164.0000
CE3 Handling and making of cables end termination for EHV single core XLPE copper cable. No 6.0000
CE4 Handling and making of Normal Straigh joint / insulated shield break type for EHV power cable with all consumables at site etc., Complete No 12.0000
CE5 Erection of Single phase earth link boxes (3 Nos.) on to the cable mounting structure connecting earth leads with all lugs, fixtures, clamps bolts and nuts complete Set 2.0000
CE6 Erection of Three phase earth link box at Joint bay with connecting earth leads, all lugs, fixtures, clamps bolts and nuts complete (for Straight/Cross Bonds) No 4.0000
CE7 Charges for conducting pre commissioning test as per IEC:840, IEC:229 and successful commissioning of single circuit. LS 1
CE8 Grounding of Equipment with 50x6 mm G.I Flat and connecting equipment to the earthmat/ground pit with all formation works like bending twisting, drilling of holes and welding inclusive of all materials mtrs 150
CE9 Cast iron pipe electrode of 100mm internal dia 13mm thick 2.75mtr long: Grounding of equipment by providing cast iron pipe of 100mm I.D. 13mm thickness 2.75 mtr long with 2 part clamp out of G.I.flat 50x6mm continuously welded allround the pipe using cast iron welding electrodes as per drawing including the cost of excavation and poring of sodium bentonite clay No 4
CE10 Supplying and providing RCC collars of 450 mm height and 450 mm dia.1.5 to 2.0 inch thick. No 4
CE11 Underground Fibre Optic cable & Accessories : Laying of 48 Fibrer Window Mono Mode (DWSM) UG Optical Fibre Cable as per drawings and specifications in cable trunch parallel to 110KV cable inside PLB pipes by pulling drawings etc including transportation handling cable drums,paving out cables using standard cable installation equipments and as per direction of the engineer incharge. mtrs 2300.00
CE12 Handling and making normal straight joint clousers for 48 fiber dual window mono mode (DWMN) OFC with all consumable at site complete No 1
CE13 Laying of PLB HDPE pipe in trenches for 400kV & 220kV mtrs 2300.00
CE14 Line interface unit (LIU) suitable for optical fibre cable : 48 F No 2.00
NOTE: 1. Any clarifications / hard copy of drawings can be obtained from the office of the Chief Engineer Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore.
2. The Erection charges shall include transportaion to site, loading and unloading.
3. Bidders shall start the line work from both the ends simultaneously by deploying more number of gangs as the ‘ROW’ issues which may crop-up can be addressed in parallel on both segments. The bidders shall take note of the same before quoting.
4. The charges for erection shall be quoted in the Itemwise Percentage rate finanacial bid.
5. Released materials shall be transported to the nearest KPTCL Projects Division Stores without any additional cost as per the directions of the Engineer in charge of the work.
6. The bidder shall quote same rates for common materials in all the price sheets.
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 3BI(ii) - Price Breakup for -CABLE Mandatory Spares
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. :
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009.
BIDDERS SHALL FILL ONLY IN THE LIGHT BLUE COLOURED CELLS.
CABLE Mandatory Spares :
Sl.No Name of the Equipment/Mataerials Unit Quantity Indicate whether "Own manufactured Item" or "Bought Out Item"
CM1 Outdoor type cable end termination suitable for 110 kV, 1C X 630 Sq mm copper conductor lead sheathed XLPE insulated cable as per technical specification. No 1
CM2 Indoor type cable termination (plug in dry type) suitable for GIS modules confirming to IEC 62271- 209 for 110 kV, 630 Sq mm, copper conductor, XLPE insulated cable as per technical specification. No 1
CM3 Insulated shield break type Joint suitable for 110kV, 1CX 630Sq mm, copper conductor, XLPE insulated, lead sheathed cable complete with all accessories as per technical specification. No 1
CM4 Insulated shield earthing Joint/Normal Straight through Joint suitable for 110 kV, 1C X 630 Sq mm, copper conductor, XLPE insulated, lead sheathed cable complete with all accessories as per technical specification. No 1
CM5 Single phase Link box outdoor structure mounting type, without SVL suitable for 110 kV, 630 Sq mm UG cable including 240 Sq mm sheath bonding cable as per the technical specification. No 1
CM6 Three phase cross bonding Link box with SVL including 240 Sq mm sheath bonding cable and 240/240 Sq mm co-axial cable as per technical specification suitable for 110 kV , 630 Sq mm UG Cable. The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) No 1
CM7 Three phase Link box without SVL including 240 Sq mm sheath bonding cable and 240/ 240 Sq mm co-axial cable as per technical specification suitable for 110 kV ,630Sq mm UG Cable. The Link box shall be burried type, water proof (capable of immerssion in water), weather proof, rust & dust proof (IP: 68) No 1
NOTE: 1. Any clarifications / hard copy of drawings can be obtained from the office of the Chief Engineer Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore.
2. The Erection charges shall include transportaion to site, loading and unloading.
3. Bidders shall start the line work from both the ends simultaneously by deploying more number of gangs as the ‘ROW’ issues which may crop-up can be addressed in parallel on both segments. The bidders shall take note of the same before quoting.
4. The charges for erection shall be quoted in the Percentage rate finanacial bid.
5. Released materials shall be transported to the nearest KPTCL Projects Division Stores without any additional cost as per the directions of the Engineer in charge of the work.
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE - 3C(i) - Price Breakup for -Station Civil Portion
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
a) Establishing 2x20 MVA, 110/11kV GIS Sub-station at BIMS (Civil Hospital) Belagavi Taluk and District. b) Construction of 01 no of 110kV Terminal Bay at 110/33/11kV Nehrunagar S/s for terminating proposed 110kVclass 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District.
BIDDERS SHALL NOTE: FILL ONLY IN LIGHT BLUE COLOURED CELLS
Bidders Name and Address along with GSTIN No.: To
The Chief Engineer, Electy., Tendering & Procurement, 9th Floor, Indhana Bhavana, KPTCL, A R Circle, BANGALORE - 560009.
Sl. No. Specifications Unit Quantity Total Quatity (a+b)
a) 110/11kV GIS S/s at BIMS b) 01 No of TB at Nehrunagar S/s
B1 Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. In all kinds of soils Depth upto 3 m cum 2090.97 2057.95 4148.92
B2 Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. In ordinary/soft rock without blasting upto 1.5 m depth cum 926.02 787.50 1713.52
B3 Earth work excavation for Foundation by mechanical means for all works & depth upto 3 m, as per drawing and technical specifications, including setting out, shoring, strutting, barricading, caution lights, including dressing of excavated surfaces, disposing off or levelling the excavated earth or sorting & stacking the selected earth for reuse in a radius of 50 m and lift upto 1.5 m including cost of labour, tools, usage of machinery & other appurtenaces required to complete the work. In ordinary/soft rock Depth exceeding 1.5 m, but not exceeding 3 m cum 463.01 0.00 463.01
B4 Construction of Embankment by excavating the available approved Gravel/Murrum deposited at a place or borrow pits during or prior excavation with all lifts and lead, transportation to site, spreading, grading to required slope and compacting to meet the requirement complete as per specifications, including cost of labour,rolling, water,all materials,usage& all other appurtenaces required to complete the work. cum 582.70 1575.00 2157.70
B5 Earth work excavation for pipeline trenches in all kinds of soils by mechanical means as per drawing and technical specifications, including setting out, construction of shoring, strutting, barricading, caution lights, bracing, using sight rails & bonding rods at every 100 mm wherever necessary as directed, removal of stumps and other deleterious matter, dressing of sides and levelling the bottom of trench to the extent required , utilising the available excavated earth locally for the work etc., and all other appurtenances complete in the following strata. cum 438.75 0.00 438.75
B6 Construction of Embankment with approved materials deposited at site from roadway cutting and excavation from drain and foundation of other structures graded with desired compaction. (Royalty shall be recovered @ Rs. 60.00/m3) cum 520.04 0.00 520.04
B7 Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete as per specifications cum 292.50 0.00 292.50
B8 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m. cum 1114.65 482.35 1597.00
B9 Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (3% cosidered for Form work) cum 480.62 239.54 720.16
B10 Providing and laying in position Cement Concrete for all Sub structures of building, Irrigation works, Sub structure works of bridges, Drain works & other parallel works from 0.50m to 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20mm nominal size graded crushed coarse aggregate - (35% considered for Form work) cum 75.54 14.04 89.58
B11 Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/ basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications.. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (10% considered for Form work) cum 233.80 139.50 373.30
B12 Providing and laying in position Cement Concrete for all Foundation works. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticizers laid in finished layers, well compacted using needle vibrators, including all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all the other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (70% considered for Form work) cum 87.05 0.00 87.05
B13 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns (70% considered for Form work) column at superstructure 3.6-6.6m cum 22.32 0.00 22.32
B14 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns (70% considered for Form work) column at superstructure 6.6-9.6m cum 22.32 0.00 22.32
B15 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns (70% considered for Form work) column at superstructure 9.6-12.6m cum 22.32 0.00 22.32
B16 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns (70% considered for Form work) column at superstructure 12.6-15.6m cum 22.32 0.00 22.32
B17 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns (70% considered for Form work) column at superstructure 15.6-18.6m cum 22.32 0.00 22.32
B18 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns (70% considered for Form work) column at superstructure 18.6-21.6m cum 22.32 0.00 22.32
B19 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - For Columns (70% considered for Form work) column at superstructure 21.6-24.6m cum 31.02 0.00 31.02
B20 Providing and laying in Cement Concrete for all Basement & surface level works, return walls, retaining walls, sunken floors etc. The granite/trap/ basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers, laid in layers, well compacted using needle vibrators, providing weep holes wherever necessary, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (50% considered for Form work) cum 34.11 0.00 34.11
B21 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (60% considered for Form work) lintel beam at Ground floor cum 65.47 0.00 65.47
B22 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (60% considered for Form work) lintel beam at First Floor cum 65.48 0.00 65.48
B23 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (60% considered for Form work) lintel beam at Second floor cum 57.92 0.00 57.92
B24 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (50% considered for Form work) Roof Slab at Ground Floor cum 88.62 0.00 88.62
B25 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (50% considered for Form work) Roof Slab at First Floor cum 85.80 0.00 85.80
B26 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (50% considered for Form work) Roof Slab Second at Floor cum 91.80 0.00 91.80
B27 Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical specifications. Mix 1:2:4 Using 20 mm nominal size graded crushed coarse aggregates cum 117.60 4.76 122.36
B28 Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates (5% considered for Form work) DPC sill coping and screed concrete cum 197.66 0.00 197.66
B29 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M25 Design Mix Using 20 mm nominal size graded crushed coarse aggregates - (10% considered for Form work) For lift walls cum 47.54 0.00 47.54
B30 Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates cum 83.74 56.16 139.90
B31 Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, aggregate cement ratio not to exceed 14:1, aggregate gradation after blending to be as per table 600-1, cement content not to be less than 140 kg/ m3 , optimum moisture content to be determined during trial length construction, concrete strength not to be less than 7 Mpa at 7 days, mixed in a batching plant, transported to site, laid with a paver with electronic sensor, compacting with 8-10 t vibratory roller, finishing and curing - For Road cum 48.75 0.00 48.75
B32 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates (5% considered for Form work) cum 48.75 0.00 48.75
B33 Wet Mix Macadam (Plant Mix Method): Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver/grader in sub-base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density. cum 65.00 0.00 65.00
B34 Providing and filling joint sealing compound as per drawings and technical specifications with coarse sand and 6 per cent bitumen by weight m 65.00 0.00 65.00
B35 Providing Size Stone masonry with hard stone in foundation & plinth with Cement mortar 1:6 (1 cement : 6 coarse sand) cum 30.58 0.00 30.58
B36 Providing Brick work with common burnt clay Non Modular bricks of class designation 3.5 in superstructure above plinth level in all shapes and sizes in Cement mortar 1:6 (1 cement : 6 coarse sand) including cost of all materials, labour, scaffolding and usage charges of machinery & other incidental charges complete as per the direction of engineer incharge of work. cum 528.33 0.00 528.33
B37 Providing and constructing load bearing wall with Solid Concrete blocks of size 400x200x200mm having block density more than 1800kg/m3 and minimum compressive strength of 4.00 N/mm2 conforming to IS 2185 (Part - I) - 2005 and constructed with CM 1:4 as per IS 2572:2005 including cost of all materials, labour, scaffolding and curing, usage charges of machinery etc complete as per specifications sqm 176.80 0.00 176.80
B38 Providing and Applying CFTRI approved two component flexible polymer modified acrylic cementitious waterproofing coating with a mix ratio of (5 Liquid :7 Powder) to the RCC surface like Roof, bathroom, toilet, balcony & utility area applied @ 2.2kg/m2 in 2 coats to achieve 1.2mm DFT, having Elongation at break greater than 120% as per ASTM D 412, Tensile strength greater than1N/mm2 as per ASTM D 412, Adhesion strength: 0.80N/mm2 as per ASTM D 4541, crack bridging upto 2mm as per ASTM C 836. The finished cost to include surface preparation, making coving of 50 mm X 50mm at all right angles of wall Junction with Polymer Repair Mortar and lay 45 gsm glass fibre mesh over the angle fillet when the first coat in still wet, treatment of cracks completely as per specification. sqm 377.25 0.00 377.25
B39 Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per m2 including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all T sections shall be pre-painted with polyster baked paint, for all heights as per specifications, drawings and as directed by Engineer in Charge. sqm 317.00 0.00 317.00
B40 Providing 12 mm cement plaster with cement mortar 1:4 (1 cement: 4 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. sqm 1277.58 0.00 1277.58
B41 Providing 18 mm cement plaster in two coats under layer 12 mm thick cement plaster with cement mortar 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster with cement mortar 1:6 (1 cement :6 fine sand) to brick masonry including rounding off corners wherever required smooth rendering, providing and removing scaffolding, including cost of materials, labour, curing complete as per specifications and as per directions of Engineer-in-charge. sqm 2781.82 0.00 2781.82
B42 Providing Flush/ Ruled pointing: Pointing on stone work with cement mortar 1:3 (1 cement : 3 fine sand) after raking joints to depth nicely lining, including cost of materials, labour, curing as per specifications and as per directions of Engineer-in-charge. sqm 58.71 0.00 58.71
B43 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. ** Polished Granite stone slab Black, Cat Eye, River Pink or equivalent. sqm 545.45 0.00 545.45
B44 Providing and laying 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6 mm nominal size) by volume, hardening compound mixed @ 2 L per 50 kg of cement or as per direction of Engineer incharge. sqm 748.00 0.00 748.00
B45 Providing and laying 5mm thick Self levelling Epoxy Flooring for Residential, Commercial, Sports & Industrial purpose made of reputed brand applied at 1L/m2 on existing Concrete substrate of 25Mpa or more. The Concrete shall be free from any defects and cracks. The epoxy compound shall have low VOC (Based on USEPA Method 24 Section 11.2.2 & ASTM D2369-98)and is chemically resistant & antimicrobial. The surface of Concrete shall be cleaned thoroughly and free from laitance and applied with primer cured for 6-8 hours. The mix shall be mixed using Hand mixing rotary machine. The underlay shall be laid with 3mm thickness and overlay at 2mm. The entire operation shall be finished in line with epoxy coving and marked with 100mm thickness yellow marking lines complete as per the direction of Engineer in chargePU Coating/Epoxy flooring sqm 737.00 0.00 737.00
B46 Providing and fixing double action hydraulic floor spring of approved brand manufacture conforming to IS : 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors, including cost of cutting floors, embedding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer-in-charge: With brass cover plate minimum 1.25 mm thickness including cost of materials, labour, usage charges of machinery complete as per specifications. each 30.00 0.00 30.00
B47 Demolishing cement concrete manually/ by mechanical means including disposal of material to the appropriate disposal area as per direction of Engineer-in-charge cum 87.50 0.00 87.50
B48 Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material to the appropriate disposal area as per direction of Engineer-in-charge cum 35.00 0.00 35.00
B49 Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) with Acid and alkali resistant tile. sqm 66.00 0.00 66.00
B50 Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding for Bathrooms: Toilet: Chemically exposed areas and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. In dado/skirting on 12 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand) with Acid and alkali resistant tile sqm 65.10 0.00 65.10
B51 Providing and fixing chromium plated brass handles of 100/125 mm with necessary screws etc. complete. no 4 0.00 4.00
B52 Providing and fixing chromium plated brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete. no 4 0.00 4.00
B53 Supplying and fixing Hold fasts. no 15 0.00 15.00
B54 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 50 mm nominal dia Pipes m 300.00 0.00 300.00
B55 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 40mm nominal dia Pipes m 250.00 0.00 250.00
B56 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal work - Exposed on wall. 25mm nominal dia Pipes m 150.00 0.00 150.00
B57 Providing and fixing Rainy dual capacity self-cleaning roof top rain water harvesting filter or equivalent filter of FL-500 specification suitable for a catchment area of about 500Sqm. No 1.00 0.00 1.00
B58 Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), Jointing with grey cement slurry @ 3.3 kg/m2 including pointing the joints with white cement and matching pigment etc., complete. sqm 83.20 0.00 83.20
B59 Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content. With water thinnable cement primer on wall surface having VOC content less than 50 g/L as per specifications and as per directions of Engineer in charge. sqm 1900.23 0.00 1900.23
B60 Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile Organic Compound ) content less than 50 g/L of approved brand and manufacture, including applying additional coats wherever required to achieve even shade and colour. Two coats as per specifications and as per directions of Engineer in charge. sqm 1900.23 0.00 1900.23
B61 Finishing walls with Acrylic Smooth exterior paint of required shade :New work (Two coat applied @ 1.67L/10 m² over and including priming coat of exterior primer applied @ 2.20 kg/10 m²) with paint of approved quality to give an even shade, after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. sqm 2781.82 0.00 2781.82
B62 Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture after thoroughly brooming the surface to remove all dirt, dust, mortar drops and foreign matter including preparing the surface even and sand paper smooth, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. sqm 200.00 0.00 200.00
B63 Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification Buildings kg 130050.00 0.00 130050.00
B64 Steel Fabrication: Supplying, fitting and placing TMT FE 550 / 550D Steel Reinforcement including cost of all materials, machinery, labour, cleaning, straightening, cutting, bending, hooking, laping/welding joints, tying with binding wire / soft annealed steel wire and other ancilary operations complete as per drawing and technical specification All other type of structures kg 27878.47 26053.22 53931.69
B65 Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2 mm and braced with flat iron diagonals 20x5 mm size, with top and bottom rail of T-iron 40x40x6 mm, with 40 mm dia steel pulleys, complete with bolts, nuts, locking arrangement, stoppers, handles, including applying a priming coat of approved steel primer including cost of materials ,labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. sqm 34.50 0.00 34.50
B66 Providing & fixing of 3-track x 2-panel sliding windows made out of multi chambered UPVC(Matching to RAL-9016) sections and with minimum TiO2(Titanium Dioxide) at 6PHR with TPE(Thermo Plastic Elastomer) and lead free, gaskets -grey colour having isolated drainage and reinforced with Galvanized Iron profile through-out the window frame. The outer frame having an overall size of 108mm width x 45mmheight with reinforcement of 1mm thickness and Sash with overall size of 39mm x 75mm with GI reinforcement of 2mm and mesh sash of size 37mm x 58mm. Coextruded Glazing bead for fixing of glass shall be of size 20mm x 24 mm. Windows shall be provided with 6mm plain float glass, standard hardware& Multi point locking system with touch lock. Wall thickness of frame & sash shall be of 2mm-2.5mm. Maximum possible size – 2419mm x 2200mm. (The cost is inclusive of all fixtures and separate charges for minor T&P's shall not be made) sqm 190.70 0.00 190.70
B67 Providing & fixing of louvered ventilator made out of multi chambered UPVC(Matching to RAL-9016) sections and with minimum TiO2(Titanium Dioxide) at 6PHR with TPE(Thermo Plastic Elastomer) and lead free with gaskets -grey colour having isolated drainage and reinforced with Galvanized Iron profile through-out the ventilator frame. The frame having overall size of 39mm x 39mm with GI reinforcement of 1mm thickness. Louver clip in Aluminium (powder coated in white) will be used on the frame along with plastic parts for fixing the 4 mm pin head glass. Wall thickness of frame shall be 2mm.Maximum possible size – 1000mm x 1000mm. (The cost is inclusive of all fixtures and separate charges for minor T&P's shall not be made) sqm 48.00 0.00 48.00
B68 Providing and fixing factory made uPVC door frame made of uPVC extruded sections having an overall dimension as below (tolerance plus or minus 1mm), with wall thickness 2.0 mm (plus or minus 0.2 mm), corners of the door frame to be Jointed with galvanized brackets and stainless steel screws, joints mitred and Plastic welded. The hinge side vertical of the frames reinforced by galvanized M.S. tube of size 19 X 19 mm and 1mm (plus or minus 0.1 mm) wall thickness and 3 nos. stainless steel hinges fixed to the frame complete as per manufacturer’s specification and direction of Engineer- in-charge 42x50 mm PVC Extruded section m 120.00 0.00 120.00
B69 30mm thick factory made polyvinyl chloride (PVC) door shutter made of a uPVC hollow section of size 60x30mm and wall thickness 2 mm (plus or minus 0.2 mm), with inbuilt decorative moulding edging on one side. The styles and rails mitred and joint at the corners by means of M.S. galvanised/plastic brackets of size 75x220 mm having wall thickness 1.0 mm and stainless steel screws. The styles of the shutter reinforced by inserting galvanised M.S. tube of size 25x20 mm and 1 mm (plus or minus 0.1 mm) wall thickness. The lock rail made up of ‘H’ section, a uPVC hollow section of size 100x30mm and 2 mm (plus or minus 0.2 mm), wall thickness. Fixed to the shutter styles by means of plastic/galvanised M.S. ‘U’ cleats. The shutter frame filled with a uPVC multi chambered single panel of size not less than 620 mm, having over all thickness of 20 mm and 1 mm (plus or minus 0.1 mm) wall thickness. The panels filled vertically and tie bar at two places by inserting horizontally 6 mm galvanised M.S. rod and fastened with nuts and washers, complete as per manufacturer’s specification and direction of Engineer-in–charge. sqm 54.00 0.00 54.00
B70 Providing and fixing Fiber Glass Reinforced plastic (FRP) Door Frames of cross- section 90 mm x 45 mm having single rebate of 32 mm x 15 mm to receive shutter of 30 mm thickness. The laminate shall be moulded with fire resistant grade unsaturated polyester resin and chopped mat. Door frame laminate shall be 2mm thick and shall be filled with suitable wooden block in all the three legs. The frame shall be covered with fiber glass from all sides. M.S. stay shall be provided at the bottom to steady the frame. m 20.00 0.00 20.00
B71 Providing and fixing to existing door frames Glass Fibre Reinforced Plastic (FRP) panelled door shutter of required colour and approved brand and manufacture, made with fire - retardant grade unsaturated polyester resin, moulded to 3 mm thick FRP laminate for forming hollow rails and styles, with wooden frame and suitable blocks of seasoned wood inside at required places for fixing of fittings, cast monolithically with 5 mm thick FRP laminate for panels conforming to IS: 14856, including fixing to frames. sqm 20.00 0.00 20.00
B72 Providing and fixing bright finished brass butt hinges with necessary screws etc. complete : 125x85x5.5mm (heavy type) no 20.00 0.00 20.00
B73 Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size, on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in- charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts bolts, fasteners etc.) including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge kg 2365.32 0.00 2365.32
B74 Providing and fixing of wall cladding using 20mm thick gang saw water cut Shiva gold granite, grey granite in CM 1:3 (1 cement : 3 coarse sand) proportion cut to required shape, pattern with paper joints, finished with cement mortal using white cement and colour pigments to match the colour of slab making through jointing with sealant, making holes 25mmx12mm grooves in joints including cost of all materials, mortar, labour, curing etc., complete. sqm 337.50 0.00 337.50
B75 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. 80x1.25 mm M.S. laths with 1.25 mm thick top cover including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. sqm 34.50 0.00 34.50
B76 Providing and fixing ball bearing for rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. no 2 0.00 2.00
B77 Extra for providing Manually operated Bevel Gear Box for operating rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. each 2 0.00 2.00
B78 Extra for providing 2 HP Mild Steel Auto Reverse Shutter Gearbox for operating rolling shutters including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. each 2 0.00 2.00
B79 Providing & Fixing in position Acoustical wall panelling with Integral Densified Square/Butt edged Fully Perforated Eco Friendly Lightweight Calcium Silicate panels/tiles with fabricated galvanised mild steel frame work for Auditoriums, Community halls, Offices, Institutions, Airports, Meeting halls, Indoor Stadiums and Studios. The Eco Friendly Lightweight Calcium Silicate wall panels/tiles shall be made from Non Cementitious Hydrated Calcium Silicate Slurry/Mixture, Reinforced recycled material with fibers and natural fillers. Free from Formaldehyde and other harmful materials. Doesn't contain any toxic ingrediants. The wall panels/tiles size of 595x595mm and 15mm thick should have Humidity Resistance (RH) of 100%, Water Resistance, Non Combustible: as per BS:476 Part-4, Fire Performance: as per BS:476 Part-6 for Fire Propagation, as per BS:476 Part-7 for Surface Spread of Flame, As per UK standards Fire Performace A1-S1-d0, Thermal Conductivity K= 0.048 to 0.050 w/m K as per ECBC code 2007, NRC (Noise Reductions Coefficient) 0.65 to 0.85 (Fully Perforated wall panels/Tiles) as per IS 8225:1987, Sound Attenuation (STA) 30-32dB, Thickness of tile should be 15mm thick with 450 kg/m3 density all around on edge resting portion with Integral Densified edge and 10mm thick with 350 kg/m3 density in the center of the body, Light Reflectance greater than 85%, Weight of material is 5-5.5 kg/m2 and Suitable for Green Building application with InOrganic Recycled content of 46- 50% out of which 18-20% should be FLYASH and meets the GRIHA & SVAGRIHA norms under the categories: GRIHA V.2015 riterion:11&12, GRIHAV.3 criterion: 17&29 and SVAGRIHA criterion:12. The frame work comprising of a frame made especially fabricated galvanised mild steel sheet of 0.50 mm thick pressed section (galvanizing @ 120 grams per m2 including both sides) i.e. vertical studs of size 48x34x36mm are placed at 600mm centre to centre in a floor and ceiling channel section of size 50x32mm fixed to the floor and soffit at 600mm centres using 12mm dia, 40mm long wedge type expanded zinc alloy dash fastner with 10mm bolt. This same channel is then to be fixed in horizontal direction at 600mm centre to centre so as to form a grid of 600x600mm. Glass wool of 50mm thickness with density of 16 kg/m3 is then to be inserted in the slots and finally Lightweight calcium silicate wall panels/tiles are to be screw fixed with self-tapping pan head nickle coated mild steel screws of size 13x3.2mm on to this grid leaving an even groove of 1mm between the panels. The joints between the panels are to be duly jointed and finished using recommended jointing calcium silicate based compound and fibre joint tape roll 50mm wide (90metre) roll and two coats of premier suitable for panelling as per manfacturer's specification as per direction of Engineer-in-charge all complete. sqm 100 0.00 100.00
B80 Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for: PVC pipes 110mm dia., 6 kg/sqcm & class 3 m 720.00 0.00 720.00
B81 Providing, lowering, laying, jointing, testing and commissioning of Glazed Stone Ware Pipes of following dia, conforming to IS 651:1992, IS 4127 with latest amendments, including conveying to work site, caulking with hemp dipped in tar and jointing with CM 1:1.5 using OPC, perfect linking and curing for 10 days and testing with water etc. with all lead, lifts and as per Technical Specifications. The cost to include the cost of all jointing materials, necessary survey works for laying of sewer lines etc. complete. The contractor will make own arrangements for procuring water for testing. 150 mm dia. pipes m 100.00 0.00 100.00
B82 Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. each 2.00 0.00 2.00
B83 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:. White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps each 5.00 0.00 5.00
B84 Bottle trap 31mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the centre of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 260 gms. each 5.00 0.00 5.00
B85 Providing and fixing Brass full way valve gate with C.I. wheel of approved quality (screwed end) : 32 mm nominal bore. each 5.00 0.00 5.00
B86 Providing and fixing C.P. brass bib cock of approved quality conforming to IS:893. each 10.00 0.00 10.00
B87 Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : Range of two urinal basins with 5 litre white P.V.C. automatic flushing cistern each 2.00 0.00 2.00
B88 Providing and fixing mirror of superior glass (of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing: Rectangular shape 453x357 mm each 2.00 0.00 2.00
B89 Providing and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete. 32 mm dia, each 5.00 0.00 5.00
B90 Providing and fixing 100 mm sand cast Iron grating for gully trap. each 10.00 0.00 10.00
B91 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangements of approved quality and colour. 600mm long towel rail with total length of 645mm, width 78mm and effective height of 88mm, weighing not less than 190g. each 2.00 0.00 2.00
B92 Providing and fixing 8 mm dia C.P. / S.S. Jet with flexible tube upto 1 metre long with S.S. triangular plate to Eureopean type W.C. of quality and make as approved by Engineer - in - charge. each 2.00 0.00 2.00
B93 Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS: 12701 marked, with cover and suitable locking arrangment and making necessary holes for inlet, outlet and overflow pipes but without fitting and the base support for tank. L 4000.00 0.00 4000.00
B94 Providing and fixing PTMT stop cock of approved quality and colour 20 mm nominal bore, 89 mm long, weighing not less than 88 g no 4.00 0.00 4.00
B95 Providing and fixing PTMT stop cock of approved quality and colour 15 mm nominal bore, 86 mm long, weighing not less than 88 g no 4.00 0.00 4.00
B96 Providing and fixing Structural Steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete including cost of materials, labour, usage charges of machinery complete as per specifications and as per directions of the Engineer-in-Charge. kg 16482.71 999.22 17481.93
B97 Constructing brick masonry chamber of internal dimension 600x600mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plastering 12 mm thick with cement mortar 1:4, CC 1:2:4 coping 75mm thk for fixing CI cover & frame etc excluding the cost of CI frame and cover. each 11.00 5.00 16.00
B98 Constructing brick masonry chamber of internal dimension 450x450mm and depth of 600mm (inner dimensions) with modular bricks of CD 75 in cement mortar 1:6, bed concrete 150mm thick with 1:3:6, plastering 12 mm thick with cement mortar 1:4, CC 1:2:4 coping 75mm thk for fixing CI cover & frame etc. excluding the cost of CI frame and cover. each 25.00 5.00 30.00
B99 Providing and fixing SFRC frame and cover conforming to IS 12592 (part-I)-1988 and IS 12592 (part-II)- 1991 with latest amendment, including cutting slabs to the required size for the opening and fixing the cover in C.C. 1:2:4 and C.M. 1:3 plastering 20 mm thick to all exposed faces, curing for 10 days with all lead and lift with apurtenances. complete. Medium Duty Set 38.00 10.00 48.00
B100 Providing and fixing false flooring as per KPTCL specfication including cost of structural steel, fasle flooring materials, labour charges, etc., complete as per direction of engineer in charge of work. sqm 317.00 0.00 317.00
B101 Providing and fixing modular cable cealing system as per KPTCL specfication including cost of materials, labour charges, etc., complete as per direction of engineer in charge of work. sqm 3.00 0.00 3.00
B102 Double Leaf doorset - Insulated Fire rated doorset (FD 120) - Staircase / exit pathway application / Refuge area. Providing and fixing of ISI marked fire doors as per IS 3614:2021, 120 minutes fire rating with 30 minutes insulation double leaf doorset tested to IS/ISO 3008. Doorset shall include grooved step frame profile of 125x75mm, made of 1.2mm GI (120GSM) and 60mm thick shutter made of 1.2mm GI (120GSM) with infill of 120kg density mineral wool. Grooved frame shall include EPDM smoke seal. Include hardwares, minimum 6nos SS ball bearing hinges of SS304 100x89x3mm, 1no of Single point Panic device and external trim with key cylinder on active leaf and 1no two point Panic device on the inactive leaf, tested as per EN1125 and CE marked. 2no of Door closer with spring size of EN 3-5, as per EN1154 and CE marked. 1no door coordinator for sequencing. 2nos vision panel 200 x 300 with 6mm clear fire rated glass and finished in desired colour of powder coating not less than 50microns including suitable anchors & fire rated puff grouting all inclusive for fixing of doorset - for staircase / exit pathway / Refuge area applications. sqm 10.00 0.00 10.00
B103 Supply, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters,belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for varialbe frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.)and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification. no 2.00 0.00 2.00
B104 Design, fabrication, supply, erection, testing and commissioning of 5 Tonne capacity EOT crane consisting of double girder box type construction, rail mounted end carraiges with long and cross travel arrangement, main and auxiliary hoists of specified capacity, rails, pendant control, gear boxes, electric motors, brakes, rope drums, wire ropes, sheaves, end buffer stoppers, pendant operated DSL bus bars with all accessories for main and auxiliary hoists for handling GIS modules including cost of all materials, machinery, labour,cutting, aligning,welding, finishing, cleaning, greasing, applying two coats of zinc chromate red oxide primer and three coats of synthetic enamel paint and all other ancillary operations complete as per specifications and approved drawings. -For GIS modules ton 5.00 0.00 5.00
B105 Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU room-Damper sqm 0.25 0.00 0.25
B106 Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications. sqm 4.48 0.00 4.48
B107 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. (a) Thickness 0.63 mm sheet sqm 220.00 0.00 220.00
B108 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. (b) Thickness 0.8 mm sheet sqm 40.00 0.00 40.00
B109 Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. sqm 1.17 0.00 1.17
B110 Supplying, Fixing,testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications - Fire damper sqm 1.17 0.00 1.17
B111 Design, supplying, erecting testing and commissioning of-Passenger /Bed-cum-passenger hospital lift with speed of 1mtr per second ,variable voltagevariable frequency drive, with r without machine room for the available wellsize ,operatingat 415V3 phase 50cycles ACsupply, powdercoated /StainlessSteel car entrance doors enclosures with suitable colour vinyl flooring, LED car illumination, emergency light, inter com and fan as desired by the user, central opening /side opening door with or without attendant operation, 7segment display buttons, call registerindicator, firemandrive, SShandrails n sidecar, full length infrared curtainin cardoor, automatic rescuede vice with batteries, voice announcing in regional/ international languages, Braille buttons with one year warranty and maintenance with necessary scaffolding and minor civil works like fixing of guiderail, counterweight etc., The total product and servicess hall adhere to IS14665/2016 (with latest amendments) part/ section1to5 with regards to general guidelines of fire safety rated doors, MRLL beams, pressure switch, manual change over fo doors during emergency, ARD of 10 times with sufficient battery backup and standard dimensions of chair car and door openings for all sizes and capacities of lifts including fitness certificate and duly observing all other safety norms prescribed and adhere to CPWD specifications, PCB Norms, National Electricity Code (NEC), NBC-2016, IEC and Karnataka State Lifts, Escalators and Passengers Conveyers Act 2012 and Rules 2014. The Supplier shall be registered in Government Electrical Inspectorate in the State of Karnataka. With Out Machine Room-SS Finish. 15 passengers 4 Stops. no 1.00 0.00 1.00
B112 Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with atest ammendments and conveying to work site including loading and unloading at both destinations and rolling and lowering into trenches, laying true to line and jointing of pipes and specials with electrofusion welding, giving hydraulic test as per relevant ISS with all lead and lifts including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excation, testing and commissioning. The rate is exclusive of required specials and fittings wherever necessary like saddle Tee, stub ends, flanged sets, bedns, reducers etc. complete. (Contractor will make his own arrangements for procuring water for testing) etc. complete. NOTE: Upto 110mm dia Coil shall be used. For :HDPE PE 80 PN 6.0, 90mm dia. m 100.00 0.00 100.00
B113 Providing, Single Phase Submersible Pump Sets of 100mm dia (4 inch) suitable for bore well confirming to IS 8034-2000 specifications, to work site with testing of as per instructions of engineer incharge of work and latest ammendments and instructions of engineer incharge of work. 1.50 HP 1.50 HP/1.1KW 12 STG each 1.00 0.00 1.00
B114 Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. (Made of G.I. wire of dia 4 mm sqm 96.00 150.00 246.00
B115 Fencing with G.I. barbed wire Angle iron post placed at required distance embedded in cement concrete blocks, every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and provided with horizontal lines and two diagonals interwoven with horizontal wires, of barbed wire weighing 9.38 kg per 100 m (minimum), between the two posts fitted and fixed with G.I. staples, turn buckles etc. complete. (Cost of posts, struts, earth work and concrete work to be paid for separately). Payment to be made per metre cost of total length of barbed wire used. With G.I. barbed wire m 1204.80 300.96 1505.76
B116 Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc.) for: Borewell depth of 0 to 50 m - Water supply Upto 50.00 mtrs. m 50.00 0.00 50.00
B117 Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc.) for:Borewell depth of 50 to 100 m m 50.00 0.00 50.00
B118 Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc.) for: Borewell depth of 100 to 150 m m 50.00 0.00 50.00
B119 Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc.) for: Borewell depth of 150 to 200 m m 50.00 0.00 50.00
B120 Sinking borewell of 165mm dia. clear, using super fast hydraulic rig of capacity 300 PSIG & above 1100 CMF and above, in all strata of earth, including over burden upto 20M, fixing of casing pipes, collars and cap with ncessary cutting, threading and welding including transportation of rig and supporting vehicles, crew charges, cost of consumables, cost of yield test at the final depth with a minimum working of compressor for one hour etc. complete. The cost excludes the cost of casing pipes, collars and caps etc.) for: Borewell depth of 200 to 250 m m 50.00 0.00 50.00
B121 Supply of ISI mark 175mm nominal bore,plain and steel casing pipe grade of steel Fe 410 of wall thickness conforming to IS 4270-2001 and latest ammendments, electrical resistance welded steel tubes, material and conforming to IS 1387-1993 and manufactured by basic open hearth electric or basic oxygen process in random length of 5-7m both ends.threaded conforming to IS 554-1985 one end fixed with socket conforming to IS 4270-2001 and the other end with screwed pipes all shall be responsibaly free from defects. The tubes shall be responsible straight end should be with ISI marking weighing 25.10kg/m.prices include Collar-Medium duty m 20.00 0.00 20.00
B122 Providing and fixing MS casing collars as per IS 1239 (part-II) 1982 with all latest amendments if any for any dia. The thickness of plate used for covering one end shall be 3mm (minimum). The dimensions of caps and colars shall be strictly as per IS 1239 (Part-II) 1982 with all amendments each 1.00 0.00 1.00
B123 Providing and laying at site of work MS casing caps as per IS 1239 (part- II) 1982 with all latest amendments if any for any dia. The thickness of plate used for covering one end shall be 3mm (minimum). The dimensions of caps and colars shall be strictly as per IS 1239 (Part-II) 1982 with all amendments including cost of material and labour charges for fixing, if any etc. complete with all lead and lifts and as directed by the Engineer in charge each 1.00 0.00 1.00
B124 Geophysical investigation at site for sinking borewells for supplying drinking water to the habitation either through the Hand Pump MWS or P.W.S.S, by vertical electrical sounding by adopting Venner or Schlumbergers’s method, including reconnaissance survey of geological formation. Geophysical investigation of existing ground water in the vicinity, its quality, quantity and acceptability of the users, indicating the location of the site, recommended depth of casing pipe required to seal the top unconsolidated formation including an extra depth of 1.0 metre in consolidated formation for proper seating of casing pipe, depth of drilling required to cover full depth of aquifer proposed to be tapped, probable yield and other information required including transportation of instruments and accessories to work site, engaging technical personal and labour required etc. each 1.00 0.00 1.00
B125 PUMPSET : Providing Submersible Pump Set of 150mm dia suitable for bore well and confirming to IS 8034-2000 ; 3Phase, SS Bowl & Impeller with Low volt Motor as per specifications, to work site as per necessary ammendments and instructions of engineer incharge of work. 6.50 HP - 90 LPM @ 132 m = 15 STG Outlet Dia - 2.00” each 1.00 0.00 1.00
B126 SUBMERSIBLE CABLE Supply and delivery at site Brand new best make PVC insulated cable of Flat 3 core (sheathed) of nominal cross sectional area as per IS 694-1990 with ISI Mark and as per its latest amendments. 1x3x4 m2 m 145.00 0.00 145.00
B127 PRESSURE GAUGE : Supply and delivery at site of brand new best make pressure gauge bourdon type as per IS 778/1984 with ISI Mark and as per its latest amendments - Size 100 mm each 1.00 0.00 1.00
B128 GATE VALVE : Supply and delivery at site of brand new best make gate valve as per IS 778/1984 with ISI Mark and as per its latest amendments Size 50 mm each 2.00 0.00 2.00
B129 NON - RETURN VALVE : Supply and delivery at site of brand new best make non-return valve as per IS 778/1984 with ISI Mark and as per its latest amendments Size 50 mm each 1.00 0.00 1.00
B130 ix) Control Panel BOARD-A: Supply, installing,testing and commissioning COMMON control panel consisting of the following INCOMING:1 No set of Phase indicating lamps with SFU of suitable rating 1 No, Analog Ammeter, 1 No Analog Voltmeter 1ni with Phase selector switch, Isolating switch OUTGOING for Main Electrical Pump: 1 No. MCB 1 No. DOL of S/D Starter suitable for respective HP 1 No. Electrcal Protection Like single Phase preventor, under voltage over Volage, under current over current & dry run protection suitable for the pump described above 1 no Indoor typ e NOTE: 1) DOLDirect Online Starter 2)S-D- Star Delta Starter for outdoor 6 -15 HP pumps each 1.00 0.00 1.00
B131 POWER CAPACITOR: Supply and delivery at site best indigenous brand new power capacitor as per IS 2834/1986 with latest amendments with KPTCL authorities and erection, electrification and commissioning of the same at the location of respective pump sets. kVAR 1.00 0.00 1.00
B132 MCB: Supply and delivery at site delivery of best indigenous brand new MCB (Miniature Circuit Breakers) of required capacity as per IS 88228/1978 and its latest amendments and with ISI Mark of 6/10/16/20/25/40 Amps with scalable box. per 3 poles 1.00 0.00 1.00
B133 GALVANISED MILD STEEL TUBES: Supply and delivery of galvanized mild steel tubes of 6mtr standard length heavy duty (C Class) as per IS 1239 (Part-I) 1990 with latest amendments with ISI Mark (one end fitted with Heavy Duty collar and other end fitted with protective cover) 50 mm each 1.00 0.00 1.00
B134 Erection elctrification & Commissioning works of pumpsets : Labour charges for Erection, Electrification and commissioning of Pump sets, including aligning and balancing of all items including supply and erection of two pair of supporting clamps, bore well caps, cable clips and water tight gland cable protectors, bolts, nuts, valve and gauges,tools and equipments etc., involved in the job as per specifications, with necessary tests as per specifications, with testing of as per instructions of engineer incharge of work Job 1.00 0.00 1.00
B135 Erection of panel board & meter board Unit : Labour charges for erection of outdoor type panel board and meter board units with all necessary materials and labour, tools and equipmentsincluding providing cement concrete foundation bed etc., complete as per specification, with testing of as per instructions of engineer incharge of work. Job 1.00 0.00 1.00
B136 Main connections: Providing main connection from pole PVC insulated sheathed steel wire cable in new trench as per IS 1554/ 1988 with latest amendments with ISI mark from KPTCL pole to meter board unit. m 145.00 0.00 145.00
B137 Earthing: Supplying and fixing and wiring earth electrode for grounding circuits IC cutouts and other equipments on the meter board in the pit. The pits should be filled up with equal proportion of salt and charcoal 150mm around the pipe to complete depth. The connection from the pipe to the conduits etc. is to established through GI wire of sizes as per clause 7.3.3 of IS 732 using 12mm bolts, nuts, washers and check nuts, the pipe shall have 16 through holes of 12mm dia. Job 1.00 0.00 1.00
B138 Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 150 mm including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer in-charge of works as per the standard procedure. sqm 875.00 0.00 875.00
B139 Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring water for testing). Before the execution of the work, the contractor shall carry out the survey. RCC NP3 Class pipe of 300 mm dia. m 150.00 0.00 150.00
B140 Providing S&S RCC SPUN / VIBRATED CAST PIPES (REINFORCED) pipes NP-3 Class conforming to IS:458-1988 with latest amentments using ordinary portland cement, for sanitary works and conveying to work site, rolling and lowering into trenches, laying true to line and level including loading and unloading at both destinations and jointing of pipes and specials, perfect linking of joints with jack to correct position including cost of jointing materials, i.e, rubber rings conforming to IS: 5382 for S&S RCC pipes, with all leads and lifts as directed and giving necessary hydraulic test as per ISS to the required pressure and commissioning etc. complete. (Contractor will make his own arrangements for procuring water for testing). Before the execution of the work, the contractor shall carry out the survey. RCC NP3 Class pipe of 900 mm dia. m 25.00 0.00 25.00
B141 Finishing with Epoxy paint (two coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete. On concrete work including preparing the surface after thorougly cleaning oil, grease, dirt and foreign matter, cost of materials, labour complete as per specifications and as per directions of Engineer-in-charge. sqm 71.50 0.00 71.50
B142 Concealed Conduit System Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary 19/20mm dia 2mm thick m 500.00 0.00 500.00
B143 Concealed Conduit System Supplying heavy gauge PVC conduit pipe ...... mm dia..........mm thick confirming to IS 2509 with suitable size bends, metal/PVC Junction boxes, adhesive paste etc., and running before concreting the slab. The conduit should be tied to the reinforcement rods by using binding wires and unused ways of junction boxes and pipe ends should be covered using PVC end enclosures, run with 18SWG GI fish wire wherever necessary 25mm dia 2mm thick m 400.00 0.00 400.00
B144 Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering upto the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary 19/20mm dia 2mm thick. m 300.00 0.00 300.00
B145 Supplying heavy gauge PVC Conduit Pipe .... dia ....... mm thick with suitable size bends, metal junction boxes adhesive paste etc., by groove cutting in the wall and fixing by bracing U or J hooks and cement plastering upto the wall surface and run with 18 SWG GI fish wire run throughout the conduit wherever necessary 25mm dia 2mm thick. m 350.00 0.00 350.00
B146 Supplying and fixing sheet Metal box made out of 18SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 100 x 75 x 65 mm each 20.00 0.00 20.00
B147 Supplying and fixing sheet Metal box made out of 18SWG sheet metal with necessary holes for cable/conduit entry as required with one coat of primer of approved make etc. 135 x 75 x 65 mm each 15.00 0.00 15.00
B148 Supplying PVC flexible conduit pipe ....mm dia fixing on surface over inverted tapered wooden plugs or phill plugs or rawl plugs and clamped using heavy gauge saddles at an interval of 300mm using NF screws and on either end of the pipe terminated complete. 25 mm m 100.00 0.00 100.00
B149 Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. a) Short point up to 3Mtr from tapping point to out let via switch box point 50.00 0.00 50.00
B150 Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping casing capping using 2x1.5Sqmm (Phase & Neutral) & 1x1.0 sqmm (Earth wire) FRLS multi strand PVC insulated copper wire (confirming to IS-694: and latest amendments) without control switch shall be fixed on the existing plastic sheet/ gang box, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet. b) Medium point above 3Mtr up to 6Mtr from tapping point to out let via switch box point 70.00 0.00 70.00
B151 Point wiring using Copper wire without switch. Supplying and wiring adopting loop system in existing PVC Conduit /casing capping using copper PVC insulated multi strand 2x1.5Sqmm copper wire without switch, the other end of the wires shall be terminated with sufficient loose length in a wood/PVC round block. complete for each outlet.( 4/9) - II. Point wiring using class B Materials c) Long point above 6Mtr up to 10Mtr from tapping point to out let via switch box point 80.00 0.00 80.00
B152 Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS 694:201 1.5 sqmm m 750.00 0.00 750.00
B153 Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS 694:201 2.5 sqmm m 750.00 0.00 750.00
B154 Wiring for lighting/power circuit using one of FRLS PVC insulated 1100V grade, multistrand copper wire with low conductor resistance single core in open or concealed system of wiring with specified IS 694:201 4 sqmm m 850.00 0.00 850.00
B155 Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 1-2Way each 50.00 0.00 50.00
B156 Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 3Way each 30.00 0.00 30.00
B157 Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 1 to 2 Module each 50.00 0.00 50.00
B158 Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 3 Module each 30.00 0.00 30.00
B159 Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 4 Module each 30.00 0.00 30.00
B160 Supplying and fixing superior quality modular switch mounting polycarbonate plate with necessary supporting back plate with required nos. of machine screws, bolts nuts etc., complete on the existing metal/PVC box 6 Module each 15.00 0.00 15.00
B161 Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A One Way Switch Each 40.00 0.00 40.00
B162 Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A Two Way Switch Each 120.00 0.00 120.00
B163 Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6A Three Way socket Each 40.00 0.00 40.00
B164 Supplying and flush mounting powder coated / galvanized metal box suitable for mounting modular switch plates. The box should be firmly flush mounted after due groove cutting in Brick/Stone/C.C wall 4-5Way Each 25.00 0.00 25.00
B165 Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. Stepped Fan Regulator Two Module Each 10.00 0.00 10.00
B166 Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 32A DP Switch Each 10.00 0.00 10.00
B167 Supplying and fixing of modular switch & connected accessorieson existing modular switch plate as per IS 3854 and IS 1293. 6/16A Universal Socket Each 15.00 0.00 15.00
B168 Supplying and fixing Moulded Case Circuit Breaker (MCCB) over the existing wood/panel board using necessary screws, bolts, nuts, necessary phase separators, handle and wiring complete. Protection of Overload and Short circuitwith adjustable thermal magnetic release, Micro processor release shall have Earth Fault as per IS/IEC 60947-2 . (Icu=100% lcs). In 4P MCCB, all Poles should have protection for Short-Cicrcuit/Over Load. For Microprocessor MCCBS Facility for segregating Priority and Non-Priority loads must be available in the MCCB. MCCB shall be provided with double insulation (insulation between front cover and internal power circuits to avoid any accidental contact with live current carrying path with the front cover open). Multi-pole breakers shall be designed to break all the poles simultaneously and they shall have a single mechanism 100 A 25 kA Each 5.00 0.00 5.00
B169 Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898 6-32A SP Each 10.00 0.00 10.00
B170 Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898 50-63A SP Each 10.00 0.00 10.00
B171 Supplying, fixing and wiring Residual current circuit breaker(RCCB) 240/450V upto 300mA sensitivity on existing wood/ panel board. 16A - 25A 2 pole Each 3.00 0.00 3.00
B172 Supplying, fixing and wiring earth leakage relay with core balanced current transformer suitable for single phase 50HzAC with latest micro controller based, digital read out of percentage leakage current, programmable delay/auto/manual reset facility suitable to mounton DIN rail/ flush mounting on panel board. Each 1.00 0.00 1.00
B173 Supplying, fixing and wiring 3 Phase Digital Ammeter / Voltmeter each 1.00 0.00 1.00
B174 Supplying and fixing of LED type panel board indicating lamp with required colour suitable for 230/440VAC. 50 Hz 12/24V D.C. each 1.00 0.00 1.00
B175 Supplying exhaust fan of 1440 RPM of 300 mm (12") size with bracket blades complete for light duty suitable to operate on 230V 50Hz, AC Supply. each 5.00 0.00 5.00
B176 Supplying of 1440rpm heavy duty exhaust fan with bracket blades suitable to operate on 230V 50Hz, AC Supply complete. - 15" Sweep (450mm) each 5.00 0.00 5.00
B177 Supplying capacitor type ceiling fan complete with down rod blades, shackle, canopies etc., for operation on 230 volts, 50 cycles. Single phase AC supply conforming to ISS-374-1979 and with double ball bearing system 48" Sweep (1200mm) Regular model each 5.00 0.00 5.00
B178 Supplying wall mounting fan suitable to operate at single-phase 230v AC supply. 400 mm Sweep each 2.00 0.00 2.00
B179 Supplying of .. TR Invertor type split Air conditioners suitable for operation on A/C supply single phase 50 Hz 230 V with hermetically sealed inverter compressor with air cooled condenser, latest R410A / R-32 refrigerant fan motor, start & run capacitors, relay & over load protector internal unit, with one indoor & one outdoor unit The condenser unit will be placed outside the room avoid noise including standard length of suitable size copper tubing covered with nitrile rubber insulation tube. suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit.5 star.2 Ton capacity No 20.00 0.00 20.00
B180 Installation charges for split type air conditioner with allied works for one indoor and one outdoor unit is to be mounted on suitable Angle Iron support upto 3.0 Ton split/cassette type A/C. No 20.00 0.00 20.00
B181 Supplying and installation of insulated refrigerant copper tubing of 5/8" and 3/8" with polythene foam insulation 3 core 80 stand copper wiring between indoor and outdoor unit Leak testing oil and gas charging for additional piping length of tube.Split No 40.00 0.00 40.00
B182 Extra for Fabrication supply and fixing of Stand fabricated using slotted angle /L angle of size 6mm x 50mm for mounting out door/indoor A.C. unit/ Batteries. No 15.00 0.00 15.00
B183 Supplying of .....feet -PVC Batten with integrated LED tube ....W with high quality diffuser with Life of 25000 burning hours & 70% lumen maintenance with CRI greater than 80. Power Input: 220-240V @ 50/60Hz & Power factor greater than 0.9 along with CE approved. 2 years Warranty against any manufacturing defect working under standard electrical condition.LED light fitting 1 x 4' - 20/22 W No 15.00 0.00 15.00
B184 Supplying & fixing miniature circuit breakers on existing MCB distribution boards using necessary fixing materials and 'C' Type curve, indicator ON/OFF, energy cross-3 with Short circuit breaking capacity of 10K and complete wiring as required confirming to IEC 60898 6-32 A TPN Each 5.00 0.00 5.00
B185 Supplying of recess mounting non integrated type LED down light 18W luminaire comprising of pressure decast/ extruded aluminium housing, with spring loaded false ceiling clA, LED of Power/COB with CCT 6500 degree K, CRI greater than 70%. efficacy greater than 100 lumen per W, 120degree beam spread, life greater than 25000 burning hours and Compliance to IS10322/ IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level. LED's are driven by HF electronic driver integrated in a separate control gear assembly., with PF greater than 0.95, power loss should less than 5% of lamp Wage, short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition LED modular down light 1'x1' 18W each 15.00 0.00 15.00
B186 Supplying of recess mounting non integral type ........ LED w luminaire comprising of pressure decast/extruded aluminium housing, with spring loaded false ceiling clA, Power LEDs with CCT 6500 degree K, CRI greater than 70%. efficacy greater than 100 lumen per W, 120degree beam spread, life greater than 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF greater than 0.95, power loss should be lesser than 5% of lamp Wage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.LED modular down light 2'x2' / 36W each 20.00 0.00 20.00
B187 Supplying of recess mounting non integral type ........ LED w luminaire comprising of pressure decast/extruded aluminium housing, with spring loaded false ceiling clA, Power LEDs with CCT 6500 degree K, CRI greater than 70%. efficacy greater than 100 lumen per W, 120degree beam spread, life greater than 25000 burning hours and Compliance to IS 10322/IEC 60598, LM 79 & LM 80. The lamp compartment is enclosed with anti glare opal diffuser which enhances the lighting level LEDs are driven by HF electronic driver integrated in a separate control gear assembly., with PF greater than 0.95, power loss should be lesser than 5% of lamp Wage., short circuit & open circuit protection to be integrated in the circuit, THD less than 20%, Life as per LM 79. The operating input voltage should be between 130 to 275 V. BIS Approved and Tested by NABL/CPRI accredited laboratory with 2 years Warranty against any manufacturing defect working under standard electrical condition.LED modular down light 2'x2' / 40-42 W each 20.00 0.00 20.00
B188 INDUSTRIAL HIGHBAY LUMINAIRE ( INTEGRAL TYPE) Industrial medium/high bay luminaire with integral type Control gear, copper wound ballast, visor glass assembly and including supply of lamps. 100W, 240V, LED Highbay luminare each 12.00 0.00 12.00
B189 Supply and fixing Battery operated portable fluoresent lamps each 5.00 0.00 5.00
B190 Fixing all types and all capacities of fluorescent /falseceiling/ spot light/CFL/LED fittings indoor on the wall/ceiling/rafters/girders using 23/0.0076" twintwisted PVC insulated wires, required Nos of round blocks and clamps. On wall/ ceiling / Rafter / Girders. each 97.00 0.00 97.00
B191 Fixing a ceiling/wall mounting fan of all capacities and all types to the existing 'S'' hook with fan regulator to the existing board together with supplying and fixing 5 A. ceiling rose, necessary length of 23 / 0.0076 inch PVC insulated twin twisted copper wire and wiring. each 7.00 0.00 7.00
B192 Fixing one exhaust fan after making a suitable notch in the wall and finishing with cement mortar and colouring to match the existing wall or brackets, with bolts and nuts and a 5 A, ceiling rose with sufficient length of 23 / 0.0076 inch PVC insulated twin core wire of approved make with wire mesh and wooden frame. each 10.00 0.00 10.00
B193 Supplying, erecting, testing and commissioning of voltage stabilizer suitable for 170 to 270 v input and load variation from no load to full load, with over load protection, spike suppression, operating at 00 C to 400 C. Range etc., complete.5kVA Capacity m 1.00 0.00 1.00
B194 Supplying and fixing of LED Bulkhead of 10W with IP65 protection and IK08 impact resistance suitable for surface and wall mounting applications. No 10.00 0.00 10.00
B195 Filling approved earth (excluding rock) in trenches, plinth, sides of foundations and other similar works etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m cum 146.25 0.00 146.25
B196 Supplying PVC ringtite pipes conforming to IS 4985:2000 with latest amendments and conveying to worksite, rolling and lowering into trenches, laying true to line and level and perfect linking at joints, testing and commissioning, including loading unloading at both destinations and cuts of pipes wherever necessary including jointing of PVC pipes and specials (excluding cost of specials) with jointing of approved type, with all labour with all lead & lift including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excavation etc. complete and giving necessary hydraulic test to the required pressure as per ISS (Contractor will make his own arrangements for procuring water for testing) etc. for: PVC pipes 160mm dia., 6 kg/sqcm & class 3 m 0.00 75.00 75.00
B197 Jelly Spreading (20-25 mm) : Supplying and providing jelly in the station yard of uniform thickness of 100 mm including the cost of materials, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer in-charge of works as per the standard procedure. sqm 0.00 450.00 450.00
1) The uploaded drawings are indicative and are to be referred for guidance purpose only. However all foundations shall be designed to suit the site soil condition and as per the approved layout.
2) The land will be handed over " As is where is condition".
Place Designation
Name of the company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 3C(ii) - Price Breakup for -UG Civil Portion
SHEET FOR TECHNO COMMERCIAL OPENING (Unpriced)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk and District.
BIDDERS SHALL NOTE: FILL ONLY IN LIGHT BLUE COLOURED CELLS
Bidders Name and Address along with GSTIN No.: To
The Chief Engineer, Electy., Tendering & Procurement, 9th Floor, Indhana Bhavana, KPTCL, A R Circle, BANGALORE - 560009.
Sl. No. Specifications Unit Quantity
D1 Earth work excavation for laying of UG cable in open ground and beneath the road surface in different strata of soil by mechanical means including deposition of earth on back with all leads and lifts including Shoring, Strutting, providing Caution Boards, Danger lighting , Bracing, Sheeting, Bailing out of water, Barricades and other works not specifically mentioned herein but required for the completion of work as per site condition in all respects and as per approved drawing. In all kind of soil for required depth. Cum 1808.64
D2 Earth work excavation for laying of UG cable in open ground and beneath the road surface in different strata of soil by mechanical means including deposition of earth on back with all leads and lifts including Shoring, Strutting, providing Caution Boards, Danger lighting , Bracing, Sheeting, Bailing out of water, Barricades and other works not specifically mentioned herein but required for the completion of work as per site condition in all respects and as per approved drawing. Ordinary/soft rock (without requiring blasting) for required depth. Cum 516.75
D3 Earth work excavation for laying of UG cable in open ground and beneath the road surface in different strata of soil by mechanical means including deposition of earth on back with all leads and lifts including Shoring, Strutting, providing Caution Boards, Danger lighting , Bracing, Sheeting, Bailing out of water, Barricades and other works not specifically mentioned herein but required for the completion of work as per site condition in all respects and as per approved drawing. Hard rock (blasting prohibited) for required depth. Cum 258.38
D4 Dismantling of Flexible pavements and disposal of dismantled materials and stacking serviceable and unserviceable materials separately By Mechanical Means By Bituminous course Cum 273.90
D5 Dismantling of Flexible pavements and disposal of dismantled materials and stacking serviceable and unserviceable materials separately By Mechanical Means Granular course Cum 739.53
D6 Dismantling of Cement Concrete Pavement : Dismantling of cement concrete pavement by mechanical means using pneumatic tools, breaking to pieces not exceeding 0.02 m3 in volume and stock piling at designated locations and disposal of dismantled materials and stacking serviceable and unserviceable materials separately. Cum 708.18
D7 Providing M-Sand : Supplying and filling in plinth, foundations / UG cable work with approved M-sand including watering, ramming, consolidating and dressing. The rate includes the cost of material, labour charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer- in-charge of works as per the standard procedure. Cum 2293.77
D8 Supplying and Providing pre cast RCC Protection Covers using M20 grade Concrete, steel of approved size/shape (as per the approved drawings) to be laid in UG cable works. The rate includes the cost of material, labour charges, loading, unloading, handling, transportation charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer-in-charge of works as per the standard procedure. Sqm 1058.00
D9 Refilling available earth around trenches/pipelines, cables in layers not exceeding 20 cms in depth, compacting each deposited layer by ramming after watering with a lead upto 50 m, and lift upto 1.5 m. Including cost of all labour complete as per specifications Cum 174.00
D10 Removal of Unserviceable Soil with Disposal upto a suitable distance as directed by the Engineer incharge of work Cum 2409.77
D11 Supplying and Providing Pre cast Cable Route/ Joint marker using M15 grade Concrete, MS rods of approved size/shape (as per the approved drawings) to be laid in UG cable works. The rate includes the cost of material, labour charges, loading, unloading, handling, transportation charges, required tools and plants etc., complete. Work shall be carried out as per the instructions of Engineer-in-charge of works as per the standard procedure. No 43.00
D12 Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing and all the other appurtenances required to complete the work as per technical specifications. Mix 1:3:6 (M10) Using 20 mm nominal size graded crushed coarse aggregates Cum 325.38
D13 Providing and laying in position Cement Concrete for all Super structures of building , Road works, Water works, Irrigation works & super structure works of bridges upto 3.50 m height. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed with super plasticisers laid in layers, well compacted using needle vibrators. The cost includes all lead & lifts, cost of all materials, quality confirming to the requirements of relevant IS codes , labour, Usage charges of machinery, curing, form work, centering & scaffolding and all other appurtenances required to complete the work as per technical specifications. M40 Design Mix Using 20 mm nominal size graded crushed coarse aggregates (5% considered for Form work) Cum 382.80
D14 HDD method for 220 kV UG Cable work: Installation of 3 rows of HDPE pipes PE 80 PN6 of 250 mm dia using Horizontal directional drilling technique (HDD method) including preparing and setting up the plant and equipment, preparing new pipe work materials, installing new pipe work and commissioning system or making the system ready for commissioning by HDD operation including excavation, shoring/ strutting etc., drilling, stringing, ramming and pulling back the new work on the design bore path alignment, proper disposal of drilling fluid and restoration of site after completion etc., for HDD technique suiting Indian conditions in all types of soil. m 48.00
D15 Providing and laying in position Cement Concrete for levelling course for all works in foundation. The granite/trap/basalt crushed graded coarse aggregates and fine aggregates as per relevant IS Codes machine mixed, laid in layers not exceeding 150 mm thickness, well compacted using plate vibrators, including all lead & lifts, cost of all materials of quality, labour, Usage charges of machinery, curing, and all the other appurtenances required to complete the work as per technical specifications. Mix 1:2:4 Using 20 mm nominal size graded crushed coarse aggregates Cum 70.00
D16 Providing and laying of warning tape / Caution tape / detector tape for HDPE pipes of 200 mm wide, 300 micron thick, blue in colour confoming to relevant ISS with latest amendments with appurtenances., complete m 2116.00
D17 Providing, laying and jointing HDPE pipes of specified grade and conforming to IS 4984-2016 with latest ammendments and conveying to work site including loading and unloading at both destinations and rolling and lowering into trenches, laying true to line and jointing of pipes and specials with electrofusion welding, giving hydraulic test as per relevant ISS with all lead and lifts including encasing the pipe alround to a depth of not less than 15 cms. with soft gravel or selected earth available from the excation, testing and commissioning. The rate is exclusive of required specials and fittings wherever necessary like saddle Tee, stub ends, flanged sets, bedns, reducers etc. complete (Contractor will make his own arrangements for procuring water for testing) etc. complete. HDPE Grade PE80-PN6.0,250mm dia m 3876.00
D18 Construction of Granular Sub-Base of required grading as per design mixing in a mechanical mix plant at OMC, carriage of mixed Material to work site, spreading in uniform layers with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per clause 401. For Grading -V Material Cum 503.98
D19 Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver/grader in sub-base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density. Cum 547.80
D20 Prime Coat over WMM/WBM: Providing and applying primer coat with SS1 grade Bitumen Emulsion on prepared surface of granular base including cleaning of road surface and spraying primer at the rate of 0.70 kg per m2 using mechanical means. Sqm 2556.40
D21 Tack coat on Granular surface treated with primer Providing and applying tack coat with RS1 Bituminous Emulsion using emulsion pressure distributor at the rate of 0.25 kg/m2 on Granular Surface Sqm 2739.00
D22 Dense Graded Bituminous Macadam Grading - II for traffic <20 MSA: Providing and laying Dense Graded Bituminous Macadam with 120 TPH capacity HMP batch type using crushed aggregates of specified grading, premixed with bituminous binder VG-30, @ 4.5 per cent by weight of total mix and filler, transporting the hot mix to work site, laying with mechanical paver finisher to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MoRTH specification clause No. 505 complete in all respects. Cum 191.73
D23 Bituminous Concrete Grading II for traffic less than 20 MSA Providing and laying Bituminous Concrete with 120 TPH capacity hot mix plant batch type using crushed aggregates of specified grading, premixed with bituminous binder VG-30, @ 5.4 per cent of mix and filler, transporting the hot mix to work site, laying with mechanical paver finisher to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per MORTH specification clause No. 507 complete in all respects Cum 109.56
Place Designation
Name of the company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE-5 COMMERCIAL DEVIATION
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Please fill Only in the Light Blue Couloured Cell.
Please key in the SlNo.,Section , Clause , Description as given in bid sheets and finally your Statement of Deviation/Variations.
This Sheet would be opened at the Techno-Commercial Opening. Please refer Vendor Manual attached for further details.
For any further assistance for submitting your bids please call up KPTCL Office.
We agree to provide all original Documents in support of the information provided for verification upon request. (Key in as YES in the space provided)
We understand that the electonic bid submitted by us is a valid offer in accordance with IT Act. (Key in as YES in the space provided)
We are fully aware of the electronic bid formalities and abide by the same. (Key in as YES in the space provided)
If you are not deviating from any of the clauses mentioned please key in as 'NO DEVIATION' in the space provided.
Bidder's Name & Address alongwith GSTIN no. :
TO, THE CHIEF ENGINEER (ELECTRICTICTY), TENDERING AND PROCUREMENT, KPTCL,9th Floor, Indhana Bhavana, BANGALORE-560009
I/we have read each of the Clauses mentioned in INVITATION FOR TENDERS , INSTRUCTION TO TENDERERS , CONDITIONS OF CONTRACT, SPECIAL CONDITIONS OF CONTRACT and COMMERCIAL TERMS AND CONDITIONS and all the sections of Bid documents.
The following are the commercial Deviations and Variations from and exceptions to the Specifications and documents for
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
These deviations and variations are exhaustive. Except these deviations, the entire work shall be performed as per your specifications and documents.
Sl. NO. SECTION CLAUSE NO. DESC. AS PER SPECIFICATION STATEMENT OF DEVIATIONS/VARIATIONS
Note : Deviations specified elsewhere in the specification will not be considered.
Place Designation
Name of the company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE-6 : TECHNICAL DEVIATION
SHEET FOR TECHNO-COMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Please key in the SlNo., Section , Clause , Description as given in Bid sheets and finally your Statement of Deviation/Variations.
This Sheet would be opened at the Techno-Commercial Opening.
For any further assistance for submitting your bids please call up KPTCL office. Please fill only in the blue coloured cells.
We agree to provide all original Documents in support of the information provided for verification upon request. (Key in as YES in the space provided)
We understand that the electonic bid submitted by us is a valid offer in accordance with IT Act. (Key in as YES in the space provided)
We are fully aware of the electronic bid formalities and abide by the same. (Key in as YES in the space provided)
If you are not deviating from any of the clauses mentioned please key in as 'NO DEVIATION' in the space provided.
Bidder's Name & Address alongwith GSTIN no. : TO,
THE CHIEF ENGINEER (ELECTRICTICTY), TENDERING AND PROCUREMENT, 9th Floor, Indhana Bhavana, BANGALORE-560009
The following are the Technical Deviations and Variations from and exceptions to the Specifications and documents for
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
These deviations and variations are exhaustive.Except these deiviations and variations, the entire work shall be performed as per your specification and documents.
Sl. NO. SECTION CLAUSE NO. DESC. AS PER SPECIFICATION STATEMENT OF DEVIATIONS/VARIATIONS
Note : Deviations specified elsewhere in the specification will not be considered.
Place Designation
Name of the company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE 7(List of special tools and tackles )
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. : TO,
THE CHIEF ENGINEER (ELECTRICTICTY), TENDERING AND PROCUREMENT, 9th Floor, Indhana Bhavana, BANGALORE-560009
List of special tools and tackles the price of which is included in bid price.
Sl. No. For equipment Description of item Unit Quantity
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
NOTE: 1 ) SHALL BE UPLOADED WITHOUT PRICES
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electy., Tendering & Procurement, 9th Floor, Indhana Bhavana, BANGALORE - 560009
We have uploaded with our proposal the following additional information.
Sl. No. Brief Description of information Ref. and Page No.
Place Designation
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE - 9 (1 of 5) : QUALIFYING REQUIREMENTS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDER'S NAME AND ADDRESS: TO,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009
a) * We have submitted bid as individual Bidder. (Key in Individual Bidder )
b) * We have submitted bid in Consortium with the following Bidders. (Key in Consortium )
Name of Consortium Partner Scope / Participation of each Consortium Partner
(* Fill-up whichever is applicable)
1.0 GENERAL INFORMATION
The Bidder, bidding for this package are requested to complete the information in the following form.
Sl. No. Particulars Bidder Details
1 Name of the Firm
2 Address of Head Office / Registered Office GST no.
5 Name of Contact person with Designation
6 Place of Incorporation/Registration
7 Year of Incorporation/Registration
8 Constitution or legal status of Tenderer [Upload copy]
9 Place of Registration [Upload copy]
10 Principal place of business
2.0 We are furnishing the following details/documents in support of Qualifying requirement for above mentioned project
Sl.No. Particulars For individual Bidder In case of Consortium :
Lead Bidder Consortium partner
(a) Written power of attorney of the signatory on the bid to commit the bidder.
1 Uploaded / Not
(b) Certificate of Registration of the Company. Please mention the date of incorporation of the company
1 Uploaded / Not
(c ) Valid Super Grade Electrical Contractor’s License issued by the Government of Karnataka OR valid Form J-1 Verification Letter issued by Chief Electrical Inspectorate, Govt. of Karnataka to Other State Electrical Contractor License Holder for the highest system voltage specified in the tendered work as on the date of techno commercial Bid submission. Please mention the date of expiry of the License certificate issued by GOK/ Undertaking to this effect
1 Uploaded / Not
(d) Self declaration regarding Litigation w.r.t KPTCL contracts over the last five years (refer IFT)
1 Uploaded / Not
(e) Self declaration for ‘not being disqualified regarding non-performance in any of the Government utilities in the past five years’. (refer IFT)
1 Uploaded / Not
(f) An undertaking to source the supply of equipment/ material from KPTCL approved vendors only as per QR for Vendor registration, available in the KPTCL website ie., kptcl.karnataka.gov.in, Link Tendering & Procurement-Application for Vendor.
1 Uploaded / Not
(g) Self declaration regarding no action against the bidder have been taken by KPTCL in respect of Risk & Cost clause
1 Uploaded / Not
(h) Self declaration regarding 'Eligibility clauses in respect of restrictions on procurement from a bidder of a country which shares a land border with India as per Annexure-XVI
1 Uploaded / Not
(i) Self declaration regarding RESTRICTIONS ON SOURCING OF EQUIPMENTS/MATERIALS BY THE BIDDER FROM A VENDOR OF A COUNTRY WHICH SHARES A LAND BORDER WITH INDIA as per Annexure -XVII
1 Uploaded / Not
Section 3 : 1.3 Work performed of similar nature in the last Ten years of both Lead Bidder & Consortium partner (in case of Consortium) as per Clause No: 3.2 (b) (i) & (ii) of ITT
Project Name Name & Address of the Employer Description of Work Voltage class Number of Sub-Stations/TBs/Length of the Line Contract Number Value of contract Rs. Lakh Date of issue of work order Specified period of completion Actual date of commissioning Remarks explaining reasons for delay in commisioning of work
Name of Consortium Partner
Note : 1 . The documentary proof of fulfilling the qualifying requirements shall be uploaded along with the bid. (i) The bidder shall upload the P.O,LOI/LOA, DWA, Work done, Performance Certificates issued by the end users not below the rank of Executive/ Divisional Engineer along with the bid. (ii) The work experience of Bidders who have executed DCW works/ Self execution works under the supervision of KPTCL officers and the works executed for BMRCL/ KIADB/ BDA/KBJNL/IPP works/other Government or Public sector organizations will also be considered subject to fulfilling the stipulated qualifying requirements and uploading necessary documentary evidence
2. The qualifying experience of the Bidder and Consortium Partner(in case of Consortium) who is having qualifying experience shall be furnished in the above performa and Documentary Proof in support of above shall be uploaded in the form of certificates issued by authorized officers of concerned organisations.
3. IF this sheet is insufficient for furnishing the qualifying experience of the Bidder then similar sheets shall be seperately uploaded.
4. In case of work executed under a contract that had been awarded on a joint venture, the experience of individual joint venture partner shall be considered limited to the scope of that partner under the said contract. The copy of the agreement executed with awarding agency shall be uploaded as proof of the same
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE - 9 (2 of 5) : QUALIFYING REQUIREMENTS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDER'S NAME AND ADDRESS: TO,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009
Section 3 : 1.5 Information on works for which Tenders have been submitted and works which are yet to be completed as on the date of this Tender of a Bidder
(A) Existing commitments and on-going works:
Description of work Place & State Contract No & Date Name and Address of Employer Value of contract (Rs. Lakh) Stipulated period of cof Completion Value of works remaining to be completed ( Rs.Lakhs) (Attach Certificates from Engineers –in- Charge) Anticipated date of commissioning
Ex-Works GST Total (Ex-works + GST)
Name of the Lead Bidder
Name of the Consortium Partner
Note:Attach Certificates from Engineers –in- Charge
B)Works for which Tenders already submitted
Description of work Place & State Name and Address of Employer Estimated value of works (Rs. Lakh) Stipulated period of Completion Date when decision is expected Remarks if any
Ex-Works GST Total (Ex-works + GST)
Name of the Lead Bidder
Name of the Consortium Partner
i) The statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed should be countersigned by the Employer in charge, not below the rank of an Executive Engineer or equivalent. OR The statements showing the value of existing commitments and on-going works as well as the stipulated period of completion remaining for each of the works listed should be verified and certified by Chartered Accountant/ Cost Auditor. However, the Bidder has to upload the PO/Work Award copies for existing commitments and on-going works
ii) A self-declaration is to be uploaded by the Lead Bidder & Consortium partner (in case of Consortium) stating that "the information with regard to assessed available tender capacity (Works on Hand) furnished are correct
iii. Bidders shall furnish Certificate from Chartered Accountants for split details of Ex-works values and GST of Contract values of the works in the prescribed format as at Clause No. 1.5 of Section-3: Qualification Information by the Lead Bidder & Consortium partner (in case of Consortium)
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE - 9 (3 of 5) : QUALIFYING REQUIREMENTS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDER'S NAME AND ADDRESS: TO,
THE CHIEF ENGINEER (ELECTRICTICTY), TENDERING AND PROCUREMENT, KPTCL, 9th Floor, Indhana Bhavana, Bangalore - 560 009
Following is the list of major supplied Substation equipments/accessories which are type tested and designed, manufactured by us in accordance with internationally recognised standards.
Sl. No. Item rating, type and Designation Qty Customer Date of Order Date of Supply Date of Commissioning Ref. of Cusomer's certificate of successful operation enclosed Ref. of layout & Customer's certificae for successful commission
Note: Documentary Proof in support of above shall be uploaded in the form of certificates issued by authorized officers of concerned organisations.
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE - 9 (4 of 5) : QUALIFYING REQUIREMENTS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. : To
The Chief Engineer, Electricity, Tendering & Procurement, KPTCL, 9th Floor, Indhana Bhavana, Bangalore - 560 009
Section 3 : 1.7 Reports on the financial standing of the tenderer(Lead bidder & Consortium partner (in case of Consortium)) ,such as Profit and Loss Statements and Auditor’s reports in the preceeding last five years, Audited Financial statements i.e Balance sheets, P&L statements, Turnover certificates duly certified by chartered Accountant as documentary evidence shall be uploaded.
SLNo. Particulars Year Lead Bidder Consortium Member
Mention Year Turnover excluding GST (in Rs.) GST Amount (in Rs.) Mention Year Turnover excluding GST (in Rs.) GST Amount (in Rs.)
Names of the constituent Firm
1 Annual turn over for the last Five years Year(1) 2020-21 2020-21
2 Liquid Assets / Credit availability or access to evidence of assets
3 Whether Audited Balance sheets and Profit & Loss statement are enclosed for the last Five Years ? (yes/No)
4 Whether Bankers certificate enclosed for credit facilities? (Yes/No)
Note: Bidders shall furnish Certificate from Chartered Accountants for split details of financial Turnover and GST in the prescribed format (Annexure-XX) of tender document.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 9 (5 of 5) : QUALIFYING REQUIREMENTS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDER'S NAME AND ADDRESS: TO,
THE CHIEF ENGINEER (ELECTRICTICTY), TENDERING AND PROCUREMENT, KPTCL, 9th Floor, Indhana Bhavana, Bangalore - 560 009
The information to be filled in by the Tenderer hereunder will be used for purposes of computing Tender capacity as provided for in Clause 3 of the Instructions to Tenderers. This information will not be incorporated in the Contract.
Lead Bidder Consortium partner Attach Copy
1.1 Constitution or legal status of Tenderer [Upload copy]
Place of Registration [Upload copy]
Principal place of business
Section - 3: 1.2 Total value of works executed (KPTCL & Non KPTCL works) and payments received in the last five years (in Rs. Lakhs) of both Lead Bidder & Consortium partner (in case of Consortium).
1.2 Total value of works executed (KPTCL & NON KPTCL works) and payments received in the last five years (in Rs. Lakhs) of both Lead Bidder & Consortium partner (in case of Consortium). Financial Year KPTCL works Non KPTCL works
Individual Bidder In case of Consortium Individual Bidder In case of Consortium
Total value of works in Rs. Lakh Lead Bidder Consortium Partner Total value of works in Rs. Lakh Lead Bidder Consortium Partner
Total value of works in Rs. Lakh Total value of works in Rs. Lakh Total value of works in Rs. Lakh Total value of works in Rs. Lakh
Note: Attach relevant Certificate/s from Chartered Accountant.
Section 3: 1.9 Name, address, telephone number & e-mail id of the Tenderers' bankers who may provide references if contacted by the Employer:
1.9 Sl.No Name, address, telephone number & e-mail id of the Tenderers' bankers
Section 3: 1.12 Information on litigations in which the Tenderer is involved:
Other Party(ies) Employer Details of Dispute Amount involved Remarks showing Present Status
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE-10 (1 of 3) Details of Tools and Plants available
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDER'S NAME AND ADDRESS: To
The Chief Engineer, Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 560 009
Following are the details of the Tools and Plants available with us.
Sl. No. Description Quantity Make Present Location / Project Remarks (if any)
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE 10 (2 of 3) Details of Technical staff employed
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDER'S NAME AND ADDRESS: To
The Chief Engineer, Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 560 009
Section 3: 1.8 Qualification and experience of the key technical and management personnel in permanent employment with the tenderer and those that are proposed to be deployed on this contract, if awarded
Sl. No. Name of the employee Designation Branch (Degree/Diploma) Year of Passing Since when employed in erection division Past Experience
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE 10 (3 of 3 )
SHEET FOR TECHNOCOMMERCIAL OPENING
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
BIDDER'S NAME AND ADDRESS: To
The Chief Engineer, Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 560 009
We propose the following deployment of manpower for the substation and Line package.
Sl. No. Category MONTHS AFTER PLACEMENT OF AWARD LETTER
1 Project manager
2 Sr. Project Manager
5 Skilled labour
6 No skilled labour
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE-11 (A) : COMPLETION SCHEDULE FOR STATION/TERMINAL BAYS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidders Name and Address: To,
The Chief Engineer, Electricity, Tendering & procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 560009
We hereby declare that following schedules shall be followed by us for the above work. The period of various activities from the date of placement of award letter shall be as follows
SL.NO Activity Period in Months for the work of Substation
Commencement Completion
1 Detailed engineering
2 Procurement of bought out items / raw materials
3 Manufacturing & Testing
5 Setting up of site office, Sheds & stores etc.
7 Concreting for
a)Structure Foundations
b)Equipment and mounting structure foundadions
c)Cable trenches
2. Installation
8 Receipt(at site) of
a)Main equipment / spares
c)Insulators & Hardwares
d)Clamps & Connectors
e)Marshalling kiosks
f)Cables & Cabling Materials
a)Main structures
b)Equipment support structures
10 Equipment Erection
12 Bus bar erection
15 Completion of testing and ready for commissioning
16 Commissioning
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE-11B : COMPLETION SCHEDULE FOR TRANSMISSION LINES/UG CABLES
SHEET FOR TECHNOCOMMERCIAL OPENING
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
Bidders Name and Address: To,
The Chief Engineer, Electricity, Tendering & procurement,KPTCL,9th Floor, Indhana Bhavana, Bangalore - 560009
We hereby declare that following shedules shall be followed by us for the above work. The period of various activities from the date of placement of award letter shall be as follows.
SL.NO Activity Period in months for work of UG Cable
Commencement Completion
1 Submission of Drawings
2 Completion of detailed engineering
3 Commencement of Manufacturing
4 Completion of Manufacturing
5 Readiness for testing
6 Readiness for Shipment
7 Receipt at Site
8 Completion of Shipment
1 Detailed Survey
2 Setting up of site office, sheds and stores etc.
3 Exacavation for foundations.
4 Foundations and other Civil Works
5 Erection of Tower alongwith accessories
6 Stringing of conductor/ groundwire alongwith accessories
7 Testing , Commissioning and Handing over.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 12 TYPE TESTS & TEST CHARGES OF EQUIPMENT/MATERIALS
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDERS SHALL INDICATE VARIOUS TYPE TESTS IN LIGHT BLUE COLOURED CELLS
ALL THE TYPE TESTS APPLICABLE FOR EACH OF THE EQUIPMENTS SHALL BE INCLUDED.
Bidders Name and Address To,
The Chief Engineer, Electricity, Tendering & procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 560009
SL.No Details of Equipments Type Test Test Charges ( in Rs )
1 Power Transformer:
20MVA, 110/11kV
Auxiliary Transformer- 100kVA, 11kV/433V
2 SF6 Circuit Breakers:
4 Current Transformer:
5 Voltage Transformers:
6 Capacitive Voltage Transformers:
7 Surge Arrestors
8 a) Relay & Protection Panels
b) Substation Automation
9 L.T. A.C Panel
10 Station Battery
11 Station Battery Charger
12 PLCC Battery
13 PLCC Battery Charger
14 1.1KV Copper control cables/LT Power Cable
15 11KV U.G Cable
16 PLCC equipment
17 Conductors & Earth Wire a) Moose ACSR
c) Coyote conductor
d) Lynx conductor
e) Panther Conductor
18 Insulators a) 120/90KN Disc Insulator Strings
b) Solid Core Insulators
c) Silicon rubber/ Disc/ Long rod insulators
d) Post Insulators
19 Station / Mounting Structures/Lightning Mask
21 Hardware Materials
22 Aluminium pipe and Clamps
23 AC DISTRIBUTION BOX
24 DC DISTRIBUTION BOX
25 Nitrojen Fire Fighting Protection System
26 UG Cable: a. 110kV 630sqmm
27 Joints & Terminations for a. 110kV 630sqmm cable
28 1phase & 3phase Link Box
30 OPGW Cable & Cable accessories
NOTE: The Type Test / Special Tests, if repeated at the insistance of owner, the applicable testing charges shall be paid by the successful Bidder upfront to the laboratory and the same shall be reimbursable by KPTCL as per actuals on submission of Bills along with proof of payment and on successful completion of all the Type Tests, specified and on approval of the same by the owner. In case equipment/material fails in the type tests during testing then the testing charges paid by the Bidder to the laboratory will not be reimbursed by KPTCL. The above Clause is applicable for all the equipments/materials, in case, the Type Test / Special Tests, are repeated at the insistance of owner(KPTCL).
Place Printed Name
Karnataka Power Transmission Corporation Limited
Schedule -13-List of Optional Spares
SHEET FOR TECHNOCOMMERCIAL OPENING
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
BIDDERS SHALL NOTE THAT QUANTITIES INDICATED IN THE PERCENTAGE FINANCIAL BID OFFER SHALL BE INDICATED HERE ALSO.
Bidders Name and Address
To, The Chief Engineer, Electricity,Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 09.
List of optional spares required to meet the specified performance for a period of three years
Sl. No. For Equipments Details of item Unit Quantity
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE - 14-Guaranteed Losses :
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidders Name and Address along with GSTIN No.: To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009
Dear Sir, i) We Declare that the ratings and performance figures of the transformer furnished by us under the Turnkey Package are Guaranteed. We further declare that in the event of any deficiencies in meeting the guarantees in repect of the characteristics mentioned below as established after conducting the factory test, you may at your discretion,reject or accept the equipment after assessing the liquidated damages as specified in relevant clause of Bid Document.
Equipment Guaranteed Losses at rated output(KW)
Max No Load loss at rated voltage and rated frequency Max Load loss at rated current and frequency and at 75 deg C at principal tap Max I2 R loss at rated current and frequency and at 75 deg C at principal tap Max Auxiliary loss at rated voltage and frequency for Power Transformer
20MVA, 110/11kV Power Transformer
Note:(i) Refer Technical Specifications (ii)The loss quoted shall be consistent in Schedule 14 and GTPs(DRS)of Power Transformer
Equipment Total Losses in KW / watts
i) 100KVA, 11KV/433V Auxiliary Transformer Note: Refer Technical Specifications , As per technical specifications, for 100 kVA, 11KV/433V Auxiliary Transformer: Maximum Losses should not exceed 1500 watts
Note: Refer Technical Specifications As per technical specifications, for 100 kVA, 11KV/433V Auxiliary Transformer: Maximum Losses should not exceed 1500 watts.
1 Size of the Cable 110kV, 630 Sqmm UG cable
Guaranteed Values Remarks
2 Losses per Km [Refer clause No. 26.5.1 (Guaranteed Loss) of SCC,Section 5 ]
a) a) Total 3 Phase Dielectric Loss at rated voltage and rated current:
i. One Circuit alive kW/km
ii. Both Circuits alive kW/km
b) b) Total 3 Phase Copper Loss at rated voltage and rated current (650A): Note: The AC resistance of conductor (Rac), at the said rated continuous current(650A for 110kV 630sqmm cable) in ground shall be considered for calculation of copper losses. The corresponding temperature at rated continuous current( 650A for 110kV 630sqmm cable) in ground shall also be indicated.
i. One Circuit alive kW/km
ii.Both Circuits alive kW/km
c) c) Total 3 Phase sheath / screen loss at rated voltage & rated current:
i. One Circuit alive kW/km
ii.Both Circuits alive kW/km
d) d) Other losses due to reinforcement:
i. One Circuit alive kW/km
ii.Both Circuits alive kW/km
e) e) Total Losses at rated voltage & rated current:
i. One Circuit alive kW/km
ii.Both Circuits alive kW/km
3 Guaranteed Weights:
a) Nominal (guaranteed) Weight of copper:- Main Conductor excluding copper wire screen in kg/m
b) Nominal (guaranteed) Weight of copper:- Copper wire screen excluding main conductor in kg/m
c) Nominal (guaranteed) Weight of Lead in kg/m
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
LIST OF VENDORS
SHEET FOR TECHNOCOMMERCIAL OPENING
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
BIDDERS NAME AND ADDRESS To, The Chief Engineer, Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 09.
Sl. No. EQUIPMENT/ MATERIAL NAME OF THE VENDOR
VENDOR 1 VENDOR 2 VENDOR 3 VENDOR 4
1 Power Transformer 20MVA, 110/11kV Transformer
2 Auxiliary Transformer- 100kVA, 11kV/433V
3 UG Cable: a. 110kV 630sqmm
4 Joints & Terminations for a. 110kV 630sqmm cable
5 SF6 Circuit Breakers:
7 Surge Arrestors
8 Current Transformer:
9 Voltage Transformers:
10 a) Relay & Protection Panels
b) Substation Automation
11 L.T. A.C Panel
12 Station Battery
13 Station Battery Charger
14 PLCC Battery
15 PLCC Battery Charger
16 1.1KV Copper control cables/ LT Power Cable
17 11KV U.G Cable
18 PLCC equipment
19 Conductors & Earth Wire a) Moose ACSR
20 b) Drake ACSR
21 c) Coyote ACSR
22 d) Lynx ACSR
23 d) Earth Wire
24 e)OPGW cable
25 Insulators a) i. 120KN Disc Insulator Strings
26 ii. 90KN Disc Insulator Strings
27 b) Solid Core Insulators
28 c) Silicon rubber/ Disc/ Long rod insulators
29 d) Post Insulators
30 Station / Mounting Structures/Lightning Mast
32 Hardware Materials
33 Aluminium pipe and Clamps
34 AC DISTRIBUTION BOX
35 DC DISTRIBUTION BOX
36 Nitrojen Fire Fighting Protection System
37 110kV GIS equipments/materials
39 OPGW Cable accessories
40 1Phase and 3 phase Link Box
Note : Any Other Materials name & its vendors are to be entered.
Place Designation
Name of the Company
SCHEDULE-16 : NO DEVIATION CERTIFICATE (ANNEXURE-I)
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
NOTE: SCHEDULE DULY SIGNED BY THE AUTHORIZED PERSON SHALL BE UPLOADED
With reference to our Bid Proposal No dated
We hereby confirm that we have read the provisions of the contract, the stipulation of these clause are acceptable to us,
and we have not taken any deviation whatsoever to these clauses:
a) Terms of payment Clause No. 37 of Section-5,Conditions of Contract (CC) and Clause No.8 of Special Conditions of Contrac (SCC)
b) EMD/Bid Security Clause No. 6, Section :1, Invitation for Tenders (IFT) and Clause No. 13, Section :2, Instruction to Tenderer (ITT)
c) Contract Performance Guarantee Clause No. 29 of Section:2, Instruction to Tenderers (ITT).
d) Penalty for delay Clause No. 41 of Section-5 : Conditions of Contract (CC).
e) Price Basis/ Price adjustment Clause No. 40 of Section-5 :Conditions of Contract (CC).
f) Defects Liability Period/Guarantee Clause No. 10 of Section-5 Special Conditions of Contract (SCC)
g) Work Schedule Clause No.17 of Section:5 Conditions of Contract (CC)
h) Taxes and Duties Clause No. 11.11 of Section-2: Instruction to Tenderers (ITT).
We further confirm that any deviation to the above clauses at SI.No. (a) to (h) found anywhere in our bid proposal, implicit or explicit, shall stand unconditionally withdrawn, without any cost, implication whatsoever to KPTCL.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE-17a FORM FOR BID SECURITY/EMD (ANNEXURE-IIA) (To be stamped on Rs.300/- Non-Judicial stamp paper in accordance with KPTCL Circular No. KPTCL/GMT/CIVIL (B7)/35/2024-MANAGER ESTATE (E-106992) dated 02.03.2024)
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
NOTE: SCHEDULE DULY SIGNED BY THE AUTHORIZED PERSON SHALL BE UPLOADED AND SENT ALONG WITH ORIGINAL BANK GUARANTEE AND ORIGINAL DD (TOWARDS BID GUARANTEE ) TO CHIEF ENGINEER ELECTRICIYT (T&P),KPTCL BANGALORE SO AS TO REACH AFTER THE LAST SUBMISSION DATE & ON OR BEFORE THE DATE & TIME OF OPENING TECHNO COMMERCIAL BIDS.
Ref No. Bank Guarantee No.
In accordance with Invitation to Bid under your specification
No. M/s having its Registered /
Head Office at (hereinafter called the 'Bidder') wish
to participate in the said Bid or and you, as a special favour have agreed
to accept an irrevocable and unconditional bank guarantee for an amount of
valid up to on behalf of Bidder in lieu of the Bid deposit required to be made
by the Bidder as a condition predecent for participation in the said Bid,in addition to the Demand draft No.
we the Bank at having our Head office at
(local address) guarantee and undertake to pay immediately on demand by Karnataka Power Transmission Corporation
the amount of (in figures and words)
without any reservation, protest, demur and recourse. Any such demand made by said `Owner' shall be conclusive and binding on us irrespective of any dispute or difference raised by the Bidder.
This Guarantee shall be irrevocable and shall remain valid up to and including
If any further extension of this guarantee is required, the same shall be extended to such required period (not exceeding one year) on receiving instructions
from M/s on whose behalf this guarantee is issued.
This Guarantee has been issued using SFMS Platform and the requisite communication in this regard has been forwarded to the Beneficiary Bank.
In witness whereof the Bank, through its authorised officer, has set its hand and stamp on this
Signature Signature
Official Addressess Designation with Bank Stamp.
Attorney as per Power of Attorney No.
Note : 1) Both the Bank Guarantee and Demand Draft shall be scanned and uploaded along with Electronic sheets. 2) This date shall be Forty Five (45) days after the last date for which the bid is valid.
Karnataka Power Transmission Corporation Limited
SCHEDULE-17b Form of Insurance Surety Bond towards EMD (ANNEXURE-IIB) (To be stamped on Rs.300/- Non-Judicial stamp paper in accordance with KPTCL Circular No. KPTCL/GMT/CIVIL (B7)/35/2024-MANAGER ESTATE (E-106992) dated 02.03.2024)
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Insurance Surety Bond No.
In accordance with Invitation for Bids under your Bid Document No
M/s having its Registered /
Head Office at (hereinafter called the 'Contractor') wish
to participate in the said Bid for
As an irrevocable Insurance Surety Bond against Bid Security for an amount of * valid for days from **
required to be submitted by the Contractor as a condition precedent for participation in the said bid which amount is liable to be forfeited on the happening of any contingencies as mentioned under the Bidding Documents.
we, the having our Head office at
guarantee and undertake to pay immediately on demand by Karnataka Power Transmission Corporation Limited, (hereinafter called the 'Owner') the amount of
without any reservation, protest, demand and recourse. Any such demand made by the 'Owner' shall be conclusive and binding on us irrespective
of any dispute or difference raised by the Contractor and/or any right/remedy available to the Contractor in terms thereof.
This Insurance Surety Bond shall be unconditional as well as irrevocable and shall remain valid upto
If any further extension of this Insurance Surety Bond is required, the same shall be extended to such required period (not exceeding one year) on receiving instructions from
M/s on whose behalf this Insurance Surety Bond is issued.
In witness where of the Insurer, through its authorised officer, has set its hand and stamp on this
Signature Signature
Official Addressess Designation with Insurer Stamp
Attorney as per Power of Attorney No.
NOTE: 1. (*) The amount shall be as specified in the SPC. (**) This shall be the last date of bid submission deadline. (@) This date shall be Forty Five (45) days after the last date for which the bid is valid 2. The Insurance Surety Bond shall be from an Insurer as per guidelines issued by Insurance Regulatory and Development Authority of India (IRDAI) as amended from time to time. 3. The Owner shall be the Creditor, the Contractor shall be the Principal debtor and the Insurance company/Insurer shall be the Surety in respect of the Insurance Surety Bond to be issued by the Insurer. 4. The Insurance Surety Bond should be on Non-Judicial stamp paper/e-stamp paper of appropriate value as per Stamp Act prevailing in the state(s) where the Insurance Surety Bond is submitted or is to be acted upon or the rate prevailing in State where the Insurance Surety Bond is executed, whichever is higher. The Stamp Paper/e- stamp paper shall be purchased in the name of Contractor /Insurer issuing the Insurance Surety Bond. 5. While getting the Insurance Surety Bond issued, Contractors are required to ensure compliance to the points mentioned in Form of Bank Guarantee/Insurance Surety Bond Verification Check List enclosed in this Section of Bidding Documents. Further, Contractors are required to fill up this Form and enclose the same with the Insurance Surety Bond.
Karnataka Power Transmission Corporation Limited
SCHEDULE-18 PROFORMA OF LETTER OF UNDERTAKINGS (ANNEXURE-V)
SHEET FOR TECHNOCOMMERCIAL OPENING
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
NOTE: SCHEDULE DULY SIGNED BY THE AUTHORIZED PERSON SHALL BE UPLOADED
(To be executed on Non-Judicial paper of RequisiteValue)
1. I*/We* have read and examined the following bid documents relating to the
(full Scope of Work)
a) Notice Inviitng Tender
b) Conditions of Contract containing section 'Invitation for Tenders’, 'Instructions to Tenderers’, ‘Conditions of Contract’ and Contract Data.
c) Special Conditions of Contract along with Annexure to
d) Drawings No.
e) Technical Specifications
2 . I / We hereby submit our Bid and undertake to keep our Bid Valid for a period of One Hundred and Eighty days (180 days) from the Last date of bid submission as notified (either original or extended). I*/We* hereby further undertake that during said period I/We shall not vary/alter or revoke my/our Bid.
This undertaking is in consideration of KPTCL agreeing to open my/ our Bid and consider and evaluate the same for the purpose of award of Work in terms of provisions of clause entitled "Award of Construct" 'cl.no. 26 of Section ITT and cl.no. 18 of SCC of the Bid Documents.
Should this bid be accepted, I*/We* also agree to abide by and fulfil all the terms, conditions of provision of the above mentioned bid.
Signature along with Seal of Co.
(Duly Authorised to sign the Tender on Behalf of the Contractor.)
NAME OF THE COMPANY (in Block Letters)
SIGNATURE Date and Postal Address
DATE Telegraphic Address
NAME AND ADDRESS Telephone No.
Karnataka Power Transmission Corporation Limited
SCHEDULE-19 CONSORTIUM AGREEMENT (To be stamped on Rs.500/- Non Judicial stamp paper in accordance with KPTCL Circular No. KPTCL/GMT/CIVIL(B7)/35/2024-MANAGER ESTATE (E-106992) dated 02.03.2024) (ANNEXURE -XIII)
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
NOTE: SCHEDULE DULY SIGNED BY THE AUTHORIZED PERSON SHALL BE UPLOADED.
CONSORTIUM AGREEMENT AMONGST M/s M/s
For Bid Specification No. OF KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
This consortium agreement executed on this day Month of Two thousand Twenty Three
amongst M/s a company incorporated under the laws of (Country) and having its registered office at
(hereinafter called the "Lead Company" which expression shall include its successors ,executors and permitted assigns),
M/s a company incorporated under the laws of (Country) and having its registered office at
(hereinafter called the "Constituent Company" which expressions shall include its successors,executors and permitted assigns)
for the purpose of making a bid and entering into a contract (In case of award) against the specification no.
For NAME OF THE WORK
for Karnataka Power Transmission Corporation Ltd. having its registered office at 9th Floor, Indhana Bhavana , Bangalore 560 009 , Karnataka (hereinafter called the "Owner"). The leader of the consortium shall abide by the general terms and conditions specified by the Purchaser. WHEREAS the Owner invited bids as per the above mentioned specifications for the design, manufacture, supply and erection, testing and commissioning of Equipments/Materials stipulated in the bidding documents under subject package
NAME OF THE WORK
AND WHEREAS Section-I ( Volume-1: Clause No. 11:- Qualifying Requirement), forming part of the bidding documents, stipulates that a consortium meeting the requirements of Section-I, ( Invitation of Bid) applicable may bid, provided the Consortium fulfills all other requirements of specification and in such a case, the Bid shall be signed by the members so as to legally bind the members and who will be jointly and severally liable to perform the Contract and all obligations hereunder.
The above clause further states that the consortium agreement shall be attached to the bid and the contract performance guarantee will be as per the format enclosed with the bidding document without any restriction or liability for either party.
AND WHEREAS the bid has been submitted to the Owner vide proposal No dated
by Lead Company based on the Constituent agreement between all the consortium under these presents and the bid in accordance with the requirements of Specifications (Qualification Requirements).
NOW THEREFORE THIS UNDERTAKING WITNESSETH AS UNDER:
In consideration of the above premises and agreements all the partners to this consortium members do hereby now agree as follows:
1 In Consideration of the award of the Contract by the Owner to the Consortium members, we , the members to the consortium agreement do hereby agree that M/s
shall act as Lead Company and further declare and confirm that we shall jointly and severally be bound up to the Owner for the successful performance of the contract and shall be fully responsible for the design, manufacture, supply and successful performance of the equipments in accordance with the Contract.
2 In case of any breach of the said contract by the Lead company or other constituent of the Consortium agreement, the Lead company do hereby agree to be fully responsible for the successful performance of the contract and to carryout all the obligations and responsibilities under the contract in accordance with the requirements of the Contract
3 Further, if the Owner suffers any loss or damage on account of any breach in the contract or any shortfall in the performance of the equipment in meeting the performance guaranteed as per the specification in terms of the contract, the Lead company of these presents undertake to promptly make good such loss or damages caused to the Owner, on its demand without any demur. It shall not be necessary or obligatory for the Owner to proceed against Lead Partner to these presents before proceeding against or dealing with the other Partner (s).
4 The Financial liability of the members of the consortium agreement to the Owner, with respect to any of the claims arising out of performance or non-performance of the obligations set forth in the said agreement, read in conjunction with the relevant conditions of the contract shall, however not be limited in any way so as to restrict or limit the liabilities of any of the members of the agreement.
5 It is expressly understood and agreed between the members to this consortium agreement that the responsibilities and obligations of each of the partners shall be as delineated hereunder (To be incorporated suitably by the member to this agreement). However, each member of the consortium will be severally and jointly responsible for the faithful performance of the contract. It is further agreed by the member that the above sharing of responsibilities and obligations shall not in any way be a limitation of joint and several responsibilities of the members under this contract.
Sl.No. Name of the Lead Bidder/Consortium Partner. Scope of the work/Participation
We further declare ourselves bound to execute our scope of work/participation as stated above;
6 This Consortium agreement shall be constructed and interpreted in accordance with the laws of India and the courts of Bangalore shall have the exclusive jurisdiction in all matters arising there under.
7 In case of an award of a Contract, we the Consortium members do hereby agree that we shall be jointly & severally responsible for the works respectively executed and Lead company shall furnishing a contract performance security from a bank in favor of the PURCHASER in the forms acceptable to purchaser for value of Five percent (5%) of the Amount put to tender (Excluding GST) plus additional security for unbalanced tenders in accordance with Clause 25.5 & 29 of ITT and Clause 43 of the CC (Conditions of Contract).
8 It is further agreed that the Consortium agreement shall be irrevocable and shall form an integral part of the contract, and shall continue to be enforceable till the owner discharges the same. It shall be effective from the date first mentioned above for all purposes and intents.
IN WITNESS WHEREOF the partners to the Consortium have through their authorized representatives executed these presents and affixed Common seals of their companies, on the day, month and year first mentioned above.
WITNESS for Lead Company
(Signature) (Signature of the authorized representative)
(Name in Block Letters) (Name)
Designation (Designation)
Common Seal of the Company
2 ( For Constituent 1)
(Signature of the authorized representative)
(Name in Block Letters) (Name)
Designation Common Seal of the Company
Karnataka Power Transmission Corporation Limited
SCHEDULE-20(a) POWER OF ATTORNEY (ANNEXURE-XI)
(For Individual Bidder / Lead Partner of Consortium)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
NOTE: SCHEDULE DULY SIGNED BY THE AUTHORIZED PERSON SHALL BE UPLOADED.
POWER OF ATTORNEY
KNOW ALL MEN BY THESE PRESENTS that we
a Company incorporated
under the laws of
and having its Registered Office / Head Office at
"Manufacturer / Bidder" which expression shall unless repugnant to the
Context or meanig thereof, include its successors, administrators and assigns)
acting through Mr its constitute, nominate and appoint
M/s a Company incorporated under the laws of
and having its Registered / Head Office at
as its duly constituted lawful Attorney (hereinafter called "Attorney"
or "Authorized Representative") to exercise all or any of the powers for and on
behalf of the "Manufacturer / Bidder" in regard to Specification No.
the bids for which have been invited by
(Address "Owner") to undertake the following acts:
i. To submit proposal and participate in the aforesaid Bid Specification of the Owner on behalf of the "Manufacturer / Bidder".
ii. To negotiate with the "Owner" the terms and conditions including price for award of the contract pursuant to the aforesaid Bid and to sign the contract with the "Owner" for and on behalf of the Manufacturer / Bidder.
iii. To receive accept and execute the contract for and on behalf of the "Manufacturer / Bidder".
iv. To do any other act or submit any document related to the above.
It is expressly understood that the Power of Attorney shall remain valid, binding and irrecoverable till submission of the Contract performance guarantee in terms of the Contract. The "Manufacturer / Bidder" hereby agrees and undertakes to ratify and confirm all the whatsoever the said "Attorney" / "Authorised Representative" quotes in the Bid, negotiates and signs the contract with the "Owner" and / or purports to act on behalf of the "Manufacturer / Bidder" by virtue of this Power of Attorney and the same shall bind the "Manufacturer / Bidder" as if done by itself.
IN WITNESS WHEREOF THE "Manufacturer / Bidder" has executed these presents at
on this day of under
the Common Seal of the Manufacturer company / Bidder.
Specimen Signature of Attorney Holder
(Name & Designation)
For and on behalf of
Common Seal of the above Manufacturer/Bidder
Has been affixed thereto in the presence of :
Karnataka Power Transmission Corporation Limited
SCHEDULE-20(b) POWER OF ATTORNEY (ANNEXURE-XV)
(FOR CONSORTIUM MEMBER)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
NOTE: SCHEDULE DULY SIGNED BY THE AUTHORIZED PERSON SHALL BE UPLOADED
POWER OF ATTORNEY
(To be stamped on Rs.500/- Non Judicial stamp paper in accordance with KPTCL Circular No. KPTCL/GMT/CIVIL (B7)/35/2024-MANAGER ESTATE (E-106992) dated 02.03.2024)
KNOW ALL MEN BY THESE PRESENTS that we
a Company incorporated
under the laws of
and having its Registered Office / Head Office at
"Manufacturer / Bidder" which expression shall unless repugnant to the
Context or meanig thereof, include its successors, administrators and assigns)
acting through Mr its constitute, nominate and appoint
M/s a Company incorporated under the laws of
and having its Registered / Head Office at
as its duly constituted lawful Attorney (hereinafter called "Attorney"
or "Authorized Representative") to exercise all or any of the powers for and on
behalf of the "Manufacturer / Bidder" in regard to Specification No.
the bids for which have been invited by
(Address "Owner") to undertake the following acts:
i. To submit proposal and participate in the aforesaid Bid Specification of the Owner on behalf of the "Manufacturer / Bidder".
ii. To negotiate with the "Owner" the terms and conditions including price for award of the contract pursuant to the aforesaid Bid and to sign the contract with the "Owner" for and on behalf of the Manufacturer / Bidder.
iii. To receive accept and execute the contract for and on behalf of the "Manufacturer / Bidder".
iv. To do any other act or submit any document related to the above.
It is expressly understood that the Power of Attorney shall remain valid, binding and irrecoverable till submission of the Contract performance guarantee in terms of the Contract. The "Manufacturer / Bidder" hereby agrees and undertakes to ratify and confirm all the whatsoever the said "Attorney" / "Authorised Representative" quotes in the Bid, negotiates and signs the contract with the "Owner" and / or purports to act on behalf of the "Manufacturer / Bidder" by virtue of this Power of Attorney and the same shall bind the "Manufacturer / Bidder" as if done by itself.
IN WITNESS WHEREOF THE "Manufacturer / Bidder" has executed these presents at
on this day of under
the Common Seal of the Manufacturer company / Bidder.
Specimen Signature of Attorney Holder
(Name & Designation)
For and on behalf of
Common Seal of the above Manufacturer/Bidder
Has been affixed thereto in the presence of :
Karnataka Power Transmission Corporation Limited
SHEET FOR TECHNOCOMMERCIAL OPENING (UN - PRICED)
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidders Name and Address
To, The Chief Engineer, Electricity, Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, Bangalore - 09.
We Declare that the ratings and performance figures of the equipment furnished by us under the Turnkey Package are Guaranteed. We further declare that in the event of any deficiencies in meeting the guarantees in repect of the characteristics as established after conducting the performance test, you may at your discretion, reject the equipment, in which case we shall replace the same with equipment as per specification and meeting the guarantee, free of charge and within a resonable time, to be mutually agreed.
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
SCHEDULE -22 - Check List
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDERS NAME AND ADDRESS To,
The Chief Engineer, Electy., Tendering & Procurement, KPTCL,9th Floor, Indhana Bhavana, BANGALORE - 560009
CHECK LIST FOR SUBMISSION OF SCHEDULES
REFERENCE OF FORM & SCHEDULE DETAILS OF FORM & SCHEDULE WHETHER INCLUDED IN TECHNO-COMMERCIAL SHEETS (ELECTRONIC) YES/NO WHETHER INCLUDED IN PERCENTAGE RATE Financial Offer (ELECTRONIC) YES/NO WHETHER INCLUDED IN COMMERCIAL
PROPOSAL BID PROPOSAL
Schedule - 1 PRICE COMPONENTS
Schedule 2 (1 of 2 & 2 of 2) Summary of Price Components
Schedule 2A Schedule of Discounts
Schedule 2B Statement of Commercial Terms & Conditions
Schedule 3A & 3B Price break up for supply & erection
Schedule 3C Price break up for civil works
Schedule 4 Price break up for mandatory spares and maintenance & Testing Equipments.
Schedule 5 Commercial deviations
Schedule 6 Technical deviations
Schedule 7 List of special Tools & Tackles
Schedule 8 Additional information.
Schedule 9 Qualification Information [Technical & Financial]
Schedule 10 Details of Tools and plants and man power deployment
Schedule 11 A & 11B Schedule for activities & Commissioning.
Schedule 12 Type Test Charges
Schedule 13 List of optional spares and cost.
Schedule 14 Guaranteed loss of transformer.
Schedule 15 List of vendors.
Schedule 16 Annexure 'A' No deviation certificate
Schedule 17a & 17b Proforma for Bid guarantee
Schedule 18 Proforma for letter of undertaking
Schedule 19 Consortium Agreement
Schedule 20a & 20b Power of attorney for Individual Bidder / Lead Partner of Consortium and Consortium Member
Schedule 21 Guaranteed Declaration
Schedule 22 Check list
DRS 1-45 Relevant Technical details for Materials / Equipments
To be Uploaded Contract Quality Assurance Programme
To be Uploaded Type Test Certificates
To be Uploaded & furnished Bid Security/EMD
To be Uploaded Written Power of Attorney
To be Uploaded Letter of Undertaking
To be Uploaded No Deviation Certificate
To be Uploaded Any Other (Please Specify)
To be Uploaded Any Other (Please Specify)
To be Uploaded Any Other (Please Specify)
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
A1 : GUARANTEED TECHNICAL PARTICULARS FOR POWER TRANSFORMERS
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Class of Power Transformer 20 MVA, 110/11kV Power Transformer
1 Name of the Manufacturer and country of origin
2 Reference standard
3 Service [Indoor/outdoor]
4 Continuous rating under service conditions specified in IS-2026 Part-I, 2011 Clause No.1.1 : HV
a. 1. With ONAN cooling - MVA
2. With ONAF cooling - MVA
b. Rated no load voltage
6 a. Rated Frequency : (Hz)
b. Number of phases
7 Current at rated voltage and on principal tap-Amp :HV
8 Maximum hot spot temperature rise calculated by formula 0C over the maximum yearly weighted average ambient temperature
9 Flux density at rated voltage and rated frequency in tesla
10 Temperature rise of top oil, oC by the thermometer (above Max. Ambient Temperature).
11 Temperature rise of winding measured by resistance (above Max. Ambient Temperature).
i. With ONAN cooling oC
ii. With ONAF cooling oC
iii. Period of operation of transformer at full load without calculated winding hot spot temperature exceeding 140oC and when
50% coolers fail
100% coolers fail [Refer Cl. No. 1.2.0.1]
12 No. of windings
13 Connections HV
14 Connection Symbol and vector group
i. Type of tap changer
ii. Tap step (percent)
iii. Total tap range (+) percent to (-) percent
iv. Tappings provided at
v. Type of regulation :
Constant flux regulation
Variable flux regulation
Combined regulation
vi)Insulation level of tap changer
16(A) Magnetization data at no load, at rated frequency
i. Current in Amps
ii. Power factor
iii. Loss in KW (core loss + dielectric loss)
iv. Max. flux density in lines/sq.cm.
a At 90% rated no load voltage
b At 100% rated no load voltage
c At 110% rated no load voltage
d At maximum rated primary voltage (i.e. 105% rated no load voltage)
16(B) i) Max. No-load loss at rated frequency at Principal Tap (KW) 0
ii) Max. No-Load loss at voltage corresponding to the Highest Tap (KW)
17 Max.load loss in KW at rated current and at 750C At Lowest Tap At Principal Tap At Highest Tap
a. For ONAN rating KW
b. For ONAF rating in KW 0
c. For OFAF rating in KW
Max. I2 R loss in KW at rated current and at 75◦C
a. For ONAN rating in KW
b. For ONAF rating in KW 0
c. For OFAF rating in KW
Max. Auxiliary loss at rated voltage and frequency 0
Note for Sl. No. 16 & 17: Guaranteed values of the losses shall be indicated which shall be firm & without indicating the tolerance limit
18 Impedance at rated current and frequency at 75oC winding temperature on rated MVA base. HV to LV
i. At normal tap in %
ii. At max. voltage tap in %
iii. At min. voltage tap in %
19 Reactance at rated current and frequency and normal tap on rated MVA base:
HV to LV - in %
20 Zero sequence impedance at reference temperature of 75oC at principal tap ………in %
21 Resistance at 75 oC
HV winding in Ohms in %
LV winding in Ohms in %
22 Efficiency at 75oC winding temperature as derived from guaranteed. loss figures At Unity p.f At 0.8 p.f
a. At 125% full load
b. At 100% full load
c. At 75% full load
d. At 50% full load
23 a. Maximum efficiency ………in %
b. Load at which maximum efficiency occurs (% of full load)
24 Regulation at full load and at 75oC
a. At unity p.f. in %
b. At 0.8 p.f. (lag) in %
25 a. Short time thermal rating of LV winding in KA & duration in seconds.
b. Short time thermal rating of HV winding in KA & duration in seconds.
26 Permissible overloading - HV
27 Test voltages HV LV
i. Lighting impulse withstand kV (peak)
ii. Power frequency voltage withstand kV (ms)
iii. Switching impulse withstand kV (peak)
28 Partial discharge level at 1.5Um / √3 kVrms (pC)
29 RIV at 1.1 times minimum phase to ground voltage
31 Noise level when energized at normal voltage and normal frequency at no load (db)
32 External short circuit withstand capacity (MVA) & duration (seconds)
33 Over flux withstand capability of the transformer :
34 Insulating and cooling medium
35 Approximate weights
a. Core with clamping (Kg)
b. Winding with insulation (Kg)
c. Core & Winding (Kg)
d. Tank & Fittings with accessories (Kg)
e. Oil required for first filling (Kg)
f. Untanking weight (Kg)
g. Total weight with oil weight & fitting (Kg)
h. Weight of total insulation (Kg)
36 Required quantity of oil in litres
37 Terminal arrangement
ADDITIONAL TECHNICAL PARTICULARS:
1 Details of Core (along with Tolerance if any):
a. Type of core configuration
b. Type of core joints
c. Flux density at 90% of rated voltage and frequency at Principal Tap Tesla :
d. Flux density at 110% of rated voltage and frequency at Principal Tap Tesla :
e. (i) Material of core lamination
(ii) Thickness of core lamination (mm)
f. Approximate core weight (please indicate core weight only)
g. Type of Joints used between core limb and yoke
2 Details of Windings:
a. Conductor area in sq.cm and current density in Amps/Sq.cm (at rated current). Current density A/sq. cm Conductor area sq.cm
b. Material of winding conductor
c. Approximate weight of winding (along with tolerance if any)in kgs
d. Type of windings
e. Winding insulation Type and class Graded or ungraded
f. i. Insulating material used for :
1. Regulating winding
3. HV TAP WINDING
ii. Between HV and TAP WDG and LV as applicable
iii. Between core & LV side.
iv. For core bolts, washers and end plates
v. Regulating winding & earth.
g. i. Type of axial coil support
ii. Type of Radial coil support :
h. Core bolt insulation voltage
i. Details of special arrangement provided to improve surge voltage distribution in the windings
j. Approximate weight of winding (Kgs) (Tolerance if any on the above)
k. Minimum clearance (mm) In oil In Air
Between Phases Phase to ground Between Phases Phase to ground
3 Details of Tank :
a. Material for Transformer Tank
b. Type of the tank
c. Minimum thickness of sheet
ii. Bottom (mm)
iii. Cover (mm)
iv. Cooling tubes/Radiators (mm)
d. Vacuum recommended for hot oil circulation (torr)
e. Vacuum to be maintained during oil filling in transformer tank (torr)
f. Vacuum to which the tank can be subjected without distortion (torr)
Transverse Axis Longitudinal Axis
g. No. & size of bi-directional wheels provided.
h. (i) Track gauge required for the wheels-longitudinal axis & transverse axis
(ii) Size of rail recommended for the track
4 Details of painting at works and site
5 (a) Minimum clear height for lifting tank cover and for lifting core & windings from tank (mm) (untanking height).
(b) Minimum clear height for lifting (mm)
II. Bushings - HV
6 Shipping details :
i. Parts detached for transport
ii. Weight of heaviest package in Kgs
iii. Weight of other heavy packages in Kgs
iv. Dimensions of largest package
a. Length in mm
b. Breadth in mm
c. Height in mm
v. Dimensions of other heavy packages:
a. Length in mm
b. Breadth in mm
c. Height in mm
vi. Transformer will be transported with oil / gas
7 Details of Bushings HV LV
b. Rated voltage class - KV
c. Rated current - Amps
d. One minute dry withstand power frequency voltage - kV (ms)
e. One minute wet withstand power frequency voltage - kV (ms)
f. (i) 1.2 / 50 micro sec. Lighting impulse withstand voltage - kV (Peak)
(ii) Switching surge withstand test voltage kV (peak)
g. (a) Creepage Distance in air
(b) Creepage Distance (protected)
h. Quantity of oil in bushing and specification of oil used (Kgs)
i. Whether test tap is provided
j. Weight of assembled bushing
k. Phase to earth clearance in air of live parts at the top of bushing.
l. Minimum clearance (mm) In Air
Between phases Phase to ground
m. Partial discharge level
8 Cooling system
a. Grade of oil
b. Total weight of oil in radiator in Kgs/litres
c. Total weight of radiator without oil in Kgs.
d. Total radiating surface in square meters
e. Method of drying out transformer at site
f. Type and make of material used for the radiators with size.
g. Type of radiator
h. Total number of Radiators/Banks for transformer and over all dimensions (LxBxH)
i. Rating of Transformer with one radiator bank out of service.
j. Total weight of radiators in Kgs
k. Type of mounting
l. Vacuum withstand capability
9 Cooling equipment Fan Motor Pump Motor
a. Make and Type (Details)
b. Number of connected units (nos.)
c. Number of standby units (nos.)
d. Rated Power (KW)
e. BHP of driven equipment
f. Capacity (cu m/min) or (Litres/Minute)
g. Rated voltage (Volts)
h. Locked rotor current (Amps)
i. Temperature range for which control is adjustable
j. Efficiency of motor at full load (percent)
k. Temp. rise of motor at full load (oC)
l. Whether the fan and/or pumps suitable for continuous operation at 85% of their rated voltage
m. Estimated time constant in hours for
i. Natural cooling
ii. Forced air cooling
10 On Load Tap Changing gear (should be SCADA Compatible)
c. Power flow (uni-directional or bi-directional or restricted bi-directional)
d. Rated voltage to Earth kV
e. Rated maximum current Amps
f. Step voltage V.
g. Number of steps
h. Control : Manual / Auto / Local/Remote/Independent / Parallel.
i. Auxiliary supply details
j. Voltage control (whether automatic or manual)
k. Line drop compensation Provided / Not provided.
l. Protective devices
m. Time for complete tap change (one step) sec.
n. Divertor selector switch Transient time - Cycles.
o. Value of maximum short circuit current Amps.
p. Maximum impulse withstand test voltage with 1.2/50 micro seconds full wave between switch assembly and earth (kV peak)
q. Maximum power frequency test voltage between switch assembly and earth - kV rms.
r. Maximum impulse withstand test voltage with 1.2/50 micro seconds across the tapping range (kV peak).
s. Approximate over all dimensions of Tap changer mm
t. Approximate over all weight Kgs.
u. Approximate over all quantity of oil-ltrs/Kgs.
v. Particulars of the OLTC control panel for installation in the control room.
w. OLTC Routine test shall be conducted on each Transformers.
i) Mechanical Endurance Test (Min. 1000 operations)
ii) Sequence Test
iii) Pressure Test
iv) Vacuum (Helium) Test
v) Auxiliary Circuit Insulation test
x. OLTC Drive Mechanism Box: Make & Type
11 Over all dimensions of transformer including cooling gear, tap changing gear etc.
d. Reference drawing No.
12 Whether oil temperature indicator provided (Yes/No).
13 (a) Type of oil level indicator
(b) whether supervisory alarm contact for low oil level provided (Yes/No)
14 Type and size of Gas operated relay and whether supervisory alarm and trip contacts provided and their size and Nos.
15 Temperature indicators Oil Temp. indicator Winding temp. indicator
a. Make and Type
b. Permissible setting ranges for alarm & trip.
c. No. of contact
d. Current rating of each contact
e. Whether remote indicator provided, if, so, whether equipment required at purchaser's control room is included.
f. Size and No.
16 Ratio and Type of CT used for winding temperature
17 Type and size of Thermostat used
For Tr. Tank OLTC
18 No. of Breathers provided (No.)
19 Type of dehydrating agent used for breathers
20 a. Capacity of conservator vessel litres
b. Volume between the highest and lowest visible oil level (litres)
21 Valve sizes and number required/ fitted
i. Drain valves - mm - No.
ii. Filter valves - mm - No.
iii. Sampling valves - mm - No.
22 a. Type and make of pressure relief device
b. No. of each type of devices per transformer unit (Nos.)
c. Minimum pressure at which the device operates (Kpa)
23 Lifting jacks
a. Governing standard
b. No. of jacks in one set
d. Capacity (tonnes)
g.Height in closed position (mm)
h.Mean diameter of thread (mm)
24 Characteristics of Insulating oil to be used
Viscosity at 40 ºC in mm²/s
Viscosity at -30 ºC in mm²/s
Pour point in ºC
Water content in mg/kg
Breakdown voltage in kV
Density at 20 ºC in g/ml
Particle content
2 – Refining/stability
Acidity in mg KOH/g
Interfacial tension in mN/m
Total sulphur content
Corrosive sulphur
Potentially corrosive sulphur
Inhibitors of IEC 60666 in %
Metal passivator additives of IEC 60666 in mg/kg
Other additives
2- Furfural and related compounds content in mg/kg
3 - Performance
Oxidation stability for uninhibited oil – 164 hrs
Total acidity in mg KOH/g
Gassing tendency
4 – Health, safety and environment (HSE)
Flash point in ºC
PCA content in %
PCB content in mg/kg
5 – N-dm Analysis
6. Details of oil preserving equipment offered.
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
Bidder's Name & Address alongwith GSTIN no. : To,
The Chief Engineer, Electricity, Tendering & procurement, KPTCL, Indhana Bhavana, Bangalore - 560009.
A1 : GUARANTEED TECHNICAL PARTICULARS FOR GIS MODULES
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Sl. No. Particulars 110kV
1.0 HIGH VOLTAGE CIRCUIT BREAKERS
1.1 Makers name and country of manufacture
1.2 a) Manufacturers type and designation
b) Single pressure type Yes/No
c) Common enclosed phases Yes/No
d) Number of breakers in series
e) Class of circuit breaker (C2-M2) Yes/No
1.3 Applicable Standards
1.4 Rated Voltage kV
1.5 Service Voltage kV
1.6 Rated continuous voltage for rated breaking capacity
1.7 Ambient temperature assumed for design:
b) Minimum daily average 0C
1.8 Continuous Current:
b) Under site condition Amps
1.9 a) Rated short time current kA
b) Rated time Sec.
1.10 Maximum rise of temperature over ambient for current rating under
a) Clause 1.8 above 0C
b) Clause 1.9 above 0C
1.11 Open/Close time
a) Closing time ms
b) Dead time ms
c) Break time ms
d) Make time ms
e) Arcing time max ms
f) Maximum tolerance in open/close time between different poles ms
1.12 Rated operating duty
1.13 Interrupting capacity based on duty cycle in clause 1.12 above
a) RMS value of AC component KA
b) Percentage DC component
1.14 Interrupting capacity
a) at maximum voltage kA rms
b) at minimum voltage kA rms
1.15 Rated transient recovery voltage
a) Method of representing TRV Four/Two parameters
b) Value of parameters
c) First pole to clear factor
d) Type of devices, used to limit the rate of rise of re-striking voltage
e) Type of devices, if any used to obtain uniform voltage distribution between breakers
1.16 Rated making capacity
a) at higher rated voltage kA (peak)
b) at lower rated voltage kA (peak)
1.17 Latching current kA
1.18 Restrike guarantee
1.19 Reignition performance
1.20 Short Circuit test certificate enclosed YES/NO
Oscillogram enclosed YES/NO
1.21 Short line fault interrupting capacity
a) Method of representing TRV Four/Two parameters
b) Value of parameters
c) Details of additional capacitors if used for TRV control
1.22 Type of main contacts
1.23 Type of arcing contacts and/or arc control device
1.24 Material of contacts:
c) Whether contacts are silver faced
1.25 Insulation level of the breaker:
a) One minute power frequency withstand voltage kV (rms)
b) Switching surge withstand test voltage kV (peak)
c) Impulse withstand test voltage kV (peak)
1.26 Rated duty of
a) Closing resistors
b) Opening resistors
1.27 Capacity to interrupt delayed zero passage fault current
a) Oscillogram enclosed Yes/No
b) Test reports enclosed Yes/No
1.28 Whether the circuit breaker is fixed trip or trip free
1.29 Method of tripping:
b) Emergency (complete description of manually operated emergency tripping device)
1.30 a) Type of tripping mechanism
b) No. of trip coils
1.31 a) Normal voltage of trip coil Volts
b) Pick-up range Volts
c) Trip amps (per coil) Amps
1.32 a) Power at normal voltage of closing mechanism Watts
b) Power at 85% of normal voltage Watts
c) Close amps (per coil) Amps
1.33 Type of closing mechanism
1.34 Normal voltage of closing coils Volts
1.35 a) Total interrupting time measured from instant of trip coil energization to arc extinction of resistor current Cycles
b) Closing time measured from instant of application of power to closing device up to arcing contacts touching Cycles
c) Reclosing time Cycles
1.36 Critical current (current giving the longest arc when a break takes place) A
1.37 Maximum voltage factor of the circuit breaker when switching off:
a) Unloaded transformer
b) Loaded transformer
c) Open circuited lines
d) Small inductive current of 10A
e) Capacitor bank
f) Breaking cable charging current (250 A for 245 Kv, 123kV for 140A, 125A for 72.5 KV)
g) Breaking line charging current (125 A for 245 kV, 123kV for 31.5A, 10A for 72.5 KV).
1.38 When switching off asynchronous system:
a) Maximum current kA
b) Maximum recovery voltage between contacts of one pole KV
c) Test reports for asynchronous switching duty enclosed Yes/No
1.39 a) Number of openings at rated capacity, the circuit breaker is capable of performing without inspection, replacement of contacts or other main parts
b) Cumulative switching capacity without requiring maintenance Million Amps
1.40 Particulars of SF-6 gas:
a) Gauge Pressure of SF-6 at 200C Bar
iii. “Gas Refill” level
iv. “Breaker Block” level
v. “Over Pressure” level
b) Maximum permissible moisture content of SF6 gas ppm by wt.
c) Type of monitor provided for SF6 gas
d) Maximum leakage rate of SF6 gas per year at normal pressure %
e) Breaker pressure relief device:
i. Rupturing pressure bar
ii. Time to rupture seconds
iii. Quantity and location on breaker
iv. Construction material of diaphragm
f) Quantity of SF6 gas in complete breaker (3-Phase) Kgs
g) Circuit breaker enclosure:
i. Design pressure Bar
ii. Routine test pressure Bar
iii. Type test pressure Bar
iv. Operating pressure Bar
v. Maximum time for de-gassing and regassing of circuit breaker compartment Hrs.
h) Circuit breaker enclosure over pressure device operating pressure Bar
i) Type of absorbent device for gas decomposition provided and quantity. Kg
j) Moisture absorbent device and quantity Kg
k) Design life time of moisture absorbers Years
l) Weight of complete circuit breaker assembly Kg
m) Material of circuit breaker enclosure
1.41 Voltage withstand V/S time graph enclosed Yes/No
1.42 INSULATORS:
c) Descriptive pamphlet No.
e) Insulation class
f) One minute dry power frequency withstand voltage kV (rms)
g) Flashover voltage kV
h) Full wave impulse withstand voltage kV (peak)
i) Switching surge withstand voltage kV (peak)
j) Puncture value of insulator in SF6 gas kV
- Design bursting pressure Gauge bar
- Routine test pressure Gauge bar
- Arcing test 3 Sec. kA
1.43 General outline drawing enclosed, No.
1.44 Type of operating mechanism pneumatic/ hydraulic/spring charged
1.45 Spring charging mechanism
a) Spring charging motor
i. Rated voltage V
ii. Rating Watts
iv. Class of insulation
v. Satisfactory operation of spring charging motor between 80%-110% of rated voltage Yes/No
vi. Time required to charge spring from fully discharged condition Sec.
vii. Overload and short circuit protection particulars
b) Is provision made for immediate charging of closing spring after a closure Yes/No
c) Adequate spring reserve for one O-C-O operation without intentional time delay Yes/No
d) Mechanical indication for spring charged/discharged condition provided Yes/No
e) Whether slow closing/opening is feasible for maintenance testing Yes/No
f) No. of close-open operations possible after failure of Auxiliary supply
1.46 Pneumatically operated mechanism and compressed air system
a) Pneumatic operating system
i. Pressure switches for monitoring air pressure provided Yes/No
ii. Minimum air pressure required for closing Kg/cm2
iii. Minimum air pressure required for tripping Kg/cm2
iv. Maximum air pressure the local air receiver can withstand Kg/cm2
v. Setting of low pressure switch Kg/cm2
vi. Setting of high pressure switch Kg/cm2
vii. No. of potential free contacts on each pressure switch
viii. Pressure at which local receiver safety valve opens Kg/cm2
ix. Capacity of local reservoir Liters
b) Compressed air system:
i. Unit or centralised
ii. Air compressor capacity
iii. Rated pressure M3/hr
iv. Pressure at which central receiver safety valve opens Kg/cm2
v. Compressor operation starts at pressure Kg/cm2
vi. Compressor operation stops at pressure Kg/cm2
vii. Time for air compressor to charge central storage reservoirs
- From atmospheric to pressure indicated in item-v above Minutes
- From pressure indicated in item-v to item-vi above Minutes
viii. Compressor motor details enclosed Yes/No
ix. Control scheme drawing enclosed Yes/No
x. Control panel with complete auto start-stop controls, protection and interlocks provided Yes/No
xi. Piping bus scheme provided as required, complete with piping valves, supports, bends etc. included to make compressed air system complete Yes/No
xii. Calculation for compressed air system sizing including compressors piping and receivers enclosed Yes/No
xiii. Compressor air pipe
c) No. of close-open operations possible after failure of ‘AC’ supply
1.47 Hydraulic operating mechanism
a) Operating mechanism pressure
i. Nominal Kg/cm2
ii. Maximum Kg/cm2
iii. Alarm level (pump up) Kg/cm2
iv. Breaker block level Kg/cm2
b) No. of stored close-open operations from nominal to “Breaker Block” pressure
c) Reduction in pressure
i. “Close” operation Kg/cm2
ii. “Open” operation Kg/cm2
d) No. of close-open operations possible after failure of ‘AC’ supply to the motor
e) Hand pump-set for emergency operation provided Yes/No
1.48 Whether all type test reports as per latest relevant IEC standards are enclosed? Yes/No
1.49 Whether all routine/acceptance tests as per latest relevant standards will be carried out on each circuit breaker Yes/No
1.50 a) Whether breaker construction suitable for uprating later Yes/No
b) If yes, feasibility and extent of uprating possible
1.51 a) Linking mechanism for single pole units For closing / For tripping
b) Details of construction of linking mechanism components like operating rod:
Material specification
1.52 Auxiliary supply for heaters
a) AC voltage supply Volts
b) Total power required Watts
1.53 Auxiliary contacts
iii. Make before break
b) Continuous current carrying capacity A
c) Breaking capacity at 220 V DC A
d) Rated voltage V
1.54 Limit switch contacts
a) Continuous current carrying capacity A
b) Breaking capacity at 220 V DC A
c) Rated voltage V
2.0 HIGH VOLTAGE DISCONNECT SWITCHES (ISOLATORS) AND EARTH SWITCHES:
These details shall be separately furnished for 110kV (a)Isolators, (b) high speed motor operated earth switches and (c) hand operated maintenance earth switches:
(a)Isolators: 110kV
2.1 Makers name and country of manufacture
2.2 Manufacturers type and designation
2.3 Reference Standards
2.4 Rated voltage kV
2.5 Maximum design voltage at which the isolator can operate kV
2.6 Frequency Hz
2.7 Derating factor, if any, for specified site condition
2.8 Mechanical endurance class of Isolators M2 Yes/No
2.9 Class of Electrical endurance for earthing Switches
i. For high speed earthing switch with short circuit making capability.
ii. For Maintenance earthing switches
2.10 Current rating:
a) Continuous at site condition A
c) One second KA
d) Three second KA
e) Fault making capability(for earth switches)
211 a) Maximum temperature of current carrying parts when carrying rated current continuously 0C
b) Ambient temperature (Maximum/Average) for which (a) is applicable 0C
c) Maximum temperature of current carrying parts after carrying 40 KA current for
2.12 a) Short circuit type test certificates or reports No.
b) Whether (a) is enclosed Yes/No
2.13 Insulation tests:
a) One minute power frequency withstand voltage:
i. Across the isolating distance KV
ii. To earth and between poles KV
b) 1.2 x 50 microsecond impulse withstand voltage (+ or – polarity):
i. Across the isolating distance KV (peak)
ii. To earth and between poles KV (peak)
2.14 Contacts and material of current carrying parts:
a) Type of main and arcing contacts.
b) Material of contacts
i. Whether contacts are silver faced
ii. Thickness of silver facing
d) Material used for current carrying parts
e) Size & thickness of contacts
2.15 Rated switching capacity:
a) Capacity to interrupt magnetizing current (at p.f.) A
b) Capacity to interrupt line charging current (at p.f.) A
c) Rated making current A
d) Capacity to switch power transformer A
e) Transformer in rush current making capacity A
f) Capacity to energize GIS bus length M
g) Capacity to de-energize GIS bus length M
2.16 Operating time:
a) Opening time ms
b) Total opening time ms
c) Closing time ms
d) Charging time ms
2.17 Clearance:
a) Between poles mm
b) Between live parts and earth mm
c) Between live parts when the switch is open
i. On the same pole mm
ii. Between adjacent poles mm
2.18 Type of interlocks
2.19 a) Torque required to operate the moor operated isolator Kg-m
b) Torque required to manually operate the isolators, high speed earth switches and maintenance earth switches Kg-m
2.20 Speed of make and break
2.21 Over travel distance after contact made
2.22 Number of auxiliary switches:
a) N.O. type “a”
b) N.C. type “b”
c) Make before break type
d) Rated voltage V
e) Rated continuous current A
f) Breaking capacity at rated voltage A
2.23 Number of fault closing operations at rated short circuit current before:
a) Maintenance is required
b) Deterioration of dielectric withstand voltage occurs
2.24 Gauge pressure of SF6 gas at 200C
a) Rated pressure bar
b) Absolute pressure (gauge) bar
c) Minimum pressure at rated kV bar
d) Maximum safe pressure bar
e) Lo-pressure alarm bar
f) Very-lo pressure alarm bar
g) Over pressure alarm bar
h) Type of relief device (diaphragm etc)
i) Absorbent device for gas decomposition products provided (if yes, type & quantity) Yes/No
j) Moisture absorbent device type & quantity Kg
k) Enclosure design pressure bar
l) Enclosure test pressure bar
m) Enclosure over pressure device operating pressure bar
n) Quantity of SF6 gas in the enclosure Kg
o) Total weight of Isolator / Earth switch assembly Kg
2.25 Provision for verifying contact position
2.26 Viewing ports provided Yes/No
2.27 Insulator data
b) Torsional strength Kg m
c) Cantilever strength upright Kg
d) Power frequency dry flash-over voltage KV
e) Power frequency wet flash-over voltage KV
f) Impulse flash-over positive wave(1.2x50us) KV (peak)
g) Impulse withstand (1.2x50us) KV (peak)
h) Power frequency puncture voltage KV
2.28 a) Manual earth switch bushing insulator data
i. Power frequency flashover voltage KV (rms)
ii. Impulse flash over voltage KV (peak)
b) High speed earth switch bushing insulator data
i. Power frequency flash over voltage KV (rms)
ii. Impulse flash over voltage KV (peak)
2.29 Switch design:
a) Rotating/tilting/lifting
b) Horizontal/Vertical break
2.30 Operating mechanism
Manual/Pneumatic/Motor
(b) high speed motor operated earth switches:
2.1 Makers name and country of manufacture
2.2 Manufacturers type and designation
2.3 Reference Standards
2.4 Rated voltage kV
2.5 Maximum design voltage at which the isolator can operate kV
2.6 Frequency Hz
2.7 Derating factor, if any, for specified site condition
2.8 Current rating:
a) Continuous at site condition A
c) One second KA
d) Three second KA
e) Fault making capability(for earth switches)
2.9 a) Maximum temperature of current carrying parts when carrying rated current continuously 0C
b) Ambient temperature (Maximum/Average) for which (a) is applicable 0C
c) Maximum temperature of current carrying parts after carrying 40 KA current for
2.10 a) Short circuit type test certificates or reports No.
b) Whether (a) is enclosed Yes/No
2.11 Insulation tests:
a) One minute power frequency withstand voltage:
i. Across the isolating distance KV
ii. To earth and between poles KV
b) 1.2 x 50 microsecond impulse withstand voltage (+ or – polarity):
i. Across the isolating distance KV (peak)
ii. To earth and between poles KV (peak)
2.12 Contacts and material of current carrying parts:
a) Type of main and arcing contacts.
b) Material of contacts
i. Whether contacts are silver faced
ii. Thickness of silver facing
d) Material used for current carrying parts
e) Size & thickness of contacts
2.13 Rated switching capacity:
a) Capacity to interrupt magnetizing current (at p.f.) A
b) Capacity to interrupt line charging current (at p.f.) A
c) Rated making current A
d) Capacity to switch power transformer A
e) Transformer in rush current making capacity A
f) Capacity to energize GIS bus length M
g) Capacity to de-energize GIS bus length M
2.14 Operating time:
a) Opening time ms
b) Total opening time ms
c) Closing time ms
d) Charging time ms
2.15 Clearance:
a) Between poles mm
b) Between live parts and earth mm
c) Between live parts when the switch is open
i. On the same pole mm
ii. Between adjacent poles mm
2.16 Type of interlocks
2.17 a) Torque required to operate the moor operated isolator Kg-m
b) Torque required to manually operate the isolators, high speed earth switches and maintenance earth switches Kg-m
2.18 Speed of make and break
2.19 Over travel distance after contact made
2.2 Number of auxiliary switches:
a) N.O. type “a”
b) N.C. type “b”
c) Make before break type
d) Rated voltage V
e) Rated continuous current A
f) Breaking capacity at rated voltage A
2.21 Number of fault closing operations at rated short circuit current before:
a) Maintenance is required
b) Deterioration of dielectric withstand voltage occurs
2.22 Gauge pressure of SF6 gas at 200C
a) Rated pressure bar
b) Absolute pressure (gauge) bar
c) Minimum pressure at rated kV bar
d) Maximum safe pressure bar
e) Lo-pressure alarm bar
f) Very-lo pressure alarm bar
g) Over pressure alarm bar
h) Type of relief device (diaphragm etc)
i) Absorbent device for gas decomposition products provided (if yes, type & quantity) Yes/No
j) Moisture absorbent device type & quantity Kg
k) Enclosure design pressure bar
l) Enclosure test pressure bar
m) Enclosure over pressure device operating pressure bar
n) Quantity of SF6 gas in the enclosure Kg
o) Total weight of Isolator / Earth switch assembly Kg
2.23 Provision for verifying contact position
2.24 Viewing ports provided Yes/No
2.25 Insulator data
b) Torsional strength Kg m
c) Cantilever strength upright Kg
d) Power frequency dry flash-over voltage KV
e) Power frequency wet flash-over voltage KV
f) Impulse flash-over positive wave(1.2x50us) KV (peak)
g) Impulse withstand (1.2x50us) KV (peak)
h) Power frequency puncture voltage KV
2.26 a) Manual earth switch bushing insulator data
i. Power frequency flashover voltage KV (rms)
ii. Impulse flash over voltage KV (peak)
b) High speed earth switch bushing insulator data
i. Power frequency flash over voltage KV (rms)
ii. Impulse flash over voltage KV (peak)
2.27 Switch design:
a) Rotating/tilting/lifting
b) Horizontal/Vertical break
2.28 Operating mechanism
Manual/Pneumatic/Motor
(c) Hand operated maintenance earth switches:
2.1 Makers name and country of manufacture
2.2 Manufacturers type and designation
2.3 Reference Standards
2.4 Rated voltage kV
2.5 Maximum design voltage at which the isolator can operate kV
2.6 Frequency Hz
2.7 Derating factor, if any, for specified site condition
2.8 Current rating:
a) Continuous at site condition A
c) One second KA
d) Three second KA
e) Fault making capability(for earth switches)
2.9 a) Maximum temperature of current carrying parts when carrying rated current continuously 0C
b) Ambient temperature (Maximum/Average) for which (a) is applicable 0C
c) Maximum temperature of current carrying parts after carrying 40 KA current for
2.10 a) Short circuit type test certificates or reports No.
b) Whether (a) is enclosed Yes/No
2.11 Insulation tests:
a) One minute power frequency withstand voltage:
i. Across the isolating distance KV
ii. To earth and between poles KV
b) 1.2 x 50 microsecond impulse withstand voltage (+ or – polarity):
i. Across the isolating distance KV (peak)
ii. To earth and between poles KV (peak)
2.12 Contacts and material of current carrying parts:
a) Type of main and arcing contacts.
b) Material of contacts
i. Whether contacts are silver faced
ii. Thickness of silver facing
d) Material used for current carrying parts
e) Size & thickness of contacts
2.13 Rated switching capacity:
a) Capacity to interrupt magnetizing current (at p.f.) A
b) Capacity to interrupt line charging current (at p.f.) A
c) Rated making current A
d) Capacity to switch power transformer A
e) Transformer in rush current making capacity A
f) Capacity to energize GIS bus length M
g) Capacity to de-energize GIS bus length M
2.14 Operating time:
a) Opening time ms
b) Total opening time ms
c) Closing time ms
d) Charging time ms
2.15 Clearance:
a) Between poles mm
b) Between live parts and earth mm
c) Between live parts when the switch is open
i. On the same pole mm
ii. Between adjacent poles mm
2.16 Type of interlocks
2.17 a) Torque required to operate the moor operated isolator Kg-m
b) Torque required to manually operate the isolators, high speed earth switches and maintenance earth switches Kg-m
2.18 Speed of make and break
2.19 Over travel distance after contact made
2.2 Number of auxiliary switches:
a) N.O. type “a”
b) N.C. type “b”
c) Make before break type
d) Rated voltage V
e) Rated continuous current A
f) Breaking capacity at rated voltage A
2.21 Number of fault closing operations at rated short circuit current before:
a) Maintenance is required
b) Deterioration of dielectric withstand voltage occurs
2.22 Gauge pressure of SF6 gas at 200C
a) Rated pressure bar
b) Absolute pressure (gauge) bar
c) Minimum pressure at rated kV bar
d) Maximum safe pressure bar
e) Lo-pressure alarm bar
f) Very-lo pressure alarm bar
g) Over pressure alarm bar
h) Type of relief device (diaphragm etc)
i) Absorbent device for gas decomposition products provided (if yes, type & quantity) Yes/No
j) Moisture absorbent device type & quantity Kg
k) Enclosure design pressure bar
l) Enclosure test pressure bar
m) Enclosure over pressure device operating pressure bar
n) Quantity of SF6 gas in the enclosure Kg
o) Total weight of Isolator / Earth switch assembly Kg
2.23 Provision for verifying contact position
2.24 Viewing ports provided Yes/No
2.25 Insulator data
b) Torsional strength Kg m
c) Cantilever strength upright Kg
d) Power frequency dry flash-over voltage KV
e) Power frequency wet flash-over voltage KV
f) Impulse flash-over positive wave(1.2x50us) KV (peak)
g) Impulse withstand (1.2x50us) KV (peak)
h) Power frequency puncture voltage KV
2.26 a) Manual earth switch bushing insulator data
i. Power frequency flashover voltage KV (rms)
ii. Impulse flash over voltage KV (peak)
b) High speed earth switch bushing insulator data
i. Power frequency flash over voltage KV (rms)
ii. Impulse flash over voltage KV (peak)
2.27 Switch design:
a) Rotating/tilting/lifting
b) Horizontal/Vertical break
2.28 Operating mechanism
Manual/Pneumatic/Motor
3.0 VOLTAGE TRANSFORMERS:
These details shall be furnished separately for 245 kV,123kV & 72.5 KV voltage transformers 110kV
3.1 Makers name & country of manufacture
3.2 Applicable standard
3.3 Type of VTs
3.4 Number of VTs
3.5 Insulation withstand level
a) Impulse withstand voltage 1.2/50 micro sec.wave KV (peak)
b) One minute power frequency withstand voltage KV (rms)
3.6 Number of secondary windings for each VT
3.7 Rated primary voltage KV
3.8 Rated secondary voltage V
3.9 Rated VA burden for each secondary winding VA
3.10 Rated power factor
3.11 Accuracy class for each secondary winding
3.12 Method of connection
a) Primary winding
b) Each secondary winding
3.13 Rated voltage factor
b) For 30 seconds
3.14 Maximum temperature rise of windings at 110% excitation and rated burden, when referred to specified ambient temperature 0C
3.15 a) Type of insulation (SF-6 foil insulation or cast resin)
b) Class of insulation of windings
3.16 Gauge pressure of SF6 gas at 200C
a) Rated pressure bar
b) Absolute pressure (gauge) bar
c) Minimum pressure at rated kV bar
d) Maximum safe pressure bar
e) Lo-pressure alarm bar
f) Very-lo pressure alarm bar
g) Over pressure alarm bar
h) Type of relief device (diaphragm etc) Yes/No
i) Absorbent device for gas decomposition products provided (if yes, type & quantity) Kg
j) Moisture absorbent device type & quantity Kg
k) Enclosure design pressure Bar
l) Enclosure test pressure Bar
m) Enclosure over pressure device operating pressure bar
n) Quantity of SF6 gas in the enclosure Kg
o) Total weight of VT assembly Kg
3.17 Transient response (if applicable)
3.18 Details of high speed switch (es) on secondary winding (alternative to fuses)
a) Make and type
c) Relay make and type
d) Relay coil rating Amp.
e) Details of operating mechanism
3.19 Time of discharging of power cables Sec
3.20 Descriptive manual enclosed with Bid Yes/No
3.21 Complete list of tests proposed by the manufacturer at works & site
3.22 Type test certificates enclosed Yes/No
3.23 Dielectric testing at site is proposed to be carried out through VTs Yes/No
3.24 Continuous, 5 Minute and short time rating of primary and secondary winding of VTs Amp / At 5% rated voltage & rated voltage factor / At 2% rated voltage
3.25 a) % voltage (ratio) error
b) Phase displacement
3.26 Capacitive discharge capability of the VT
3.27 Material of winding primary & secondary
3.28 Material and minimum thickness of VT enclosure
4.0 CURRENT TRANSFORMERS:
These details shall be furnished separately for 245 kV,123kV & 72.5 KV current transformers for all ratios: 110kV
4.1 Applicable standards
4.2 Type of CTs
4.3 Number of CTs
4.4 Insulation withstand level
a) Impulse withstand voltage 1.2/50 micro second wave KV (peak)
b) One minute power frequency withstand voltage KV (rms)
4.5 Number of cores per CT
4.6 Rated primary current for each core A
4.7 Rated secondary current A
4.8 a) Ratio taps for each core
b) Whether it is possible to adjust tap setting of any core independent of other cores Yes/No
4.9 Turns ratio for each core
4.10 Application of each core
4.11 (A) For Relaying Cores (PS Class):
(Data shall be furnished for all ratio taps. Bidder shall furnish data against sub-items as may be applicable for that particular core)
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
4.11 (B) For Relaying cores (5P20 class):
(Data shall be furnished for all ratio taps. Bidder shall furnish data against sub-items as may be applicable for that particular core)
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
a) Accuracy class
b) Rated burden VA
c) Accuracy Limit Factor
d) Minimum knee point voltage Vk Volts
e) Maximum excitation current at half the knee point voltage mA
f) Maximum secondary resistance Ohms
4.12 For metering cores:
(Data shall be furnished for all ratio taps)
a) Accuracy class
b) Rated burden VA
c) Rated power factor
d) Instrument security factor
a) Accuracy class
b) Rated burden VA
c) Rated power factor
d) Instrument security factor
a) Accuracy class
b) Rated burden VA
c) Rated power factor
d) Instrument security factor
a) Accuracy class
b) Rated burden VA
c) Rated power factor
d) Instrument security factor
a) Accuracy class
b) Rated burden VA
c) Rated power factor
d) Instrument security factor
4.13 Short time thermal current rating
b) Rated time Sec
4.14 Dynamic current rating kA (peak)
4.15 Maximum temperature rise of windings at rated primary current and rated burden, when referred to specified ambient temperature 0C
4.16 a) Type of insulation (SF6 foil or cast resin)
b) Class of insulation of windings
4.17 Magnetization characteristics: Mfr’s dwg. No.
4.18 Recommended setting of protective device (spark gap, etc) mm
4.19 Gap setting flashover characteristics Manufacturers drawing No.
4.20 Secondary impedance value Ohms
4.21 In case of ring type CTs whether it is possible to remove the CT without affecting / dismantling the adjacent compartment Yes/No
4.22 Gauge pressure of SF6 gas at 200C
a) Rated pressure bar
b) Absolute pressure (gauge) bar
c) Minimum pressure at rated kV bar
d) Maximum safe pressure bar
e) Lo-pressure alarm bar
f) Very-lo pressure alarm bar
g) Over pressure alarm bar
h) Type of relief device (diaphragm etc)
i) Absorbent device for gas decomposition products provided (if yes, type & quantity) Yes/No (Kg)
j) Moisture absorbent device type & quantity Kg
k) Enclosure design pressure bar
l) Enclosure test pressure bar
m) Enclosure over pressure device operating pressure bar
n) Quantity of SF6 gas in the enclosure Kg
o) Total weight of CT Kg
4.23 Complete list of tests proposed by the Manufacturer at works and site enclosed Yes/No
4.24 Type test certificates for each type of CTs enclosed Yes/No
4.25 Current error
4.26 Phase displacement error
4.27 Material of primary & secondary winding
5.0 LIGHTNING ARRESTERS:
These details shall be furnished separately for LAs for 245kV,123kV & 72.5 KV GIS 110kV
5.1 Maker’s name
5.2 Country of manufacture
5.3 Manufacturers type designation
5.4 Applicable standards
5.5 Arrester class and type
5.6 Rated arrester voltage KV
5.7 Rated frequency Hz
5.8 a) Nominal discharge current (8/20 micro second wave) KA
b) Minimum discharge capability KJ/kV
5.9 Power frequency over voltage withstand capability voltage for:
a) 30 Sec. KV (rms)
b) 1 min. KV (rms)
c) Continuous KV (rms)
5.10 Maximum residual voltage at nominal discharge current KV (rms)
5.11 Discharge voltage at 5 KA discharge current KV (rms)
5.12 Discharge voltage at 10 KA discharge current KV (peak)
5.13 Discharge voltage at 20 KA discharge current KV (peak)
5.14 Minimum residual voltage of arrester KV (rms)
5.15 Impulse current withstand
a) High current short duration (4/10 Micro Second wave) KA (peak)
b) Low current long duration A (peak)
c) Virtual duration of rectangular wave Micro-sec.
5.16 One minute power frequency (dry) withstand voltage of arrester housing KV (rms)
5.17 Impulse withstand test voltage of arrester housing with 1.2/50 Micro Second wave KV (peak)
5.18 Total height of the arrester mm
5.19 Total weight of complete arrester including enclosure and gas Kg
5.20 Pressure relief class (as per IEC 99)
5.21 a) Range of milli-ammeter provided for leakage current measurement mA
b) Type and make of above
5.22 Drawings/information submitted with the bid
5.23 Explosion proof/non-explosion proof
5.24 Surge monitor provided Yes/No
5.25 Grading shields provided Yes/No
5.26 Whether type test reports are enclosed Yes/No
5.27 Volt/time characteristic enclosed Yes/No
5.28 Complete list of routine acceptance tests which will be carried out on the arresters enclosed Yes/No
5.29 VENDOR agreeable to carry residual voltage test at the nominal discharge current Yes/No
5.30 Gauge pressure of SF6 gas at 200C
a) Rated pressure bar
b) Absolute pressure (gauge) bar
c) Minimum pressure at rated kV bar
d) Maximum safe pressure bar
e) Lo-pressure alarm bar
f) Very-lo pressure alarm bar
g) Over pressure alarm bar
h) Type of relief device (diaphragm etc)
i) Absorbent device for gas decomposition products provided (if yes, type & quantity) Yes/No (Kg)
j) Moisture absorbent device type & quantity Kg
k) Enclosure design pressure bar
l) Enclosure test pressure bar
m) Enclosure over pressure device operating pressure bar
n) Quantity of SF6 gas in the enclosure Kg
o) Total weight of LA assembly Kg
5.31 Material and minimum thickness of LA enclosure
6 SF6 BUS DUCTS:
Following data shall be furnished separately for a) 110kV GIS, 110 kV interconnection between transformer/UG cable/Over headline and 110 kV GIS. b) 110 KV GIS, 110kV interconnection between 110/11 KV transformer and 110 KV GIS and 110 KV interconnection between110/11 KV transformer & 110 KV GIS.
6.1 Equipment Rating
a) Nominal Operating Voltage kV
b) Highest Operating Voltage kV
c) Basic Impulse Insulation Level kV (peak)
d) Frequency Hz
e) Bus rating (continuous) at 200C ambient Amps
f) Rated short time current (3 sec) KA (rms)
g) 1 min. power frequency withstand voltage kV
h) Impulse withstand voltage 1.2/50 Micro Sec. wave kV (peak)
i) Switching surge withstand voltage kV (peak)
j) Maximum permissible operating temperature of current carrying parts (above ambient 450C) 0C
k) Temperature rise of enclosure at rated current (for site condition and above 450C ambient) for
ii. Outdoors 0C
iii. State assumptions on which calculations are based
l) Maximum safe continuous current that can be carried at site condition at:
i. 200C Ambient A
ii. 300C Ambient A
iii. 400C Ambient A
iv. 450C Ambient A
v. Limiting factors and the empirical relationship used to calculate these current ratings Yes/No
m) Maximum temperature (Hot spot) of conductor while carrying rated current at maximum ambient temperature 0C
n) Maximum temperature (Hot spot) of enclosure at rated current at maximum ambient temperature 0C
o) Temperature of conductor when rated short circuit current is carried for three seconds when short circuit occurs at maximum operating temperature
NOTE: Calculations to be furnished for the above.
6.2 Gauge pressure of SF6 gas at 200C
a) Nominal SF6 pressure Bar
b) Maximum SF6 pressure Bar
c) “Gas Refill” level Bar
d) “Breaker Block” level Bar
e) “Zone Trip” level Bar
f) “Over Pressure” alarm level Bar
g) Maximum permissible moisture content of SF6 gas ppm by wt.
h) Maximum leakage rate per year at nominal pressure
i. For complete station %
ii. For single gas compartment %
i) Amount of SF6 gas required to completely charge the complete installation including any tank storage system (please indicate separately for both the packages) kg
j) Amount of SF6 gas required for largest gas compartment kg
k) Design pressure of the enclosure bar
l) Routine test pressure of the enclosure bar
m) Test pressure of the enclosure bar
6.3 Pressure Relief Device (s)
a) Rupturing Pressure (gauge) Bar
b) Time to rupture, smallest section Seconds
c) Quantity and location on each section
d) Construction material of diaphragm
e) Write-up on features adopted for preventing burn through in the various enclosures, enclosed Yes/No
6.4 A Lengths & accessories of exit bus ducts considered in the layout proposed by the BIDDER (please indicate separately for interconnections with Over headline/UG cable/ transformers) For Over Head Tr. line/UG cable On 110 KV side On 11 KV side
on 110kv side for each transformer on 11kv side for each transformer
a) Straight lengths
d) Interface with transformer bay SF6 to air bushing
e) SF6 gas to air bushings for line bay
6.5 Design Data
a) Capacitance per meter bus duct pf
b) Resistance/meter/phase at 200C
i. Conductor Ohm
ii. Enclosure Ohm
c) Inductance reactance / meter / phase at 200C Ohm
d) i. Surge impedance of the enclosed bus Ohm
ii. Description of methods and calculations used to determine surge impedance and capacitance enclosed Yes/No
e) Electrical Resistance at 200C of
i. Bus enclosure Ohms/mtr
ii. Conductor Ohms/mtr
f) Maximum potential rise of enclosure at short circuit current V
g) Maximum power loss per single phase meter at 200C
ii. Conductor W
h) Total maximum power loss at 200C (please give basis and detailed calculation with method for verifying losses)
i. Complete 245 kV, 123kV & 72.5 KV GIS W
ii. 245 KV,123kV & 72.5 KV Interconnection W
iii. Total 245 kV,123kV & 72.5 KV GIS including Transformer/over headline/UG cable exit bus duct W
i) Weight per single phase meter of bus duct (Exit bus duct) Kg
j) Weight per three phase meter of bus duct (main bus duct) Kg
k) Maximum unsupported span between supports (for main & exit bus ducts respectively) m
l) Allowable tolerance in height of support platform mm
m) Insulator material
i. Material (state alloy)
ii. Cross sectional area Sq.mm
iii. Minimum unsupported span
i. Material (state alloy)
ii. Outer diameter (OD) mm
iii. Thickness mm
iv. Finish of interior of pressurized bus duct enclosure
v. Vacuum withstand capacity of various types of enclosures m bar
f) Paint shade of exterior surface
i. Outer diameter (if spherical) mm
ii. Thickness mm
iii. No. of standard angles employed mm
q) Weight of each assembled bay, separately Kg
r) Distance between phase centre lines mm
s) Maximum electrical stress
i. SF6 gas kV/mm
ii. Insulator kV/mm
t) Material used in fabricating the following:
i. Breaker contacts
ii. Disconnecting switch surfaces
iii. Grounding switch surfaces
iv. Internal bus
v. Internal bus contact surfaces
vi. Bus enclosure
u) Description of technique used to control thermal expansion in:
v) v) Maximum length of single phase exit bus duct gas compartment (for 245 kV GIS & 72.5 KV GIS) m
w) Total weight of gas in this compartment kg
x) Total weight of largest sized compartment kg
y) y) Maximum length of single/three phase gas compartment (for main bus bar of 245 kV GIS & 72.5 KV GIS) m
z) Total weight of gas in this compartment kg
aa) Total weight of largest sized compartment kg
ab) Whether field connection of enclosure sections are made by means of bolting or welding (in case of welding specify the extent of field welding and the procedure which VENDOR proposes to adopt at site)
ac) Extra paint for retouching up at field included in the supply Yes/No
ad) Describe method of particle control employed
ae) Are shipping sections completely assembled lengths of bus duct Drawings, supporting this data and clearly illustrating the construction of the bus duct compartments, shall be submitted with the bid.
7.0 SF6 GAS TO AIR BUSHING (To be connected to transformer / Overhead Lines)
Following data shall be furnished for 110/11 KV Transformer.
7.2 Type (OIP/RIP etc)
7.4 Transport dimensions
7.5 Height above ground level required to remove bushings
7.6 Insulation class
7.7 Current rating
a) Continuous at an ambient of 450C Amps
b) Short time (3 Sec) Amps
7.8 SF6 gas service pressure (gauge) Bars
7.9 Design pressure (gauge) Bars
7.10 Test pressure (gauge) Bars
7.11 Bursting pressure (gauge) Bars
7.12 Permissible leakage rate at rated differential pressure, per year
a) 1 bar Mltr/Year
b) Rated pressure Mltr/Year
7.13 One minute dry & wet power frequency withstand voltage kV (rms)
7.14 Flashover voltage kV
7.15 Full wave impulse withstand voltage kV (peak)
7.16 Switching surge withstand voltage kV (peak)
7.17 Very Fast Transient Over voltage (Peak & Duration) kV/n sec.
7.18 Corona discharge voltage kV
7.19 Partial discharge extinction voltage (p.d. level less than 10 p.c) kV
7.20 Creepage distance
- Protected at 900 mm
7.21 Permissible safe cantilever loading on installed bushing Kg
7.22 Nature of dielectric medium employed in the bushing Kg
7.23 Volume of insulating medium per bushing
7.24 Material of bushing terminal clamp
7.25 Temperature range
a) SF6 gas side 0C
b) Transformer side 0C
7.26 Maximum oil pressure in bushing gauge Bar
7.27 Mounting position Deg from vertical position
7.28 Distance of bushing axis to grounded transformer wall under oil mm
7.29 Cantilever test load, 900 to bushing axis on both ends one after another at room temp and at inside pressure of
a) 2 bars (for 1 min) N
b) Rated pressure (for 1 min) N
7.30 Permissible cantilever moment at bushing flange
8.0 GENERAL DATA
8.1 The following data shall be furnished for 72.5 KV
a) Gas section diagram enclosed
b) No. of gas compartments per cable/overhead line incomer bay
c) No. of gas compartments per transformer bay
d) No. of gas compartments in main buses 1 & 2 respectively
e) No. of gas compartments in bus coupler bay
a) Material (state alloy) mm
b) Outer diameter (OD) mm
d) Finish of interior of pressurized GIS enclosure
e) Vacuum withstand capacity of various types of enclosures m bar
f) Paint shade of exterior surface
8.3 Mechanical strength of enclosures:
a) Design pressure Gauge bars
b) Operating pressure Gauge bars
c) Type test pressure Gauge bars
d) Routine test pressure Gauge bars
e) Leakage test pressure 30 min Gauge bars
f) Safety factor (type test/operating pressure)
8.4 Internal Arcing
a) Enclosure burn-through time at various currents Sec
b) Enclosure rupturing pressure Gauge bars
c) Barrier insulator rupturing pressure Gauge bars
d) Max. pressure rise at 40 kA (smallest section) Gauge bars
e) Data on burn-through preventive measures enclosed Yes/No
f) Test data submitted Yes/No
8.5 Description of the proposed methods to limit switching surges for breaker and disconnects enclosed Yes/No
8.6 Values of maximum switching surges guaranteed
8.7 Total losses when complete switchgear is operated at its rated capacity KW
8.8 Break-up of losses at rated current
a) 245 kV GIS KW
b) Bus duct between 245 kV GIS and transformer/UG cable KW
b) Bus duct between 123 kV GIS and transformer/UG cable
a) 72.5 KV GIS KW
b) Bus duct between 72.5 KV GIS & Transformer. KW
8.9 Interfaces:
a) Maximum lateral and longitudinal movement at interface due to expansion and contraction. mm
b) Maximum tensile and compressive forces at interface kg
c) Tolerance on positioning of flanges mm
d) SF6 gas pressure at interface
ii. Nominal permissible bar
e) Permissible tolerance on phase spacing of transformer terminals ±mm
f) Permissible tolerance on height of transformer terminals ±mm
g) Maximum allowable tolerance on phase spacing of transformer terminals that can be achieved by the compensator (bellow) ±mm
h) Maximum allowable tolerance on height of transformer terminals that can be achieved by the compensator (bellow) ±mm
i) Write-up on special grounding requirements enclosed Yes/No
8.10 Insulation System Monitoring Devices
a) Gas density detector
b) Gas pressure detector
c) Gas moisture content detector
d) Fault detector device
e) Optional equipment available
8.11 Generic Origin of Components
The Bidder is requested to list all material, metallic and non-metallic within switchgear interior, which are in contact with or might come into contact with the sulphur hexafluoride. Material Trade Name / Material Generic Origin / Material Location
8.12 Clearances:
The Bidder shall complete the following questionnaire in detail and provide any additional information not specifically requested but which may be of assistance to the PURCHASER in evaluating the integrity of the switchgear.
a) Minimum Insulating Clearance:
i. Main bus Creepage / Strike / Profile
ii. Line bus Creepage / Strike / Profile
iii. Circuit breaker to earth across contacts Creepage / Strike / Profile
iv. Disconnecting switch to earth across contacts Creepage / Strike / Profile
v. Earth switch to earth (enclosure) & across contacts Creepage / Strike / Profile
vi. SF6/XLPE insulated cable termination chamber Creepage / Strike / Profile
a) Name of manufacturer
b) Electrical Properties
c) Compatibility with material used in GIS
d) Impurities in percentage
e) Size of cylinder in which gas is proposed to be supplied
f) Condensation temperature
g) Physical properties
h) Tests to be conducted by the manufacturer at works.
i) Tests proposed to be conducted at site to detect and limit the moisture content in gas compartments
8.14 SF6 Gas Handling Equipment:
a) Make and Type of the Plant
b) Description of gas handling equipment
i. Compressor type
ii. Vacuum pump type
iii. Filtering equipment type
iv. Moisture removal equipment type
8.15 c) Time for evacuation of largest 3 Phase section of switchgear minutes
d) Time for refilling of largest 3 phase section of switchgear minutes
e) Nominal section capacity of vacuum pump m3/hr
f) Maximum vacuum obtainable by vacuum pump bar
g) Motor rating of vacuum pump kw
h) Storage capacity service tank kg
i) Gas filling capacity of compressor kg/hr
j) Maximum pressure of compressor bar
k) Rating of compressor motor kw
l) Operating voltage Volts
m) Control voltage Volts
n) Drying (moisture removal) capability of gas plant
o) Filtration/particle removal capability of the gas plant
p) Size of the molecular sieve
q) Length, width and height of the plant
r) Total weight of the plant
s) Electrical output
i. Compressor kw
ii. Vacuum pump kw
iii. Control system kw
8.16 a) Type and quantity of gas required at site for purging of GIS during erection
b) Above gas will be supplied by the Vendor as part of this contract Yes/No
8.17 a) Details of Portable SF6 gas detector to be supplied, provided Yes/No
b) Sensitivity of SF6 detector in atmosphere ppm
a) Rating of main ground bus
b) Touch potential
ii. Calculations enclosed Yes/No
c) Maximum expected circulating current in earth mat during normal operation A
8.19 Whether support framework included in the supply
a) Material Yes/No
b) Whether hot dip galvanized Yes/No
8.20 a) Required tolerance in surface level of the civil works to be carried out by the PURCHASER ± mm per meter
b) Foundation channels included in the supply
8.21 Insulators/Section barriers for GIS (For each type):
a) Type of insulators used
c) 1-minute power frequency dry withstand test voltage kV (rms)
d) Dry flashover value kV (rms)
e)1.2/50 microsec impulse withstand test voltage kV (peak)
f) Puncture value of insulator in SF6 gas kV
g) Maximum electrical field strength at rated voltage phase to earth kV/mm
h) Gas barrier routine test pressure Gauge bar
i) Gas barrier routine test pressure Gauge bar
j) Arcing test 3 sec kA
k) Weight of insulator kg
l) Partial discharge levels at 120% working voltage
i.For one bay (sensitivity 5 pico columbs)
ii. For individual insulator (sensitivity 5 pico columbs)
8.22 Whether the GIS complies to Cl. No. 4.1.7 of section–B of GIS specification regarding subsequent repairs/testing, in the event of a fault
9.1 BIDDER’s program for full type/routine testing of the GIS in accordance with IEC-62271-203
9.2 Tests to be carried out at site after erection (furnish complete details of the tests including details of the testing equipment, special adaptors and other accessories to be supplied by Bidder)
9.3 Detailed procedure for power cable HVDC testing including details of cable testing and isolating facilities and necessary adaptor interface to be supplied by Bidder.
9.4 What provisions are made for testing of circuit breakers, etc., at site and detailed procedure
9.5 What provisions are made for high voltage test connections
9.6 Procedure for leakage tests for acceptance
9.7 Detail the features in equipment to carry out partial discharge measurements at works/site
9.8 BIDDER’s programme for full production testing of each complete breaker as per IEC standard
9.9 Information regarding the insulation testing of following to earth and across open contacts:
i. Each complete breaker
ii. Disconnect switch
iii. Earth switch
9.10 The short circuit test reports should tabulate current, voltage and TRV on a unit test basis and on an equivalent breaker basis. The basis for assigning the rated interrupting time, proof of operating duty and pressures of dielectric and driving mechanism shall be clearly stated.
9.11 Procedure for obtaining voltage withstand vs time and its validity for the total equipment
9.12 Details of V F T O test on SF6 gas to oil bushing for transformer
10.0 Estimate of erection & testing/commissioning:
10.1 Downtime required to errect extension equipment by the side of equipment in service Days
10.2 Whether outage of the complete GIS will be required for erection, testing & commissioning for the extension Yes/No
10.3 Power supply required during erection, testing and commissioning
10.4 Detailed schedule of erection, testing and commissioning enclosed Yes/No
11.0 Reliability and Maintainability Programme:
11.1 Target for proposed equipment
11.2 Equipment life Years
11.3 Forced outage rate %
11.4 Forced outage duration Hours
11.5 Fixed outage of occurrences No. per year
11.6 Availability %
11.7 Mean time between failure (MTBF) Months
11.8 Mean time to repair (MTTR) Hours
11.9 Planned maintenance outage rate %
11.10 Planned maintenance outage duration Hours
11.11 Number of planned maintenance outages No. per year
11.12 Guaranteed number of loaded/unloaded operation of various equipment of GIS e.g. circuit breaker, disconnects, earthing switches, etc (Please mention itemwise).
Circuit breaker
Earthing switches
12.0 Previous Operational Experience
12.1 The ratings, classification and number of units are
12.2 Previously supplied to delivery in
12.3 Function Performed
12.4 Total equipment years
12.5 Total service life or number of operations
12.6 MTTF (Major Failures) – Failure modes & rates
12.7 MTTF (Minor Failures) – Failure modes & rates
12.8 List of in-service flash over in previously supplied equipment (date, owner, description of event, repair procedure and time)
12.10 Reliability forecasts
12.11 Repair / maintenance of one bay / any component of the bay will require outage of any other bay in same station Yes/No
12.12 Repair / maintenance of one bus bar will require outage of other bus bar in same station Yes/No
12.13 During later extensions, outage of parts already in service will be required for erection/testing Yes/No
13.0 Design Data
13.1 Ventilation requirements enclosed Yes/No
13.2 Special light fitting requirements if any, enclosed Yes/No
13.3 Suggested lighting level Lux
13.4 Details of recommended system for fire fighting enclosed Yes/No
13.5 Data for design of switchgear building enclosed Yes/No
13.6 Floor loading beneath breaker poles Kg/sq.m
13.7 Floor loading beneath bus ducts Kg/sq.m
13.8 Allowable max. tolerance for GIS floor ± mm/meters
13.9 Maximum floor loading
13.10 Recommended crane capacity & speed Tonnes & m/min.
13.11 Heaviest item weight Tonnes
13.12 Total auxiliary DC supply requirement
i. Continuous A
ii. Short time A
13.13 Total auxiliary AC supply requirement
14.0 INDUCTION MOTORS
14.1 Application/Designation
14.2 Manufacturer
14.3 Applicable Standards
14.5 Type of Duty
14.6 Duty Designation
14.7 Supply conditions:
a) - Rated Voltage V
- No. of phases
b) Allowable variations in
c) Permissible unbalance in supply voltage %
a) Full load Amps
b) Starting % FL
14.9 Full load efficiency %
14.1 Full load power factor
14.11 Method of starting
a) Starting % FLT
b) Maximum % FLT
14.13 Class of Insulation
14.14 a) Ref. Ambient Temperature 0C
b) Temperature rise by Res-Method 0C
14.15 Type of Enclosure
14.16 Degree of Protection
14.17 Suitable for Outdoor operation Yes/No
14.18 Normal winding connection Star/Delta
14.19 Type & No. of Terminals brought out
14.20 Winding suitable for 24 V space heating Yes/No
14.21 Shaft Orientation
14.22 Dimensional drawing enclosed Yes/No
15.0 LOCAL CONTROL PANELS
15.1 Make and country of manufacture
a) Type of construction
b) Degree of protection
15.2 Type of sheet steel (hot rolled/cold rolled)
15.3 Thickness of sheet steel
15.4 Paint treatment and colour shades
15.5 Weight of each panel Kg
15.6 Dimensions (width x depth x height) mm
15.7 Mimic bus, material colours
15.8 Space required for installation m2
15.9 General arrangement drawing attached Yes/No
15.1 Largest package for transport
b) Dimension mm
15.11 Instruments, components etc., transported, mounted on panels or separately packed
15.12 Cable glands included Yes/No
15.13 Fire retardant Instrument/control cables for interconnection as per Section-D included Yes/No
15.14 a) Cable installation hardware included Yes/No
b) Cable entry Top/bottom
15.15 Special cables (if required) included Yes/No
15.16 Special tools & devices for maintenance included (list attached) Yes/No
15.17 List of recommended spares for normal maintenance for a period of 5 years furnished (list attached) Yes/No
15.18 Components list of each panel enclosed Yes/No
15.19 Technical and descriptive literature of all components attached Yes/No
15.20 Auxiliary/Interposing relays
b) Type designation
c) Nominal voltage & variation %
d) Contacts hand reset/self reset
e) No. of pairs of contacts
i. Make contacts
ii. Break contacts
f) Speed of operation of relay
g) Pick-up/drop off ratio
h) Burden of the relay
i) Contact rating
i. Continuous A
j) No. of pairs of contacts
i. Make contacts
ii. Break contacts
k) Speed of operation of relay
l) Pick-up/drop off ratio
m) Burden of the relay
n) Contact rating
i. Continuous A
iii. Making current and duration A, AC/DC
iv. Resistive breaking A
v. Inductive A/DC
o) Detailed literature furnished Yes/No
15.21 Control switches
b) Front dimensions
c) Type of switch (stayput spring return/ discrepancy)
d) Type of handle
e) Contact development
f) Integral escutcheon plate or circuit label provided Yes/No
g) Contact rating
i. Continuous current A
iii. Breaking current
- Inductive A, DC
h) Elec. life expectancy based on 120 switching operation per hour operations No. of
i) Detailed literature furnished Yes/No
15.22 Push buttons
b) Actuator type
i. Momentary/maintained
ii. Shrouded to prevent inadvertent operation Yes/No
c) Whether integral engraved inscription plates provided Yes/No
d) Contact rating
i. Continuous rating A
ii. Voltages Volts
iii. Making current A
iv. Resistive breaking current A
v. Inductive breaking current A/AC
e) Electrical life expectancy based on 300 switching operation cycles per hour No. of operations
f) Detailed literature furnished Yes/No
15.23 Indicating lamps
c) Series resistor
i. Ohm value Ohm
d) Life of lamp in burning hours hours
15.24 Panel wiring:
a) Material & size of conductor
i. For CT circuits Sq.mm
ii. For other circuits Sq.mm
b) Solid/Stranded conductor
c) Tinned/Untinned
d) Material of insulation & sheath
i. Fire retardant low smoke Yes/No
ii. Oxygen index at 2500C
iii. Acid gas generation %
iv. Smoke generation under fire (in terms of % of light passed) %
e) Voltage grade V
f) Colour coding is provided Yes/No.
g) Numbered ferrules on either side Yes/No
h) Insulated sleeves provided at both ends Yes/No
ii. Current rating A
iii. Clamp/bolt type
iv. Moulded inter-terminal barriers provided Yes/No
v. Maximum conductor size & No. of conductors it can receive Sq.mm
vi. Disconnecting type for CT circuits Yes/No
vii. Terminal marking facility provided Yes/No
viii. Crimp type connectors provided at the terminals Yes/No
ix. 20% spare terminals provided Yes/No
a) Outer sheathing fire retardant Low smoke type Yes/No
ii. Thickness mm
d) Safe pulling force V
e) Overall diameter
f) Voltage grade
ii. Stranded/Solid
iii. Tinned/Untinned
h) Core identification colour/printed numbers
i) Drum lengths
j) The critical oxygen index at 2500C when tested as per ASTM-9 2863-1979
k) Acid gas generation by weight when tested as per IEC-754-1 %
l) Smoke generation as a % of light transmission when tested as per ASTM-D-2843-n %
m) Finished cable passes flammability tested as per IEC-3321 & Swedish Standard SS-424-14-75 Yes/No
n) Vendor agreeable to conduct above tests on all cables supplied to verify the value given in items of j, k, l, m above, in addition to routine tests Yes/No
o) Standard to which the cable conform to
15.26 Space heater rating
a) Power supply V
16.0 SF6 GAS CYLINDER DETAILS:
16.1 Manufacturer of the Cylinder
16.2 Standard to which cylinders conform
16.3 Type of cylinder Seamless
16.4 Manufacturer of SF6 gas
16.5 Standard applicable to SF6 gas
16.6 Water capacity of the cylinder Litres
16.7 Quantity of SF6 gas Kg
16.8 Filling ratio
16.9 Filling pressure at 150C Bars
16.1 Design pressure of cylinder Bars
16.12 Maximum permissible service pressure Bars
16.13 Developed pressure (gauge) at 650C Bars
16.14 Specifications of the valves fitted to cylinders
17 Shipment/Packing details
a) Bidders proposal for packing of various items for shipment
b) Maximum permissible shock that various equipment can withstand during shipment/transportation
c) Impact recorders (accelerometers) will be provided by the supplier as per specification
d) Weight and dimension of the largest shipment package
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
A1 : GUARANTEED TECHNICAL PARTICULARS FOR UG Cable
GUARANTEED TECHNICAL PARTICULARS FOR 110 KV 630sqmm UG Cable
Sl.No. PARTICULARS
1 Name of the Manufacturer
2 Country of Manufacture
3 Type of cable / cable code
4 Applicable standard
a. Rated Nominal voltage
b) Rated Maximum voltage
6 Continuous Current carrying capacity in Amps (Calculation to be shown seperately)
7 Permissible voltage & frequency variation for satisfactory operation
8 Type of process of manufacturing of cable
a) Triple extrusion (Yes/No)
b) Whether VCV method/CCV method/Any other method
9 Suitability for :
a. Earthed system
b. Unearthed system
a) Nominal cross section (sq.mm)
d) Diameter of conductor (mm)
e) Number of wires per conductor (Nos.)
f) Nominal diameter of wire in conductor (mm)
11 Conductor screen
a) Material and type
b) Thickness (mm)
c) Maximum volume resistivity at 90 ± 2°C before and after ageing (ohm-cm)
12 Maximum value of Electric stress at
a) Conductor screen kV/mm
b) At the insulation kV/mm (Calculation to be shown separately)
13 Insulation XLPE
a) Curing process (furnish details separately)
b) Material/Composition
c) Dia over insulation
d) Radial thickness
i. Nominal (mm)
ii. Average (mm)
iii. Minimum (mm)
iv) t max-t min ≤ 0.15 t max
e) Specified insulation resistance at 90°C
f) Insulation resistance at 20°C
14 Insulation screen (Non metallic)
b) Nominal thickness (mm)
c) Maximum volume resistivity at 90 ± 2°C . (ohm-cm)
d) Maximum dielectric stress (Calculation to be provided)
15 Tape swellable (Longitudinal water / Moisture / Protection)
b) Thickness (mm)
16 Radial Water Barrier (Lead Sheath)
a) Type / composition
c) Nominal thickness
d) Tolerance on thickness
e) Diameter of cable over metallic sheath (mm)
17 Bedding Tape over Inner sheath
ii) Dimension (Wxt) (mm) x (mm)
18 Concentric screen / Plain Copper Wires
b) Dia of copper wire
19 Binder open Helix, contact copper Tape over screen / Armour wires
b) Dimension (Wxt)
20 Non-woven water swellable Tape over Binder Tape
21 Overall sheath
i) Material & Type
22 Conductive coating on outer sheath
23 Anti-termite treatment to outer sheath
24 External overall dia of cable
25 Weight of Cable /M (Kgs)
26 Short circuit rating of conductor 90°C operating temperature for 1 Sec.
27 a) Minimum cable bending radius (in terms of cable diameter)
b) Recommended minimum installation radius
28 Permissible maximum tension
29 Continuous current rating under specified installation conditions at conductor temperature of 65°C and 90°C
Ground Temperature 30°C
Thermal resistivity of soil 150°C CM/W
Depth of laying 1500 mm
Ambient Air temperature 50°C
No. of circuits 1 OR 2
Spacing between two circuits (600 mm)
Formation Trefoil Touching
Single Point / cross Bonded Both End Bonded
65 deg. C Amps 90 deg. C Amps 65 deg. C Amps 90 deg. C Amps
Current Rating conductor size 630 Sq. mm
a) In Ground /Trench
i. of each circuits (when both the circuits alive)
ii. of one circuits (when other Circuit is isolated)
i. of each circuits (when both the circuits alive)
ii. of one circuits (when other Circuit is isolated)
c) In HDPE ( 160mm dia) pipe, one cable per pipe.
i. of each circuits (when both the circuits alive)
ii. of one circuits (when other Circuit is isolated)
i. of each circuits (when both the circuits alive)
ii. of one circuits (when other Circuit is isolated)
30 Maximum permissible conductror temperature for continuous operation under specified installation conditions (deg. C)
31 Conductor temperature at rated current (deg. C)
32 Temperature rise for 20% over current
33 Emergency overload rating
34 Basic impulse level at conductor temperature of 90 deg. C (KV)
35 Impulse wave shape
36 Power frequency with stand voltage (KV)
37 Tan Delta at 50 Hz (at Uo kV and 90 (-5/+10) deg. C
38 Sheath voltage at max. load single : Point bonded, trefoil touching ( both circuits alive) V/KM
39 Withstand voltage of sheath on spark test
40 Permissible short circuit current ratings of conductor
iii) 0.5 Sec KA
41 Conductor resistance DC & AC
a) at 20 deg. C (d.c)/A.C. ohm/KM
b) at 90 deg. C (d.c)/A.C. ohm/KM
c) at 105 deg. C (d.c)/A.C. ohm/KM (over load temp) a.c. (ohm)
42 Equivalent star resistance at 50 Hz of 3 phase current
a) at 20 deg. C ohm/KM
b) at 90 deg. C ohm/KM
c) at 10% continuous overload temperature (ohm/KM)
43 Star reactance at 50 hz (ohm/KM)
44 Approximate impedance at 50 hz per KM
a) at 20 deg. C ohm/KM
b) at 90 deg. C ohm/KM
c) at 10% continuous overload temperature (ohm/KM)
45 Self electrostatic capacitance per phase (Micro farad/KM)
46 Maximum power factor at charging KVA of cables when laid direct in ground at normal voltage & frequency
a) at ambient Temperature
b) at Maximum conductor Temperature
47 a) Positive and negative sequence impedance (ohm/KM)
b) Zero sequence impedance (ohm/KM)
48 Zero sequence data
a) Series resistance (ohm/KM)
b) Series reactance (ohm/KM)
c) Shunt capacitive reactance (ohm/KM)
49 Sheath voltage under maximum operating conditions asseming all circuits comected KV/KM
50 a) Sheath resistance at 20 deg. C ohm/KM
b) Screen resistance at 20 deg. C ohm/KM
c) Combined resistance at 20 deg. C ohm/KM
51 Surge impedance of cable (ohm/KM)
52 IR value at ambient temperature per KM
53 Maximum magnitude of partial discharge at 1.5 Uo.
At Ambient Temperature (Pc)
At High Temperature (Pc)
54 Dielectric dissipation factor at rated voltage
55 Guaranteed Losses per Km (Calculation sheet to be furnished) corresponding to rated current (Sl. No. 6) & rated voltage ( sl. No. 5) [Refer clause No. 26.5.1 (Guaranteed Loss) of SCC, Section 5]
56 Note: (i) For 630sq.mm Cable
a) Total 3 Phase Dielectric Loss at rated voltage and rated current
i. One Circuit alive KW/KM
ii. Both Circuits alive KW/KM .
b) Total 3 Phase Copper Loss at rated voltage and rated current
i. One Circuit alive KW/KM
ii.Both Circuits alive KW/KM
c) Total 3 Phase sheath / screen loss at rated voltage & rated current
i. One Circuit alive KW/KM
ii.Both Circuits alive KW/KM
d) Other losses due to reinforcement
i. One Circuit alive KW/KM
ii.Both Circuits alive KW/KM
e) Total Losses at rated voltage & rated current
i. One Circuit alive KW/KM
ii.Both Circuits alive KW/KM
57 Charging Current at rated Voltage per Km (Amps)
58 Short circuit Capacity of Conductor for one second at 90 deg. C prior to short circuit and 250 deg. C during short circuit (KA)
59 Circulating current under the BEB condition in
i. Lead sheath Amps
ii. Copper wire screen Amps
iii. In both Amps
when current in conductor is 500A
60 Circulating current in lead sheath armouring /Cu screen (when the conductor is carrying 31.5 KA S.C. current. KA
61 Combined short circuit capacity of Metallic sheath and screen for 1 Sec. at metallic sheath/screen temperature of 75 deg. C (conductor temperature 90 deg. C before S.C and 250 deg. C during S.C K.A:
62 Screening factor of cable for calculating interferance on control and communication cables :
63 Approximate value of attenuation of carrier current signals operating over a frequency range
i. 50 KC/s - dB/KM
ii. 100 KC/s - dB/KM
iii. 150 KC/s - dB/KM
iv. 200 KC/s - dB/KM
64 Shipping weight and size of cable drum
a) Size of Drum
i. Dia of Drum (M)
ii. Width of Drum (M)
iii. Gross Weight (Kgs)
iv. Legth of cable per Drum (M)
v. Weight of Cable (Kg/M)
vi. Weight of Copper (Main conductor excluding copper wire screen) (Kg/M)
vii. Weight of Lead (Kg/M)
viii. Weight of Copper (Copper wire screen excluding main conductor) (Kg/M)
65 Guaranteed Maximum life in years
DERATING FACTORS
1 VARIATION IN GROUND TEMPERATURE :
Ground Temperature (deg. C) : 15 20 25 30 35 40 45
2 VARIATION IN DEPTH OF LAYING :
Depth of Laying (Meters): 0.7 0.9 1.0 1.2 1.3 1.35 1.5 1.8
3 VARIATION IN THERMAL RESISTIVITY OF SOIL
Thermal Resistivity of Soil : (deg. C cm/watt) 100 120 150 200 250
4 VARIATION IN AIR TEMPERATURE :
Air Temperature (deg. C) : 25 30 35 40 45 50 55
5 VARIATION DISTANCE (MM) :
Axial Distance (mm) Between circuits 100 200 300 400 600 800
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
BIDDERS NAME AND ADDRESS ALONG WITH GSTIN NUMBER
110kV, 630Sq. mm Cable end Termination (Sealing End)
Sl.No. PARTICULARS Out door type In door type
1 Manufacturer's Name
2 Country of Manufacture
3 Class and Type
4 No. of years the design is in commercial use
5 Rated Voltage kV
6 Rated continuous current Amps.
7 Total Creepage distance (mm)
8 Maximum conductor size, Cu/Al, (sq.mm)
9 Details of terminal connector
10 Power frequency voltage 1 min. dry withstand test (kV rms)
11 Power frequency voltage wet with stand voltage KV Time : Sec. KV
12 Power frequency voltage 6 H Dry withstand voltage kV. Rms.
13 Flash over voltage Dry kV rms
14 Radio interference voltage (R.I.V) Test (Micro Volts)
15 Pratial discharge (corona) extinction test :
a) Extinction voltage kV rms
b) Minimum detector sensitivity PC
16 Impulse voltage Lightning voltage Dry with stand kV (Crest)
17 Direct voltage 15 Min. Dry with stand KV
18 Description of materials used in the terminations with electrical & mechanical particulars
19 Mounting Structure Details for termination
20 Electrical & Mechanical Particulars of
a) Heat Shrinkable Tubing
b) Heat Shrinkable Moulded parts
c) Heat Shrinkable adhesives / sealents
21 Type tested to (standard(s))
22 Other details
Please enclose complete Technical literature
The Bidder shall furnish a typical sketch of foundation for all types of foundation for all types of soil conditions with the Bid.
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR 110KV UG CABLES ACCESSORIES
110kV, 630Sq. mm NORMAL STRAIGHT JOINT (EARTHING TYPE) AND (STRAIGHT JOINT INSULATED)
Sl.No. PARTICULARS
1 Name of the manufacturer
2 Country of Manufacture
3 Type (Design) of joint
4 No. of years the design is in commercial use
5 Rated voltage KV
6 Rated Current Amps
7 Suitable for cable conductor Sq.mm
8 Connector, type, material
9 Partial discharge test 123 KV PC
10 A.C. withstand voltage KV
11 Impulse withstand voltage +ve and -ve 10 times kV KV
12 Load cycling 90° C +5° C (No. of cycles)
13 Load cycling as above under 1 M water at 160 KV (No. of cycles)
14 D.C. withstand 92 KV/230kV Hrs.
15 D.C. withstand voltage 15 Min.
16 Conductor thermal short circuit 250° C, 1 sec.
17 Shield thermal short cuircuit 250° C 1 Sec
18 Type tested to standard (s)
19 Maximum Conductor temperature in joint at rated current
20 Additional Information
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR 110KV UG CABLES
I. 110kV, 630Sq. mm CABLE COVERING PROTECTION UNITS / SURGE VOLTAGE LIMITERS :
1 Manufacturers Name
2 Country of manufacturer
3 Type of Material
4 Dimensions / weight mm/Kg
5 Rated voltage KV
6 Characteristics
7 Nominal discharge current KA
8 Power frequency withstand voltage KV
9 Power frequency spark over voltage KV
10 Reseal voltage
11 Pressure relief class
12 Impulse high current short duration discharge (AMPS)
13 Additional Requirements
II. Link Box Details & other Accessories:
Sl. No. Technical Particulars
1. a) Details of Link Box Materials
b) Type of application
d) Accessibility
f) At Circuit end
h) Special arrangement
2 Cross-bonding Link Box (CBB) Concentric bonding leads of suitable size to suit 3 Nos of Co-axial cable entries to CBB
3 Sheath Bonding Cables
4 Cross Bonding of cable sheath
5 No. of joints
6 Sheath standing voltage to earth for rated cable current
7 Sheath standing voltage to earth when an external 13-symmetrical through fault
8 Transposition of cables: No. of cable Transpositions and other details
III. List of consumables to be supplied by the Vendor
Sl. No. Description Quantity
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
BIDDERS NAME AND ADDRESS
Test Data on the 110kV XLPE cable and accessories
Sl.No. DETAILS REQUIRED STANDARDS AS PER WHICH TESTED DATA/TEST RESULTS TO BE FURNISHED
1 FOR IMPULSE TEST (HOT CONDITIONS):i. Number of samples tested.
ii. Cable cross section and insulation wall thickness
iii. Type of terminations
iv. Type of joints
v. Basic impulse level (wave form and peak voltage)
vi. Breakdown level
2 FOR POWER FREQUENCY TEST (COLD/HOT CONDITIONS):i. Number of samples tested
ii. Cable cross section and insulation wall thickness
iii. Type of terminations
iv. Type of joints
v. Voltage applied and duration
vi. Breakdown level
3 FOR LONG TERM TESTS:i. Length of the cable loop
ii. Cable cross section and insulation wall thickness
iii. Number and type of terminations & joints
iv. Installation conditions (air, buried)
v. Voltage applied and duration
vi. Conductor temperature at the end of heating cycle
vii. Breakdown conditions (if any)
NOTE: Details should be furnished for each and every sample for item (1) and (2) and for each and every long term test for item (3).
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
BIDDERS NAME AND ADDRESS DRS-1F
Test Data on the 110kV XLPE cable and accessories
Sl.No. DETAILS REQUIRED STANDARDS AS PER WHICH TESTED DATA/TEST RESULTS TO BE FURNISHED
1 FOR IMPULSE TEST (HOT CONDITIONS):i. Number of samples tested.
ii. Cable cross section and insulation wall thickness
iii. Type of terminations
iv. Type of joints
v. Basic impulse level (wave form and peak voltage)
vi. Breakdown level
2 FOR POWER FREQUENCY TEST (COLD/HOT CONDITIONS):i. Number of samples tested
ii. Cable cross section and insulation wall thickness
iii. Type of terminations
iv. Type of joints
v. Voltage applied and duration
vi. Breakdown level
3 FOR LONG TERM TESTS:i. Length of the cable loop
ii. Cable cross section and insulation wall thickness
iii. Number and type of terminations & joints
iv. Installation conditions (air, buried)
v. Voltage applied and duration
vi. Conductor temperature at the end of heating cycle
vii. Breakdown conditions (if any)
NOTE: Details should be furnished for each and every sample for item (1) and (2) and for each and every long term test for item (3).
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
SCHEDULE OF Tests for UG Cable and Cable Accessories
Sl.No. Details Required STANDARD AS PER WHICH TESTED DATA/TEST RESULTS TO BE FURNISHED
D Special Tests(Specified)
E Other tests at works/site recommended by the tenderer
II Total cost towards inspection and tests(special routine and acceptence tests)included in the price bid(if changeable to owner)(Break-up details to be furnished separately)
Note:Details have to be furnished for tests on cables as well as accessories,each separately.
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
BIDDERS NAME AND ADDRESS
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR UNARMOURED U.G FIBRE OPTIC CABLE
Sl.No. Description
1 Manufacturer’s Name
2 Country of Manufacture
3 Class and Type
4 No. of years the design is in commercial use
5 Type of Material
6 Dimensions / Weight mm/Kg
7 Fibre Description:
8 Mode Field Diameter:
9 Cladding Diameter:
10 Mode Field concentricity error:
11 Cladding non-circularity
12 Cable cut off wavelength
13 1550 loss performance
14 Proof Test Level
15 Attenuation coefficient
19 Giga Bit Ethernet Distance
20 10 Giga Bit Ethernet Distance
21 Connector loss
23 Outer jacket
25 Chromatic Dispersion: Maximum:
27 Zero dispersion wavelength:
29 Zero Dispersion Slope
30 Polarization mode dispersion coefficient
31 Blend performance
32 List of consumables to be supplied by the vendor
33 Type Tested to Standard (S)
34 Colour Coding & Fibre Identification:
35 Strength Members
36 Filling Compound:
37 The Sheath /Inner Jacket
38 The Outer Jacket /Termite Protection
40 Mechanical parameters & Tests
Tensile strength
Crush test (Compressive Strength):
Cable Bending test (Repeated bending
41 Other complete Technical Details
42 Additional Information
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR RELAY & PROTECTION PANELS
(Bidder should indicate the guaranteed technical data of all equipments / materials for each type of rating separately)
Relay & Protection Panels
Sl. No. Description
I Description, Construction & formation details :
1 Make and Type reference of manufacturer
i) type of construction.(duplex or simplex)
ii) type of scheme ( numerical type or static type)
b) for power transformer
3 Thickness of sheet steel (mm):
i. Door, Top and Bottom of panel
4 Tentative overall dimensions (L*B *H) (mm) of each panel
5 Dead weight of each panel (Kgs)
6 Approximate weight of each panel with all components (Kgs)
7 Details of packing for transport
8 Overall dimensions of transport package (L*B*H) (mm)
9 Approximate gross weight of transport package (Kgs)
10 Exterior paint film thickness (microns) and paint colour
11 Interior paint film thickness (microns) and paint colour
12 Cubicle Lighting : Volts, wattage, Type of holder and fitting whether provided with door control switch or not.
13 Safety earthing :
a. Material of conductor
b. Size (W*T) (mm)
c. Surface treatment and finish of conductor.
d. Type of end connection
14 Panel front/rear component identity board
c. Size of lettering and colour
d. Method of fixing
15 Panel wiring :
a. Type and material of wire conductors, insulation and voltage grade.
b. Conductor cross sectional area or strands/gauge of wire and colour scheme adopted for :
i. VT secondary circuits and annunciation circuit.
ii. Other Circuits.
c. Type of wire termination
16 Mimic bus details :
a. Type painted / strip fixed
c. Whether colour scheme specified will be followed
d. If not specify deviations.
II. TERMINAL BLOCKS AND CONNECTORS (USED FOR PANEL WIRING)
1 Make and Type reference of manufacturer
2 Insulation and voltage grade
3 Constructional details
4 Current rating of studs, size and material
5 Whether shrouding provided or not
6 Whether space terminals provided or not
7 Literature enclosed.
III. INDICATING LAMPS :
1 Wattage and voltage of lamp
2 Size of lens and material thereof
3 Type of lamp holder
4 Whether provided with series resistor? If yes, specify Ohmic value power loss
IV FUSE HOLDERS AND FUSES :
1 Make and Type reference of manufacturer
2 Insulation and voltage grade
3 Type of Insulation material
4 Type of fuses
5 Rating of fuses provided for different circuits
6 Literature enclosed.
VI. SELECTOR SWITCHES :
1 Make and Type reference of manufacturer
2 Type of handle / Switch
3 Mounting details
4 Number of positions
5 Number of contracts available in each position.
6 Making capacity of contacts
7 Breaking capacity of contacts
8 Whether locking arrangement is available.
9 Whether detailed literature and drawings encolsed. (YES/NO)
VII. PUSH BUTTONS :
1 Make and Type reference of manufacturer
2 Mounting details
3 Type of contact
4 Current and voltage rating
5 No. of contacts
6 Whether shrouding provided to prevent inadvertent operation (YES/NO)
7 Whether provided with integral engraved inscription plates (YES/NO)
VIII AUXILIARY CT's VT'S :
1 Make and Type reference of manufacture
b. Ratios available
d. Standard to which it conforms
e. Accuracy class
f. Short time current / voltage rating
g. Temperature rise
h. One minute power frequency withstand voltage
j. Mounting dimensional details
k. Panel in which to be provided with quantity thereof and connected ratio
3 For CT's only
a. Knee point voltage (KPV) (Volts)
b. Excitation current at KPV and 50% KPV (ma)
c. Internal impedance of primary and secondary windings in ohms
4 Literature enclosed.
IX. SPACE HEATERS :
1 Make and Type reference of manufacture
2 Type of space heater (Tubular / strip type)
3 Rating Wattage
4 Whether thermostat provided (YES/NO)
II INSTRUMENT TEST TERMINAL BLOCKS :
1 Make and Type reference of manufacturer
2 Insulation class and rating
3 Size and mounting details
4 Type of CT terminal shorting mechanism (LINK / SCREW)
5 Type of VT terminal Isolating Mechanism
6 Whether detailed literatures enclosed. (YES/NO)
C GENERAL PROTECTION RELAYS :
I The tenderer shall furnish guaranteed Technical particulars for all types of meters offered, in the following proforma (separate sheet shall be enclosed for each type of relay :)
1 Manufacturer's name or trade marks
2 Type designation
3 Size and mounting details (whether in draw out case)
4 Rated Values of both input and auxiliary energizing quantities
5 Values of the limits of the operative range(s) of the auxiliary energising quantity (ies)
6 Contacts data, Number and rating of main and auxiliary contacts
7 Rated value or setting range of the characteristic quantities and or angle
8 Limiting short-time thermal withstand values
9 Limiting dynamic values.
10 i. Burden data ( in case of poly input relays - data shall be furnished for appropriate set of input terminals).
a. At highest tap - AC current / voltage coil
b. At lowest tap - AC current / voltage (coil)
ii. DC power consumption.
11 Impulse and dielectric test voltage(s)
12 Details of accessories (If essential to the relay performance)
13 Details of accessories (Optional items)
14 Whether provided with seal in trip contacts
15 a. Type of operating characteristics
b. Accuracy of operating characteristics, operating time with details
16 H.F. disturbance test voltage (s)
17 Whether literature enclosed
18 Type of relay flag indicator and rating of target coil
II In addition to the above details, the following details shall also be furnished for relays specified below :
1 DOCR / DEFR :
a. Directional sensitivity
b. Minimum voltage at which the directional units operate
c. Characteristic angle
2 OVER FLUXING RELAY :
a. Whether provided with timer if so time setting available for Alarm and delayed trip.
3 Distance Protection Scheme for 220KV / 110KV / 66KV Lines:
A Type of distance measuring element
a. Starting unit
i. Type of scheme
b, No. of measuring element or comparator with details
c. Setting range of the distance measurement
d. No. of zones
i. Overall range for all zones.
ii. Reach setting range at rated current.
Zone - 1 (forward) - ohms
Zone - 2 (forward) - ohms
Zone - 3 (forward) - ohms
Off set zone 3 reverse - ohms
Zone extension (if any)
e. Characteristic of each zone
Phase fault unit
Earth fault unit
Phase fault unit
Earth fault unit
Phase fault unit
Earth fault unit
Zone - 3 off set
Zone -1 in ohms
1. Reach of the relay along with characteristic angle at rated current and voltage
2. Reach of the relay in resistive direction at rated current & voltage
3. Reach in reactive direction at rated current & voltage
Zone - 2 in ohms
1. Reach of the relay along with characteristic angle at rated current and voltage
2. Reach of the relay in resistive direction at rated current & voltage
3. Reach in reactive direction at rated current & voltage
Zone - 3 in ohms
1. Reach of the relay along with characteristic angle at rated current and voltage
2. Reach of the relay in resistive direction at rated current & voltage
3. Reach in reactive direction at rated current & voltage
Zone - 3 in Reverse ohms
1. Reach of the relay along with characteristic angle at rated current and voltage
2. Reach of the relay in resistive direction at rated current & voltage
3. Reach in reactive direction at rated current & voltage
f. Power swing blocking characteristic setting
i. Forward reach
ii. Reverse reach
g. Setting range of residual compensation
h. Setting range of mutual compensation
i. (i) Operating time
(ii) Time setting range
Power swing blocking
Zone - 1 (reach)
Zone - 2 (reach)
Zone - 3 (forward reach)
K. Polarising scheme
B. Additional featues provided :
a. Fault locator
b. Carrier aided tripping scheme
c. Power swing blocking
d. Broken conductor detection
e. Synchronous check
f. Weakend infeed
g. Switch on to fault
h. Fuse failure supervision
C. Facilities available for Fault Locator
a. Name and type reference of manufacturer
b. Rating and setting available
c. Rated V A burden
d. Power consumption voltage and current element
e. Memory capacity with details
f. Triggering method
h. Method of accuracy
D Auto Recloser:
a) Reclosing facilities available b) Single phase/three phase dead time range. c) Reclaim time range d) No. of modes selectable by selection switch e) Provision of Check synchronizing features and its time setting, range phase angle setting, voltage difference setting. f) Provision of deadline charging set range of voltage. g) Lock out facility.
E Disturbance Recorder:
a) No. of event channels b) No. of analog signals. c) Sampling rate d) Recording Band width e) Over current triggering – range. f) Under current triggering – range. g) Over voltage triggering – range. h) Pre fault time – range. i) Post fault time – range. j) Limit time – range. k) No. of recorded disturbances. l) Total recording time with 8 Analog and 16 event channels recorder. m) Voltage channels – details. n) Period of built in calendar. o) Current channels – details,
F EVENT RECORDER
a) Time tagging resolution. b) Events capacity i) Max. NO. of events per disturbance report. ii) Max. No. of disturbance reports
c) Time tagging error with synchronization. i) Once in One second ii) Once in ten seconds. iii) Once in sixty seconds
d) Timer tagging error without synchronization.
4 Restricted Earth fault Relay.
a) Manufacturer Type P designation
b) Operating time 2 x setting
5 Differential protection scheme :
a. No. of restraining coils and operating coils.
b. Harmonic restraints provided with details
c. Rated VA Burden and power consumption of
i. Restraining coil
ii. Operating coil
d. Type of slope setting :
If variable, range of slope setting through fault current stability. Maximum & minimum range of HV / MV / LV current ratio over which the relay can be used.
e. Whether provided with switching inrush current restraint, if so type.
6 Trip circuit supervision relay:
a) Name of manufacturer.
b) Type & Designation.
c) Whether preclosing & post closing supervision provided.
7 High speed trip relay
a) Name of manufacturer.
b) Type & Designation.
c) Contact rating.
Current rating-
i) Continuous rating
ii) Rating for 5 secs.
d) Break Resistive load inductive load (with L/R = 40 msec.
e) Operating time at rated voltage (max).
f) Resetting time.
g) Whether supervisory relay included.
8 Local breaker back up protection.
a) Name of manufacturer.
b) Type & Designation.
c) Operating time
d) Resetting time
e) Setting range
9 Bus bar protection
a) Name of manufacturer.
b) Type & Designation.
c) Type of relay (numerical)
d) Principle of operation (biased/low impedance)
e) Operating time
f) Resetting time
g) Setting range.
h) Whether will it cause tripping for the differential current below the load current of heavily loaded feeder (Bidder shall submit application check for the same).
III The tenderer shall confirm whether the following details will be furnished at the time of approval of drawings:
a. Identification and location of removable parts.
b. Data of permit suitable connection of the relay (including the polarity)
c. Data concerning the earthing of metallic part
d. To indicate parts of modules which should not be replaced without observing precaution prescribed by the manufacturer.
GUARANTEED TECHNICAL PARTICULARS FOR ELECTRONIC TRIVECTOR METERS
Sl. No. PARTICULARS
1 Type of Meter
2 Class of Accuracy
3 Standard to which the meter conforms
4 Current rating for which accuracy is guaranteed for
a. Basic Current (ib)
b. Continuous Current overloading capability
c. Short time over current
d. Minimum Starting Current
5 a)Voltage rating for which accuracy is guaranteed for
b)Over voltage withstand capacity - continuous
c)Voltage Range
6 Other Parameters for which accuracy is guaranteed
a. Reference Temperature
b. Standard Reference Frequency (Hz)
c. Accuracy Guaranteed for
d. Frequency Range
e, For single Phase Loads / In- put
f. For two Phase Loads / In - put
g. For In-put / Loads without neutral in -puts unbalanced Voltages
h. Temperature Range
7 Insulation Resistance
8 Sampling Plan for measurement of Voltage, Current and Frequency
9 Power Loss in each Current circuit at Basic Current in VA & WATT
10 Power Loss in each Voltage circuit at reference in VA & WATT
11 Display device (Hardware details)
a. Type of Display i.e. LCD
b. Character size of display digits
c. No. of Display digits used
2. For parameter identification
d. Life of display unit (Guaranteed)
e. Method adopted for digit over flow
12 Display details (Software)
13 a. Non-volatile memory retention time in absence of power
b. Non - volatile memory capacity in KB.
c. RAM Capacity
d. Maximum number of Parameters which can be stored in non-volatile Memory at each half an hour intervals for Six Months.
14 Maximum demand
a. Parameters that can be dynamically selected
b. Integration Period Range
c. Provision for Automatic Rest
d. Type of MD Computation
15 Communication Inter-phase available
- for calibration
- for data transfer
16 Electro magnetic interference / Electro magnetic comparativity level
17 Mounting arrangement
18 Meter sealing arrangement
b. Meter terminal block
c. MD reset bush button
d. Battery unit
19 Degree of protection against moisture etc.,
20 a. Provision for real time clock
b. Real time clock accuracy
c. Life of real time clock (Guaranteed)
21 Power Supply backup
22 Measuring principle employed for
d. Maximum demand parameters
NOTE 1. Measuring principle adopted for each of the items above should be specified.
2. Measurement logic employed in case of Harmonics and contents up to which meter recognizes for measurement shall be furnished.
23 Abnormal conditions that will be identified with limiting values
24 Guarantee period offered for
a. Performance and accuracy
b. Components not covered under guarantee
25 Micro processor
a. Address in bits
b. Sampling rate
26 Compatibility of the software for the following
a. For generation of consumer bill directly with the existing KPTCL billing software
b. Compatibility of software provided for MRI, down loading from earlier version already supplied to KPTCL
c. Compatibility of software for generation of report for earlier versions
27 Additional features available
28 Agreement to furnish protocol details for development of required software through third party
29 Platform on which the meter communicates
30 Levels of security
a. For changing real time
b. Fir changing display parameters
c. For changing Load survey parameters
d. For changing TOD Registers, clock setting
e. Measuring principle, computation
31 Specification of reference standard offered
32 Specification of Laptop Computer offered
33 Specification of MRI kit offered
34 Specification of equipment offered for checking communication capability through RS232/RS485 port
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
GUARANTEED TECHNICAL PARTICULARS FOR CIRCUIT BREAKERS
(Bidder is to indicate technical data for each type of rating)
Circuit Breaker Rating 145kV 72.5kV 33kV
a. Name of the Manufacturer
b. Country of Manufacture
c. Type of Circuit Breaker
d. Manufacturer's type designation
e. Standard Applicable
f. Rated Voltage (kV ms)
g. Rated Current :
i. Under normal condition (A)
ii. Under site conditions (A)
h. Rated frequency (Hz)
i. Number of poles
j. Whether 3 pole or single pole unit
k. Whether all the 3 poles ganged electrically or mechanically
l. Whether dead tank or live tank design
m. Type of installation
n. No. of break per pole
o. Latching Current (kA)
2 Guaranteed Ratings
a. Rated short circuit breaking current
i. Symmetrical component at highest system voltage (kA)
ii. DC Component (%)
iii. Asymmetrical breaking current at highest system voltage (kA)
b. Rated Making Capacity
i. At higher rated voltage (kAp)
ii. At lower rated voltage (kAp)
c. i. Maximum Total break time under any duty condition for any current up to rated breaking current with limiting conditions of voltage and pressure (ms)
ii. Rated breaking time (ms)
d. Closing time (ms)
e. Minimum opening time under any condition with limiting voltage and pressure (ms)
f. Maximum opening time under any condition with limiting voltage and pressure (ms)
g. Maximum close open time under any condition with limiting voltage and pressure (ms)
h. First pole to clear rating
i. Short time current rating (kA) for 1 Sec.
j. Rated operating duty
k. Maximum breaking capacity under kilometric faults and rated TRV characteristic (kAp)
l. Maximum breaking capacity under phase opposition (kAp)
m. Maximum line charging breaking current with temporary over voltage up to 1.4 p.u. (A)
n. Maximum over voltage (p.u.) on switching transformer on no load and corresponding charging current
o. Maximum period between closing of first contact & last contact in a pole (ms)
p. Maximum pole discrepancy (ms)
q. Maximum arc duration and corresponding current under lockout pressure.
r. Small fault current breaking capacity (kAp)
s. Pre-insertion resistor (if applicable)
i. Value / pole (Ohms) with tolerance
ii. Minimum and Maximum duration of insertion per pole (ms)
iii.Thermal rating for the c-1m-o-co-2m-c-1m-o-co for terminal fault considering maximum resistance and time setting.
iv. Thermal rating for the same duty as (iii) above for reclosing against trapped charges.
t. Maximum temperature rise for main contacts over design ambient temperature of 50oC
u. Rated voltage & pick up range for trip coil (V)
v. Rated voltage & pick up range for closing coil (V)
w. Rated pressure and limits of pressure of operating mechanism
x. Rated pressure and limits of pressure of extinguishing medium
y. Minimum dead time for
i. Three phase reclosing (ms)
ii. Single phase reclosing (ms)
z. Data of restriking voltage
i. Amplitude factor
ii. Phase factor
iii. Natural frequency
iv. Rate of rise of restriking voltage
3 Dielectric withstand of complete breaker
a. One minute dry & wet power frequency withstand voltage
i. Between live terminal and ground (kV rms)
ii. Between terminals with breaker contacts open (kV ms)
b. 1.2/50 micro impulse withstand test voltage
i. Between live terminals and ground (kVp)
ii. Between terminals with breaker contacts open (kVp)
c. Corona extinction voltage (kV rms)
d. Maximum radio interference voltage (micro V) at 1.1 Ur/v3
e. Total creepage distance
i. To ground (mm)
ii. Between terminals (mm)
4 Operating Mechanism
a. Type of operating mechanism for
b. Manufacturer's type designation
c. Normal power consumption (W) at rated voltage
ii. Closing coil
4.1 Pneumatic operating mechanism
a. Rated operating pressure (kg/sq.cm)
b. Range of pressure for (kg/sq.cm)
c. Air Consumption at rated pressure for
i. Closing (m3)
ii. Opening (m3)
iii. Close-open (m3)
d. Pressure drop/meter length of piping
e. Number and Capacity (m3) of breaker local air storage receivers
f. No. of close operations for which sufficient air is available in local receiver
g. Capacity of compressor (m3/hr) and working pressure (kg/cm2)
h. Maximum time for which compressor can operate continuously (min)
i. Time to fill
i. Air receiver after one CO operation (min)
ii. For making up of losses occurring in hours (min)
j. Pressure at which compressor
i. Starts (kg/cm2)
ii. Stops (kg/cm2)
k. Material of compressed air piping
l. Inner & outer dia of main piping (mm)
m. Whether interpole piping included in scope of supply
n. Manufacturer's name for
ii. Air receiver
iii. Pressure reducer
iv. Stop valves
v. Drain valves
o. Safety valve
i. Low pressure stage blow off at (kg/cm2)
ii. Intermediate stage blow off at (kg/cm2)
iii. High pressure stage blow off at (kg/cm2)
p. Safety valve opens at (kg/cm2)
q. No.of stored CO operation in breaker air receiver
r. Alarm switch closes on air receiver at (kg/cm2)
s. Lockout pressure (kg/cm2)
iii. Auto reclose
4.2 Hydraulic operating mechanism
a. Rated pressure of oil in operating cylinder (Kg/cm2)
b. Limits for pressure (Kg/cm2)
c. Quantity of oil (liter)
d. Details of arrangements to prevent change of position of breaker in the event of loss of hydraulic pressure.
e. Details of monitoring arrangement for hydraulic pressure.
f. No. of close -open operations possible after loss of AC supply to drive motor.
g. Details of hand pump set provided for emergency operation.
h. Pressure drop starting from lowest pressure at which motor starts for
i. C – operation
ii. O - operation
iii. CO - operation
iv. O - CO - operation
v. 2 - CO - operation
i. Time required to make up pressure upto loss of nitrogen pressure after
i. C – operation
ii. O - operation
iii. CO - operation
iv. O - CO - operation
v. 2 - CO - operation
4.3 Spring charged mechanism
a. Number of close open operations possible after failure of AC supply to motor.
b. Time required for motor to charge the closing spring (min).
c. Whether indication of spring charged condition provided in central control cabinet.
5 Type of Breakers
5.1 SF6 Circuit Breakers :
a. Quantity of SF6 per pole (m3) at rated pressure.
b. Guaranteed maximum leakage rate per year.
c. Rated pressure of SF6 in operating chamber (kg/cm2).
d. Limits of pressure at which breaker operate correctly (kg/cm2)
e. Standard to which SF6 gas complies.
f. Whether 20% spare SF6 gas. Stored in unused gas cylinders, included in proposal.
g. Capacity & filling ratio of containers in which SF6 gas would be shipped (m3) and the corresponding pressure (kg/cm2)
h. Whether breakers are dispatched filled with SF6 or required to be filled at site.
i. Type and make of SF6 pipe coupling used.
j. Type and make of mandatory maintenance equipment.
i. SF6 gas filling and evacuation trolley (portable)
ii. SF6 gas drying, filling, evacuating equipment and its capacity.
iii. Operating analyzer Type and make
iv. SF6 gas leak detector
k. Parameters of SF6 gas for initial filling and satisfactory operation.
ii. Dielectric strength kV/mm
iii. Acidity (ppm)
iv. Water content (ppm)
v. Oil content (ppm)
vi. Condensation temperature (oC)
vii. Resistivity (Ohm-cm)
l. Whether details of SF6 gas viz test methods, handling etc. enclosed.
m. Type and material of gasket used to ensure gas tight joints for
i. Metal to metal joints
ii. Metal to porcelain joints
n. Method of housing SF6 gas compressors and equipment
i. At Circuit Breaker
ii. In control cubicle
o. Type and make of
ii. Pressure gauge
p. Densimeter Settings
q. Minimum time interval between each make/break operation (ms)
a. Whether OGA drawing enclosed
b. Weight of complete 3 phase breaker for foundation design (kg)
c. Weight of heaviest part of breaker (kg)
d. Impact loading for foundation design
e. Seismic level for which breaker is designed
f. Minimum safety clearance from earthed objects
g. Noise level in (dB) at base of the breaker
h. Minimum clearance in air
i. Between live parts (mm)
ii. Live parts to earth (mm)
iii. Live parts to ground level (mm)
6 Constructional Details
a. Whether arcing contacts provided
b. Type and material of main contacts and arcing contacts
c. Contact pressure on main contacts (kg/cm2)
d. Contact separation in arcing position (mm)
e. Contact separation in open position (mm)
i. Main contacts
ii. PIR contacts
f. Whether pressure relief device for each of the gas chamber of SF6 CB provided
g. Rate of contact travel.
i. Opening (m/sec)
ii. Closing (m/sec)
h. Whether the making & breaking contacts are hermetically sealed
i. Type and capacity of device used to obtain uniform voltage distribution between breaks
j. Over voltage withstand capability of grading components (kV rms)
k. Number of auxiliary contacts per pole provided for Owner's use
l. Rated voltage of auxiliary contacts (V)
m. Current rating of auxiliary contacts
i. Continuous (A)
ii. DC breaking with 20 ms time constant (A)
n. Whether auxiliary contacts silver plated
o. Whether support structure included in supply
p. Height of support structure
q. Material of support structure
r. Standard to which the design of support structure conform
s. Whether foundation bolts for breakers and cabinets included in scope of supply
7 Detailed Literature
a. Whether the following are enclosed.
i. Type test reports as per IEC-56
ii. Factory test report and/or field test report incase of reactor switching duty
iii. Details of operating mechanism
iv. Drawing of breaker of support structure.
v. Calculations for compressed air plant sizing
vi. Details of SF6 gas filling, evacuating and testing plant
vii. Details of SF6 gas leak detector
viii. Precautions in use of SF6 gas
ix. Leaflets & literature bringing out salient features of equipment offered.
x. Schematic diagrams of switching mechanism for closing resistor showing the duration of insertion along with calculation for thermal rating of closing resistors.
xi. Whether drawings showing contacts in close, arc initiation, full arcing, arc extinction and open position enclosed
xii. Method of checking of Voltage distribution devices at site enclosed
xiii. Details along with a complete catalogue of operation analyzer enclosed
xiv. Data on capabilities of circuit breaker in terms of time and number of operations at duties ranging from 100% fault currents to load currents of the lowest possible value without requiring any maintenance or checks.
xv. Effects of non simultaneity between contacts within a pole or between poles and also show how it is covered in the guaranteed rated break time
xvi. Details and type of filters used in interruptor assembly and also the operating experience with such filters
xvii. Curves supported by test data indicating the opening time under close open operation with combined variation of trip coil voltage and pneumatic/hydraulic pressure.
xviii. All duty requirements specified along with adequate test reports.
CIRCUIT BREAKER - CONTROL CABINETS :
1 Manufacturer's Name
2 Indoor/Outdoor application
3 Design ambient air temperature (oC)
4 Standards applicable
5 Thickness of sheet steel (mm) and whether cold rolled or hot rolled
6 Degree of protection provided
7 Bill of material for all the equipment mounted on control cabinet giving the following details:
a. Make and type
b. Applicable Standard
c. Voltage rating
d. Current rating
e. Duty class. If applicable
f. Manufacturer's catalogue No.
g. Total heat load of cabinet (for purpose of ventilation requirement)
8 Colour of finish paint IS : 5
9 Control Wiring
a. Size of conductor
i. For CT circuits
ii. For other circuits
b. Conductor Solid/Stranded
c. Number of Strands/conductor
10 Terminal Blocks
b. Current rating
i. Power terminals (A)
ii. Other terminals (A)
11 Space Heater Rating at 240 V AC
12 Control cabinet drawing showing the following:
a. Outline dimensions, floor opening, floor/ wall/ pedestal fixing arrangements, weights etc.
b. Front view, inside view showing the mounting arrangement of various equipment.
13 Schematic/wiring diagram of control cabinet enclosed
14 Interconnection drawing showing cable, connections to the control cabinet enclosed
15 Type test report to verify degree of protection enclosed
16 Details of terminal rows:
i. Whether arranged vartical or horizontal
ii. Clearance from adjacent components.
iii. Distance between rows.
iv. Whether transparent protection cover provided.
CIRCUIT BREAKERS - TERMINAL CLAMPS AND CONNECTORS
1 Manufacturer's Name
2 Applicable Standards
4 Material of connector
b. Bolts & Nuts
c. Spring Washers
5 Rated Current
6 a. Rated terminal load (kg)
b. Factory of Safety
7 Minimum thickness of any part (mm)
8 Weight of clamp complete with hardware (kg)
9 Type test reports as per IS enclosed
10 OGA drawing enclosed.
CIRCUIT BREAKERS - BUSHING/SUPPORT INSULATOR :
1 Manufacturer's Name
3 Applicable Standards
ii. Diameter (Top)
iii. Diameter (Bottom)
5 Total creepage distance (mm)
6 Rated voltage (kV)
7 Power frequency withstand voltage for 1 minute (kVrms) dry and wet
8 1.2/50 micro sec. impulse withstand voltage (kVp)
9 250/2500 micro sec. switching impulse withstand voltage (kV p) dry and wet
10 Corona Extinction voltage (k V)
12 Maximum allowable span (mm)
13 Cantilever Strength (kg)
14 OGA drawing enclosed.
1 Manufacturer's Name & address
2 Equipment driven by motor
4 Country of origin
7 Type of enclosure and method of cooling
8 Applicable standard to which motor generally conforms
9 Type of mounting
10 Direction of rotation as viewed from non-driving end
11 Standard continuous rating at 40 deg. C ambient temperature as per Indian Standard (KW)
12 Derated rating for specified Normal condition ie., 50 deg. C ambient temperature (KW)
13 Rated Voltage (V)
14 Rated speed at rated voltage and frequency(rpm)
15 Full load current at rated voltage and frequency (A)
16 Power factor at rated load
17 Efficiency of motor at rated voltage and frequency (with out any tolerance) at
i. Density duty point(%)
ii. 100% of full load (%)
18 Starting current (Amps) at
i. 100% Voltage
ii. 85% Voltage
a) Starting (Kg-Metre)
b) Pull up (Kg-Metre)
c) Pull Out(Kg-Metre)
20 Stator winding Insulation
i) Class & type
ii) Tropicalised
iii) Temperature rise over specified ambient of 50 deg. C ( deg. C)
iv) Method of temperature measurement
21 Stator winding connector
22 Number of star terminals brought out
23 Type of terminal box for stator leads
24 Bearing type
ii. Non Driving End
25 Type of Construction of Rotor
26 Weight of Motor
i. Stator (Kg.)
ii. Rotor (Kg.)
iii. Total Weight (Kg.)
27 Type Test Report Enclosed
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEEED TECHNICAL PARTICULARS FOR LATTICE TYPE MOUNTING STRUCTURES
(Bidder should indicate the guaranteed technical data of all equipments / materials for each type of rating separately)
Mounting Structures
1 Standars adopted
i. Properties of section
ii. Bolts & Nuts
iii. Galvanising
2 Minimum Sheared edge distance (mm)
3 Minimum Rolled edge distance (mm)
4 Quality of Zinc used for galvanising
5 Maximum percentage increase in structure weight due for galvanisation
6 Quantity of Zinc required for galvanisation per MT of structurals
7 Size of bolts and nuts (including foundation bolts & nuts for support structure)
iii. Foundation Bolts
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
ISOLATORS AND TERMINAL CONNECTORS
(Bidder to indicate technical data for each type of rating separately)
Isolators and Terminal connectors ratings 110kV 110kV 66kV 66kV 33kV 11KV
a. Name of the Manufacturer
b. Country of Manufacture
c. Manufacturer's type designation
d. Standard applicable for isolators and earthing switches
e. Rated Voltage Ur (kV)
f. Rated Current Under site conditions (A) at 50oC ambient
g. Rated frequency (Hz)
h. Number of poles
i. Whether all 3 poles are ganged mechanically
j. Pole to pole spacing
k. Type of installation
2 Guaranteed Ratings
a. Rated short time current of isolator for Is (kA) and dynamic current (kAp)
b. Opening time of isolator and earth switch (s)
c. Closing time of isolator and earth switch (s)
d. Temperature rise over 50oC ambient temperature corresponding to maximum continuous current (oC)
3 Dielectric withstand capacity of completely assembled isolator/isolator and earth switch
a. One minute dry power freq. Withstand test voltage (kV ms)
i. Against ground (kV rms)
ii. Across isolating distance (kV rms)
b. 1.2/50 micros a impulse withstand test voltage
i. Against ground (kVp)
ii. Across isolating distance (k Vp)
c. 250/2500 micros switching surge withstand test voltage (dry & wet)
i. Against ground (kVp)
ii. Across isolating distance (kVp)
d. Corona extinction voltage (k V rms)
e. Radio interference level at 1.1 Ur/ /3 (in micro volts) at 1.0 MHz
f. Total creepage distance to ground (mm)
4 Operating Mechanism
A. For Main Blades
a. Type of motor operating / manually driven mechanism
b. Manufacturer's Type / designation
c. Rated torque of the mechanism
d. Type and rating of motor
B. For Earth Switches
a. Type of motor operating / manually driven mechanism
b. Manufacturer's type designation
c. Rate troque of the mechanism
d. Type and rating of motor
4.1 Interlocks:
a. Whether mechanical/constructional interlock between isolator and earth switch provided.
b. Details of electrical interlock enclosed for
ii. Earth Switch
c. Arrangement provided to prevent electrical or manual operation unless interlock conditions are satisfied whether interlock coil is continuously rated
d. Rated DC control voltage and variation allowed
e. Power consumption (W)
a. Rated DC control voltage (V)
b. Limits of voltage
c. Power consumption of control coils (W)
5 Constructional Features
a. Minimum clearance in air
i. Between phases (mm)
ii. Between live parts to earth (mm)
iii. Distance between terminals of same phase (mm)
b. Whether position of earth switch can be interchanged at site to either side of pole
c. Minimum clearance between live part and earth switch blade throughout the entire operational are of earth switch (mm)
d. Terminal pad details
i. Diameter & length
ii. Material of pad
e. Insulator data
iii. No. of insulator stacks / phase
iv. No. of insulators/stack
f. Main Contracts
i. Type of contacts
ii. Contract area (cm2)
iii. Material of contacts
iv. Contact pressure (kg / cm2)
v. Maximum current density under normal current carrying capacity (A/cm2)
vi. Thickness of silver plating
g. Number of auxiliary contacts on isolator/pole for owner's use
h. Number of auxiliary contacts on earth switch pole for Owner's use
i. Auxiliary contacts
i. Rated voltage (V)
ii. Rated Continuous current (A)
iii. Rated Dc breaking current with 20 ms time constant (A)
j. Mounting dimenstions of isolators
i. Distance between supports
ii. Top dimensions of support
k. Height from mounting plane to top of terminal stud
l. Whether cable glands required included in the scope for inter pole cabling to be done by the Owner.
Whether the following are enclosed :
a. Type test reports as per IEC 129
b. OGA drawings for isolator with & without earth switches
c. Operation manual for isolators
d. Details of motor operating / manually driven mechanism
e. Recommended drawing for mounting details for isolator and drives.
f. Leaflets & literature bringing out salient features of equipment offered.
g. Details of constructional interlock
CONTROL CABINETS
1 Manufacturer's Name
2 Indoor / Outdoor application
3 Design ambient air temperature (oC)
4 Standards applicable
5 Thickness of sheet steel (mm) and whether cold rolled or hot rolled
6 Degree of protection provided
7 Bill of material for all the equipment mounted on control cabinet giving the following details :
a. Make and Type
b. Applicable Standard
c. Voltage rating
d. Current rating
e. Duty class, if applicable
f. Manufacturer's catalogue No.
g. Total heat load of cabinet (for purpose of ventilation requirement)
8 Colour of finish paint IS : 5
9 Control Wiring
a. Size of conductor
i. For CT circuits
ii. For other circuits
b. Conductor Solid / Stranded
c. Number of Stranded/conductor
10 Terminal Blocks
b. Current rating
i. Power terminals (A)
ii. Other terminals (A)
11 Space Heater Rating at 240 V DC
12 Control cabinet drawing showing the following
a. Outline dimensions, floor opening, floor/wall/pedestal fixing arrangements weights etc.,
c. Front view, inside view showing the mounting arrangement of various equipment
13 Schematic / wiring diagram of control cabinet enclosed
14 Interconnection drawing showing Owner's external cable, connections to the control cabinet enclosed Isolators & Terminal Connectors
15 Type test report to verify degree of protection enclosed.
16 Details of terminal rows
i. Whether arranged vertical or horizontal
ii. Clearance from adjacent components
iii. Distance between rows
iv. Whether transparent protection cover provided.
16 TERMINAL CLAMPS AND CONNECTORS
1. Manufacturer's Name
2. Applicable Standards
4. Material of connector
b. Bolts & Nuts
c. Spring washers
5. Rated Current
6. a. Rated terminal load (kg)
b. Factor of safety
7. Minimum thickness of any part (mm)
8. Weight of clamp complete with hardware (kg)
9. Type test reports as per IS enclosed.
10. OGA drawing enclosed
BUSHING / SUPPORT INSULATOR
1 Manufacturer's Name
2 Type test report to verify degree of protection enclosed.
3 Applicable Standards
i. Diameter (Top)
ii. Diameter (Bottom)
5 Total Creepage distance (mm)
6 Rated voltage (kV)
7 Power frequency withstand voltage for 1 min. (k V rms) dry and wet
8 1.2/50 micro sec. Impulse withstand voltage (kVp)
9 250/2500 micro sec. Switching impulse withstand voltage (kVp) dry and wet
10 Corona Extinction voltage (k V)
12 Max. allowable span (mm)
13 Cantilever Strengthh (kg)
14 OGA drawing enclosed
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR RIGID BUS & ACCESSORIES
(Bidder should indicate the guarantteed technical data of all equipments/materials for each type of rating separately)
1.00 Tubular Bus Conductor
1.01 manufacturers Name and address
1.01 Applicable Standards
1.03 Size of tubular Bus Conductor (mm)
a Standard pipe size (IPS)(mm)
b Outside diameter (mm)
c Tolerance on outside diameter
d Thickness (mm)
e Tolerance on Thickness
1.04 Moment of Interia (mm4)
1.05 Section Mudulus (mm3)
1.06 Radius of gyration (mm)
1.07 Natural frequency of vibration for the Site condition (c/s)
1.08 Reactance per phase for configuration at site (ohms)
1.09 Conducivity of IACS (%)
1.10 DC Resistance of 2033
1.11 Constant mass temperature co-efficient of resistance
1.12 Weight (Kg/m)
1.13 Current rating at site conditions (Amps)
1.14 Tubular bus conductor temperature Due short circuit (oC)
1.15 Final allowable tabular bus conductor Temperature due to short circuit (oC)
1.16 Short circuit current rating for 1 sec. duraion (kA)
1.17 Critical disruptive (Corona) voltage (Line o Neutral) KV)
1.18 Ratio inerference at rated voltage (micro volts m)
1.19 Yield srength at tensile stress of 1335 Kg/cm2 for aluminium tubular bus conductor (Kg)
1.20 Minimum braking strength at tensile stress of 1545 Kg/cm2 for aluminium tabular bus conductor (kg)
1.21 Deflection on tabular bus conductor for 13 span (mm)
1.22 Maximum transport length of tabular bus conductor (Meter)
1.23 Data Applicable to Bells
b Type of fiting (Internal/external)
2.00 Clamps and Connections 220KV 110KV 66KV 33KV
2.01 Manufacturers Name and address
2.02 Applicable standards
2.03 Application
2.04 Type of fiting (Internal/external)
2.05 For connection to
a Conductor size and arrangement
b Equipment terminal and arrangement
2.06 Material (state percentage composiion of consiuents and impurities present)
b Bolts and Nuts
c Spring washers
d Liners, if any
2.07 Rated current (A)
2.08 Maximum temperature rise over reference ambient temperature when carrying rated current (oC)
2.09 Rated terminal load and factor of safey (Kg)
2.10 Minimum thickness of any part (mm)
2.11 Weight of clamp complete with hardware (Kg)
2.12 Machine accuracy for matting surface
2.13 Service (Indoor/Outdoor)
3.00 Marshalling Kiosk 220kV 110kV 66kV 33kV
3.01 Manufacturers Name and address
3.02 Indoor/Outdoor application
3.03 Design ambient air temperature
3.04 Thickness of sheet steel (mm)
3.05 Degree of protection provided
3.06 Bill of material for all equipment mounted in marshalling Kiosks giving following details:
b Applicable Standards
c Voltage rating
d Current rating
e Duty class if applicable
f Manufacturers catalogue No.
g Total heat load of Kiosk (for purpose of ventilation requirement)
3.07 Colour of finish paint (as per IS:5)
3.08 Busbars 220kV 110kV 66kV 33kV
b Temperature rise at rated current over specified ambient temperature (o C)
c Continuous current rating (A)
d Short circuit current rating for one sec. (KA)
3.09 Control wiring
a Size of conductor (mm2)
i. For CT circuits
ii. For other circuits
b Conductor (solid/stranded)
3.10 Space Heater Rating at 240 V Ac
3.11 Marshalling Kiosk drawing enclosed showing the following:
a Outline dimensions floor opening Floor/wall pedestal fixing arrangements, weight etc. (YES/NO)
b Front view and inside view showing the mounting arrangments of various equipments. (YES/NO)
3.12 Schematic wiring diagram of marshalling kiosk enclosed (YES/NO)
3.13 Interconnecion drawing showing Employer's external cable connection to the marshalling Kiosk enclosed. (YES/NO)
3.14 Type test report to degree of protection enclosed.
3.15 Terminal blocks
a Make and type
b Current rating
i Power Terminal (A)
ii Outer Terminal (A)
GUARANTEED TECHNICAL PARTICULARS OF CLAMPS AND CORONA BELLS ASSOCIATED WITH ALUMINIUM PIPE:
2 Type of clamps, purpose and size of the pipe
3 Type of corona bell (internal fitting or external fitting)
4 Standards applicable
5 Material (state percentage composition)
ii Bolts and Nuts
iii Spring washers
6 Current rating (amps)
7 Maximum thickness of any part (mm)
8 Minimum thickness of any part (mm)
9 Size of bolts used in each case
11 List of type tests enclosed
12 Year in which type test conducted
13 List of routine tests conducted
14 List of drawings enclosed
Note: Pariculars in respect of different clamps may be furnished separately or in tubular columns in the annexure.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR CURRENT TRANSFORMERS
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Voltage Class and ratio of CT 110kV 110kV 66kV 66kV 33kV 11kV 11kV
Sl.No. PARTICULARS
1 Name of the manufacturer
2 Country of origin
3 Standard Governing specification
5 Manufacturer's type designation
6 a. Nominal system voltage KV
b. Highest system voltage KV
7 a, Rated primary current
b. Rated secondary current Amp
c. Rated transformation ratio Amp
8 Rated Secondary terminal Voltage at
i. Rated Current
ii. 10 Times the rated current
iii. 20 Times the rated current
9 Ratio of current Transformer
10 Number of Cores
11 Details of Core
i. Rated Burden
ii. Accuracy Class
iii. Accuracy limit factor
iv. Instrument Security factor
v. Knee point voltage at
vi. Secondary winding
resistance (Ret. In Ohms)
vii. Magnetising current at Vk/4
i. Rated Burden
ii. Accuracy Class
iii. Accuracy limit factor
iv. Instrument Security factor
v. Knee point voltage at
vi. Secondary winding
resistance (Ret. In Ohms)
vii. Magnetising current at Vk/4
i. Rated Burden
ii. Accuracy Class
iii. Accuracy limit factor
iv. Instrument Security factor
v. Knee point voltage at
vi. Secondary winding
resistance (Ret. In Ohms)
vii. Magnetising current at Vk/4
i. Rated Burden
ii. Accuracy Class
iii. Accuracy limit factor
iv. Instrument Security factor
v. Knee point voltage at
vi. Secondary winding
resistance (Ret. In Ohms)
vii. Magnetising current at Vk/4
i. Rated Burden
ii. Accuracy Class
iii. Accuracy limit factor
iv. Instrument Security factor
v. Knee point voltage at
vi. Secondary winding
resistance (Ret. In Ohms)
vii. Magnetising current at Vk/4
12 Current error at rated primary current
13 Phase displacement at rated primary current
14 Composite error at rated accuracy limit primary current in %
15 Rated short time current and duration
a. Thermal ( I th) KA (rms) for 1 sec KA
b. Dynamic (I dyn) (peak)
16 Temperature rise of the windings (by resistance method) over an ambient temperature of 45oC
a)At rated current Deg C
b)At 100% overload for 5 minutes Deg C
17 Partial discharge level
18 Particulars of windings
a. Primary winding :
ii. No.of turns
iii.Current density at rated current Amp / Sq.mm
iv. Size of conductor
v. class of insulation
b. Secondary winding
ii. No. of turns
iii.Current density at rated current Amp / Sq.mm
iv. Size of conductor
v. Class of insulation
vi. Resistance computed to 75 deg C Ohm
vii. Insulating material used
c. Rated insulation levels :
i. One minute power withstand voltage KV (rms)
ii. Intersection withstand voltage of primary windings KV (rms)
iii. Impulse withstand voltage KV (rms)
19 Particulars of core :
ii. Flux density :
a. At rated primary current Tesla
b. At 15 times rated primary current Tesla
iii. Thickness of steel lamination mm
iv. Whether CRGO steel stampings are used?
v. Watt loss/Kg. of steel
vi. Knee point e.m.f
20 Particulars of porcelain housing / bushing
i. Specification to which it confirms
ii. Name of manufacturer
iii. Power frequency withstand voltage for one minute
a. Dry KV (rms)
b. Wet KV (rms)
iv. Dry lightning impulse withstand voltage 1.2/50 micro sec. Wave shape KV (rms)
v. Visible power frequency discharge voltage KV (rms)
vi. Creepage distance in air
a. Protected mm
vii. Weight of porcelain housing / bushing kgs
21 Overall dimensions :
i. Total weight of copper used
a. Primary winding kg
b. Secondary winding kg
ii. Weight of core kg
iii. a. Quantity of insulating oil liters
b. Weight of insulating oil kgs
iv. Total weight kgs
23 Particulars of terminal connector
i. Name of the manufacturer
ii. Rated current Amps
iii. Temperature rise above an ambient of 45 deg.c
a. At rated current Deg C
b. At 150% of rated current for 15 min Deg C
CONTROL CABINET :
1 Manufacturer's Name
3 Design ambient air temperature (oC)
4 Standards applicable
5 Thickness of sheet steel (mm) and whether cold rolled or hot rolled
6 Degree of protection provided
7 Bill of material for all the equipment mounted on control cabinet giving the following details
b. Applicable Standard
c. Voltage rating
d. Current rating
e. Duty class, if catalogue No.
f. Manufacturer's catalogue No.
g. Total heat load of cabinet (For purpose of ventilation requirement)
8 Colour of finish paint IS : 5
9 Control Wiring
a. Size Conductor
i. For CT circuits
ii. For other circuits
b. Conductor Solid Stranded
c. Number of Strands / conductor
10 Terminal Blocks
b. Current terminals (A)
i. Power terminals (A)
ii. Other terminals (A)
11 Space Heater Rating at 240 VAC
12 Control cabinet drawing showing the following
a. Outline dimensions, floor openings, Floor/wall/pedestal fixing arrangements, Weights etc.
b. Front view, inside view showing the Mounting arrangement of various Equipment.
13 Schematic / wring diagram of control Cabinet enclosed
14 Interconnection drawing showing cable, Connections to the control cabinet enclosed.
15 Type test report to verify degree of Protection enclosed
16 Details of terminal rows
i. Whether arranged vertical or horizontal
ii. Clearance from adjacent components
iii. Distance between rows
iv. Whether transparent protection cover provided
SUPPORT INSULATOR
1 Manufacturer's Name
3 Applicable Standards
ii. Diameter (Top)
iii. Diameter (Bottom)
5 Total creepage distance (mm)
6 Rated voltage (KV)
7 Power frequency withstand voltage for 1 min (KV rms) dry and wet
8 1.2/50 micro sec. Impulse withstand voltage (KVP)
9 250/2500 micro sec. Switching impulse
10 Corona Extinction voltage (KV)
12 Max. allowable span (mm)
13 Cantilever Strength (Kg)
14 OGA drawing enclosed
TERMINAL CLAMPS AND CONNECTORS
1 Manufacturer's Name
2 Applicable Standards
4 Material of connector
b. Bolts & Nuts
c. Spring washers
5 Rated Current
6 a. Rated terminal load (Kg)
b. Factor of safety
7 Minimum thickness of any part (mm)
8 Weight clamp complete with hardware (Kg)
9 Type test report as per IS enclosed
10 OGA drawing enclosed
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR ACSR CONDUCTOR
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Sl. No. Bidders Name
ASCR Conductor ASCR Conductor ASCR Conductor ASCR Conductor ASCR Conductor
Description Unit
MOOSE COYOTE LYNX DRAKE PANTHER
1 Name & Address of manufacturer
2 PARTICULARS OF RAW MATERIALS
a Minimum Purity of aluminium %
b Maximum Copper content %
2.2 Steel Wires/Rods
c Phosphorous %
a Minimum Purity of zinc %
3 STEEL STRANDS
b Maximum Copper content mm
3.2 Minimum Braking load of strand KN
3.3 Maximum Resistance of 1m length of strand at 20 deg C Ohm
4 STEEL STRANDS AFTER STRADING
4.2 Minimum Braking load of strand KN
4.3 Galvanising
a Minimum weight of zinc coaing per sqm. Of uncoated wire surface Gm
b Minimum number of one minute dips that the galvanised strand can withstand in the standard preece test Nos.
c Min.No. of twists in a guage length equal to 100 times dia of wire which the strand can withstand in the torsion test. Nos.
5 ACSR Conductor
5.1 UTS of conductor KN
5.2 Lay ratio of conductor
a Outer steel layer
b 12 wire aluminium layer
c 18 wire aluminium layer
d 24 wire aluminium layer
5.3 DC resistance of conducor at 20 deg. C Ohm/km
5.4 Minimum Corona Extincion Voltage (line to ground)
5.5 RIV at 1MHz
a a 305KV (rms) under dry conditions microvolts
5.6 Standard length of conductor in one drum M
5.7 Direction of lay for outside layer NA
5.8 Linear mass of the conductor
a Standard Kg/km
b Minimum Kg/km
c Maximum Kg/km
6 Drum is as per specificaion Yes/No
7 No. of cold pressure butt welding equipments available at works Nos.
1 Name & Address of manufacturer
2 PARTICULARS OF RAW MATERIALS
2.1 Steel Wires/Rods
c Phosphorous %
a Minimum Purity of zinc %
3 STEEL STRANDS
3.2 Minimum Braking load of strand KN
3.3 Galvanising
a Minimum weight of zinc coating per sqm. Of uncoated wire surface Gm
b Minimum number of one minute dips that the galvanised strand can withstand in the standard preece test Nos.
c Min. no. of twists in a guage length equal to 100 times dia of wire which the strand can withstand in the torsion test. Nos.
4.0 STRANDED EARTHWIRE
4.1 UTS of conductor KN
4.2 Lay length of outer seel layer
4.3 DC resistance of conducor at 20 deg. C Ohm/km
4.4 Standard length of conductor in the drum Mtrs
4.5 Direction of lay for outer layer NA
4.6 Linear mass of earth wirer
c Minimum Kg/km
5.0 Drum is as per specificaion Yes/No
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GAURANTEED TECHNICAL PARTICULARS FOR VOLTAGE TRANSFORMERS (COMMON TO 110 KV, 66 KV AND 33 KV CLASS)
(Bidder should indicate the guaranteed technical data of all equipments / materials for each type of rating separately)
Bidders name VOID
Class of Voltage Transformers 110KV 66KV 33KV
2 Manufacturer's type and designation
3 Rated primary voltage
4 No.of secondary winding
5 Rated secondary voltage
i. Winding No.I
ii. Winding No. II
iii. Winding No. III
i. Winding No.I
ii. Winding No.II
iii. Winding No.III
7 Accuracy Class
i. Winding No.I
ii. Winding No. II
iii. Winding No.III
8 Maximum ratio error with rated burden and 9% normal primary voltage for secondary winding.
9 Maximum phase angle error with rated burden and 5% normal primary voltage for secondary winding
10 Grade of oil
11 Temperature rise at 1.2 times rated voltage with rated burden
12 Rated voltage factor and time
13 Temperature rise for
14 One min. power frequency withstand test (dry) voltage
15 One min. power frequency withstand test (wet) voltage.
16 1.2 /50 micro sec. Impulse wave withstand test voltage
17 One min. power frequency withstand voltage on accessories.
18 Weight of oil
19 Total weight
20 Overall dimensions
21 Mounting details
22 Surface treatment
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR POST INSULATORS AND DISC INSULATORS
(Bidder should indicate the guaranteed echnical data of all equipments/mzaterials for each type of rating separately)
Post Insulators & Disc String Insulators
1.00 POST INSULATORS 245KV 123KV 72.5KV 36KV
1.01 Manufacurer's name and Address
1.02 Type of Insulators Units
1.03 Applicable Standard
1.04 No. of Units per Sack
1.05 Whether corona ring provided or not (Yes/No)
1.06 Diameter (mm)
1.07 Bolt circle diameter (mm)
1.08 Spacing bewteen two units (mm)
1.09 Creepage Distance
b Protected (mm)
1.10 Power frequency wihstand volage of insulator
i. Dry (KV rms)
ii. Wet (KV rms)
b One complete stack
i. Dry (KV rms)
ii. Wet (KV rms)
1.11 1.2/50 micro sec.impulses withstand voltage
b Complete stack
1.12 Visual discharge volage for falling power frequency voltage for complete stack
1.13 Radio interference voltage of compete stack
i Test Voltage(KV rms)
ii Radio interference voltage (micro volt)
1.14 Weight of complete stack (Kg)
1.15 Cantilever Strength
ii Underhung (Kg)
b Complete stack
ii Underhung (Kg)
1.16 Tensile Strength (Kg)
1.17 Torsional Strength (Kg.m)
1.18 Compression Strength (Kg)
1.19 250/2500 micro second switching surge withstand voltage
i Dry (KV Peack)
ii Wet (KV Peack)
b Complete stack
i Dry (KV Peack)
ii Wet (KV Peack)
1.20 Whether shed profile of insulaor is conforming to IEC-815? (Yes/No)
1.21 Whether calculation characterising shed profile as per IEC-815 are enclosed with bid? (Yes/No)
1.22 Wheher offered BPI is alternate shed type?
1.00 INSULATOR STRINGS 220KV 110KV 66KV 33KV
1.01 Manufacturer's Name
1.02 Type of string
a Single/Double
b Suspension/Tension
1.03 Applicable standards
1.04 Type of Insulators
a Ball & socket/oher
b Whether fog type
1.05 Insulating Material
1.06 No. of unis per string
1.07 Size of each unit
a Diameter of disc (mm)
b Spacing between adjacent units (mm)
a Each disc (Kg)
b Complete String (mm)
1.09 Creepage Distance
a Each disc (mm)
b Complete String (mm)
1.10 power frequency withstand voltage of the complete string with corona control ring
1.11 Lightening impulse withstand voltage of the complete string for both positive and negative
1.12 Switching surge withstand voltage of the complete string with corona ring.
1.13 Power frequency puncture withstand voltage of each Disc (KV rms)
1.14 Electro Mechanical strength (KG) of each disc.
1.15 Minimum corona extinction voltage level of the complete string with corona ring (Dry condition)
1.16 RIV level of the complete string with corona control ring shall be below 1000 micro at 1 MHz when subjected to a test voltage indicated against clause 1.15 above. (Dry condition)
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR INSULATOR HARDWARE AND CLAMPS
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
220KV 110KV 66KV 33KV
1.00 Insulator hardware
1.01 Manufacturer's Name and address
1.02 Applicable Standards
b Nuts bolts and washers
e Strain and suspension/drop clamp (kg)
1.04 Ultimate Strength
a Complete assembly (kg)
b Suspension /drop clamp (kg)
c Strain clamp (kg)
d D-shackle (kg)
e Ball eye (kg)
f Ball clevis (kg)
g Clevis eye (kg)
h Socket eye (kg)
I Socket clevis (kg)
j Yoke Plate (kg)
1.05 Magnetic power loss at
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR SURGE ARRESTORS
(Bidder should indicate the guaranteed technical data of all equipments / materials for each type of rating separately)
Surge Arrestors 96KV 60KV 30KV 9KV
SURGE ARRESTORS
a. Manufacturer's Name
b. Manufacturer's type / designation
c. Applicable standards
ELECTRICAL CHARACTERISTICS
2 A. Arrester class and Type
b. Rated arrester voltage (kV)
c. Maximum continuous operating voltage (COV) at design ambient temeprature
d. Nominal discharge current (8/20 micro sec. Wave) (kA)
e. i. Minimum discharge capacity (kJ/kV) referred to rated voltage of minimum of discharge characteristics
ii. Line discharge class, as per IEC
f. Maximum equivalent front of waver protection level (discharge voltage with 0.5 * 1.5 micro sec, 10 kA impulse current).
g. i. Minimum switching surge residual voltage at 1 kA (kV p)
ii. Maximum switching surge residual voltage at 1 kA(kVp)
h. Maximum residual voltage for 8/20 micro sec. Current wave
i. At 50% nominal discharge current (kVp)
ii. At 100% nominal discharge current (kVp)
iii. At 200% nominal discharge current (kVp)
i. One minute power frequency (dry) withstand Voltage of arrester (k Vrms)
j. Impulse withstand test voltage of arrester housing with 1.2/50 micro sec. Wave (kVp)
k. Impulse current withstand
i. High current short duration (4/10 micro sec. Wave) kAp
ii. Low current long durationn (A peak)
l. Maximum internal ionisation at 50 Hz voltage equal to
m. Reference voltage and corresponding reference current of arrester.
n. Maximum internal leakage current at (mA).
iii. COV at 150oC
iv. Reference voltage
o. Pressure relief class
p. Are the protection levels affected by pollution of external insulation
q. Energy absorption capacity in kJ per operation of the arrester, during a switching surge discharge.
r. Maximum amount of energy that may be dispatched into the arrester during discharge into the arrester during discharge assuming that discharge takes place within 1 min period and state the switching surge current.
s. Internal pressure required to operate pressure relief device as a percentage of burst pressure of porcelain
t. Dynamic over voltage withstand kVp
ii. For 0.01 sec.
iii. For 0.1 sec.
u. Minimum prospective symmetrical fault current (kA rms)
v. Rejection rate of ZnO blocks during manufacturing and operation for the past three years (%) seperately
w. Rated voltage of ZnO disc (kV)
i. No. of ZnO discs in a unit
ii. No. of units/arrester
iii. Height / Thickness of ZnO discs 9(mm)
iv. Diameter of ZnO disc. (mm)
3 EXTERNAL INSULATION
b. Applicable standard
c. Impulse voltage withstand test voltage of housing with 1.2 / 50 micro sec wave (kVp)
d. One minute power frequency withstand voltage of arester housing dry and wet (kv rms)
e. Total creepage distance of arrester housing (mm)
f. Cantilever strength of complete arrester (kg)
4 OVERALL DIMENSIONS
A. Overall dimensions
i. Overall Height (mm)
ii. Height upto top of terminal pad from mounting plane
iii. Material of terminal pad
iv. Size of terminal pad
v. Mounting dimensions and diameter of mounting holes
vi. Diameter of insulator
b. Total weight of complete arrester (kg)
TERMINAL CLAMPS AND CONNECTIONS
1 Manufacturer's Name
2 Applicable Standards
4 Material of connector
b. Bolts & Nuts
c. Spring washers
5 Rated Current
6 a. Rated terminal load (kg)
b. Factor of safety
7 Minimum thickness of any part (mm)
8 Weight of clamp complete with hardware (kg)
9 Type test reports as per IS enclosed
10 OGA drawing enclosed.
BUSHING / SUPPORT INSULATOR
1 Manufacturer's Name
3 Applicable Standards
ii. Diameter (Top)
iii. Diameter (Bottom)
5 Total Creepage distance (mm)
6 Rated voltage (kV)
7 Power frequency withstand voltage for 1 min. (k Vrms) dry and wet
8 1.2/50 micro sec. Impulse withstand voltage (kVp) dry and wet
9 250/2500 micro sec. switching impulse withstand voltage (kVp) dry and wet
10 Corona Extinction voltage (kV)
12 Max. allowable span (mm)
13 Cantilever Strength (kg)
14 OGA drawing enclosed.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR STATION AUXILIARY TRANSFORMERS
(Bidder should indicate the guaranteed technical data of all equipments/materials )
Sl. No. Description
2 Name of Manufacturer
3 Place of Manufacture
4 Reference standard
5 Service (indoor/outdoor)
6 Voltage Ratio
7 Rating in kVA
8 Rated Frequency (Hz)
9 Number of phases
10 Vector group
11 Core Material used and Grade
Over fluxing without saturation (Curve to be furnished by the manufacturer in support of his claim)
12 Maximum temperature rise of:
a. Winding by resistance method (0C)
b. Oil by thermometer (0C)
13 Magnetizing (No-load) current at :
14 Core loss in watts
a. Normal voltage
b. Maximum voltage
15 Resistance of windings at 200C (with 5% tolerance)
a. HV Windings (ohms)
b. LV Windings (ohms)
16 Full load losses (watt) at 750C 0 0
17 Total losses at 100% load at 750C
18 Total losses at 50% load at 750C
19 Current density used for : (Ampere/Sq.mm)
20 a. Clearances : mm (in oil)
c) HV Phase to Phase
d) End insulation clearance to earth
e) Any point of winding to tank
i. Clearances : mm (in air)
HV - Phase to Phase
LV - Phase to Phase
21 Efficiency at 750C (@ Unity P.F. and 0.8 P.F.)
22 Regulation at :
a) Unity P.F. and
b) 0.8 P.F. at 750C
23 % Impedance at 750C
24 Tap changing gear:
Type of tap changer
Total tap range (+) percent to (-) percent
Tappings provided at
25 Permissible overloading
26 Noise level when energized at normal voltage and normal frequency at no-load (db)
27 Insulation level in kV
Nominal system voltage (NSV)
Highest system voltage (HSV)
Power frequency withstand voltage
d) Lightning impulse withstand voltage
28 Mass of : (kg)
a) Core lamination (minimum)
b) Windings (minimum)
c) Tank and fittings
e) Oil quantity (minimum ) (litre)
f) Total weight
(i) Quantity for first filling (minimum) (litre)
(ii) Grade of oil used
(iii) Maker’s name
(iv) BDV at the time of filling (kV)
(v) Water content at the time of filling (in PPM)
30 Transformer:
Overall length x breadth x height (mm x mm x mm)
Tank length x breadth x height
Thickness of plates for
i) Side plate (min)
ii) Top and bottom plate (min)
Conservator dimensions
Heat dissipation by tank walls excluding top and bottom
Heat dissipation by cooling tube
Diameter and thickness of cooling tube
Total radiating surface in square metre
Whether calculation sheet for selecting cooling area to ensure that the transformer is capable of giving continuous rated output without exceeding temperature rise is enclosed.
32 Inter layer insulation provided in design for :
Top and bottom layer
In between all layer
Details of end insulation
Whether wedges are provided at 50% turns of the HV coil.
33 Insulation materials provided
a) For conductors
34 Material and size of the conductor used and current density
HV Dia (mm) SWG
LV i) Strip size
ii) No. of conductors in parallel
ii. Total area of cross section (all particulars as required in tender).
Current density - HV
Material of winding conductor
35 Whether the name plate gives all particulars as required in tender
36 Particulars of bushings HV/LV
Current Rating (Amps)/Voltage rating (kV)
Dry power frequency withstand voltage (kV rms)
Wet power frequency withstand voltage (kV rms)
Lightning impulse withstand voltage (kVp)
Creepage distance (mm)
37 Type of insulation used in
38 Type of insulation used on
ii) Core bolt washers
iii) Core laminations
39 Vacuum to which the tank can be subjected without distortion (torr)
40 Weight of insulated conductor
41 a) Weight of core
42 Weight of complete Transformer for transport
43 Period for which this design of transformer has been in commercial use.
44 Reactance of windings at 750C/ph
45 Resistance of windings at rated current and frequency
46 Type & size of Gas operated relay and whether supervisory alarm and trip contacts provided.
48 Temperature indicators
a)Oil temperature indicator
b) Winding temperature indicator
ii) Permissible setting ranges for alarm & trip
iii) No. of contacts
iii. Current rating of each contact
49 Ratio and type of CT used for winding temperature
50 No. of Breathers provided (Nos.)
51 Type of dehydrating agent used for breathers
52 Type , make and number of pressure relief device
Minimum pressure at which the device operates, Kg/cm2
53 Valves - sizes and numbers required/fitted
a) Drain cum sampling valve
b) Fitter valve
54 Characteristics of insulating oil to be used
b) Density (Max) at 20° C
c) Kinematic viscosity (max)
d) Interfacial tension
e) Flash point (Min)
f. Neutralization value
i) Total acidity (Max)
ii) Inorganic acidity/Alkalinity
a. Pour point (max)
b. Corrosive sulphur
i. Electric strength (break down voltage (min) with 2.5mm gap)
i) New Unfiltered oil as in received condition.
ii) After filtration.
j. Dielectric dissipation factor (tan delta) at 90°C (Max)
Water content (Max)
l. Specific Resistance (Min) (Resistivity)
i) At 90°C (min)
ii) At 27°C (min)
m. Oxidation Stability
i) Neutralization value after oxidation (Max.)
ii) Total sludge after oxidation (Max.)
n. Ageing characteristics after accelerated ageing (Open breaker method with copper catalyst)
a) Resistivity at 27°C
b) Resistivity at 90°C
c) Dielectric loss factor (tan delta) at 90°C
d) Total acidity mg KOH/g
e) Sludge Content (Max.)
o. Presence of oxidation inhibitor (Percent by weight)
55 Date of commencement of production of distribution transformer at the factory of the supplier
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUANRANTEED TECHNICAL PARTIULARS FOR LTAC PANELS
SL. NO. PARTICULARS
II Country of manufacturer
III Air circuit breakers of incoming and bus coupler circuits
1 Type of breakers
b Whether draw out type
2 Interupting rating
3 normal voltage
4 normal current
5 Making current
6 Method of extinguishing arc
7 Type of closing mechanism
8 Max. current for closing coil
9 Max. current for tripping coil
10 Temperature rise of contact under continuous full load over 45 C ambiens
11 Material & type of contacts
12 Type of overload protection provided externally by IDMTL with adjustable time lag.
a Thermal element
b Instataneous element
13 Range of adjustments of over load setting
14 Type of earth fault protection
15 Range of adjustments of earth fault protection
16 Time/current characteristics: CT over current protection moulded case (or equivalent) air breaker switch fuse units for distribution feeders
c Normal Voltage
d Normal current
e Interrupting rating
ii. Aymmetrical
f Method of extinguishing are
g Making current
h Fusing factor for fuses
I Temperature rise of contact under continuous full load over 45 C ambient
j Material & type of contacts
k Type of overload protection
l Range of adjustment of overload setting
m Time current characteristics of fuses of over current protection
V Current Transformers
b Accuracy class
c Normal VA class
d Accuracy class
e Rated over current factor
f Rated time of over current in seconds
a Sectional area
b Material of bus bar
c Current Carrying capacity
d Maximum arc rise
e Clearances between bus bar.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR POWER CABLES (LV CABLES)
SL. No PARTICULARS
1.1kV Grade PVC Power Cables
3 Manufacturer’s type designation
4 Applicable Standard
5 Rated voltage (volts)
6 Type & Category
7 Suitable for earthed or unearthed system
8 Continuous current rating when laid in air in a ambient temp. of 50°C and for maximum conductor temp. of 70°C of PVC Cables (For information only)
9 Ration factors applicable to the current ratings for various conditions of installation.
10 Short Circuit capacity
a)Guaranteed short circuit Amp. (rms) KA for 0.12sec duration at rated conductor temperature of 90 degree C, with an initial peak of 105kA.
b). Maximum conductor temp. allowed for the short circuit duty (deg. C) as stated above.
c) Cross section area (Sq.mm)
d) Number of wires (No.) minimum
e) Form of conductor
f) Direction of lay of stranded layer
12 Conductor resistance (DC) at 20°C per km - maximum
a) Composition of insulation
b) Nominal thickness of insulation (mm)
c) Minimum thickness of insulation
14 Inner Sheath
b) Calculated diameter over the laid up cores, (mm)
c) Thickness of sheath (minimum) mm
a) Type and material of armour
b) Direction of armouring
c) Calculated diameter of cable over inner sheath (under armour), mm
d) Nominal diameter of round armour wire (minimum)
e) No. of Armour wires/stripes
f)Short circuit capacity of the armour along for 1 second – for info. Only
g) DC resistance at 200C (Ω/Km)
16 Outer sheath
a) Material (PVC Type)
b) Calculated diameter under the sheath
c) Min. thickness of sheath (mm)
d) Colour of Sheath
a) Guaranteed value of minimum oxygen index of outer sheath at 270C *
b)Guaranteed value of minimum temperature index at 21 oxygen index *
c). Smoke density rating as per IEC 61034 *
d). Maximum HCL emission as per IEC 60754-1 *
e)All the factory acceptance test to be done as per relevant IS/IEC and KPTCL specification
18 a)Overall diameter of cable
b). Tolerance of overall diameter (mm)
a) Max./standard length per drum for each size of cable (single length) with ±5% Tolerance (mtrs)
b) Non standard drum lengths
20 Whether progressive sequential marking on outer sheath provided at 1 meter interval
21 Identification of cores
a) Colour of cores
22 Whether cables offered are ISI marked
23 Whether cables offered are suitable for laying as pr IS 1255
24 1.0 Continuous current rating of the cable
a) In ground at soil temperature 30°C and soil thermal resistivity of 150°C cm/watt and depth of burial about a metre (A)
b) In air at 40°C (A)
c) Overload capacity and duration (A, Hr)
d) Derating Factors for :
i) Soil temperature and thermal resistivity
ii) Ambient temperature
iii) Single core cables laid in trefoil circuits
2) General Technical Data (Power cables)
2.1) Equivalent star impedance per km of 3 Ph, circuit at power frequency at maximum conductor temperature (Ohm)
2.2) Maximum electrostatic capacitance per core per km of cable (F)
2.3) Maximum charging current per conductor per km at nominalvoltage (A)
2.4) Loss tangent at normal frequency and rated voltage
2.5) Maximum dielectric loss of cable per km at normal voltage and frequency Watts/km
2.6) Short circuit capacity for 1 Sec. KA (rms)
2.7) Short Circuit current capacity of armour (kA for 1 sec)
2.8) Maximum dielectric stress at core screen (kV/cm)
2.9) Maximum overall dia. of cable (mm)
3.0) Construction details including type of material used and thickness of each material for each type of cable in a tabular form.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL PARTICULARS FOR AC DISTRIBUTION BOXES (OUTDOOR)
(Bidder should indicae he guaranteed Technical data of all equipments/materials for each type of rating separately)
1.0 DB ASSEMBLY
1.3 Reference Standard
1.4 Voltage (Nom/Max)
1.5 Phase, Frequency No.Hz
1.6 Short Ciruit rating inerrupting symmetrical KA short time for 1 sec. KV rms
1.7 Construcion
Metal clad air insulated flour mounting Yes/No
Suitable for mouning against building wall Yes/No
a Degree of proecion
b Minimum thickness of sheet mm
1.9 DB fully assembled wired and tested at factory Yes/No
2.0 Consruction
a Compleely compartmentalised
b Working height limits from floor level mm
2.2 Control compartment providedwith individual front access door
2.3 DE section provided with removable back cover full height cable chamber
2.4 Horizontal wire way for iner panel wiring provided for each DB
2.5 All meters, relays lamps etc., flush mounted type
2.6 Vertical section size (LxDxH) mm
3.2 Material and grade
3.3 Reference Standard
3.4 Continuous currents at site condiion 50 deg ambient and within cubicles
a Main busbar Amp
b Vertical Busbar (min) Amp
3.5 Conductor section
a Main Busbar Sq.mm
b Vertical Busbar (min) Sq.mm
3.6 Max. Temp rise over 40 deg ambient deg C
3.7 Short time current for 1 sec KA rms
3.8 Separatechamber / phase barrier/ shrouding provided for
b Vertical Busbar (min)
3.9 Bus connections
a Silver plated
b Provided with anti-oxide grease
c Bimetallic connectors between dissimilar metals
3.10 Minimum clearance of bare busbar and connection
a Phase to Phase mm
b Phase to Ground mm
3.11 Busbar support spacing mm
3.12 Busbar colour coded Yes/No
3.13 Bus supportt insulators
c Reference Standard
e Minimum creepage distance mm
f Cantilever srength Kg/Sq.cm
3.14 Type of insulation used for busbars
3.15 Withstand voltage of busbar insulation material
4.3 Reference Standard
4.4 Switch standard
4.5 Switch furnished with
a Operating handle
b Door Interlock
c Provision for padlocking in ON & OFF positions
4.6 All feeders provided with bolted disconnect link
4.7 Current rating at 40 deg C ambient & wihin cubicle
4.8 Breaking current at 415 volts AC or 220 V DC
5.3 Reference Standard
5.4 Rupturing capacity KA rms
5.5 Continuous current at 40 deg C ambient and within cubicle Amps
5.6 Cut off currents KA Peak
5.7 Fuse characteristics furnished for various fuse rating
6.0 Thermal overload relays & single phase preventers
a Temperaure compensate?
c Number and Type of contacts
d Thermal overload characteristics
e Tolerance of current Injunction 1 pole
d Watts/Voltage
e Series resistor Ohm
f Lamp & Lens replaceable from fron
8.0 Terminal Block
8.4 Voltage Grade
8.5 20% Spare terminals furnished
9.0 CABLE TERMINATION
9.1 Cable entry provision from top & bottom
9.2 Cable termination & connection arrangement furnished as specified
9.3 Power cable lugs
9.4 Power Cable Glands
d With tapered washers
9.5 Removable gland plate
a material for multicore cable
b Material for I/C cable
c Thickness of the plate
10.0 Ground bus
10.1 Ground bus furnished
11.0 Name plate
11.2 Tthickness
12.0 Space Heater
12.1 Cubicle Heater
a Thermostat controlled
d Individual Switches & fuses provided
13 Tropical protecion
a Any special treament for tropical proection
b Screens are of corrosion resisant materials
15.1 Routine tests on DB to be performed
a Operating under simulate service conditions
b High voltage test
c Primary current & volage shall be applied to instrument transformer
d Routine test cerificate of all major equipment will be furnished
e Any other tests (to be specified)
16.0 Typical drawings/Data function
16.1 General arrangement
16.2 Foundation plan
16.3 Control scheme
16.4 Bill of Materials
17.0 Overall dimension & weight
1 AC Disctribution board
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR DIESEL GENERATING SETS
(Bidder should indicae the guaranteed technical data of all equipments/materials
for each type of rating separately)
1.00.00 General
1.01.00 Bidder's name and address
1.02.00 Manufacturer's name, type and address for
a Diesel engine along with accessories
e Batery Charger
f DG control panel for site condition
2.02.00 Revoluions per minute
2.03.00 Number and arrangement of cyliners
2.04.00 No. of strokes
2.05.00 Method of starting
2.06.00 Time required for startting from cold
2.07.00 Auxiliary power consumption
2.08.00 Type of governor
2.08.01 Sensitivy of Governor
2.09.00 Guaranteed limits of governing
a Permanent variation
b Full load thrown off
c Full load put on
2.10.00 total speed variation
2.11.00 Specification of fuel oil
2.12.00 Specification of lube oil
2.13.00 Guaranteed fuel consumption
2.14.00 Lubricating oil consumption
2.15.00 Mechanical efficiency
2.16.00 Thermal efficiency
2.17.00 Method of aspiration
2.18.00 Method of cooling of engine and lubricating oil
2.19.00 Amount of water required for cooling system
2.20.00 Total weight
2.21.00 Space requirement including clearances
2.22.00 Maker's name, type and technical Literature for the following:
a Air filter cum silencer
c Pressure guages
d Level indicator
f Fuel oil pump
2.23.00 Mechanical auxiliaries load connected on main shaft with rating
3.00.00 Storage tank
a Type and shape
c Number specified
d Material of construction
e Overall dimensions
f Plate thickness
4.00.00 Alternator
4.01.00 Rated KW capacity
4.02.00 Rated KVA capacity
4.03.00 Rated Terminal voltage
4.04.00 Rated power factor
4.05.00 Rated stator current
4.06.00 Rated speed
4.07.00 Rated frequency
4.08.00 No. of phases
4.09.00 Excitation current and voltage at rated power output and power factor
4.10.00 Efficiencies and power factor at 110%. 100%, 75%, 50% and 25% of full load
4.11.00 Inherentt regulation (o C)
4.12.00 % Impedance
a Xd" Saturated
b Xd" Unsaturated
4.13.00 Type of exciter used, Capacity rating of exciter
4.14.00 Class of insulation
4.15.00 Permissible temperaure rise of
a Armature winding
b Field winding
4.17.00 Short circuit ratio gap
4.18.00 Overload capacity
4.19.00 Insulation level test voltage
4.20.00 Total weight & dimensions
4.21.00 Applicable standards
4.22.00 Automatic voltage regulator type, Technical, specifications and characteristics curves
4.23.00 Elecrical auxiliaries load connected to generator terminals with rating
5.00.00 Engine alternator set
5.01.00 Starting time (in sec)
5.02.00 Interval between starting impulse (in sec)
5.03.00 No. of starting impulses
5.04.00 Time for picking up the load
6.00.00 Control Panel / Board
6.01.00 Manufacurer's name and address
6.02.00 Sheet steel thickness
6.03.00 Dimensions
6.04.00 Colour shadeas per IS:5
6.05.00 Degree of protection
6.06.00 Mounting details
6.07.00 Make, type technical specification and catalogues for each type component to be mouned in conrol panel enclosed.
6.08.00 Current Transformer Measurement Protection
a Type and make
b Rated ransformation ratio
c Rated primary current
d Rated secondary current
f Insulation class
h Class of accuracy
i Accuracy limit factor
j Applicable standards
a Voltage Grade
c Conductor material
d (mm2) size of conductor
i For AC circuits
ii For DC Circuits
e No of conductors
f Maximum current rating
g Colour code used
h Type of terminals
i Size of erminals
j Applicable standards
6.10.00 Indicating Instruments
c Scale size (in degree)
f Relevant catalogue enclosed
7.00.00 Battery Charger
7.01.00 Manufacturer's name and address
7.02.00 Type of rectifier
7.03.00 Rated ouput current (Amps)
7.04.00 Output voltage range (Volts)
7.05.00 Applicable standards complete technical specification and literature to be furnished
8.00.00 Battery
8.02.00 Name of Manufacurer and address
8.03.00 No. of cells
8.04.00 Capacity in AH
8.05.00 Capaciy current of
i Full charged battery
ii Fully discharged battery
8.06.00 Average life in years
8.07.00 Applicable standard
8.08.00 Weight of the battery
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR STATION /PLCC BATTERY SET AND BATTERY CHARGERS
(Bidder should indicate the guaranteed technical data of all equipments/ materials for each type of rating separately)
Sl. No. PARTICULARS Units 220 V, 300 AH Battery sets
2 Plante type or Grid Plate type:
Type reference:
3 Nominal Voltage per cell Volts
4 Manufacture’s Name
5 Standards to which battery is manufactured
6 IS Nomenclature
7 Number of cells in the battery bank
8 Nominal Voltage of Battery Volts
9 Declared Capacity at 27 degree C upto 1.85 ecv
iii). End of Life AH
10 Rated Capacity at minimum ambient temperature Ah
11 Rated Capacity at maximum ambient temperature Ah
12 Capacity in AH at various end cell voltages and duration of discharge
15 minutes 1.65
45 minutes 1.71
13 Open circuit voltage of each battery cell
a). Fully charged
b). Floating condition
c). When completely discharged at
14 Maximum momentary current for 1 min till 1.60 e.c.v.
15 Expected life of battery under normal operation & maintenance conditions Years
16 Internal Resistance of each cell (IR) milli ohms
a). at Fully charged condition
b). at Fully discharged condition
c). at Floating condition
17 Total Resistance of Battery including inter connectors between the cells Ohms
18 Loss in Capacity in 21 hours due to self discharge %
19 Recommended Charging rate for
a). Float charging
i. Limit current A
b). Boost Charging
i. Starting Current A
ii. Finishing current A
20 Trickle Charging Rate
21 Equalizing Charge
c). Duration Hrs.
d). Interval between successive equalizing charge Months
22 a). Time to full charge at finishing rate only Sec
b). Time to full charge at higher starting rate sec
c). Time for full charge to charge by two step charging at starting up and finishing rates Sec
23 Recommended Specific gravity of Electrolyte at 27deg. C
a). for first filling
b). at full charge
c). when Battery is discharged at 10 hours rate
24 Permissible max. temperature of electrolyte
a). During Initial Charging deg C
b). During Normal Charging deg C
25 a.Amount of electrolyte and Specific gravity at 27 deg. C
for first filling
b) Electrolyte conforms to Standard
26 Overall dimensions
i). Each cell L x W x H mm
(tolerance of +/-2mm in each case)
ii). Complete Battery mm
27 Distance between cell centres mm
28 Quantity of Electrolyte per cell litres
29 Quantity of Electrolyte for battery (including 10% extra) litres
30 Weight (+/-5%)
Each cell i). without acid Kg
ii). With acid kg
31 Complete Battery i). without acid Kg
ii). With acid kg
32 Total shipping weight of Battery units Kg
33 Material and type of Plates
(i). Positive Plates
a). Material and Type
b). Height of Positive Plate mm
c). Thickness of Positive Plate mm
d). Area of Positive Plate Sq.m
e). No. of positive plates per cell
f). Whether positive plates of individual cells are interchangeable
(ii) Negative Plates
a). Material and Type
b). Height of Negative Plate mm
c). Thickness of Negative Plate mm
d). Area of Negative Plate Sq.m
e). No. of Negative plates per cell
f). Whether Negative plates of individual cells are interchangeable
34 Material and type of Separators
a). Material and Type
b). Thickness of separator mm
35 Clearance between bottom of the plate and the bottom of the container mm
36 Clearance between top of the plates and top of container mm
37 Clearance between edges of plates and inner surface of container mm
38 Sediment space (depth) mm
39 Whether explosion vents are offered
40 Type of Vent and Filling Plugs
a). Thickness of Container mm
b). Material of Container & Type
c). Outside dimensions (L x B x H)
a). Type of cover
b). Material of cover
44 Material of Inter-Cell Connectors
45 Thickness of Inter-Cell Connections mm
46 Method of connection
47 a). Inter-row, Inter-tier connectors and end take-offs furnished?
b). Description, Size, current rating, Type & Material
48 Connection hardware with 5% extra furnished?
49 Material of Bolt, Nut and Washer for inter-cell and Cable Connections
50 Cell insulators provided. If yes, material of insulator Yes/No
a). Number of racks per battery
b). Number of cells per rack
c). Type of racks
d). Material of rack
e). Dimensions of the racks
g). Shipping weight
52 Racks provided with
a). Numbering tags for cells
c).Whether anti acid coating is provided
53 Insulator with 5% extra furnished for
54 Ventilation requirements
55 Cubic content of battery rooms m3
56 Gas generation per single cell per hour Lit
57 No. of air exchanges required per hour
58 Standard Maintenance accessories provided Yes/No
59 Gasification Voltage per Cell Volt
60 Recommended Max. period of cell storage before the first Charge (After Installation and filling of Electrolyte)
61 Recommended Storage life of Battery (dry shelf life)
62 Does the battery meet the required duty cycle curve Yes/No
63 Short circuit current at Battery terminals when
a). Float at 2.1 Volts/Cell
b). Boost charge to 2.75 Volts/Cell
64 Time for which the Battery can withstand short circuit at terminals.
70 Dimensioned layout drawings of the rack & battery to be attached with the tender. Yes/No
Battery Charger Battery Charger for 110V, 200 AH Battery sets
1 Manufacturer’s type of designation
2 Type of Rectifier and rating as per IS – 3895 with latest version
3 Input AC supply.
c) No. of Phases
e) Power Factor
4 Percentage Tap provided on the Transformer +/- & Voltage ratio of Transformer & KVA rating.
i) For Boost Charger
ii) For Float Charger
5 Boost/Quick charge current
6 Float Charge Current
7 Trickle Charge Current
8 Whether Auto/Manual feature is provided
9 Whether voltage across load is constant while boost/quick charging the battery
10 Whether Automatic change over from Boost Charging mode to Float Charging is provided when AC failure takes place.
11 a) Allowable limits to voltage variation on A.C. side for satisfactory charging of DC side.
b) Type of device on AC side
12 Instantaneous forward voltage drop versus instantaneous current at rated service (a graph to be enclosed)
13 Type of voltage control for Boost Charger, Float charger & Trickle Charger
14 Instantaneous reverse current versus instantaneous reverse volts at rated service (a graph to be enclosed)
15 Range of variation of DC voltage and device used for the same
16 Rated DC output for
a) Boost Charger
b) Float Charger
17 D.C. output voltage regulation from no load to full load
18 Maximum ripple content in %
19 Maximum permissible temperature rise over an ambient temperature
20 Whether the charger is tropicalised
21 Over load capacity
22 Duration of overload
23 Efficiency at
24 Dimensions of the charger width x Height x depth in mm
25 Weight of the charger in Kgs
26 Recommended spares
27 List of major accessories provided
28 Other Details, if any
29 Rating & make of Thyristor
30 Meters (Ammeter/Voltmeter)
31 Heat Sink for Boost Charger & Float Charger Whether provided
DETAILS OF COMPONENTS & RATING
I DC Distribution Board
i. Maker's Name
ii. Country of Manufacturer
iii. Number of Circuits with rating
i. Sectional Area
iii. Current Carrying Capacity
iv Maximum Temperature rise over 45oC ambient with continuous full load condition
v. Type of Supporting Insulator
III Small Wiring
IV Moulded Case (OR Equivalent) Air Break Switch & Fuse Units
iii. Normal Voltage
iv. Normal Current
v. Interrupting Capacity
vi. Fusing Factor for fuses
vii. Temperature rise of contact under oC continuous full load condition over 45oC ambient temperature
viii. Material & Type of Contact
V Dimensions of Battery Charging Panel (Including DCDB)
VI Dimensions of DC Distribution Panel
VII i. Number of Crates for Shipment, Shipping Dimensions of the largest crate
ii. Whether equipments and the Switchboards are tropicalized or not
iii. How is access provided to the switchboard interior
iv. Mounting Arrangements for cable glands provided.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR NICKEL CADMIUM BATTERY SET and BATTERY CHARGER
(Bidder should indicate the guaranteed technical data of all equipments/ materials for each type of rating separately)
Sl. No. PARTICULARS Units 220 V, 300 AH Battery sets
2 Nickel Cadmium type:
Type reference:
3 Nominal Voltage per cell Volts
4 Manufacture’s Name
5 Standards to which battery is manufactured
6 IS Nomenclature
7 Number of cells in the battery bank
8 Nominal Voltage of Battery Volts
9 Declared Capacity at 27 degree C upto 1.0 ecv
iii). End of Life Ah
10 Rated Capacity at minimum ambient temperature Ah
11 Rated Capacity at maximum ambient temperature Ah
12 Capacity in AH at various end cell voltages and duration of discharge Ah
13 Open circuit voltage of each battery cell
a). Fully charged
b). Floating condition
c). When completely discharged at
14 Maximum momentary current for 1 min till 1.0 e.c.v.
15 Expected life of battery under normal operation & maintenance conditions Years
16 Internal Resistance of each cell (IR) milli ohms
a). at Fully charged condition
b). at Fully discharged condition
c). at Floating condition
17 Total Resistance of Battery including inter connectors between the cells Ohms
18 Loss in Capacity in 21 hours due to self discharge %
19 Recommended Charging rate for
a). Float charging
i. Limit current A
b). Boost Charging
i. Starting Current A
ii. Finishing current A
20 Trickle Charging Rate
21 Equalizing Charge
c). Duration Hrs.
d). Interval between successive equalizing charge Months
22 a). Time to full charge at finishing rate only Sec
b). Time to full charge at higher starting rate sec
c). Time for full charge to charge by two step charging at starting up and finishing rates Sec
23 Recommended Specific gravity of Electrolyte at 27deg. C
a). for first filling
b). at full charge
c). when Battery is discharged at 5 hours rate
24 Permissible max. temperature of electrolyte
a). During Initial Charging deg C
b). During Normal Charging deg C
25 a) Amount of electrolyte for first filling and Specific gravity at 27 deg. C
b) Electrolyte conforms to Standard
26 Overall dimensions
i). Each cell L x W x H mm
(tolerance of +/-2mm in each case)
ii). Complete Battery mm
27 Distance between cell centres mm
28 Quantity of Electrolyte per cell litres
29 Quantity of Electrolyte for battery (including 10% extra) litres
30 Weight (+/-5%)
Each cell i). without acid Kg
ii). With acid kg
31 Complete Battery i). without acid Kg
ii). With acid kg
32 Total shipping weight of Battery units Kg
33 Material and type of Plates
(i). Positive Plates
a). Material and Type
b). Height of Positive Plate mm
c). Thickness of Positive Plate mm
d). Area of Positive Plate Sq.m
e). No. of positive plates per cell
f). Whether positive plates of individual cells are interchangeable
(ii) Negative Plates
a). Material and Type
b). Height of Negative Plate mm
c). Thickness of Negative Plate mm
d). Area of Negative Plate Sq.m
e). No. of Negative plates per cell
f). Whether Negative plates of individual cells are interchangeable
34 Material and type of Separators
a). Material and Type
b). Thickness of separator mm
35 Clearance between bottom of the plate and the bottom of the container mm
36 Clearance between top of the plates and top of container mm
37 Clearance between edges of plates and inner surface of container mm
38 Sediment space (depth) mm
39 Whether explosion vents are offered
40 Type of Vent and Filling Plugs
a). Thickness of Container mm
b). Material of Container & Type
c). Outside dimensions (L x B x H)
a). Type of cover
b). Material of cover
44 Material of Inter-Cell Connectors
45 Thickness of Inter-Cell Connections mm
46 Method of connection
47 a). Inter-row, Inter-tier connectors and end take-offs furnished?
b). Description, Size, current rating, Type & Material
48 Connection hardware with 5% extra furnished?
49 Material of Bolt, Nut and Washer for inter-cell and Cable Connections
50 Cell insulators provided. If yes, material of insulator Yes/No
a). Number of racks per battery
b). Number of cells per rack
c). Type of racks
d). Material of rack
e). Dimensions of the racks
g). Shipping weight
52 Racks provided with
a). Numbering tags for cells
c).Whether anti acid coating is provided
53 Insulator with 5% extra furnished for
54 Ventilation requirements
55 Cubic content of battery rooms m3
56 Gas generation per single cell per hour Lit
57 No. of air exchanges required per hour
58 Standard Maintenance accessories provided Yes/No
59 Gasification Voltage per Cell Volt
60 Recommended Max. period of cell storage before the first Charge (After Installation and filling of Electrolyte)
61 Recommended Storage life of Battery (dry shelf life)
62 Does the battery meet the required duty cycle curve Yes/No
63 Short circuit current at Battery terminals when
a). Float (Volts/Cell)
b). Boost charge (Volts/Cell)
64 Time for which the Battery can withstand short circuit at terminals.
65 Dimensioned layout drawings of the rack & battery to be attached with the tender. Yes/No
Battery Charger Battery Charger for 110V, 200 AH Battery sets
1 Manufacturer’s type of designation
2 Type of Rectifier and rating as per IS – 3895 with latest version
3 Input AC supply.
c) No. of Phases
e) Power Factor
4 Percentage Tap provided on the Transformer +/- & Voltage ratio of Transformer & KVA rating.
i) For Boost Charger
ii) For Float Charger
5 Boost/Quick charge current
6 Float Charge Current
7 Trickle Charge Current
8 Whether Auto/Manual feature is provided
9 Whether voltage across load is constant while boost/quick charging the battery
10 Whether Automatic change over from Boost Charging mode to Float Charging is provided when AC failure takes place.
11 a) Allowable limits to voltage variation on A.C. side for satisfactory charging of DC side.
b) Type of device on AC side
12 Instantaneous forward voltage drop versus instantaneous current at rated service (a graph to be enclosed)
13 Type of voltage control for Boost Charger, Float charger & Trickle Charger
14 Instantaneous reverse current versus instantaneous reverse volts at rated service (a graph to be enclosed)
15 Range of variation of DC voltage and device used for the same
16 Rated DC output for
a) Boost Charger
b) Float Charger
17 D.C. output voltage regulation from no load to full load
18 Maximum ripple content in %
19 Maximum permissible temperature rise over an ambient temperature
20 Whether the charger is tropicalised
21 Over load capacity
22 Duration of overload
23 Efficiency at
24 Dimensions of the charger width x Height x depth in mm
25 Weight of the charger in Kgs
26 Recommended spares
27 List of major accessories provided
28 Other Details, if any
29 Rating & make of Thyristor
30 Meters (Ammeter/Voltmeter)
31 Heat Sink for Boost Charger & Float Charger Whether provided
DETAILS OF COMPONENTS & RATING
I DC Distribution Board
i. Maker's Name
ii. Country of Manufacturer
iii. Number of Circuits with rating
i. Sectional Area
iii. Current Carrying Capacity
iv Maximum Temperature rise over 45oC ambient with continuous full load condition
v. Type of Supporting Insulator
III Small Wiring
IV Moulded Case (OR Equivalent) Air Break Switch & Fuse Units
iii. Normal Voltage
iv. Normal Current
v. Interrupting Capacity
vi. Fusing Factor for fuses
vii. Temperature rise of contact under oC continuous full load condition over 45oC ambient temperature
viii. Material & Type of Contact
V Dimensions of Battery Charging Panel (Including DCDB)
VI Dimensions of DC Distribution Panel
VII i. Number of Crates for Shipment, Shipping Dimensions of the largest crate
ii. Whether equipments and the Switchboards are tropicalized or not
iii. How is access provided to the switchboard interior
iv. Mounting Arrangements for cable glands provided.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR
D.C DISTRIBUTION PANELS WITH DC EARTH FAULT INDICATORS
( Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
SL.No Bidders Name
1.3 Reference Standard
1.4 Voltage (Nom/Max)
1.5 Short Circuit Rating a) Short Time for 1sec KA
1.6 Insulation Level 1Min., 50 Hz voltage withstand KV rms
1.7 Construction
a)Metal clad air Insulated floor mounting: Yes/No
b)Suitable for mounting against building wall Yes/No
a)Degree of Protection
b)Minimum thickness of sheet mm
1.9 DB fully assembled wired and tested at factory Yes/No
a)Completely Compartmentalised
b)Working height limits from floor level mm
2.2 Control compartment provided with Individual front access door
2.3 DB Section provided with
a)Removable back cover
b)Full Height cable chamber
2.4 Horizontal wireway for inter panel wiring provided for each DB
2.5 All meters, relays lamps etc.. Flush mounted type
2.6 Vertical Section Size (LxBxH)mm
3.2 Material & Grade
3.3 Reference Standard
3.4 Continuous Currents at site condition 50 deg. Ambient and within cubicle.
b)Vertical Busbar(min)
3.5 Conductor Section
a)Main Busbar sq.mm
b)Vertical Busbar sq.mm
3.6 Max.temp rise over 40 deg. Ambient deg.C
3.7 Separate chamber/barrier/shrouding provided for
b)Vertical Busbar
3.8 Bus Connections
a)Silver Plated
b)Provided with antioxide grease
c)Bimetallic Connectors between dissimilar metals
3.9 Minimum Clearance of busbar and connection
a)Phase to Phase mm
b)Phase to ground mm
3.1O Busbar support spacing mm
3.11 Busbars colour coded Yes /No
3.12 Bus Support Insulator
c)Reference Standard
d)Voltage Class
e)Minimum Creepage distance mm
f)Cantilever Strength Kg/Sq.cm
3.13 Type of insulation used for Busbars
3.14 Withstand voltage of busbar insulation material
4 CONTROL MODULE
4.1 Control Modules
a)Fixed type for incoming & outgoing feeders
4.2 Power/Control disconnects silver plated for good contacts
4.3 Draw out Modules of same type & rating are physically & electrically interchangeable
5 Insulation Level 1Min., 50 Hz withstand KV rms
6.3 Reference Standard
6.4 Switch Standard
6.5 Switch furnished with
a)Operating handle
b)Door Interlock
c)Provision for padlocking in ON & OFF positions
6.6 All feeders provided with bolted disconnect link
6.7 Current rating at 40 deg.C ambient & within cubicle
6.8 Breaking current ar 220V D.C
7.3 Reference Standard
8.4 Utilization Category
8.5 Operating Coil Voltage
8.6 Continuous Current rating @ 45 deg. C and within cubicle A
8.7 Power Consumption
a)During Closing VA
b)After Closing VA
8.8 Auxiliary contacts furnished per contact
a)Normally Open (NO)
b)Normally Closed (NC)
8.9 Auxiliary contact rating Amps
a)Make and Continuous
b)Break(Inductive) at 220V DC
9 PUSH BUTTON & LAMPS
9.1 Push Button
c)Contact Rating Amps. Make & Continuous break/220 KV DC
10 SECONDARY WIRING
10.1 Type of insulation
10.2 Voltage Grade
10.3 Conductor Size
10.4 Conductor Size(Minimum)
a)Potential Circuit Sq.mm
b)Current & Control Circuits Sq.mm
10.5 Wires identified at both ends with ferules
11 TERMINAL BLOCK
11.4 Voltage Grade
11.5 20% spare terminals furnished
12 CABLE TERMINATION
12.1 Cable entry provision from top & bottom
12.2 Cable Termination & connection arrangement furnished as specified
12.3 Power Cable Lugs
12.4 Power Cable Glands
d)With tapered washers
12.5 Removable Gland Plate
a)Material for multicor cable
b)Material for I/C Cable
c)Thickness of the plate
13.1 Ground Bus furnished
15 SPACE HEATER
15.1 Cubicle Heater
a)Thermostat Controlled
d)Individual switches and fuses provided
16 TROPICAL PROTECTION
a)Any Special treatment for tropical protection
b)Screens are of corrosion resistant materials
17 PAINTING Finish of DB
18.1 Routine tests on DB to be performed
a)Operating under simulated service conditions
b)High Voltage Test
c)Primary current & voltage shall be applied to instrument Transformer
d)Routine test Certificates to all major equipments will be furnished
e)Any other tests(to be specified)
19 TYPICAL DRAWINGS/DATA
19.1 General arrangement
19.2 Foundation Plan
19.3 Control Scheme
19.4 Bill of materials
20 OVERALL DIMENSION & WEIGHT 2.DC Distribution Panel
B TECHNICAL PARTICULARS OF EARTH FAULT INDICATOR
21 Earth Fault Indicator for DC Co.
21.3 Reference Standard
21.4 Input Supply details
a)Voltage Normal/Max
d)Consumption VA
21.5 Fault sensing characteristics
a)Fault resistance level
b)Max. Permissible loop length/resistance of cable
d)No. of Sensors Provided
e)Max.No of outgoing feeder that can be covered
f)Mention if there are any limitations on outgoing feeder load current, fault current etc.,
21.6 Insulation level 1 Min. 50 Hz voltage withstand KV rms
21.7 Construction
a)Completely Compartmentalised Modular type
b)Working height limit from floor level
c)Construction such as Metal Clad, Fabrication Steel, aluminium house air Insulated etc.,
d)Suitable for mounting against building wall Yes/No
e)Degree of protection
f)Min.Thickness of sheet metal mm
g)Physical Dimension
21.8 Earth fault Indicator fully assembled wire and tested at factory
21.9 Earth fault Indicator section accessibility to individual compartments
21.1O Mounting arrangements
21.11 Design-Assembly
a)Drawout Modules of same type and rating are physically and electrically interchangeable
b)Whether of Modular type
c)Indicators provided for power ON/OFF
Positive Lead to ground Fault
Negative Lead to ground Fault
Identification of faulty feeder
d)Controls provided for
1)Positive accept
2)Negative accept
4)LED test switch
e)Audio alarms provided with details
f)Auxiliary annunciation provided for remote panel
g)Permissible maximum room temperature
21.12 Earth Terminal
21.14 Detailed Literature on construction working etc., enclosed
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR CONTROL CABLE
(Bidder should indicate the guaranteed technical date of all equipments/materials for each type of rating separately)
SL. No PARTICULARS
3 Manufacturer’s type designation
4 Applicable Standard
5 Rated voltage (volts)
6 Type & Category
7 Suitable for earthed or unearthed system
8 Continuous current rating when laid in air in a ambient temp. of 50°C and for maximum conductor temp. of 70°C of PVC Cables (For information only)
9 Ration factors applicable to the current ratings for various conditions of installation.
10 Short Circuit capacity
a)Guaranteed short circuit Amp. (rms) KA for 0.12sec duration at rated conductor temperature of 90 degree C, with an initial peak of 105kA.
b). Maximum conductor temp. allowed for the short circuit duty (deg. C) as stated above.
c) Cross section area (Sq.mm)
d) Number of wires (No.) minimum
e) Form of conductor
f) Direction of lay of stranded layer
12 Conductor resistance (DC) at 20°C per km - maximum
a) Composition of insulation
b) Nominal thickness of insulation (mm)
c) Minimum thickness of insulation
14 Inner Sheath
b) Calculated diameter over the laid up cores, (mm)
c) Thickness of sheath (minimum) mm
a) Type and material of armour
b) Direction of armouring
c) Calculated diameter of cable over inner sheath (under armour), mm
d) Nominal diameter of round armour wire (minimum)
e) No. of Armour wires/stripes
f)Short circuit capacity of the armour along for 1 second – for info. Only
g) DC resistance at 200C (Ω/Km)
16 Outer sheath
a) Material (PVC Type)
b) Calculated diameter under the sheath
c) Min. thickness of sheath (mm)
d) Colour of Sheath
a) Guaranteed value of minimum oxygen index of outer sheath at 270C *
b)Guaranteed value of minimum temperature index at 21 oxygen index *
c). Smoke density rating as per IEC 61034 *
d). Maximum HCL emission as per IEC 60754-1 *
e)All the factory acceptance test to be done as per relevant IS/IEC and KPTCL specification
18 a)Overall diameter of cable
b). Tolerance of overall diameter (mm)
a) Max./standard length per drum for each size of cable (single length) with ±5% Tolerance (mtrs)
b) Non standard drum lengths
20 Whether progressive sequential marking on outer sheath provided at 1 meter interval
21 Identification of cores
a) Colour of cores
22 Whether cables offered are ISI marked
23 Whether cables offered are suitable for laying as pr IS 1255
24 1) Continuous current rating of the cable
a) In ground at soil temperature 30°C and soil thermal resistivity of 150°C cm/watt and depth of burial about a metre (A)
b) In air at 40°C (A)
c) Overload capacity and duration (A, Hr)
d) Derating Factors for :
i) Soil temperature and thermal resistivity
ii) Ambient temperature
iii) Single core cables laid in trefoil circuits
2) General Technical Data (Power cables)
2.1) Equivalent star impedance per km of 3 Ph, circuit at power frequency at maximum conductor temperature (Ohm)
2.2) Maximum electrostatic capacitance per core per km of cable (F)
2.3) Maximum charging current per conductor per km at nominalvoltage (A)
2.4) Loss tangent at normal frequency and rated voltage
2.5) Maximum dielectric loss of cable per km at normal voltage and frequency Watts/km
2.6) Short circuit capacity for 1 Sec. KA (rms)
2.7) Short Circuit current capacity of armour (kA for 1 sec)
2.8) Maximum dielectric stress at core screen (kV/cm)
2.9) Maximum overall dia. of cable (mm)
3.0) Construction details including type of material used and thickness of each material for each type of cable in a tabular form.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR CROSS LINKED POLYETHYLENE INSULATED 11KV CABLES (11kV HT UG Cable)
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Sl. No. PARTICULARS Unit HT UG Cable
a) Name of manufacturer
b) Place of manufacture
3 Applicable specification & standards voltage Grade
4 Suitable for effective Earth/Unearth system
6 Permissible voltage & frequency variation for satisfactory operation
7 Continuous current for standard condition as per IS:
a) In air (450C) Amps
b) In Ground (450C) Amps
c) In Duct Amps
b) Shape of conductor
c) Nominal cross sectional area mm²
d) Number of wire: (min) No
e) Diameter of Wire : mm before compacting & strand Diameter mm
f) Maximum DC resistance of the conductor at 200C Ω/KM
9 Conductor Screening
c) Thickness (Min) mm
d) Continuous working temp deg.C
e) Max allowable temp at termination of short circuit deg.C
b) Thickness of Insulation (Nom) mm
i) Between Cores mm
ii) Between Cores & Inner Sheath
c) Minimum thickness of insulation at any one point (mm)
d) Extrusion Type
e) Specific insulation resistance at 900C Ohm-cm
11 Insulation Screening:
b) Min. Thickness of extruded semi conducting layer mm
c) Metallic Part: (Material)
d) Size of copper Tape mm
e) Whether over lapping provided
f) Short Circuit rating in 1 sec. KA
12 Inner Sheath
b) Extrusion Type
c) Thickness (Min) mm
d) Nominal Dia over Inner Sheath mm
b) Type of armouring
c) Nominal Dimension of Armour wire mm
d) Minimum Number of Armour wire
e) Whether Galvanised
f) Mass of Zinc coating gm/mm²
g) Nominal Dia over Armouring mm
h) Short Circuit rating in 1 sec KA
14 Outer Sheath
b) Extrution type
c) Min. thickness of sheath mm
d) Nominal Overall diameter of cable mm
e) Colour Minutes
15 Short circuit withstand capacity
a) Short Circuit withstand capacity KA
b) Duration of short circuit sec
16 AC resistance per core at operating temperature ohm/km
17 Reactance Ohm/Km ohm/km
18 Capicitance per core μF/Km
19 Allowable maximum conductor temperature when carrying current
20 Insulation resistance at 270C (Volume resistivity) ohm-cm
21 Loss tangent
22 Maximum cable charging current at normal operating voltage A/km
23 FRLSH Properties:
a. Min. Oxygen Index.
b. Min. Temperature Index.
c. Max. Halogen Acid gas generation.
d. Max. smoke density rating.
e. Max. light transmittance.
24 Recommended Minimum bending radius. mm
25 Safe pulling force. Kg
26 Cable weight Kg/Km
27 Length of cable per drum Mtrs.
Additional data
28 Core identification
29 Standard Packing Length and Tolerance Mtrs
30 Scheme of identification of the cable
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR MCVCB / PCVCB 11KV SWITCH GEAR COMPONENTS
(Bidder should indicate the guaranteed technical data of all equipment/materials for each type of rating separately)
1) Type of instrument
3) Whether magnetically shielded or not
4) Scale length and range
5) Whether tropicalised
6) Short time overload capacity
7) VA burden current coil
8) Power consumption of current coil
9) ISS grade of accuracy
10) Description leaflet
11) Temperature at which instrument calibrated
II. Multifunction Meter:
1) Type of Instrument
3) Whether magnetically shielded or not
4) Scale length & range
5) Whether tropicalised
6) Short time overload capacity
8) Power consumption
9) ISS grade of accuracy
10) Description leaflet
11) Temperature at which instrument calibrated
12) List of display parameters:
13) Communication protocol:
III. ELECTRONIC TRIVECTOR METER
1) Type and Rating
3) Whether magnetically shielded or not
4) Whether troplicalised
5) Rates VA burden – current coil - Potential coil
6) Continuous over load rating - Current coil - Potential coil
7) Accuracy class and grade
8) Adjustments provided
9) Limits of error at UPF and at 125% 25% and 10% of rated current
10) Limits of error at 0.5PF and at 125% 25% and 10% of rated current
11) Type of Registering Mechanism
12) Display sequence
13) Details of display a. Parameters that can be measured b. Details of print out parameters Refer Cl. 9.5.0 E
14) Whether the meter can be used to get demand details
15) Whether optical readout facility provided
16) Whether detailed literatures enclosed
17) Additional features provided
1 a. Type and particulars of windows b. Whether the annunciator is electro mechanical type Yes/No
1) Particulars of wiring
2) Rated voltage
3) Power consumption
4) Instantaneous making capacity of contacts
5) Breaking capacity
6) Overall dimensions of annunciator group
7) Descriptive leaflet of schematic diagram
V.(A) GENERAL PROTECTION RELAYS :
I The tenderer shall furnish guaranteed Technical particulars for all types of meters offered, in the following proforma (separate sheet shall be enclosed for each type of relay :)
1) Manufacturer's name or trade marks
2) Type designation
3) Size and mounting details (whether in draw out case)
4) Rated Values of both input and auxiliary energizing quantities
5) Values of the limits of the operative range(s) of the auxiliary energising quantity (ies)
6) Contacts data, Number and rating of main and auxiliary contacts
7) Rated value or setting range of the characteristic quantities and or angle
8) Limiting short-time thermal withstand values
9) Limiting dynamic values.
10) i. Burden data ( in case of poly input relays - data shall be furnished for appropriate set of input terminals). a. At highest tap - AC current / voltage coil b. At lowest tap - AC current / voltage (coil) ii. DC power consumption.
11) Impulse and dielectric test voltage(s)
12) Details of accessories (If essential to the relay performance)
13) Details of accessories (Optional items)
14) Whether provided with seal in trip contacts
15) a. Type of operating characteristics b. Accuracy of operating characteristics, operating time with details
16) H.F. disturbance test voltage (s)
17) Whether literature enclosed
18) Type of relay flag indicator and rating of target coil
VI (B) PROTECTIVE RELAYS
1 Non-directional IDMT Inst. OCREFR Relays
b) Current coil rating
c) VA burden 1) Highest tap 2) Lowest tap
e) Power consumption 1) Highest tap 2) Lowest tap
f) Time of operation at maximum dial setting at: 1) 5 times tap setting current 2) 10 times tap setting current
g) Type of characteristics
h) Whether drawout type or not
i) Trip Contact Rating amps.
j) Whether seal in contacts provided or not.
2 DIRECTIONAL OVER CURRENT RELAY
b) Current coil rating
c) VA burden i. Highest tap ii. Lowest tap.
e) Power consumption 1) Highest tap 2) Lowest tap
f) Time of operation at maximum dial Setting at: 1) 5 times tap setting current 2) 10 times tap setting current
g) Type of characteristics
h) Whether draw out type or not
i) Trip contact rating amps.
j) Whether seal in contacts provided or not
k) Minimum voltage at which relay operates
VII CIRCUIT BREAKER:
1 RATING a. No. of poles b, Rated voltage c. Rated normal current d. Rated frequency e. Making capacity in peak kA f. Breaking capacity : i) Symmetrical in KA and MVA i) Assymmetrical ii) The maximum Capacity of the Capacitor bank for which the breaker is designed to open g. Short time current in kA h, Operating duty
2 DETAILS OF SHORT CIRCUIT TYPE TEST CERTIFICATES
3 CONSTRUCTIONAL PARTICULARS: a. No. of breaks in series per pole b. Total length of breaks per pole c. Type of main contacts d. Type of arcing contacts e. Type arc control device f. Min. clearance in air a) Between live parts b) Between live parts and earth g. minimum clearance in VCB h. Mechanical endurance i. Electrical endurance j. Method of closing mechanism i) Type of operating mechanism ii) Whether hand or power or both iii) Whether the circuit breaker is designed to close and latch on making or is fitted with a making current release. iv) Whether the circuit breaker is trip free. v) Time required to charge the spring. vi) Details of spring charging motor power required at designed normal voltage k. Normal voltage of shunt trip coil l. Power required at normal voltage in VA
4 OPERATING PARTICULARS
a. a. Opening time
a) With no current b) At rated breaking current
b. Closing arc duration at
a) 10% SC breaking current b) 60% SC breaking current C) 80% SC breaking current d) 100% SC breaking current
c. Speed of Break at -
a) 10% SC breaking current b) 60% SC breaking current c) 80% SC breaking current d) 100% SC breaking current
VIII CURRENT TRANSFORMER:
a) Make b) Type C) Ratio d) Burden e) Accuracy class as per ISS
IX POTENTIAL TRANSFORMERS
a) Make b) Type c) Ratio d) Burden e) Accuracy class
X AUXILARY TRANSFORMER
a) Make b) Type C) Ratio d) Details of OFF load taps
1. size 2. Material 3. Whether insulated 4. Make/ type of busbar insulator 5. Creepage distance of busbar insulator
XII ELEVATING STRUCTURE
i. Sections used for main supports ii. Sections used for cross angles. iii. No./Size of foundation bolts. iv. Total weight support structure v. Total weight of circuit Breaker impact load to be Taken for design of foundation
Date Designation
Place Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR STATION AND YARD LIGHTING
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
LIGHTING SYSTEM: (Lighting Fixtures & Accessories (Data to be submitted separately for each type and size)
1 Manufacturer's Name and country of manufacture
2 Country of manufacturer for
3 Applicable standards for
4 Manufacturer's type and catalogue No. for
5 Nominal working voltage (volts)
6 Maximum permissible supply voltage variation for satisfactory operation of
a)fixtures(+,- O/L)
b)Accessories(+,- O/L)
7 Power factor at nominal working voltage and frequency
8 Full Load input current at Nominal working voltage (Amps)
9 Power loss per ballast at nominal working voltage and frequency (watts)
10 Maximum hot spot temperature of ballast case (0C)
11 Maximum average ballast winding Temperature(0C)
12 Ambient temperature within the fitting in continuous operation at the design ambient air temperature (0C)
13 Insulation class of ballast winding (0C)
14 Average life expectancy of
15 Lamp output at the design temperature
a)After 100 burning hours (Lumens)
b)After 1000 burning hours(Lumens)
16 lamp output at the end of the Expected life period (Lumens)
17 Average light output of the fitting as a percentage of lamp output
a)Downwards (%)
18 Beam angle for flood lights in
a)Horizontal plane (Degrees)
b)Vertical plane (Degrees)
19 a)Cable/Conduit entry size
b)Size and type of cable
20 Earthing terminal
b)Suitable for earthing conductor of size
21 Weights of Fixtures(kg)
22 a)Starting current & P.F for lamp (Amps)
b)Operating current (Amps)
c)Time Vs Mains current & P.F characteristics during starting enclosed (yes/No)
Reference cat No.
Conduits & Accessories (For each type & size)
1 Manufacturers name and country of manufacture
2 Manufacturers type designation
3 Applicable standards
4 Whether descriptive pamphlet is enclosed yes/no
Junction Boxes(For each type & size)
1 i)Manufacturer's name and country of manufacture
ii)Manufacturer's type designation
iii)Material specification
iv)Type of enclosure
b)Current rating (Amps)
c)Voltage rating (Volts)
d)Stud type (Yes/No)
e)Complete with insulated Barriers(yes/no)
vi)Whether descriptive pamphlet is enclosed? (Yes/no)
Lighting panels(for each type & size)
a)Manufacturers name and country of manufacture
b)Indoor/Outdoor applications
c)Design ambient air temp (0C)
d)Thickness of sheet steel(mm)
e)Degree of protection provided(as per IS:2147 or equivalent)
f)Bill of material for various Equipment giving make, type Rating., etc. enclosed(yes/no)
g)Colour of finish paint
ii. Temp rise at rated current over specified ambient (500c)
iii. Continuous current rating at 500C
iv. Whether suitable for one second current rating of 5 KA, A.C or 4KA, DC As applicable (yes/No)
v. Cross section
vi. Application standard
i)Control wiring
i. Material of conductor
ii. Size of conductor/dia of wire(2)
j)Conductor - solid/stranded
k)Terminal blocks
ii. Current rating
a)Power terminals (Amps)
b)Other terminals(Amps)
l)All tests are specified in specifications will be carried out (yes/no)
2 Air Break Switches (for each type of size)
a)Manufacturers name and country of manufacture
b)Manufacturers type description
c)Applicable standard
d)Rated voltage(volts) & frequency(Hz)
e)Rated current (Amps)
f)Rated Breaking current (Amps)
g)Maximum through fault current withstand derating factor for use under site ambient conditions
h)Temperature rise of contacts when carrying continuous rated current under site conditions (0C)
3 Fuses (For each type & size)
a)Manufacturers name and country of manufacture
b)Manufacturers type description
c)Applicable standard
d)Rated voltage(volts)
e)Rated current (Amps)
f)Whether fuse is mounted in an insulated carrier (Yes/No)
g)Whether fuse carrier has an Aperture for fuse failure indication (Yes/No)
h)Category of duty (IS:2208)
i)Rupturing capacities(Prospective Current)(KA)
j)Maximum led through current for 1sec(KA)
k)Whether time/current characteristics are enclosed (Yes/No)
4 Miniature Circuit Breaker(for each type and rating)
a)Manufacturers name and country of manufacture
c)Rated Voltage
f)Current Rating
i)Continuous at 50 degC Ambient(Amps)
ii)1 sec (KA rms)
g)Breaking capacity/single pole/Double Pole/Tripple pole)
i)Symmetrical (KA rms at volts)
ii)Asymmetrical (KA rms at volts)
h)Total interrupting cycle time
i)Type of blowout device
j)Type of overload(thermal/magnetic)
k)Terminal suitable for cable size pole/Tripple pole
l)Upto what fault current Discrimination between incomer fuse & M.C.B will be obtained
m)Miniature breaker conform to
5 Contactors(For each type DC/AC size)
a)Manufacturers name and country of manufacture
b)Rated voltage & permissible variation(volts)
c)Rated Burden(V.A)
d)Rated current(thermal) of main contacts
e)No. & type of Aux. contacts(if any)
f)Rated voltage of coil(volts)
g)Pick up voltage
h)Rated duty class
i)Drop off voltage
j)Applicable standard
Lighting Wires(For each Type & size)
1 Manufacturers name and country of manufacture
2 Standards applicable
3 Rated volatage(volts)
4 Continuous current rating when laid in conduit in an ambient Temperature of 50 degC (Amps)
b)Nominal cross sectional area (mm2)
c)Number & diameter of wires(No/mm)
a)Composition of insulation
b)Thickness of insulation
c)Tolerance on thicknes of insulation
d)Specific insulation resistance at 60 degC
7 Colour scheme for identification of wires
8 Whether descriptive pamphlet is enclosed yes/no
Painting, Printer, Finish Coat
1 Paints(for each type)
a)Manufacturers name and country of manufacture
b)Manufacturers type designation/brand name
2 Number of coats provided for
a)Junction Boxes
3 Applicable standards
4 Name and address of the contractor sub-contractor who shall supply, install and commision the lighting system in accordance with the Technical specifications
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR CAPACITOR BANK WITH SERIES REACTORS AND NEUTRAL CURRENT TRANSFORMERS:
(Bidder should indicate the guaranteed technical data of all equipment/materials for each type of rating separately)
I CAPACITOR UNITS
1 Standards applicable
2 Name of the make
3 Rated voltage of individual unit
4 Rated KVAR of each unit
5 50 C/S test voltage and duration between terminals
6 Impulse test voltage between terminals
7 Power frequency withstand volage-10secs
8 Capacitance of each unit
9 Continuous KVA for which the unit is designed
10 Temperature rise of container at rated output and at ambient of 45 degC
11 Tolerance for KVA output plus and minus
12 Maximum unbalance in phase current%
13 Details of voltage rise caused by the blow fuses (for internal fuse type)
14 Type of insulating liquid and quantity in each unit
15 Type of containers and thickness
16(i) a)Shape of basic element
b)Type of dielectric
c)Thickness of dielectric(by weight)
d)Thickness of dielectric layers between Aluminium foils
e)Voltage rating of each Capacitor (element)
f)Voltage stress
g)Is each element provided with fuse
(ii) Type of fuse
(iii) Make of fuse
17 Whether provided with internal over pressure dis-connector (yes/no)
18 Whether instruments to detect internal fuse failure is provided
19 Dimensions and weight
20 a)Material of dielectric
b)Dielectric loss per unit(watts)
c)Dielectric loss for the entire capacitor bank
21 Whether CRCA containers of unit capacitor provided with earthing terminals
22 Whether the unit capacitors and capacitor banks are of outdoor type requiring no protection from the direct rays of the sun and rain.
23 Upper limit and lower limit of temperature for which capacitors are designed
II CAPACITOR BANK
1 Rated voltage of capacitor bank
2 KVAR rating of capacitor bank at
a)Nominal system voltage
b)Rated voltage
3 Rated current at rated voltage
4 Rated frequency
5 Number of units in series and parallel in each phase of individual groups(schematic diagram of connections to be enclosed)
6 No. of banks offered
7 Over voltage to which the remaining units in series groups of phase leg are subjected when elements of unit capacitors be come defective(calculations to be enclosed)
8 Area required for the installation & clearance
III TECHNICAL PARTICULARS FOR REACTOR
1 Type and make
2 Reference standard
3 Rated voltage
4 Rated current
5 a)No. of phases 3 phase / 1 phase
b)Type of connection neutral side / line side
6 Rated capacity/inductance
7 Continuous rating in % of rated current of capacitor bank
8 Rated frequency
9 Compensation % of series reactor
10 Rated short time current and duration
11 Basic insulation level
a)Impulse withstand voltage KV peak
b)Power frequency withstand voltage KV rms
c)Switching surge withstand voltage KV peak
12 Reactance at rated output, rated MVAR
13 Description of wdg. Insulation
14 Winding resistance
15 Material of winding Cu/Al
16 Maximum current density A/Sq.mm
18 Maximum temp.rise
19 Terminal arrangement
20 Maximum system voltage for which reactor is designed
21 Type of shielding adopted in the reacor
22 Fitting and accessories
24 Noise level and ref. standard db
25 Vibration level
26 harmonic content if any
27 Approximate weight
IV NEUTRAL CURRENT TRANSFORMER
2 Manufacturers type designation
3 Rated voltage
4 Rated primary current
5 Rated secondary current
6 Secondary terminal voltage at normal current
7 Secondary terminal voltage at 10 times normal voltage
8 Core details: knee point voltage VA Class of accuracy
9 Rated current dynamic (peak value)
10 One minute power frequency dry withstand voltage KV/RMS
11 One minute power frequency wet withstand test voltage on secondaries KV/RMS
12 One min power frequency withstand test voltage on secondaries kv/RMS
13 1.2/50 Micro second impulse withstand voltage (KV/peak)
15 Mounting details
16 Overall dimensions
1 Rated voltage of the fuse
2 Current rating of the fuse link or refill unit
3 Maximum continuous current capability
4 Current rating of the fuse base of fuse carrier contacts
5 Time current characteristics for an ambient Air temp of 27 deg C Furnished/ Not furnished
6 Rated capacitive breaking current
7 Maximum values which the fuse can withstand for 5 and 100 discharges
8 Maximum available capacitor energy which the fuse can withstand at the specified voltage without bursting
9 Minimum pre arcing time and maximum total clearing time at inductive and capacitive power frequency current
10 Cold resistance of fuse link and percentage tolerance of resistance value.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR 11KV 400 A, SPECIAL (ROSTERING) G.O.S
Sl. No. Particulars 400 A, SPECIAL (ROSTERING) G.O.S 800A / 400A, Double break Isolators
1.0 Individual units
2 a)Unit description as per ISS-5350/part-III/ 1971
b)Mechanical strength as per clause 3.2 of IS-5350 part-III / 1871
2.0 Impulse withstand voltage test conducted as per IS-2544-1963
3.0 Power frequency withstand test
4.0 Puncture voltage
5.0 Creeping distance
6.0 Failing load as per IS 5350 part III /1971
7.0 Height of insulator(min)
8.0 Insulating part dia
9.0 Top metal fitting pitch circle dia
10.0 Bottom metal fitting pitch circle dia
11.0 a)No. of bolts
b)Bolts holes dia
c)Nominal dia of mounting face not to exceed
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF TOWERS
BIDDERS NAME AND ADDRESS
1 Standards adopted : i) Properties of Section
ii) Bolts and Nuts
iii) Galvanising
2 Minimum sheared edge distance (mm)
3 Minimum Rolled edge distance (mm)
4 Quality of Zinc used for galvanizing
5 Maximum percentage increase in structure Weight due for galvanization
6 Quality of Zinc required for galvanization Per MT of structurals
7 Size of bolts and nuts (including foundation bolts and nuts for support structure) i) Fasternes
iii) Foundation Bolts
8 i. Name of designer of Towers
ii. Name of fabricators of Towers
9 Maximum Working stress employed in design: i. Tension of net sectional area Kg/Sq.mm
ii. Compression of Gross Sectional area Kg/Sq.mm
iii. Shearing stress on bolts Kg/Sq.mm
iv. Bearing stress on bolts Kg/Sq.mm
v. Strut formula adopted for determining Crippling stress in designs Kg/Sq.mm
10 OTHER PARTICULARS:
i. Maximum slenderness ratio used in designs: a) Main members
b) Lattice members having nominal stresses
c) Redundant member having nominal stresses
d) Members under tension only
ii. Standards according to which properties of sections have been adopted in Design
iii. Standard specifications according to which the quality of steel for the sections assumed in designs.
iv. Standard to which galvanizing will conform
v. Minimum edge shear distances
vi. Minimum shear edge distances.
vii.Minimum rolled edge distances
viii. Quality of zinc required per Metric tonne of tower weight
ix. Sizes of bolts and bolt holes
x. Standards to which bolt holes confirm
xi. Maximum percentage increase in tower due to galvanizing
xii. Name of manufacturer of bolts and nuts
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
GUARANTEED TECHNICAL PARTICULARS OF TOWER FOUNDATIONS
BIDDERS NAME AND ADDRESS
I Properties of concrete used 1:2:4 Mix (M15) a) Effective weight in dry locations
b) Effective weight in wet locations
c) Maximum compressive strength
d) Maximum tension strength
e) Maximum bond strength
f) Maximum shear strength
g) Maximum punching shear strength
II Thickness of the minimum layer of concrete from the extreme edge of the concrete
III Minimum thickness of chimney: a) In wet locations
b) In dry locations
IV Quantity of cement required per Cmt. Of finished concrete: a) 1:2:4 Concrete
b) 1:3:6 Concrete
V Formula adopted for calculating side thrust:
The Bidder shall furnish a typical sketch of foundation for all types of foundation for all types of soil conditions with the Bid.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
GUARANTEED TECHNICAL PARTICULARS FOR DISC INSULATORS
BIDDERS NAME AND ADDRESS
Sl.No. Description Single Suspension Double Suspension Single Tension Double Tension
1 a) Type of Insulator (Ball and Socket)
b) Size and designation of ball and socket with standard to which it conforms ( mm)
2 Maker's Name and Address
3 No. of Insulator Discs/Long rod per string
4 Dimensions of Single Disc/Single long rod a) Disc Diameter in mm
b) Unit spacing in mm
c) Leakage/creepage distance
5 Mechanical values of single Disc/Single long rod a) Combined mechanical and electrical strength in KN.
b) Mechanical Breaking strength in KN
c) Routine mechanical test load in KN
6 Electrical values of Single Disc/Single long rod: a) Low frequency flash over voltage (dry) in KV:
b) Low frequency flash over voltage (wet) in KV
c) Impulse flashover voltage 1.2x50Cys Positive ----------KV Negetive----------KV
d) Power frequency withstand voltage of single disc/single long rod Dry ……………..kV Wet……………...kV
e)Impulse withstand voltage of single disc/long rod. 1.2x50 Cys Positive ……………. KV Negetive……………..kV
f)Power frequency puncture voltage kV of single disc/long rod.
6 Net weight of Insulator unit in kG.
7 Minimum visible discharge test voltage kV
8 Maximum RIV at 10 kV (RMS)
9 Standard specification to which the Insulators conform.
10 COMPLETE STRING: a) Total Creepage distance
11 Total length of string (Insulator only) in mm.
12 Power frequency withstand voltage of single Disc. a) Dry ………….. kV(rms) b) Wet……………kV(rms)
13 Impulse withstand voltage ……..kVP
14 Switching Impulse withstand voltage of single disce a) Dry …………KV(rms) b) Wet………….KV(rms)
15 Maximum Voltage distribution ……%
16 Reference drawing (Single Disc)
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
GUARANTEED TECHNICAL PARTICULARS FOR SILICON RUBBER HOUSED COMPOSITE INSULATORS
BIDDERS NAME AND ADDRESS
Sl.No. Description Single Suspension Double Suspension Single Tension Double Tension
1 Manufacturer’s name, address & country.
2 Bidder’s name, address & country
3 Size & designation of Ball & Socket(mm)
4 Standard to which Ball & socket will conform
5 Section length of insulator (mm)
6 No. of units per string
7 Number of weather sheds per unit.(nos)
8 Material of housing and weathershed
9 Creepage distance of insulator in mm.
10 Dry arc distance (mm)
11 Specified Mechanical Load (SML) of insulator in KN
12 Dry Power frequency withstand Voltage (KV rms)
13 Wet Power frequency withstand Voltage (KV rms)
14 Positive Lightning Impulse withstand Voltage under Dry condition (KVp)
15 Negative Lightning Impulse withstand Voltage under Dry condition (KVp)
16 Dry Power frequency Flash over Voltage (KV rms)
17 Wet Power frequency Flash over Voltage (KV rms)
18 Positive Lightning Impulse Flash over Voltage under Dry condition (KVp)
19 Negative Lightning Impulse Flash over Voltage under Dry condition (KVp)
20 Maximum RIV including CC rings, Arcing horns, Clamps etc. at 1.1 times maximum Corona inception Voltage (KV rms) line to ground voltage ( micro volts)
21 Corona extension Voltage (KV rms)
22 Whether details regarding method of fixing end fitting to FRP rod, method of detecting harmful cracks on FRP rod during crimping and method of manufacturing are enclosed.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
GUARANTEED TECHNICAL PARTICULARS FOR PORCELAIN LONG ROD INSULATOR
BIDDERS NAME AND ADDRESS
Sl.No. Description Single Suspension Double Suspension Single Tension Double Tension
1 Manufacturer’s name, address & country.
2 Bidder’s name, address & country
3 Size & designation of Ball & Socket(mm)
4 Material of disc
6 Type of locking device and its material
8 Tolerance on Core dia mm
9 Nominal length (Section length mm
10 Tolerance on Nominal Length mm
11 Dry Arcing distance mm
12 Shed profile (type) mm
13 Shed spacing mm
14 Shed profile (Regular/Alternating) mm
15 Shed dia (Big/Small) mm
16 Tolerance on Shed dia (Big/Small) mm
17 Minimum Creepage distance mm
18 Guaranteed mechanical load KN
19 Routine mechanical load KN
20 Material a. Weather sheds & housing with % contents of silicon b. End fittings
21 Power frequency withstand voltage of single unit a. Dry KV(rms) b. Wet KV(rms)
22 Impulse withstand voltage of single unit (Dry) a. Positive KV(peak) b. Negative KV(peak)
23 Switching surge withstand voltage (wet) KV(rms)
24 Minimum corona extinction voltage at 50 Hz AC KV(rms)
25 RIV at MHz for phase to earth of 305KV micro volts
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
GUARANTEED TECHNICAL PARTICULARS OF HARDWARE OF INSULATORS
BIDDERS NAME AND ADDRESS
Sl.No. Particulars Single Suspension Double Suspension Single Tension Double Tension
1 Maker’s Name and Address
2 Size and designation of ball and socket with standard to Which it conforms.
3 Details of Hardware a. Breaking strength kGs
b. Slipping strength kGS.
c. Dimensions mm
d. Length of string mm
e. Distance between arcing horn tips
f. Size of arcing horn i. Line side
4 Manufacturing process of dead end clamp whether cast or extruded
5 Angle of inclination of jumper terminal in case of dead end clamps.
6 Guarantee of conductivity of dead end clamp a. Results of heating cycle test carried out if any
b. Value of electrical resistance
7 Materials of security clips and pins used
8 Results of type test, routine and sample test carried out if any.
9 Components: Material with minimum Bending Strength chemical suspension tension composition a) Socket Clevis
c) Anchor Shackle
d) Clevis Clevis
h) Security Clip
k) Sag adjustment plate
l) Horn holder ball eye
m) Twisted shackle -- i. Whether the parts are designed for interchangeability for different types of string.
ii. Standard specifications to which the materials conform to
iii. Standarad specifications to which galvanising conforms to.
iv. Corona performance
v. Whether reference drawings attached
vi. Whcther reference type tests and other test report attached.
10 CLAMPS i. Type
ii. Material with chemical composition a. Clamp
b. Keeper plate
c. Side strap or link
iii. Slip strength
iv. Breaking strength
v. Magnetic Power loss in Watts.
vi. Electrical Resistance
11 PREFORMED ARMOUR RODS: a. Materials with chemical composition
b. Breaking strength
d. Conductivity
e. No. of Rods per set
f. Diameter of rod with tolerance
g. Length of rod with tolerance
12 BOLTS AND NUTS a) Make of Bolts and Nuts
b) Standard specifications to which Galvanising conforms,
13 COMPLETE STRING i. RIV at 266 kV in micro volts
ii. Minimum corona extinction voltage
iii. Maximum voltage across any disc
iv.Mechanical failing load Kgf
v. No. deformation load Kgf
14 Total weight of hardware
15 Whether hardware fittings are suitable for Hot line maintenance
16 Whether ball and socket meets the ‘GO’ and ‘NO GO’ gauge Test as per IS:2485 (Part-II 1972)
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
BIDDERS NAME AND ADDRESS
GUARANTEED TECHNICAL PARTICULARS OF ACCESSORIES OF ACSR CONDUCTOR AND 7/3.15mm GROUND WIRE
Sl.No. Description ACSR Conductor Ground wire
Mid-Span joint Repair Sleeves Mid-Span joint Repair Sleeves
1 Maker’s Name and Country
3 Suitable for Conductor size
4 Outside Diameter of Sleeves: a) Before Compression i. Aluminium
b) After Compression i.Aluminium
5 Inside diameter of sleeves before compression a. Aluminium
6 Length of Sleeves a) Before Compression i. Aluminium
b) After Compression i. Aluminium
7 Weight of Sleeves per joint a. Aluminium kG
8 Guaranteed breaking strength of the mid span joint as percentage of ultimate tensile strength of Conductor / ground wire given in the specification.
9 Conductivity of the compression joint expressed as percentage of the conductivity of the conductor/ground wire
10 Corona performance: a) Corona inception voltage (KV) rms i) Dry
b)Corona power loss per unit in Watts at rated voltage. i. Dry
c)Corona power loss per Unit in Watts at rated voltage i. Dry
d)Radio Interference Voltage at one mega hertz d1) Dry condition at: i. Normal rated line voltage
ii. 5% above rated line voltage
11 Full details of the hydrualic compressors and dies required
12 Guaranteed slip strength of the mid-span joints expressed as percentage of ultimate tensile strength of conductor/earthwire.
13 Resistance as percentage of measured resistance of equivalent of conductor.
14 Standard specifications to which the materials will be manufactured and tested.
15 Packing details
Guaranteed Technical Particulars for Vibration Dampers for ACSR Conductor and Ground Wire
Sl.No. Particulars ACSR Conductor 7/3.15mm Ground Wire
1 Maker’s Name and Country
3 Suitable for Conductor size
4 Total weight of each damper ( in kG)
5 Diameter of balancing weights (in mm)
6 Length of balancing weights (in mm)
7 Weight of each balancing weights (in mm)
8 Tolerance in balancing weights %
9 Slip strength of steel messenger cable
10 a) Diagram showing power dissipated by the damper in watts for various vibration frequencies and amplitudes.
b) Diagram showing the Vibration energy per conductor bundle for various frequencies under varied winds and spans
11 Natural frequency of Damper a) Upper (Cycles per second)
b) Lower (Cycles per second)
12 The Number of Dampers required per span for various span lengths and their spacings.
13 Position of fixing damper on each sub-conductor from the clamp mouth. a) At tension points i. First damper mm
ii. Second damper if required mm
b) At suspension points from the mouth of the clamp. i. First damper mm
ii. Second damper if required mm
14 Corona Performance a) Corona Inception Voltage i.Dry
b) Corona power loss per unit in watts at rated voltage. i. Dry
c) Corona power loss per unit in Watts at rated voltage. i. Dry
d) Radio interference voltage at one mega hertz. d1) Dry condition at : i. Normal rated line voltage
ii. 20% above rated voltage
d2) Wet condition at : i. Normal rated line voltage
ii. 5% above the rated line voltage
15 Test report of the damping characteristics and energy dissipation.
16 Whether a write up explaining the suppression of aeolian vibration and the sub-conductor oscillation by vibration dampers is given in the tender.
17 Max. bending amplitude under given conditions with 2 dampers per span per sub-conductor.
18 Damping efficiency of the damper.
19 Wind velocity range for which damper will be effective.
20 Standards to which materials will be manufactured and tested
21 Packing details
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
DETAILS OF TYPE TESTS CONDUCTED
(All the names of type tests and IS/IEC Nos. to be clearly mentioned)
BIDDERS NAME AND ADDRESS
Sl.No. Particulars of type test Certificate detail Nos. etc. Date of Test Laboratory where conducted
I DISC INSULATOR 120 KN/90KN (AS PER IS 731) a) Visual Examination
b) Verification of dimensions
c) Visible discharge test
d) Impulse voltage withstand test
e) Wet power frequency voltage withstand test
f) Temperature cycle test
g) Electromechanical failing test
h) Mechanical failing load test
i) 24 hours Mechanical strength test
j) Puncture test
k) Porosity test
l) Galvanising test
m) Radio interference test
II INSULATOR HARDWARE (AS PER IS 2486) a) Slip strength test for clamps
b) Mechanical test for clamps
c) Electrical resistance test for tension clamps
d) Heating cycle test for tension clamps
e) Verification of dimensions
f) Galvanizing test/electroplating test
g) Visual examination
h) Mechanical strength for complete string units.
III ACSR CONDUCTOR (AS PER IS-398 and other relevant standards) a) Visual Examination
b) Measurements of diameter of individual wires
c) Measurement of lay ratio
d) Breaking load test
e) Ductality test
f) Wrapping test
g) Resistance test
h) Galvanizing test
i) Load test on composite conductor
j) Surface condition test
l) Radio Interference test
IV ACCESSORIES FOR ACSR CONDUCTOR AS PER IS 2121 and other equivalent standards
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS FOR FIRE FIGHTING EQUIPMENTS
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
SL.NO TECHNICAL PARTICULARS OF PRESSURISED WATER TYPE FIRE EXTINGUISHERS-PORTABLE
1.01 Manufacturer
1.02 Number offered
1.03 Guaranteed Performance
i)Capacity, litters
ii)Maximum effective range when Tested in still air condition, M
iii)Minimum period during which the jet shall be maintained at a length of not less than 6m secs.
iv)Maximum period for discharge of 95% of the solution secs.
1.04 Construction Features:
i)Relevant standard and method of operation
ii)Test pressure of extinguisher body kg/cm2 g
iii)Whether handle is provided (YES/NO)
iv)Provided seal to indicate that the Extinguisher has not been used? (YES/NO)
1.05 Material of construction(specify code/standard No.)
1.06 Approximate weight of Extinguisher (cylinder filled kg)
1.07 Dimensions in mm.
i)Cylinder length
ii)cylinder diameter
iii)Cylinder body thickness
iv)External diameter of extinguisher
v)Overall height of extinguisher
vi)Throat diameter of nozzle
1.08 Codes and Standards followed
1.09 Supplied First Charge (YES/NO)
1.1O List of Accessories provided
1.11 Necessary and condition of Refilling
1.12 Drawing/Literature Enclosed with offer? (YES/NO)
1.13 Whether Approved by Tariff Advisory committee of India? (YES/NO)
1.14 TECHNICAL PARTICULARS OF DRY CHEMICAL POWDER TYPE EXTINGUISHER-PORTABLE
1.14.1 Manufacturer
1.14.2 Number offered
1.14.3 Guaranteed Performance
i)Capacity, litres
ii)Maximum effectice range when tested in still air condition, M
iii)Minimum period during which the jet shall be maintained at a length of not less than 6m secs.
iv)Maximum period for discharge of 95% of the solution secs.
1.14.4 Contruction features
i)Relevant standard and method of operation
ii)Test pressure of extinguisher body.
iii)Test pressure for hose(if any)
iv)Whether handle is provided (Yes/No)
v)provided seal to indicate that the extinguisher has not been used? (Yes/No)
vi)Chemical charge in container
vii)Gas used for transporting the Dry powder
1.14.5 Material of construction
vi)Hose, if any
1.14.6 Approximate weight of Extinguisher(cylinder filled)
1.14.7 Dimensions in mm.
i)Cylinder length
ii)cylinder diameter
iii)Cylinder body thickness
iv)External diameter of extinguisher
v)Overall height of extinguisher
vi)Throat diameter of nozzle
vii)Length & size of hose, if any
1.14.8 Codes and Standards followed
1.14.9 Supplied First Charge of chemical
1.14.10 List of Accessories provided
1.14.11 Necessary and condition of Refilling
1.14.12 Drawing/Literature Enclosed with offer?
1.14.13 Whether Approved by Tariff Advisory committee of India?
1.15 TECHNICAL PARTICULARS OF CARBON DIOXIDE TYPE EXTINGUISHERS-PORTABLE
1.15.1 Manufacturer
1.15.2 Country of origin
1.15.3 Year of manufacture
1.15.4 Numbers offered
1.15.5 Guaranteed Performance
ii)Maximum effective range when Tested in still air condition
iii)Maximum period for discharge
1.15.6 Construction Features:
i)Method of operation
ii)Test pressure of extinguisher body
iii)Pressure test connection provided on body (Yes/No)
iv)Gas being used as pressuring medium
1.15.7 Material of construction
1.15.8 Approximate weight of Extinguisher(cylinder filled)
1.15.9 Dimensions in mm.
i)Cylinder length
ii)cylinder diameter
iii)Cylinder body thickness
iv)External diameter of extinguisher
v)Overall height of extinguisher
vi)Throat diameter of nozzle
1.15.10 Codes and Standards followed
1.15.11 Supplied First Charge of chemical (Yes/No)
1.15.12 List of Accessories provided
1.15.13 Necessity and condition of Refilling
1.15.14 Drawing/Literature Enclosed with offer? (Yes/No)
1.15.15 Whether Approved by Tariff Advisory committee of India? (YES/NO)
1.16 TECHNICAL PARTICULARS FOR NITROGEN INJECTION FIRE EXTINGUISHING (for 10MVA & Above).
1.16.1 Power supply
1.16.2 Control Box -- 220/110V DC
Fire Extinguishing cubicle(lighting) -- 230V AC
1.16.3 Fire Extinguishing cubicle for 100MVA,31.5 MVA 20MVA , 10 MVA capacity
Nitrogen cylinder capacity
1.16.4 Fire Extinction period
On system activation
On commencement of Nitrogen injection
1.16.5 Control Box
1.16.6 Fire Detectors
Heat Sensing temperature
GUARANTEED TECHNICAL PARTICULARS FOR NITROGEN INJECTION FIRE PROTECTION SYSTEM FOR TRANSFORMERS (for 10MVA & Above).
1 Name of manufacturer and country of origin
2 Reference standards
3 Details of system equipments
a. Fire extinguishing cubicle
iii)Capacity of Nitrogen cylinder
iv)Pressure of Nitrogen filling
v)Minimum distance of FE cubicle from the transformer
vi)Method of mounting
vii)Whether the following items are provided in FE cubicle. If so furnish make, type & other details
- Contact manometer
- Pressure regulator
- Oil release unit
- Gas release unit
- Oil drain assembly
- Pressure / limit switches
- No. of contacts & spare contacts(NO & NC)
viii)Oil drain valve
- Type of metal
ix)Nitrogen Injection valve
- Quantity required
x)Oil Drain pipe
xi)Nitrogen Injection pipe
- Number of openings in the transformer tank
iii)Type & Thickness of sheet steel
iv)Details of components provided in the control box
v)Control voltage
vi)Method of mounting
vii)Whether audio and visual alarms provided?
c)Transformer Conservator Isolator Valve (TCIV) (Main /Backup)
iv)Whether suitable for pipe of size 80mm dia
v)No. of contacts & spare contacts (NO & NC)
d)Fire Detectors/ Linear Heat Detectors
iii)Quantity Required
iv)Method of Fixing
v)Effective heat sensing area
vi)Temperature recommended for effective heat sensing
vii)Number of contacts NO/NC
iv)Method of mounting
iii) No. of cores & size.
4 Time of operation
Transformer Tank Explosion Prevention Fire Protection
a. For system activation
b. For reduction of pressure in the tank/for extinction of fire, by nitrogen release
5) Whether details literature/ drawings furnished
6) Details of Pre-commissioning tests to be conducted
7) Any other technical details not covered above.
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
BIDDERS NAME AND ADDRESS ALONG WITH GSTIN NUMBER
GUARANTEED TECHNICAL PARTICULARS
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Technical Parameters Remote Terminal Unit
General Requirements
1.01 Name of the manufacturer
1.02 Type of RTU
1.05.1 Analog Inputs
1.06 Communication Port
1.08 Suitability
1.09 Site Survey
1.1 Functional Requirements
1.11 Programmable Logic Capability
1.12 Communication Interface
1.15 Intelligence level
1.16 Expandability
1.17 Communication Media
1.18 Slave Mode
1.19 Scan Groups
1.2 Exception Reporting
1.21 Time Synchronisation
1.22 Power Supply
1.23 P/S Protection
1.24 Power Failure
1.25 Grounding and Protection against EPR
1.26 Redundancy
1.27 Multi Drop
1.28 DDTA(Data Delivery Time Analysis)
1.31 RTU Address
1.32 I/O Requirements
1.32.01 Analog Input
1.32.01.A.a Interface
1.32.01.A.b Maximum No. of MFTs in Daisy Chain
1.32.01.A.c Wiring
1.32.01.A.d Supply
1.32.01.A.e Outputs
1 System Volts in kV
System Current in A
2 System Volts THD %
System Current THD %
3 Volts L1-N in kV
Volts L2-N in kV
Volts L3-N in kV
4 Volts L1- L2 in kV
Volts L2- L3 in kV
Volts L3- L1 in kV
5 Volts L1-THD %
7 Current L1-Thd %
Current L2 -Thd %
Current L3 -Thd %
8 Neutral Current
10 kWh (7 digit Resolution)
11 kVArh (7 Digit Resolution)
13 MW Maximum Demand
Current Maximum Demand
14 Primary Current
15 Demand Integration Time
17 Pulse output Durations
Pulse Rate Devisors
19 RS-485 Parity
20 Mod-Bus Address
22 Max Voltage:
Short Duration:
Short Duration:
26 Max. Burden:
29 Measuring Ranges:
31 Up Date time
34 Operating Temp
Relative Humidity
1.32.02 A/D Converter
1.32.03 Digital Inputs
1.32.04 Status Input Requirements
1.32.05 Single Contact Digital Status input (SS)
1.32.06 Double Contact Digital Status input points (DS)
1.32.07 Three State Status
1.32.09 Binary Coded Decimal Input (BCD)
1.32.10 Binary Word Input
1.32.11 Digital Outputs (D/O)
1.32.12 Two State DCO
1.32.13 Two State Momentary Control Relay
1.32.14 Latching Contact Output
1.32.15 Control Security
1.32.16 Rise/Lower Pulse Outputs
1.32.17 Digital Word Output
1.33 Maintenance Port
1.34 Support Facilities
1.35 Remote Downloading to RTU
1.36 Maintenance Support
1.37 Interface Cabinets
1.38 Enclosures
1.39 Interconnections
1.4 Terminal Blocks
1.43 Noise Level
1.44 Environmental
1.45 Critical Up time
1.47 Maintainability
1.54 Initialization/Restart
1.55 Monitoring
1.57 Diagnostics
1.58 Interposing Relay/Opto Couplers/Opto Isolators
1.59 DC transducer
2.02 Current Cables
2.03 Voltage Cables
2.04 Signal Cables
2.05 Control Cables
2.06 Supply Cables
3 RTU INSTALLATIONS
3.01 Power Supply
3.02 LT-AC Panel
3.03 Positioning
3.05 RTU Ground
3.06 Wiring Diagrams
3.07 Circuit Diagram
3.08 Terminal Block
3.09 Interface to Communication Equipments
3.11 Inspection
3.12 Scheme diagram
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
GUARANTEED TECHNICAL PARTICULARS
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Technical Parameters UPS with Battery
General Requirements
1.01 Name of the manufacturer
1.02 Supply Voltage for UPS
1.03 Operating Frequency
1.04 Rectifier Module
1.05 Inverter Specification
1.06 Protection
1.07 Output Indications
1.09 Panel Meters
1.1 Bypass Arrangements
2 Isolation Transformer
2.02 Electrical Specification
2.02.01 Power Rating
2.02.03 Cooling
2.02.04 Winding
2.02.05 Input Supply
2.02.07 Transformation Ratio
2.02.08 Protection
3.01 Battery Sets
3.05 Battery Stand
3.06 Accessories
3.07 Charging and Discharging
3.08 Commissioning
Place Designation
Name of the Company
Karnataka Power Transmission Corporation Limited
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
BIDDERS NAME AND ADDRESS ALONG WITH GSTIN NUMBER
GUARANTEED TECHNICAL PARTICULARS
(Bidder should indicate the guaranteed technical data of all equipments/materials for each type of rating separately)
Technical Parameters Data Concentrator Unit
General Requirements
1 Name of the manufacturer
1.02 General Specification
1.03 Operational Requirement
1.04 Communication
1.05 Hardware Specification
1.06 Software Specification at Control Centre
1.07 Operating Temperature
1.08 Power requirement
1.10 Environmental and Safety Standards
1.11 Installation of DCU
Place Designation
Name of the Company
KARNATAKA POWER TRANSMISSION CORPORATION LIMITED
Bid Enquiry No: KPTCL/2026-27/SS/WORK_INDENT3786
1.Establishing 2x20MVA, 110/11kV GIS Sub-station at BIMS(Civil Hospital) in Belagavi Taluk & District, 2.Construction of 1No. of 110kV Terminal Bay at 110/33/11kV Neharu Nagar Sub-station for terminating proposed 110kV class 630sqmm XLPE UG cable from proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, 3.Laying of 110kV class, 630sqmm XLPE UG cable for a distance of 2.164km from existing 110/33/11kV Neharu Nagar Sub-station to proposed 110/11kV GIS Sub-station at BIMS (Civil Hospital) in Belagavi Taluk & District, on Partial Turnkey basis, including Supply of all matching Materials/Equipments (Excluding Supply of 11kV Switchgear), Erection (including Civil Works) of all Materials/Equipments, Testing and Commissioning.
TECHNICAL DATA SHEET
GUARANTEED TECHNICAL PARTICULARS OF SUB-STATION AUTOMATION
Sl.No. Particulars
A SUBSTATION AUTOMATION SYSTEM MASTER CONTROL UNIT OF HMI
a) Name and Country of Manufacture.
b) Manufactures type and designation
c) Memory capacity
Operating system software type
d) Type of drives provided
i) 3.5” Floppy & MG drive.
ii) Magnetic optical drive (rewritable)
e) Update time of
i) digital input
ii) Analog Input
f) Response time for
i) Alarm Function
ii) Control Function
g) Response time for
i) Alarm function
ii) Control function
h) Whether semi of fully colour graphic type
i) Total number of bay units which can be connected without effecting the response/update time of the system
j) Whether facility and hardware for transfer of data to remote sub-station motorized.
k) Communication protocol adopted for
l) Applicable standard
m) Type of auxiliary supply required
n) Speed of data processing in instruction per sec.
o) List of manufacture whose bay units can be connected to master unit without additional.
p) Whether equipment offered is of industrial grade
q) All necessary software provided for proper functioning of the system as a whole.
r) List of all software provided
s) Max. Possible distance return bay unit & master.
v) Power Consumption
ab) Processor speed
ad) Cache Memory
ae) Communication Port
B BAY CONTROL UNIT
a) Name of Country of Manufacture
b) Manufacturers type and designation
c) Type of Mounting
d) No. of bay control units offered
e) Memory capacity
f) Data Storage capacity
g) Standard applicable
h) Rated auxiliary voltage
i) Rated frequency
j) No. of binary inputs
k) No. of outputs
m) Type of Communication protocol
n) No. & type of communication port
o) Operation temperature range
p) System response time
q) (i) Exchange of display
ii) Presentation of binary change
iii) Presentation of analog change
iv) Order to process output
v) Order to update display
vi) Report generation
vii) Max. temperature
r) Whether data is received on failure of unit. If yes, indicate the duration
s) Speed of transmission between bay and Master control unit
t) No. of inputs it can accommodate (specify voltage & current separately)
u) Resolution for digital inputs
v) Update time of
a) analog inputs
b) digital inputs
w) Whether data processing is done in bay unit or master control unit.
x) Power concentration
i) Name & county of Manufacture
ii) Manufactures type & designation
iii) Whether standard or the numerical keyboard included in the programming terminal.
D) Local Area Network LAN
3) Communication Medium
5) Maximum distance
E) Network Operating system
F) SCADA Software
2) Operating system
3) Facilities Provided (Full details to be enclosed in separate sheet)
1) Colour Printer
2) Manufacturer name
3) Country of Manufacture
5) A3 and A4 size paper supplied
6) Throughput rate
8) Available data interface
9) Print colour
10) Max. Temperature
11) Max. Humidity.
G(b) Alarm/Event Printer
1) Manufacturer name
2) Country of Manufacture
5) Paper Loading Facility
9) Available Data Interface
10) Print Colour
11) Max. temperature
12) Max. Humidity (Rh.)
1) Manufacturer name
2) Country of Manufacture
6) Available Data interface
H Following information is attached separately with the bid
a) Type, Make and Model No. for each item/sub-item with relevant catalogues / descriptive information Yes/No
b) List of installation of similar Equipment now in service with contact Yes/No
Persons name and address Yes/No
Detailed drawing with dimensions of each equipment panel and interfaces Yes/No
Full functional description specific to project along with proposed Architecture/scheme enclosed Yes/No
I SYSTEM SOFTWARE
1) Multitasking operating system
2) Background executive
3) File handling utility
4) Magnetic tape/disk data transfer utility
5) Online debugger
6) Object Module library utility
7) Report generator utility for display & Print
8) Communication utility
9) Graphic display generation utility
10) Online system backup capability
11) Test and Maintenance Programs (Diagnostic software)
12) System generation at site
13) Data base utility
14) Data acquisition, processing and alarm monitoring/reporting
15) Communication
16) Operator interface (MMI)
17) Network Operating system
18) Utilities like debugging and software downloading
19) Mathematical and logic function
II PROCESS SOFTWARE
1) Plant data base
2) Control software
3) Graphic display with points assignment
4) Logs or reports with points assignment
5) Software for communication with external computer system
6) Relay setting software
7) Any other software.
Note: Bidder shall supplement information in this Data Sheet with a write up on each topic
Processing capacity
Programmable real time clock Yes/No.
Watch dog timer Yes/No
Auto Restart Yes/No
Time synchronization Yes/No
PROCESS INPUT SYSTEM
No. of high resolution inputs
Name of the Company
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Tender doc BIMS WI3786.docx
Tender Document • 0.55 MB
Sec 7 Tech spec.zip
Others - Technical Specifications • 37.15 MB
NIT BIMS dtd 04-06-26.pdf
Tender Document • 1.86 MB
Sec 11a Techno Com_WI3786.xlsx
Technical Information / Worksheet • 1.47 MB
Circulars and Guidelines.zip
Tender Document • 3.25 MB
sec 8 Drawg n sketch.zip
Others - Drawings n sketches • 3.10 MB