Loading…
Loading…
Tender Value
₹3.9 L
EMD Value
₹7,886
Closing Date
2 Jul 2026, 3:00 pmDue tomorrow
Similar tender results from the same govt authority in the past 3 years.
Director TMC
Engineering services, Ground Floor, Pusph Building, ACTREC Kharghar Node, Navi Mumbai - 410210
Work place for Anaesthesia Consultant at M-OT,7th floor RRS Bldg,ACTREC
2026_TMC_912001_1
CB/ ET-15/WORK PLACE FOR ANAESTHESIA CONSULTANT/2026
Open Tender
Civil Works
60 days
ACTREC, Kharghar
as per Tender Document
5 documents required · 5 mandatory
₹0
₹7,886
ACTREC,Kharghar
11 Jun 2026
11 Jun 2026
3 Jul 2026
11 Jun 2026
2 Jul 2026
11 Jun 2026
11 Jun 2026 - 18 Jun 2026
18 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Civil Work | - | - | - | - |
| 2 | Supply and installation of Double skin modular wall panels made of 0.8mm thick GI powder coated sheets on both sides with PUF of density 40±2kg/m³ as infill, GI profiles for reinforcement along the periphery, floor track suitable to accommodate the epoxy floor flush with wall panel. Joint shall be sealed with cleanroom compatible silicon sealant. The Thickness of Panel shall 80mm with Riser Panel arrangement (Including Prefilter, Damper & Riser Grill - all clean room compliant) wherever required as per the instruction of Engineer In charge and as per approved drawing. The panels should certified for use in clean room facility with 60 minutes fire resistance certification. Including providing and fixing of PVC conduit 32 mm in the wall panels and Factory made cut-outs concealed in wall panel for Electrical sockets, switch boards, MGs, etc. Including provision of Vision Glass Panel made from 6mm thick Toughened Glass completely sealed with appropriate sealant for the size in the drawing and completely integrated to the wall panels as perthe drawings and instruction from Engineer incharge. | 14.4 | Sqm | - | - |
| 3 | Supply and installation of 46 mm thick doors made with PU painted 0.8mm thick GPSP sheets on both sides with PUF as infill, 1.2 mm thick GPSP powder coated sturdy door frames, hardware like SS push plate, SS 'D' handle on both sides, SS ball bearing butt hinges, Stainless steel push plates on push side. - SS 304 ( With Engraving ), Double glazed view panel of std.size , Dorma TS-71 Std.arm door closure for active leaf, concealed flush bolt for double door and provision for automatic bottom drop seal, Stainless Steel kick plates SS 304 etc. Item includes cost of supply and installation of all accessories and fixtures as mentioned above excluding door interlock and door access control and should be clean room compliant fixtures. Alongwith provision of toughened Vision glass/View Panel with 30mm thick border and silicon sealant if required flushed with door and Automatic door bottom seal. Includes provision of door frame. | 2.4 | Sqm | - | - |
| 4 | WOODEN CABINET Providing & fixing cabinet made up of 19 mm. Commercial ply of approved make for top, bottom, sides & shelves & 8mm commercial ply approved make for back side Door shutter made up of 19mm thick commercial ply and outer surfaces and top of shelves for open type cabine should be laminated with 1.5mm thick approved plastic laminate sheet of required colour including all brass fittings such as hinges, tower bolts, ball catches, stopper, handle, kNosbs as per shown in drawing or approved by Engineer-In-Charge etc.and all exposed edges lipping with 6mm Thick T.W. lipping patti.locking arrangement with Godrej multipurpose lock etc. all complete as specified & directed by Engineer-In-Charge. With shutter | 6 | sqm | - | - |
| 5 | COMPUTETR TABLE Providing making & supplying computer table made out fo 19mm commercial ply for table top, mounted on the vertical side fo 19mm commercial ply and cabinet made out of 19mm commercial ply for sides, shelves & shutters making concealed monitor arrangement by providing 8mm thick clea r glass on table top of required size with edge polish as shown in drawing drawer and ready made key board drawer with heavy sliding channels with powder coated handle for shutter,cable manager drawers all edges shall be lipped with 6mm thick T.W. lipping patti. All exposed faces should be 1.5mm thk laminate of approved colour and non laminated area should be french polished inclu. cost of other materials labor etc. as per drawing and as specified and directed by Engineer-In-Charge. | 5 | Rmt | - | - |
| 6 | ELECTRICAL WORKS | - | - | - | - |
| 7 | Submain Wiring from DB to sockets | - | - | - | - |
| 8 | SITC of Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed PVC conduit as required. 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire including PVC conduicts , bends , and all fixing accessories ( Rate for one mtr circuit i.e. 3 x 2.5sqmm wire) for power points | 325 | Rmt | - | - |
| 9 | LIGHTING | - | - | - | - |
| 10 | LED Panel light 2x2 ft. (System lumen efficacy ≥105 <120 lm/Watt)Supplying, installation, Testing & Commissioning of Panel light 2x2 ft., of following body material andconstruction as per IS : 10322 with driver as per the requirement with Driver efficiency >85%, Operatingvoltage AC 140-270 Volt, frequency 50/60 hz, Operating temp range -5 0C to 40 0C, internal
surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80,UGR (Unified Glare Rating) < 19, Flicker free, (flicker should be below 5 %), life time (LED, Driver& electrical circuitry), of minimum 50000 Burning Hours with, 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K/6500°K (As per ANSI Bin), SDCM(Standard Deviation Colour Matching) <3, Maximum powerconsumption should not more than the specified rating and Fixture shall be of relevant BIS standard.Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c external connections with 1.5 sq mm FRLS/HFFR, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output.
LM79 & LM80 Test report and all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminium housing such that LED junction temperature shall not rise above 90°C). | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.87 MB
BOQ_958500.xls
BOQ • 0.34 MB
TD.pdf
Tender Documents • 1.49 MB
AnnexureForm.xls
Additional Documents • 0.12 MB
Download all tender documents and submit your bid