Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹3.1 LAccepted-AOC | ₹3.1 L | 1 | Accepted-AOC Being L1 bidder |
| 2 | 2₹3.3 L+₹13,641 (4.35%)Rejected-AOC | ₹3.3 L+₹13,641 (4.35%) | 2 | Rejected-AOC Being L2 bidder |
| Sl No | Description | Qty | Unit | AAKASH ENTERPRISES L2 | Parth Trading L1 |
|---|---|---|---|---|---|
| 1.00 | Active Power Transducer
(MW Transducer)
Should have following specifications :-
(a) 3 phase 4 wire voltage & current unbalanced
(b) Input: - 63.508V AC, 0 - 0.8748 A , AC 50 Hz.
(c) Aux. Power Supply:- 220 V AC/DC
(d) Accuracy: - ±0.5% of span.
(f) CTR :- 1600/ 1 A ,AC 50 Hz.
(g) Range: - 0-16 MW.
(h) with LCD display, Fully onsite programmable input voltage range and input current range, Measuring range programmable, onsite selectable output type( DC current/ DC voltage), Output range Programmable
(i) Output :- Dual isolated 4-20 mA DC
(j) Make: AE,Masibus, Rishabh, Southern, Minilec, Meco or equivalent | 2 | Nos. | 8,775 ₹10,354.5 Lowest | 8,880 ₹10,478.4 |
| 2.00 | Active Power Transducer
(MW Transducer)
Should have following specifications :-
(a) 3 phase 4 wire voltage & current unbalanced
(b) Input :- 63.508V AC, 0 - 1.021 A ,AC 50 Hz.
(c) Aux. Power supply: - 220 V AC/DC.
(d) Accuracy: - ±0.5% of span.
(e) PTR:- 6600/√3/110//√3 V, AC 50 hz
(f) CTR :- 3000/ 1 A ,AC 50 Hz.
(g) Range: - 0-35 MW.
(h) with LCD display, Fully onsite programmable input voltage range, Measuring range programmable, onsite selectable output type( DC current/ DC voltage), Output range Programmable
(i)Output:- Dual isolated 4-20 mA DC
(j)Make: AE,Masibus, Rishabh, Southern, Minilec, Meco or equivalent | 2 | Nos. | 8,775 ₹10,354.5 Lowest | 8,880 ₹10,478.4 |
| 3.00 | AC Voltage Transducer
Should have following specifications :-
(a) Input :- Nominal 110V, AC 50 Hz
(b) Range Input :- 0-166.667 V AC.
(c) Aux. Power supply: - 220 V AC/DC.
(d) Accuracy: - ±0.5% of span.
(f) Range :- 0-10KV
(g) Output: - Dual isolated 4-20mA DC.
(h) with LCD display, Fully onsite programmable input voltage range, Measuring range programmable, onsite selectable output type( DC current/ DC voltage), Output range Programmable
(i) Make: AE,Masibus, Rishabh, Southern, Minilec, Meco or equivalent | 4 | Nos. | 4,680 ₹5,522.4 Lowest | 5,300 ₹6,254 |
| 4.00 | AC Current Transducer
Should have following specifications :-
(a) Input :- 0-1A, AC 50 Hz
(b) Aux. Power supply: - 220 V AC/DC.
(c) Accuracy: - ±0.5% of span.
(d) Output: - Dual isolated 4-20mA DC.
(e) with LCD display, Fully onsite programmable input voltage range, Measuring range programmable, onsite selectable output type( DC current/ DC voltage), Output range Programmable
(f) Make: AE,Masibus, Rishabh, Southern, Minilec, Meco or equivalent | 15 | Nos. | 4,680 ₹5,522.4 Lowest | 5,300 ₹6,254 |
| 5.00 | Watt Transducer
(a) Range : 0-250 MW
(b) Input : 0-873 W
(c) PTR : 15.75√3KV/110√3V
(d) CT : 10000/5A
(e) Output : 4-20 mA DC (Dual Output)
(f) Make : AE, Rishabh, Southern, Minilec, Meco or equivalent
(g) Fully onsite programmable input voltage range and input current range with LCD Display
(h) Onsite selectable output type (DC current / DC voltage).
(i) Aux Supply : 220 V DC / AC ( both),
(j) Type : 3Phase 4 wire | 2 | Nos. | 8,785 ₹10,366.3 Lowest | 8,800 ₹10,384 |
| 6.00 | Watt Transducer
(a) Range : (-) 228.6 -0 - (+) 228.6 MW
(b) Input : (-) 190.5 – 0 - (+) 190.5 W
(c) Output : 4-12-20 mA DC (Dual Output)
(d) PTR : 220KV√3/ 110√3V
(e) CTR : 600/1 A
(f) Accuracy : ± 0.5%
(g) Aux Supply : 220 V DC / AC (both),
(h) Make : AE, Rishabh, Southern, Minilec, masibus or equivalent
(i) Fully onsite programmable input voltage range and input current range with
LCD display
(j) Onsite selectable output type (DC current / DC voltage).
(k) Type : 3Phase 4 wire
(l) Make: AE,Masibus, Rishabh, Southern, Minilec, Meco or equivalent | 5 | Nos. | 8,775 ₹10,354.5 Lowest | 8,800 ₹10,384 |
| 7.00 | MVAR Transducer
(i) Range : (-) 228.6-0 - (+) 228.6 MVAR
(ii) Input : (-) 190.5 – 0 - (+) 190.5 VAR
(iii) Output : 4-12-20 mA DC (Dual Output)
(iv) PTR : 220KV√3/ 110√3V
(V) CTR : 600/1 A
(vi) Accuracy : ± 0.5%
(Vii) Aux Supply : 220 V DC / AC ( both),
(viii) Type : 3Phase 4 wire
(ix) Make : AE, Rishabh, Southern, Minilec,masibus or equivalent.
(x) Fully onsite programmable input voltage range and input current range with
LCD display
(xi) Onsite selectable output type (DC current / DC voltage) | 4 | Nos. | 8,775 ₹10,354.5 Lowest | 8,800 ₹10,384 |
| 8.00 | Watt Transducer (Universal)
(a) Range : (-) 228.6 -0 - (+) 228.6 MW
(b) Input : (-) 190.52 – 0 - (+) 190.52 W
(c) Output : 4-12-20 mA DC (Dual Output)
(d) PTR : I/P 110V
(e) CTR : I/P 1 A
(f) Class : 0.5
(g) Aux Supply : 220 V DC/AC ( both),
(h) Make : AE,Masibus, Rishabh, Southern, Minilec, MEco or equivalent
(i) Fully onsite programmable input voltage range and input current range with
LCD display
(j) Onsite selectable output type (DC current / DC voltage).
(k) Type : 3Phase 4 wire | 1 | Nos. | 8,785 ₹10,366.3 Lowest | 8,800 ₹10,384 |
| 9.00 | MVAR Transducer (Universal)
(i) Range : (-) 228.6-0 - (+) 228.6 MVAR
(ii) Input : (-) 190.5 – 0 - (+) 190.5 VAR
(iii) Output : 4-12-20 mA DC (Dual Output)
(iv) PTR : I/P 110V
(V) CTR : I/P 1 A
(vi) Accuracy : ± 0.5%
(Vii) Aux Supply : 220 V DC / AC ( both),
(Viii) Make: AE, Rishabh, Southern, Minilec,masibus or equivalent
(ix) Fully onsite programmable input voltage range and input current range with
LCD display
(x) Onsite selectable output type (DC current / DC voltage).
(vii) Type : 3Phase 4 wire | 1 | Nos. | 8,940 ₹10,549.2 | 8,800 ₹10,384 Lowest |
| 10.00 | AC Voltage Transducer
Should have following specifications :-
(a) Input :- 0-150 V AC, 50 Hz
(b) PT :- 220KV√3/110√3 V.
(c) Aux. Power supply: - 220 V AC/DC.
(d) Accuracy: - ±0.5% of span.
(f) Range :- 0-300KV
(g) Output: - Dual isolated 4-20mA DC. 500 ohm (max)
(h) with LCD display, Fully onsite programmable input voltage range, Measuring range programmable, onsite selectable output type( DC current/ DC voltage), Output range Programmable | 3 | Nos. | 4,680 ₹5,522.4 Lowest | 5,300 ₹6,254 |
Tender Value
₹3.4 L
EMD Value
₹6,700
Closing Date
16 Sept 2025, 3:00 pmClosed
CE ATPS CHACHAI
CE ATPS CHACHAI 484220 MP
Procurement of different type of transducers and panel meter of ATPS MPPGCL Chachai.
2025_MPPGC_440030_1
865/ETI
Open Tender
Electrical Goods/Equipments
Item Rate
60 days
ATPS CHACHAI
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
Yes
₹6,700
Yes
10 Aug 2026
14 Aug 2025
18 Sept 2025
14 Aug 2025
16 Sept 2025
14 Aug 2025
DC Ammeter (i) Range : 0-200 A (ii) Size : 72*72 (iii) Accuracy : 1.5 or BETTER TYPE (iV) Scale : 240° (V) Make : AE, Rishabh, Southern, Minilec, or equivalent (Vi) Input range : 0-75 mV
DC Ammeter (i) Range : 0-100-600 A (ii) Size : 72*72 (iii) Accuracy : 1.5 or BETTER TYPE (iV) Scale : 240° (V) Make : AE, Rishabh, Southern, Minilec, or equivalent (Vi) Input range : 0-75 mV
DC Ammeter (i) Range : 0-100 A (ii) Size : 72*72 (iii) Accuracy : 1.5 or BETTER TYPE (iV) Scale : 240° (V) Make : AE, Rishabh, Southern, Minilec, or equivalent (Vi) Input range : 0-75 mV
DC Ammeter (i) Range : 0-150 A (ii) Size : 72*72 (iii) Accuracy : 1.5 or BETTER TYPE (iV) Scale : 240° (V) Make : AE, Rishabh, Southern, Minilec, or equivalent (Vi) Input range : 0-75 mV
DC Voltage Transducer (i) Input : -15V-0-+15 V DC (ii) Output : 4-20 mA (DUAL and GALVANICALLY ISOLATED) (iii) Accuracy : ± 0.5% or BETTER TYPE (iV) Aux Supply : 220 V AC/DC , 1Ph 50 HZ (V) Make : AE, Rishabh, Southern, Minilec, Masibus or equivalent (Vi) Test voltgae : 2KV, 50 HZ/MIN
AAKASH ENTERPRISES (BID ID -1342908)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .