| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹46.3 LAccepted-AOC | L1 | Accepted-AOC BEING L1 BIDDER | |
| 2 | L2₹49.0 L+₹2.0 L (4.21%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹50.3 L+₹3.3 L (6.97%)Rejected-Finance | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹51.1 L+₹4.1 L (8.64%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹53.9 L+₹6.8 L (14.5%)Rejected-Finance MES CHOWPATTI HASIMARA DIST JALPAIGURI WB PIN 735215 | HASIMARA | JALPAIGURI | WEST BENGAL | 735215 | L5 | Rejected-Finance Other than L1 |
Tender Value
₹44.5 L
EMD Value
₹89,000
Closing Date
4 Sept 2024, 6:00 pmClosed
GE (AF) HASIMARA
GE (AF) HASIMARA PO-HASIMARA DIST- ALIPURDUAR PIN-735215
REPAIR/MAINT INCL REPLACEMENT OF SERVICE CONNECTIONS AT VARIOUS LOC IN MES/BASRA/IN-LIVING AREA, REPAIR/MAINT OF SOLAR WATER HEATERS, SIGNBOARDS AT INSTALLATIONS, ROUNDRAL LIGHTS, POST TOP LIGHTS AND ALLIED WORKS, WORK SERVICES FOR CLEANING OF VARIOU
2024_MES_664628_1
C/8789/2024-25/E8
Open Tender
Civil Works
Item Rate
210 days
GE (AF) HASIMARA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) HASIMARA
₹89,000
Yes
1 Oct 2024
8 Jul 2024
6 Sept 2024
8 Jul 2024
4 Sept 2024
22 Jul 2024
Amount
Excavation in trenches not exceeding 1.5 metre wide and not exc 1.5 metre in depth for foundation of pole/stay, or cable trenches etc n. exc. 10 Sqm on plan and getting out in soft/loose soil, complete all as specified and directed.
Returning filling in incl spreading, leveling watering and well ramming in layers not exceeding 25cm in soft/loose soil, complete all as specified and directed.
Removing excavated materials to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 metre above the starting point in any type of soil, complete all as specified and directed.
Supply and laying double walled corrugated (DWC) HDPE duct pipe of 40mm dia conforming to IS, approved colour complete with fittings for cable protection, complete all as specified and directed.
Supply and laying double walled corrugated (DWC) HDPE duct pipe of 50mm dia conforming to IS, approved colour complete with fittings for cable protection, complete all as specified and directed.
S&F GI tubing 40mm bore (light grade) with all fittings for protection of cables, laid in trenches including making good to the distrurbed surface including taking down/up old unserviceable pipe of any description, complete all as specified and directed (Note : Excavation and earth work shall be measured and paid separately)
Supply, laying and testing cable XLPE Insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 Sqmm 4 core including taking down old unserviceable UG cable of any description, complete all as specified and directed.
All as per item No 7.00 here-in before but 35 Sqmm 3.5 core, complete all as specified and directed.
All as per item No 7.00 here-in before but 50 Sqmm 3.5 core, complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6.3cm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, connected to galvanised means of earth wire 4mm dia with bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 20mm bore and watering pipe GI medium grade of 20mm bore and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC (1:3:6) type C-2 all as shown in electrical plate No-3 of SSR part-I (2009) connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion including demolition of old unserviceable earthing of any description, complete all as specified and directed. Notes : (i) Proper earthing pit should be provided with pit cover. (ii) GI earth wire from earth pit to pole/panel/DB shall deemed to be included in the unit quoted rate.
Horizontal boring under the road (with manual method) below 1mtr from the road surface and dia of hole not exc 100mm, with out damaging the existing road, getting out and disposal of soil to a distance not exceeding 50m from the site of work, complete all as specified and directed.
Supply, fabricating, installing, testing and commissioning of outdoor type LT bus bar box, factory made, of size not less than 900mm (L) x 900mm (B) x 450mm (D) factory fabricated, cubical panel, floor mounted double door, dust and vermin proof CPRI approved made out of 3.15 mm thick CRCA sheet mounted on 40 x 40 x 5mm angle iron supports at the base duly painted with synthetic enamel paint (spray painting) over and including priming coat and panel board with front and back opening and locking arrangement compete including finishing with two coats of powder coated paint of approved shade over one coat of red oxide zinc chrome primer including all busbar of copper strip 40mm x 10mm for three phase 4 wire 415 Volts, 50 Hz, AC supply, including suitable size cable glands, lugs etc, in proper arrangement for ventilation, including taking down of old unserviceable bus bar box, complete all as specified and directed.
S&F sheet metal enclosure for double door MCB DBs, phosphatised, powder coated, Triple Pole & Neutral (TPN), suitable for 4 way, 415 volts, IP 43 & IK 09 with metal door fixed on wall with din rail, neutral and earth bar, fixed in proper position including taking down old unserviceable one, complete all as specified and directed.
S&F isolator, four pole, capacity 100 Amps, 415 Volts fixed in proper position including connecting wire as per site requirement, complete all as specified and directed.
S&F MCB Single Pole and Neutral (SPN) of capacity 40 to 63 Amps, 240 Volts, breaking capacity 10 KA, ‘C’ series, complete all as specified and directed. (Make: Legrand Cat No. 4086 18 to 20 or equivalent model in Schneider/ABB/L&T
S&F MCB Single Pole (SP) of capacity 6 to 32 Amps, 240 Volts, breaking capacity 10 KA, ‘C’ series, complete all as specified and directed. (Make: Legrand Cat No. 4085 87 to 95 or equivalent model in Schneider/ABB/L&T
Supply and draw sub main wiring in repairs of two run 6.0 sqmm single core (FRLSH) PVC insulated, unsheathed multistranded copper conductor cable 1100 Volt grade, drawn through and including PVC conduit (ISI marked), medium duty, of not less than 25mm size including all conduit accessories, concealed to the surfaces of the wall/ceiling including one run of 6.0 sqmm single core (FRLSH) PVC insulated unsheathed copper earth continuity including taking down existing sub-main wiring, complete all as specified and directed. Note: (i) Two runs of single core cable with one run of earth continuity conductor including PVC conduit & accessories shall be measured and paid as one length. (ii) Cutting chases shall be measured and paid separately.
Cutting chases, pinning in, making good to facings in stone concrete wall/blocks/slab where required and pointing in CM (1:3) to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.and cutting chases for concealed conduit wiring etc, cutting exc 10cm but n.exc 20cm girth including making good distrubed surfaces, complete all as specified and directed.
M & L in replacement of MS box of size 900 x 750 x 300mm (double door), dust proof with front opening hinged door both side, made out of 2mm thick MS sheet cubical type factory fabricated including fixing transparant glass (04 Nos) infront of meter and meter mounting arrangment inside the box with powder coated painting for mounting of, electric meter etc inside the box fixed in wall by necessary cutting of wall of suitable size in concealed and making good the surface, by applying cement work, brick work and matching colour (oil bond distemper) etc including dismantling of MS box, electric meters and fixing the new/existing electric meters in new box carefully, marking identification number of meter including necessary electric connection by suitable size of copper conductor cable of suitable length and testing on completion, including taking down old unserviceable MS box, complete all as specified and directed. Note : (i) Cost of plastering work involved while taking out old existing meter and refixing the new meter box shall deemed to be included in the unit quoted rate. (ii) PVC flexible conduit required within the meter boxes is deem to be included in this item rates.
S&F 15mm bore GI water tubing and connection medium grade with all fitting fixed to wall or in ceiling or laid in floors including taking down old unserviceable GI tubing, complete all as specified and directed..
S&F 20mm bore GI water tubing and connection medium grade with all fitting fixed to wall or in ceiling or laid in floors including taking down old unserviceable GI tubing, complete all as specified and directed..
S&F in repairs of 15mm bore bib taps, cast copper alloy, 'chromium plated' fancy type, screwed down, screwed for iron pipe or for brass ferrule, compelete all as specified and directed.
S & F 15mm bore gun metal globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed, complete all as specified and directed.
S & F 20mm bore gun metal globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed, complete all as specified and directed.
S&F rotational moulded polyethylene water storage tanks, triple layered, (cylindrical vertical with closed top) ISI marked, confirming to IS 12701-1989, hoisted and fixed in position all as specified in SSR Part I (1000 ltr capacity) including 20mm Nipple suitable for HDPE water tank and ball valves high pressure of PTMT with epoxy coated aluminium rod & high density plastic ball, screwed for iron pipe and fixed to 20mm bore pipe inculding dismantling of old water tank, complete all as specified and directed.
S&F in repair MS framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering, doors, etc. to be pre ared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging, also fastening and fixing, complete all as specified and directed.
S&F in repair steel wire fabric of weight n. exc. 4 kg/Sqm complete to wood or steel members, complete all as specified and directed.
S&F MS screw bolts (machine made) with hexagonal or square heads at one end and screwed the other or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nuts, length of bolt n. exc. 5cm long dia of neck 11 to 15mm, complete all as specified and directed.
M&L for preparing of new steel & iron surfaces of any description not otherwise described over n. exc. 10cm width or girth and applying two coats of synthetic enamel paint (1st grade quality) over a coat of red oxide primer, complete all as specified and directed.
M&L for preparing of new steel & iron surfaces of any description not otherwise described over 10cm width or girth and applying two coats of synthetic enamel paint (1st grade quality) over a coat of red oxide primer, complete all as specified and directed.
M & L for PCC (1:2:4) type B-2 (using 40mm graded crushed stone aggregate) as in foundation of columns, filling and mass concrete etc, complete al as specified and directed.
Servicing of solar heating system of capacity upto 500 LPD including checking all the connection, arresting leakages from joints, cleaning of top glass of solar panel, cleaning of water tank, replacement of unserviceable heating element and other required to made serviceable, complete all as specified and directed. (Note : Spares shall be measured and paid seperately)
De-scaling, cleaning of hot water tanks and incl heat collecting units with anti scale chemical, complete all as specified and directed.
Replacement of rubber gasket of heat collecting units of solar heating system of 500 ltr capacity, complete all as specified and directed.
S&F electric heating element 3 KW capacity, 240 volt, complete all as specified and directed.
S&F toughened glass suitable size as per sample of solar heating system of 500 ltr capacity, complete all as specified and directed.
S&F in replacement of aesthetically designed LED post top light fittings 40 Watt polycarbonate diffuser with IP65 protection with aluminium enclosure, powered with and including high power LEDs as light source and die casted heat sink with symmetrical light distribution and excellent heat dissipation including fixing material such as suitable dia GI pipe as per OEM instruction, concealed connection from terminal box to light fittings including cutting chases to existing wall for fixing of same and making good to the disturbed portion as per existing, complete all as specified and directed. Make : Havells cat part No NEBULAPT40WLED857PSYMTOPC or equivalent model in Bajaj/ Philips / Crompton/Wipro.
S&F in replacement of 10 watt LED bollard light fitting including lamp IP-65 protection, Inverted Pyramid Tripod type LED Bollard with soft 360 light distribution, control wiring and excavation and earth works PCC (1:3:6) type C-1 as foundation block including fixing to garden / pathway and making good to the disturbed portion, complete all as specified and directed. Make : Crompton Model No LBLSN-10-CDL or equivalent model in Bajaj/Philips/Wipro/Havells Note : Excvation and earth work, PCC shall deemed to be included in the unit quoted rates.
S&F in replacement garden light LED 35W new generation technology suitable for outdoor areas with functionality during night and aesthetics during the day IP-65 protection, die cast aluminium Post top lantern designed with long life LED engine & Electronic Driver, complete including fixing material and connecting wire of suitable size upto control gear box, complete all as specified and directed. Make : Havells model No VICTORIAPT 35W LED 757PSYMTOTG or equivalent model in Philips/Bajaj/Wipro/ Crompton
M & L for detecting fault through cable fault deductor by injecting suitable energy pulse to detect exact position of fault for XLPE, LTcable, 1100 volts grade heavy duty aluminium conductor any size including transporting chagres and clearing of rectification of fault of electric supply by removing of burnt out portion of cable, loop, etc including earth work, complete all as specified and directed
M&L straight through joints (epoxy) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 10 to 16 Sqmm 3.5/4.0 core and testing, complete all as specefied and directed.
M&L straight through joints (epoxy) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 25 to 50 Sqmm 3.5 core and testing, complete all as specefied and directed.
M&L straight through joints (epoxy) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 70 to 150 Sqmm 3.5 core and testing, complete all as specefied and directed.
M&L straight through joints (epoxy) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 185 to 240 Sqmm 3.5 core and testing, complete all as specefied and directed.
M&L straight through joints (epoxy) cable joint kit including jointing materials for making joints of UG electric cable 1100 volt grade heavy duty with PVC/XLPE insulated aluminium conductor nominal cross sectional area 300 to 400 Sqmm 3.5 core and testing, complete all as specefied and directed.
S&F water proof junction box made from SMC sheet ready made of size 350 x 270 x 190mm with aluminium bus bar of 120 Amp capacity for RYB and neutral fixed inside the junction box with necessary supporting insulators fixed on hylem sheet/insulating sheet, MS sheet steel fixed inside the bottom portion of box to connect the cable gland complete, entire assembly fixed to pole/wall with MS clamp 20 x 3mm and nuts & bolts and connecting cables from junction box to fittings including dismantling of old junction box of any size, complete all as specified and directed.
S&F water proof junction box made from SMC sheet ready made of size 400 x 300 x 190mm with aluminium bus bar of 150 Amp capacity for RYB and neutral fixed inside the junction box with necessary supporting insulators fixed on hylem sheet/insulating sheet, MS sheet steel fixed inside the bottom portion of box to connect the cable gland complete, entire assembly fixed to pole/wall with MS clamp 20 x 3mm and nuts & bolts and connecting cables from junction box to fittings including dismantling of old junction box of any size, complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in gorund (earth pit not less than 2.25 Mtr normal ground level),and top edge of earth plate not less than 1.5 mtr below normal ground level, connected to galvanised means of earth wire 4mm dia with bolts, nuts & check nuts, and washers of galvanised iron protection pipe light grade of 20mm bore and watering pipe GI medium grade of 20mm bore and filled with alternate layer of charcoal and common salt, watering funnel with wire mesh, earth pit chamber and cover CI frame PCC (1:3:6) type C-2 all as shown in electrical plate No-3 of SSR part-I (2009) connected to earthing test point all as specified and indicated including all earth work excavation, returning filling and disposal of surplus soil and testing on completion, including demolition of old unserviceable earthing of any description, complete all as specified and directed. Notes : (i) Proper earthing pit should be provided with pit cover. (ii) GI earth wire from earth pit to pole/panel shall deemed to be included in the unit quoted rate.
Restringing and tightening of ACSR conductor of any size and type maintaining stranded sag including providing aluminium binding wire, jumpers on LT over head lines with jumper clip, complete all as specified and directed. Note:- (i) Pole to pole shortest distance shall be measured for payment. (ii) Burnt/damaged jumpers of appropriate size shall be replaced by the contractor without any extra cost.
Trimming of tree branches of girth n. exc. 15cm along the alignment of both sides of LT/HT over head electric line which are touching or falling on ACSR conductor/ poles or near by sub stns etc at any at any height from GL and making sufficient clearance (not less than 1.5m) from conductor and taking down the same on the ground carefully, avaoiding damage of tne conductor/pole and removing to a distance n. exc 100m, complete all as specified and directed. Note :(i) Trimming of the branches/twigs shall be done on both sides of the conductor. (ii) Actual length of cutting along with the alignment of overhead electric line shall be measured for payment
M&L for porcelain viereous white or brown shackle type insulator including galalvanaized mild steel straps, washers, insulator bolts, washers and nuts 550 volts grade 50mm height 65mm dia and 9mm dia bolt, complete all as specified and directed.
M&L for pin type porcelain vitreous, white or brown insulator including one galvanized mild steel spoindle, two galvanized iron washers and one galvanaized iron nut, 50mm beight 65mm dia for 550 Volts grade, complete all as specified and directed.
S&F in replacement Aluminium Conductor Steel Reinforced (ACSR) and fixing on electric poles and binding to insulators and including aluminium binding wire PVC insulated R, Y, B and Neutral black as in OH conductors including stringing, tighten-ing, complete all as specified and as directed.
S&F in replacement galvanised steel wire 3.15 or 4mm dia as guard/earth wire on LT OH Line,re-stringing,binding and clamping etc, complete all as specified and directed
M & L for cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia, complete all as specified and directed.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under aluminium coat and one aluminium finishing coat of paint complete for base support frame for water tanks at roof top/ground floor including dismantling of old unserviceable cross arm/bracings etc, complete all as specified and directed.
M&L for PCC (1:4:8) type D-2 (using 40mm graded crushed stone aggregate) as in foundation of poles, filing and mass concrete etc. including formwork (as required), complete all as specified and directed.
M&L for PCC (1:3:6) type C-1 (using 20mm graded crushed stone aggregate) as in coping of poles, etc. including necessary formwork (as required), complete all as specified and directed.
M&L for PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate) as in coping of poles, etc. including necessary formwork (as required), complete all as specified and directed.
M&L steel tubular swaged welded pole, type 410 SP-31 (9.00 metres long) including cast iron base plate, finial taper plug, cap, mild steel bolts, nuts, screws, etc. including applying two coat of black bituminous paint internally and externally up to planting depth and applying with two coats of aluminium painting over a coat of red oxide primer on external exposed surfaces including writing MES LT pole and blue reflector strip with synthetic enamel paint (1st grade quality), complete all as specified and directed. Note : Earth work and PCC work shall be measured and paid separately.
M&L for painting PCC poles, 8.5 meter in height above GL including cross arms and bracings on existing surface after cleaning and removing dust, rust & dirt with two coats of cement based paint over a coat of alkali resistant primer painting with black & white alternate strips of 30cm each externally from ground level up to 1.5 mtr with synthetic enamel paint numbering of pole, complete all as specified and directed.
M&L for painting steel tubular poles, 8.5 meter in height above GL including cross arms and bracings on existing surface after cleaning and removing dust, rust & dirt by applying two coat of aluminium paint painting over a coat of red oxide primer with black & white alternate strips of 30cm each externally from ground level up to 1.5 mtr with synthetic enamel paint and numbering of pole, complete all as specified and directed.
S&F in replacement of first aid kit box/emergency medical box wall mouted type made out of powder coated GI sheet of 18 gauge and the size of the box will be 36cm(H) x 26cm(W) x 13 cm(D) with front transparent acrylic glass and multi compartment 4 shelf for better organize of medicines with security lock on door, openable window at front side with help of hinge at one side and locking arrangement at another side, openable window must painted with "FIRST AID" with red paint and whole box will fixed on wall at height not less than 2mtr including medicene and other items as under :- Sterilized dressings(04), Cotton Wool 10 gm (02), Antiseptic Solution 100 ml (01), Burn Ointment (01), Scissor (01), Digital Thermometer (01), Disposal Gloves(02), Disposal Mask (20), Adhesive / Microporous Tape 1/2" (01), Band- Aid (10), safety pins(05), Sofraxime Cream (01), Cold Rub(01), Roller Bandage 5 cm (02), Roller Bandage 10 cm (02), cotton Buds (10), First-Aid Guide booklet, Hand Sanitizer (02), Handiplast (12), Antiseptic cream (01), Antiallergic medicene, Cough medicene, Pain killer, Fever and cold medicene and any other essential medicene, complete all as specified and directed.
Uprooting grass/weeds/plants up to 30cm depth by scrapping soil in order to make free ground from all sort of vegetation (grass/weeds/plants) and hand packing carefully by packing round pebbles approximately of size 20 to 40mm after carefully picking form heap of pebbles/stones, complete all as specified and directed.
Cleaning of area around E/M sub division by scraping the grass and creepers from roof and spraying grass killing chemical with spray gun, as per manufacturer's instructions for prevention of weeds and grass at surrounding of E/M sub station area, complete all as specified and directed.
Supply and spreading unslaked lime at E/M sub station area (approxmately 600 Sqm) to destroy the roots of grass and herbs, complete all as specified and directed.
Supply and filling dry river sand at surrounding of E/M installations / sub stations /cable trenches including watering and consolidation, complete all as specified and directed.
Supply and filling crushed stone aggregate, free from any foreign particles, 25mm gradded, for spreading at E/M sub station area, complete all as specified and directed.
Demolition of brick work or stone/ boulder masonry, built in cement mortar including all quoins, pillars, manholes etc., separation of serviceable materials from the unserviceable, stacking the serviceable materials within 100m and disposal of unserviceable materials, debris and rubbish to a distance not exceeding 100m, complete all as specified and directed.
M&L for brick work with fly ash bricks, old size, straight or curved on plan exc 6 mtr mean radius built in CM (1:6) including demolition of brick work, complete all as specified and directed.
M&L for rendering 15mm thick on fair faces of brick work or concrete surfaces in CM (1:6) and finished even and smooth without using extra cement, complete all as specified and directed.
M&L for preparation of newly plastered surfaces of wall and applying three coats of white wash, complete all as specified and directed.
M&L for complete removal of existing treatment of old painted steel or iron surfaces of any description over 10cm width or girth and applying two coats of synthetic enamel paint (1st grade quality), complete all as specified and directed.
Demolition of cement concrete un-reinforced in ground floors and pavings n. exc. 15cm thickness (below or above ground level), complete all as specified and directed.
M&L 75mm thick PCC (1:3:6 ) type C-2, (using 40mm graded stone aggregate) for sub base of floor, plinth prtection, path/ hard standing etc, complete all as specified and directed.
Supply and installation information display board of size 100cm x 130cm at E/M installations to display the maintenance chart/shock treatment/Do's and Dont's/fire fighting/first aid/circuit diagram etc, the border of the board made out of 2nd class hard wood bead width n. exc. 25cm of thickness 30mm including varnishing display area of board made of 1st class hard wood 25mm thick hard wood including soft material for pinning of information on board including covered with green velvate cover (not less than Rs. 400 /- per Sqm) and complete board should be covered with talcum sheet, transparent type, and charts are pined on the board with spikes, complete all as specified and directed.
Note: An amount of Rs.75,180.00 on account of Credit Schedule for schedule 'A' part - II shall be deducted from the total amount of BOQ to arrive at the contract sum.
SHRI D P AGARWAL (BID ID -3082618)
M/S SARDAR MAL NAHATA (BID ID -3081824)
M/S ROY ENTERPRISE (BID ID -3080945)
BHARAT ELECTRIC (BID ID -3081601)
M/S RATHIN ENTERPRISES (BID ID -3081967)
M/S BISHAL ENTERPRISES (BID ID -3082867)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .