Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.7 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹18.5 L+₹55,055 (3.07%)Rejected-Finance | L2 | Rejected-Finance Other Than Lowest Bidder | |
| 3 | L3₹19.4 L+₹1.4 L (7.94%)Rejected-Finance | L3 | Rejected-Finance Other Than Lowest Bidder |
Tender Value
₹19.5 L
EMD Value
₹38,960
Closing Date
1 Nov 2022, 6:00 pmClosed
CWE Jalandhar Cantt
HQ CWE Nalwa Road Jalandhar Cantt Pin-144005
Please refer tender documents
2022_MES_554189_1
8322/38/E8
Open Tender
Electrical and Maintenance Works
Item Rate
273 days
Jalandhar Cantt
Class E Category b(ii) for contractors enlisted with MES
8 documents required · 8 mandatory
₹500
Garrison Engineer Kapurthala
₹38,960
Yes
6 Dec 2022
24 Sept 2022
8 Nov 2022
24 Sept 2022
1 Nov 2022
20 Oct 2022
Amount
Excavation in trenches in soft/loose soil not exceeding 1.50 mtr wide and not exceeding 1.50 mtr in depth for ltaking out old cable/laying of under ground cable/foundation of poles/stays including segregation of old serviceable bricks complete all as specified and directed by Engineer-in-Charge.
All as per item No.1 above but depth exceeding 1.5 metre & not exceeding 3.00 metre.
Returing, filling in, including spreading, leveling watering and well ramming inlayers not exceeding 25 cms thick each layer complete all as specified and directed by Engineer-in-Charge.
Removal of surplus soil to a distance not exceeding 50 mtr away and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-charge.
Supply and Laying Un-reinforced precast concrete cable cover class HV Type 1, flat size 300mm x 180 mm x 40 mm thick.
M&L for Protection to cable with one layer of new bricks laid flat butting to each other in such a way that the length of the bricks is at right angle to the central axis of the cable using old size sub-class ‘B’ bricks.
Supplying, filling in trenches spreading, leveling sand cushioning 8 cm below and 15 cm above the cable for under ground cable complete all as specified & directed.
Supply and lay in trenches in road cross / floor/wall etc. tube galvanised iron light grade with all fittings for protection of cable of 100 mm bore including taking out unserviceable complete all as specified and directed.
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm including taking out existing cable of any size.
Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor 1100 Volts grade of size 3.5 core 185 Sq mm including taking out existing cable of any size.
Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured electric power cable (heavy duty) with stranded aluminium conductor 1100 Volts grade of size 3.5 core 120 Sq mm including taking out existing cable of any size.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm
Disconnecting the HT & LT connections of existing transformer mounted on four pole structure carefully and transporting the transformer to MES store yard and depositing all as directed.
Supply, install, test and commissioning of step down transformer , out door type suitable for pole mounting complete with standard accessories or fittings suitable for HT 11 KV/433 Volts, AC , 50 cycles , 3 phase ,4 wire, copper wound,oil immersed,naturally cooled, with off load tapings on Primary side to vary secondary voltage + 7.5% with tapings at every 2.5% rating of capacity 250 KVA including bushing on HT side and LT side conforming to IS-1180(part-I)2014,energy efficiency level 3 including amendments as on the date of receipt of tender with following requirments:-
Note : This items includes the following
(a) Three Nos porcelain bushings HT 11 KV with brass bushings rods nuts and washer inside cable end box
(b) One cable box LV side consisting of four nos porcelain with brass bushing rods complete with nuts and washers with two nos cable gland suitable for 3.5 core 400 Sqmm LT U/G Cable
(c) Oil conservator with filler type drain valve and oil level guage with transformer oil
(d) Dehydrating breather with first fill of dehydrating agent
(e) Explosion bent
(f) Thermometer pocket on tank cover
(g) Rating plate and terminal marking plate
(h) The earthing terminal two Nos to facilitate fixing of earth strip
(j) Oil filling hole with cap/plug with connection plate complete
(k) Air relief valve plug.
(l) Initial filling to transformer oil with required capacity
(o) The contractor will produce all purchase voucher, test certificate,mannual of the transformer.
Supply and erection in replacement of steel tubular swaged pole 11 metres long designation 410-SP-55 complete with cast iron base plate, finial taper plug, bolts, nuts and screws etc including painting of pole with two coats of aluminum paint over a coat of red oxide primer from top of the pole to 1.5m above the bottom of the pole and painting with two coats of black paint over a coat of red oxide primer upto 1.5m from bottom of the pole complete, all as specified and directed.(Note: (i) Poles are being planed for erecting 4 pole structure (ii) Excavation and earth work and PCC shall be measured and paid separately under respective item)
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural mild steel sections conforming to Fe-410-0 grade including necessary nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape and size as directed and including applying two coats of aluminium paint (under & finishing coats) over a coat of red oxide zinc chromate primer on exposed steel surfaces complete all as specified.
Supply and fixing lighting arrester metal oxide non-linear type rupturing capacity 65 Kilo Amps porcelain conforming to IS-3070 Pt-I suitable for 11 KV, HT overhead line complete including nuts, bolts, clamps, bracket etc and connecting with GI earth wire, discharge capacity 65 Kilo Amps including taking out unserviceable lightning arrester all as specified and directed.
Supply and install tripple pole HT 11 KV outdoor gang operated air break switch of rating upto 200 Amps with fixed contacts of phosphorus bronze and moving contacts of copper with mechanically operating from ground level vertical mounted complete with HT insulator on steel frame operating rode made out of 25 mm GI pipe medium grade worked from ground level with handle and locking arrangement with 12 insulators with dropout fuses fixed including taking out existing GO switch complete all as specified. (clamps/cross arms shall be measred and paid for seperatly)
S&F Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia. for 11000 volts grade complete all as specified.
S&F Disc type insulator, porcelain, vitreous, 145 mm high and 255mm dia, ball & socket type, white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified.
Material and labour for PCC 1:4:8 type D2 (using 40 mm graded stone aggregates) as in foundation bed and around the pole as mass concrete including necessary form work and finishing the exposed surface even and smooth without using extra cement complete all as specified and directed.
All as per description of seiral item No 21 here-in-before but PCC (1:2:4) type B-1 using 20 mm graded stone aggregates as in coping of poles.
Earthing with copper Earth Plate Electrode 600x600x3.15mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with copper Earth Strip of size 20x3mm by means of Bolts, Nuts, Check Nuts and Washers of copper and connected Earthing Testing Point/Bus-bar including GI 40mm bore (dia) light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt, Magneisum Sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore (dia) medium grade including necessary Excavation in any type of soil, Returning, Filling in and Removal of surplus Spoil disposal to out side MD land and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one, complete all as per specified and as directed.
Earthing with Galvanised Earth Plate Electrode 600x600x 6mm thick burried directly in Ground (Earth Pit not less than 2.25 Metre below Ground Level) with Top edge of the Plate not less than 1.50 Metre below Ground Level, connected with GI Strip of size 32x 6 mm by means of Bolts, Nuts, Check Nuts and Washers of GI or steel and connected Earthing Testing Point/Bus-bar including GI 40mm bore (dia) light grade Protection Pipe, Earth Plate surrounded by a packed thickness of Char Coal or Coke Dust mixed with Common Salt, Magneisum Sulphate (1 : 1 : 0.5) in alternate layers of not exc 150mm thick, PCC Pit in Cement Concrete 1:3:6 (20mm graded stone aggregate) and Pre-cast RCC Cover Slab of size 350x350x50 mm in Cement Concrete 1:2:4 (20mm graded stone aggregate), reinforced with 10mm dia TMT Bars @ 100mm Centre to Centre in both ways, GI Wire Mesh, Funnel with GI Watering Pipe 20mm bore (dia) medium grade including necessary Excavation in any type of soil, Returning, Filling in and Removal of surplus Spoil disposal to out side MD land and all as shown in Electrical Plate No. 3 of MES Schedule Part-I and Testing on Completion including taking down old unserviceable one, complete all as per specified and as directed.
Earthing complete with galvanised iron earth plate electrode 600mm X 600mm X 6mm thick, with and including earthing of GI Strip of size 25 x 4 mm protected by 15mm dia GI pipe medium grade upto a length of 7.5m. The plate shall be buried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level, connected to earth lead as described here-in-before by means of bolts, nuts, washers and checknuts made out of galvanised iron or mild steel, earthing lead protected by as described here-in-before and connected to main switch board or main control board or electric pole all as shown on electrical plate No.3 of MES Sch Part-I including necessary earth work and excavation in any type of soil, plain cement concrete 1:3:6, type C1 chamber, reinforced cement concrete cover slab with locking arrangement and handle of 10mm dia MS round bars 450mm long, 1:2:4 type B1, 50mm thick with 8mm dia TMT bars at 140mm centre to centre both ways, GI pipe of bore 20mm light grade for watering with funnel, wiremesh, salt, charcoal, lugs including testing complete all as specified and as directed.
Supply and fix Copper strip 20 x 3.15 mm buried in ground
Supply and fix Galvanised iron strip 32 x 6mm buried in ground
Supply, install, testing and commissioning of LT, Automatic Power Factor Correction (APFC) Panel for 3 Phase, 415 V & 50 Hz system of capacity 100 KVAR with incoming MCCBs, CPRI approved, weather/vermin proof, made out of 3 mm thick CRCA sheet, factory assembled modular and non compartmentalized construction, outdoor type, with front side hinged double door with locking arrangement, floor mounted free standing type, duly powder coated, with Al Bus Bars and Multistrand copper cables of appropriate size for each feeder of with 12-step APFC Relay comprising of following all as dirceted:- (i) MCCB, Thermal Magnetic type, 160 Amp, 3 Pole, 25 KA. (ii) MD-XL capacitor 440V of following rating, with heavy duty capacitor switching contractor:-
(a) 5 KVAR with 10kA MCB & Capacitor duty contactor - 2 Nos. (b) 10 kVAR with 10kA MCB & Capacitor duty contactor- 4 Nos. (c) 25 kVAR with 10kA MCB & Capacitor duty contactor- 2 Nos. (d) Microprocessor based intelligent power factor 8-Step relay with RS 485 Port type RVT of ABB Make equivelent in Siemens/ Schneider (e) CONTROL COMPONENTS: (i) CTR: 200/5A CL: 1, 5VA -3Nos. (ii) Digital Multi meter to measure Volt, amps and PF - 1No. (iii) Indication Lamps for RYB (LED Type) - 3Nos. (iv) Out going Indication Lamps (LED Type) - ON/OFF - 8 Nos.
Taking down existing old unsv LT panel & Supply, install, testing and commissioning of LT distribution panel, CPRI approved, weather/vermin proof, made out of 3.15 mm thick CRCA sheet, factory assembled cubicle pattern modular and compartmentalized construction, outdoor type, with front and backside hinged double door with locking arrangement, floor mounted free standing type, duly powder coated, 3 phase and neutral 630 amps current carrying capacity aluminium bus bar with epoxy insulated coating with colour code and insulated support with aluminium earth bus of size 25x3mm with terminal switch, cable galleries, inter connecting bus bar connection/linkage, complete with the following switch gears and mounting the panel board on ground with PCC (1:2:4) type B-1 using 20mm graded stone aggregate bedding upto a height of 45 cm above gorund level, complete all as specified and directed by Engr in Charge and comprising the following :-
(a) MCCB 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA- 01 No ( In Coming)
(b) MCCB 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA- 01 No (out Going)
(c) MCCB 4 Pole, 415 V, Adjustable type, 200 Amps with breaking capacity 36 KA- 04 Nos ( Out going)
(d) MCCB 4 Pole, 415 V, Adjustable type, 100 Amps with breaking capacity 25 KA- 01
(e) On load Changeover switch 415 V in sheet metal enclosure 4 pole of capacity 400 Amps - 01 No( Out going)
(f) Digital Volt Meter 0-500V - 01 No
(g) Digital Ampere Meter 0-500 A with 3 Nos of CTs
(h) Indicator LED type
Taking down existing old unsv LT panel & Supply, install, testing and commissioning of LT distribution panel, CPRI approved, weather/vermin proof, made out of 3.15 mm thick CRCA sheet, factory assembled cubicle pattern modular and compartmentalized construction, outdoor type, with front and backside hinged double door with locking arrangement, floor mounted free standing type, duly powder coated, 3 phase and neutral 400 amps current carrying capacity aluminium bus bar with epoxy insulated coating with colour code and insulated support with aluminium earth bus of size 25x3mm with terminal switch, cable galleries, inter connecting bus bar connection/linkage, complete with the following switch gears and mounting the panel board on ground with PCC (1:2:4) type B-1 using 20mm graded stone aggregate bedding upto a height of 45 cm above gorund level, complete all as specified and directed by Engr in Charge and comprising the following :-
(a) MCCB 4 Pole, 415 V, Adjustable type,250 Amps with breaking capacity 36 KA- 01 No ( In Coming)
(b) MCCB 4 Pole, 415 V, Adjustable type, 100 Amps with breaking capacity 35 KA- 04 Nos (out Going)
(c) MCCB 4 Pole, 415 V, Adjustable type,63 Amps with breaking capacity 25 KA- 02 Nos ( Out going)
(d) On load Changeover switch 415 V in sheet metal enclosure 4 pole of capacity 250 Amps - 01 No
(e) Digital Volt Meter 0-500V - 01 No
(f) Digital Ampere Meter 0-250 A with 3 Nos of CTs
(g) Indicator LED type
GULSHAN SINGH GHAI AND SON
Shree Balaji Construction
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .