EE ETD Banda
220 KV Substation Tindwari Road Banda
Electrical Work
2025_UPTCL_1007697_1
T-48/ETDB/2024-25
Open Tender
Electrical Works
Lump-sum
60 days
Banda
Electrical Work
2 documents required · 2 mandatory
₹590
EE ETD Banda
₹2,300
10 Mar 2025
18 Feb 2025
7 Mar 2025
18 Feb 2025
6 Mar 2025
18 Feb 2025
18 Feb 2025 - 6 Mar 2025
Amount
Details of Work.
REPAIRING AND OVERHAULING OF of 245KV SF-6 ABB MAKE COMPRESSOR BASED CIRCUIT BREAKER AT 220KV S/S BANDA. WORK CONSIST OF : (A) COMPLETE DISMANTLING OF POLE MECHANISM ASSEMBLY,MAIN SPRING ,RATCHET GEAR AND OTHER CONNECTED PARTS.NECESSARY REPAIRING/RECTIFICATION OF DEFECTIVE PART. (B) REPLACEMENT OF ALL DAMAGED AND DEFECTIVE PARTS CLOSING LATCH ASSEMBLY , TRIPED LATCH,CLOSE COIL AND ITS PROPER ADJUSTMENT.CLEANING AND GREASING. (C) CHECK SF-6 GAS AND FILL UPTO SPECIFIED LIMIT IF REQUIRED. PROPER ADJUSTMENT AND CALIBRATION OF GAS PRESSURE SWITCH. (D) DISMANTLING OF ALL POLE LINKAGE ,PINS AND ROD ASSEMBLY,CLEANING ,GREASING AND ITS PROPER ADJUSTMENT. (E) CHECK SATISFACTORY CLOSE/TRIP OPERATION OF BREAKER BOTH BY LOCAL AND REMORT. (F) MEASUREMENT CLOSING AND TRIPPING TIME BY DIGITAL METER. (G) REPLACEMENT OF WIRING IF REQUIRED.
MEASUREMENT OF CONTACT RESISTANT (CRM) , CLOSING TRIPPING TIME ANALYSIS AND OPERATION TIME OF 245KV SF-6 CB.
REPAIRING AND OVERHAULING OF of 145KV SF-6 CGL MAKE COMPRESSOR BASED CIRCUIT BREAKER AT 132KV S/S BANDA. WORK CONSIST OF : (A) COMPLETE DISMANTLING OF POLE MECHANISM ASSEMBLY,MAIN SPRING ,RATCHET GEAR AND OTHER CONNECTED PARTS.NECESSARY REPAIRING/RECTIFICATION OF DEFECTIVE PART. (B) REPLACEMENT OF ALL DAMAGED AND DEFECTIVE PARTS CLOSING LATCH ASSEMBLY , TRIPED LATCH,CLOSE COIL AND ITS PROPER ADJUSTMENT.CLEANING AND GREASING. (C) CHECK SF-6 GAS AND FILL UPTO SPECIFIED LIMIT IF REQUIRED. PROPER ADJUSTMENT AND CALIBRATION OF GAS PRESSURE SWITCH. (D) DISMANTLING OF ALL POLE LINKAGE ,PINS AND ROD ASSEMBLY,CLEANING ,GREASING AND ITS PROPER ADJUSTMENT. (E) CHECK SATISFACTORY CLOSE/TRIP OPERATION OF BREAKER BOTH BY LOCAL AND REMORT. (F) MEASUREMENT CLOSING AND TRIPPING TIME BY DIGITAL METER. (G) REPLACEMENT OF WIRING IF REQUIRED.
MEASUREMENT OF CONTACT RESISTANT (CRM) ,CLOSING TRIPPING TIME ANALYSIS AND OPERATION TIME OF 145KV SF-6 CB.
Rates qouted by the bidders shall be without taxes. Taxes applicable if any to paid extra
S N ENTERPRISES (BID ID -5015288)
M/S V.K.T. SYSTEMS (BID ID -5017236)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .