Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹80.2 LAdmitted-Finance | L1 | Admitted-Finance | ||
| 2 | L2₹86.3 L+₹6.1 L (7.56%)Admitted-Finance | L2 | Admitted-Finance | ||
| 3 | L3₹94.6 L+₹14.3 L (17.9%)Admitted-Finance 53 VAISHAILI ENCLAVE SECTOR 9 INDIRA NAGAR LUCKNOW | LUCKNOW | L3 | Admitted-Finance |
Tender Value
₹85.4 L
EMD Value
₹1.7 L
Closing Date
17 Sept 2026, 3:30 pmClosed
Superintending Engineer
IWD IIT Kanpur
Rejuvenation of the complete central AC system i.e. SITC of AHU ducting CHW piping insulation grills etc. including dismantling and removal of old central AC system due to proposed renovation of all labs at Gr. Floor ACMS building
2026_IITK_921418_2
17/AC/SE/2026/154
Open Tender
Electrical Works
Percentage
240 days
IIT Kanpur
As per tender
2 documents required · 2 mandatory
₹0
₹1.7 L
6 Oct 2026
9 Sept 2026
18 Sept 2026
9 Sept 2026
17 Sept 2026
9 Sept 2026
9 Sept 2026 - 17 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1DS CS AHU with mixing box | |||||
| 1.1 | Supply of double skin Horrizontal type Ceiling suspended air handling units (AHU) of panels consisting of pre coated G.I.casing of thickness 0.6 mm outside layer and 0.6 mm inside layer with 48+-2 mm thick injected PUF of density not less than 40 Kg/CuM and i/c 10 mm thick Open cell nitrile acoustic insulation inside Fan section or with 25 mm thick injected PUF of density not less than 40 Kg/CuM and i/c 25 mm thick Open cell nitrile acoustic insulation injected between intermediate & inner skin with 0.6 mm perforated Al./GI inner sheet. of AHU. All frame work shall be thermal break with extruded aluminium profile with thermal barrier. The air handling units shall be complete with mixing chamber box with manually Supply/Return & fresh air aluminium damper, Filter-section with 25 mm thick boxs type synthetic fiber washable pre filter's section (90% down to 10 microns), coil section with 6 Rows (0.5 mm thick) Deep chilled water cooper coil & aluminium fins construction, fan section complete with Forward curved DIDW centrifugal fan, V-belts, drive package, VFD compatible variable speed squirrel cage induction motor, Motor shall be suitable for 415±10% volts, 50 Hz, 3phase AC supply having fire retardent flexible connection, 20 G SS-304 stainless steel drain pan and vibration isolator for fan & motor all complete as per standerd specification. AHU shall be selected for a maximum face velocity of 500 FPM (2.5 MPS), Fan outlet velocity shall not exceed 1800 FPM (9.1 m/s). | - | - | - | - |
| 1.2 | 1200 CFM, 6 Rows CS AHU with mixing chamber, SP-30 mm WG | 2 | Nos | 1,22,370 | ₹2,44,740 |
| 1.3 | 1500 CFM, 6 Rows CS AHU with mixing chamber, SP-30 mm WG | 6 | Nos | 1,28,129 | ₹7,68,774 |
| 1.4 | 1800 CFM, 6 Rows CS AHU with mixing chamber, SP-30 mm WG | 7 | Nos | 1,42,525 | ₹9,97,675 |
| 1.5 | 2000 CFM, 6 Rows CS AHU with mixing chamber, SP-30 mm WG | 4 | Nos | 1,55,482 | ₹6,21,928 |
| 2DS CS AHU without mixing box | |||||
| 2.1 | SITC of double skin Horrizontal type Ceiling suspended air handling units (AHU) of panels consisting of pre coated G.I.casing of thickness 0.6 mm outside layer and 0.6 mm inside layer with 48+-2 mm thick injected PUF of density not less than 40 Kg/CuM and i/c 10 mm thick Open cell nitrile acoustic insulation inside Fan section or with 25 mm thick injected PUF of density not less than 40 Kg/CuM and i/c 25 mm thick Open cell nitrile acoustic insulation injected between intermediate & inner skin with 0.6 mm perforated Al./GI inner sheet. of AHU. All frame work shall be thermal break with extruded aluminium profile with thermal barrier. The air handling units shall be complete with manually supply aluminium damper, Filter-section with 25 mm thick boxs type synthetic fiber washable pre filter's section (90% down to 10 microns), coil section with 6 Rows (0.5 mm thick) Deep chilled water cooper coil & aluminium fins construction, fan section complete with Forward curved DIDW centrifugal fan, V-belts, drive package, VFD compatible variable speed squirrel cage induction motor, Motor shall be suitable for 415±10% volts, 50 Hz, 3phase AC supply having fire retardent flexible connection, 20 G SS-304 stainless steel drain pan and vibration isolator for fan & motor all complete as per standerd specification. AHU shall be selected for a maximum face velocity of 500 FPM (2.5 MPS), Fan outlet velocity shall not exceed 1800 FPM (9.1 m/s). | - | - | - | - |
| 2.2 | 1200 CFM, 6 Rows CS AHU W/O mixing chamber, SP-35 mm WG | 2 | Nos | 1,06,534 | ₹2,13,068 |
| 2.3 | 1500 CFM, 6 Rows CS AHU W/O mixing chamber, SP-30 mm WG | 1 | Nos | 1,10,853 | ₹1,10,853 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.54 MB
Tendernotice_2.pdf
PDF • 1.05 MB
Contractdocuments.pdf
Tender Documents • 1.03 MB
BOQ_972632.xls
BOQ • 0.44 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .