Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹8.2 LAccepted-Finance | 1 | Accepted-Finance L1 | |
| 2 | 2₹8.4 L+₹16,274.33 (1.98%)Rejected-Finance R 40 VIKAS MARG SAKAR PUR DELHI 92 | 2 | Rejected-Finance L2 | |
| 3 | 3₹8.7 L+₹44,799.12 (5.45%)Rejected-Finance | 3 | Rejected-Finance L3 | |
| 4 | 4₹9.0 L+₹81,550.49 (9.93%)Rejected-Finance | 4 | Rejected-Finance L4 |
Tender Value
₹8.9 L
EMD Value
₹17,884
Closing Date
19 Mar 2026, 11:00 amClosed
EX. ENGINEER (ELECT)/CSPZ
OFFICE OF THE EX. ENGINEER (ELECT)/CSPZ UNDER GROUND CAR PARKING ASAF ALI ROAD, DELHI-110002
Provision of Electrical Installation for upgradation into Ayushman Arogya Mandir of Community Hall Ballimaran 2508, ward no 79 under CSPZ.
2026_MCD_270492_1
83/MWEEE-I/2025-26/TC
Open Tender
Electrical Works
Percentage
60 days
CSPZ
refer special conditions
2 documents required · 2 mandatory
₹590
₹17,884
21 Mar 2026
11 Mar 2026
19 Mar 2026
11 Mar 2026
19 Mar 2026
11 Mar 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. class C
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS/HFFR PVC insulated copper conductor, single core cable in surface/recessed steel conduit as required.
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
4 X 2.5 sq. mm + 2 X 2.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
Supply & Fixing following size/module,GI box alongwith modular base & cover plate for moduler switches in recess etc.as reqd.
6 Module (200 mm x 75 mm)
8 Module (125 mm x 125 mm)
12 Module (250 mm x 150 mm)
Supply & Fixing following modular switch/socket on the existing modular plate & switch box i/c connections but excluding modular plate etc.as reqd.
5/6 Amp.Switch
15/16 Amp.Switch
3 pin 5/6 Amp.Socket Outlet
6 pin 15/16 Amp.Socket Outlet
Supplying and fixing suitable size G.I box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch, connections, painting etc.as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
8 way, Double Door
12 way, Double Door
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (b) 40 amps
Supplying and fixing following rating, Two pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) 40 Amp.
SITC of LED surface mounted Batten light of following body material and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85% ,Operating voltage AC 140-270 Volt, freq 50/60 hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection ,THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5 %), life time (LED,Driver & electrical circuitary), of minimum 50000 Burning Hours with , 70% of initial Lumen maintained till life ends, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard and trade mark certificate ( T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty. System lumen efficacy ≥105 <120 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C). CRCA Sheet Body (Thickness ≥ 0.50 mm) (A) 18-22 W
SITC of Window type Air conditioners complete with copper power cable upto 3 Mtr, wireless Remote, suitable for working between 180- 260V with low & high voltagecutoff and 50 hz ,1 phase AC supply capable of performing, cooling, dehumidification, air circulation, R-32/R-410A /R-407B Green Refrigerant with Scroll / rotary compressor with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB), antifreeze thermostat on the coil as a safety feature, complete with fixing including T&P & labour etc as required complete in all respect as specified of following capacity. Sound level of up to 50dB inside the room is acceptable. The unit shall be in confirmation with IS 1391 Part-I 2023 and CPWD Specification. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. The system shall be able to operate up to50 0C (out door ambient temperature). 1.5 TR with fixed speed 5 Star BEE rating
SITC of full HD LED Monitor,55 INCHES complying with the following specifications: Resolution : Full HD : 1920 x 1080 or better Backlight : LED Brightness : 300 NITS min. Contrast : 1200 : 1 or better Power supply : 230v + / - 10%, 50 Hz at site with connections and along with all accessories etc. complete as required.
Supplying, installation, Testing & Commissioning of following capacity at full load (Unity Power Factor) ON LINE Uninterrupted Power Supply (UPS)system suitable for Single Phase input, Single Phase output AC Supply. The UPS shall include a Rectifier, inverter, battery bank suitable for 30 minutes back up (Battery VAH capacity shall not be less than 1600 VAH per KVA of UPS rating per Hour backup time) on full load (Battery shall be VRLA, SMF in ABS Container) and Static Bypass switch along with provision for manual bypass, suitable isolation transformer for additional protection against neutral faults etc. The UPS systems shall be Microprocessor based Digital Control, using Insulated Gate Bipolar Transistor (IGBT)'s both for therectifier & inverter with PWM (Pulse Width Modulation) Technology. Thequality of design, manufacturing and inspection process should confirm to the relevant Inter-national standards such as IEC/EN/VDE. The operating efficiency of the UPS systems shall be >95% at 100% non-linear loads. Current total harmonic distortion (ITHD)/ total demand distortion (TDD) on the input grid shall be < 5% at 100 %load. (The required LC filters shall be included in UPS cost), extreme power factor kit to be include to limit the input pf to 0.99 and output power factor shall be unity (i.e. kw rating of the UPS shall be kva rating x 1 ) however UPS shall be suitable to take load at 0.7 laging to 0.7 leading power factor loads. UPS shall be suitable for incoming supply AC single phase 160-270V 50 Hz and delivering output AC supply true sine wave single phase 220/230/240 Volt, 50 Hz +/- 0.2Hz, Overload capacity of 120% for 10 mins and 150% for 1 minute. Operating temperature 0 to 40 deg C, Relative humidity 0-95% non condensing, noise level less than 60db at 1 meter distance, Protection for Under voltage, over voltage, abnormal output voltage, battery over charging,output over current, short circuit, battery deep discharge , 10 KV surge.Display for watt/VA,Amp and Voltage power parameters etc. UPS shallcomply with low voltage electromagnetic compatibility (EMC) achieved asper EN 6204, EN6204 Part I and Part 2, it shall be a Voltage and FrequencyIndependent (VFI) type UPS (as per standard IEC 62040-1, 2 & 3) . The UPS should be with IGBT Based Inverter Technology, Communication RS232/RS485/SNMP port open protocol for BMS integration as per approved by Engineering in charge. Required battery racks, DC breaker of suitable rating and interconnecting copper conductor cable of suitable size and connectors and all required accoseries are inclusive in the cost. TheUPS should have QR code which should contain drawing, test report OEM manual, Geo- Tag of manufacturing location etc. 2KVA
Installation of exhaust fan in the existing opening,including making good the damage,connection,testing & commissioning etc.as reqd. Upto 450 mm sweep
Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required.
SITC of following rack capacity with glass front door, steel rear door, power supply, MCB, cable manager, drawer shelves and wiring channels to accommodate CCTV systems equipment and complete with accessories as reqd.6 U
SITC of 2MP fixed lens Bullet IP Camera with following specifications:- Image Sensor: 1/3 2MP CMOS or better** Minimum Illumination: 0.08 lux color, 0 lux with IR or better ** Shutter Speed:1/3 – 1/100,000 s Frame Rate: 1-25/30 fps or better ** Lens: 2.8mm fixed Video Compression: H.265 or better ** S/N Ratio: >45dB Resolution: (1920x1080) or better ** Protocol: should comply to IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS, IEEE802.1X IR Range: Minimum 30m Operating Temperature: -30 to 50 deg Cent Weatherproof Standard:IP66 or better ** Safety standard: UL
SITC of 8 channel NVR with the following specifications: Camera resolution:upto8MP Interface: 1 HDMI, 1VGA minimum Compression :H.265or better Network Throughput :80Mbps or better** USB Port: 2 USB port (USB2.0)minimum Hard disk interface: 1 SATA port suitable for 6TB each Protocol: IPv4/v6, TCP/IP, HTTP, HTTPS, FTP, PPPoE,DDNS Operating temp: -10 to 55 deg Cent Safety standard: UL
SITC of 8 port Giga PoE switch, 8(PoE 10/100) + 2(10/100) port long distance switch
SITC of 4 TB surveillance HDD
SITC of Pigtails 1 meter with Splicing and testing.
SITC of LIU boxes complete with all accessories etc. as required of 12 ports
SITC of full HD LED Monitor,32 INCHES complying with the following specifications: Resolution : Full HD : 1920 x 1080 or better Backlight : LED Brightness : 300 NITS min. Contrast : 1200 : 1 or better Power supply : 230v + / - 10%, 50 Hz at site with connections and along with all accessories etc. Complete as required.
Supplying & Installation of Hot Cold & Normal Floor Standing Top Loading Water dispenser with Cooling Cabinet Fridge cold water storage capacity up to 3.5 ltr with hot water storage capacity up to 1 ltr as required.
SITC of ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. metal (Aluminum alloy) blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, steel/Al body Power Factor not less than 0.9, Service Value (CM/M/W) minimum as below, 350 RPM (tolerance as per IS : 374-2019), THD (Total Harmonic Distortion) less than 10%, remote (preferably mobile app based) for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Ceiling Fan compliant to IS 374:2019 fan Supply, earthing etc. complete as req 1400mm, service value ≥ 6.0 CM/Min/Watt, air delivery 245 CM/Min (Minimum)
SITC of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celsius. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electro technical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature) 2.0 TR with 5 Star BEE Rating
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
SITC of wall mounted fan 400mm sweep rated voltage 220-230 AC rated frequency 50HZ speed 1280-1350 RPM with desired color.
S/I/T/C of stand for split AC
S/I/T/C of copper pipe for split AC
S/I/T/C of Drain Pipe
S/I/T/C of 3 Core, 4 Sqmm. Electrical wire for Air Conditioner
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.84 MB
Tendernotice_2.pdf
PDF • 26.38 MB
Tendernotice_3.pdf
PDF • 0.70 MB
DNIT01_0001.pdf
Tender Documents • 9.94 MB
BOQ_315355.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .