| Sl No | Description | Qty | Unit | M/s MAHAJAN CONSTRUCTION CO. L1 | Santokh Singh and Associates L2 |
|---|---|---|---|---|---|
| 1.00 | S & F and , installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made Meter Panel. The Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4:Meter Panel type Wall Mounted type on Mounting Structure RAL 7016 Mini. Size 600 x 750 x 170mm . The Meter Panel should be anti-acid, anti corrosive & Fully Transparent Door for meter Vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and Enclousers make Hensel or approved in MES. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. One Main Incomer MCCB 63A TP 25KA Adj. Thermal /Magnetic Release with spreader link. MCCB/MCB Nob Operated by Flip Cover. Indicator Provided on each phase. Provision for fixing Four Nos three Phase Sub-Meters. Output supply by MCB DP 32Amp 4 Nos & 1 SP 6A. Meter Enclosures & Enclosures Accessories as per RAL 7035. Ten Nos Terminal Blocks Provided for output Supply. Note :-(1) Contractor will Submit the Meter Panel Drawings for Approval and Switchgear Make :- Legrand,Schneider,L&T. (2) Taking down of existing meter panel or TPN DB is included in the quoted rate. (3) Taking out old meter and refixing that in new meter panel is included in the quoted rate. | 25 | Each | 55,900 ₹13,97,500 Lowest | 62,000 ₹15,50,000 |
| 2.00 | S & F and , installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made Meter Panel. The Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4:Meter Panel type Wall Mounted type on Mounting Structure RAL 7016. The Meter Panel should be anti-acid, anti corrosive & Fully Transparent Door for meter Vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and Enclousers make Hensel/Clipsal. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. One Main Incomer MCCB 100A TP 25KA Adj. Thermal /Magnetic Release with spreader link. MCCB/MCB Nob Operated by Flip Cover. Indicator Provided on each phase. provisin to fix Six Nos Three Phase Sub-Meters. Output supply by MCB DP 32Amp 6 Nos. Meter Enclosures & Enclosures Accessories as per RAL 7035. Ten Nos Terminal Blocks Provided for output Supply.
Note :-(1) Contractor will Submit the Meter Panel Drawings for Approval and Switchgear Make :- Legrand,Schneider,L&T. (2) Taking down of existing meter panel or TPN DB is included in the quoted rate.(3) Taking out old meter and refixing that in new meter panel is included in the quoted rate. | 25 | Each | 66,800 ₹16,70,000 | 50,000 ₹12,50,000 Lowest |
| 3.00 | Supply and fixing in replacement of sheet metal enlosure for DBs when MCBs to be used double door factory made flush fixed complete with 200 amps rated bus-bar 240 volts single phase 12 ways including necessary brick work and plaster to match with the existing surface complete all as specified and directed. | 380 | Each | 1,100 ₹4,18,000 Lowest | 1,200 ₹4,56,000 |
| 4.00 | S&F in replacement MCBs single pole (SP) 6 to 32 Amps with 10 KA breaking capacity of 'B' series in distribution boards complete all as specified and directed. | 380 | Each | 85 ₹32,300 Lowest | 110 ₹41,800 |
| 5.00 | S&F in replacement MCBs single pole and neutral (SPN) 40 to 63 Amps with 10 KA breaking capacity of 'C' series in distribution boards complete all as specified and directed. | 50 | Each | 390 ₹19,500 | 220 ₹11,000 Lowest |
| 6.00 | S&F in replacement MCBs single pole 40 to 63 Amps with 10 KA breaking capacity of 'C' series in distribution boards complete all as specified and directed. | 90 | Each | 350 ₹31,500 | 120 ₹10,800 Lowest |
| 7.00 | Supply and fixing in replacement of MCCB 100 Amps , AC 415 Volts 16KA 4 pole,ics=100% icu, Thermal and magnetic adjustable with spreader terminal including making connections with suitable size lugs complete all as specified and directed. | 10 | Each | 1,800 ₹18,000 | 1,600 ₹16,000 Lowest |
| 8.00 | Supply and fixing in replacement of sheet steel enclosure distribution boards, double door factory made TPN Vertical 4 way 3 phase 415 volts 4 way with 200 amps rating copper bus bar and PVC insulated copper jumpers of suitable size from the MCCB to the out going circuits one incoming MCCB and 12 outgoing MCBs circuits comprising of 3 phase 4 wire of suitable rating complete all as specified and directed with the following accessories :- (a) MCCB 100 amps, 16 KA, ics=100% icu,thermal and magnetic adjustable with spreader terminal, FP, 415 volts, 50 Hz = 01 No. (Note:- Out going MCB shall be measured and paid for separately) | 10 | Each | 7,500 ₹75,000 Lowest | 11,000 ₹1,10,000 |
| 9.00 | S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 6.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 6.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed. Note : Two Nos of 6.0 Sqmm Wire and one No of 6.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length. | 2,050 | RM | 118 ₹2,41,900 Lowest | 175 ₹3,58,750 |
| 10.00 | S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 4.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 4.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed. Note : Two Nos of 4.0 Sqmm Wire and one No of 4.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length. | 1,450 | RM | 110 ₹1,59,500 Lowest | 155 ₹2,24,750 |
Tender Value
₹49.9 L
EMD Value
₹99,860
Closing Date
18 Nov 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE NAMS
GE NAMS Amritsar
REPAIR/ MAINT AND UPKEEP OF JUNCTIONS BOXES, CIRCUIT BREAKERS AND ASSOCIATED WORKS IN KHETRAPAL AND TARAPORE ENCLAVE AT NAMS UNDER GE NAMS
2025_MES_737244_1
GE NAMS-75/2025-26
Open Tender
Civil Works
Item Rate
270 days
GE NAMS
CLASS D CATEGORY b(i)
8 documents required · 8 mandatory
₹500
GE NAMS
₹99,860
5 Feb 2026
28 Oct 2025
25 Nov 2025
28 Oct 2025
18 Nov 2025
11 Nov 2025
Amount
S & F and , installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made Meter Panel. The Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4:Meter Panel type Wall Mounted type on Mounting Structure RAL 7016 Mini. Size 600 x 750 x 170mm . The Meter Panel should be anti-acid, anti corrosive & Fully Transparent Door for meter Vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and Enclousers make Hensel or approved in MES. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. One Main Incomer MCCB 63A TP 25KA Adj. Thermal /Magnetic Release with spreader link. MCCB/MCB Nob Operated by Flip Cover. Indicator Provided on each phase. Provision for fixing Four Nos three Phase Sub-Meters. Output supply by MCB DP 32Amp 4 Nos & 1 SP 6A. Meter Enclosures & Enclosures Accessories as per RAL 7035. Ten Nos Terminal Blocks Provided for output Supply. Note :-(1) Contractor will Submit the Meter Panel Drawings for Approval and Switchgear Make :- Legrand,Schneider,L&T. (2) Taking down of existing meter panel or TPN DB is included in the quoted rate. (3) Taking out old meter and refixing that in new meter panel is included in the quoted rate.
S & F and , installation, commissioning and testing Polycarbonate ASTA CPRI approved OEM made Meter Panel. The Panel shall be made of modular POLYCARBONATE THERMOPLASTIC ENCLOSURES which should be UV resistance in accordance with IEC 61439-1, clause 10.2.4:Meter Panel type Wall Mounted type on Mounting Structure RAL 7016. The Meter Panel should be anti-acid, anti corrosive & Fully Transparent Door for meter Vision. Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262. The manufacturer of panel shall submit a copy of his CPRI TEST REPORT IN POLYCARBONATE only also share panel assemble by OEM, channel partner or sister concerned assembly will not accepted. DEGREE OF INGRESS PROTECTION IP 65 IN ACCORDANCE WITH IEC 60529. The gasket should be internally embedded made of polyurethane and Enclousers make Hensel/Clipsal. The manufacturer of panel SHALL submit a copy of TYPE TEST REPORT of a board made out of Polycarbonate thermoplastic panel in accordance with IEC 60439-1. The CPRI report shall have mention of following tests performed and passed out satisfactorily Temperature Rise, Dielectric Properties, Short circuit withstand current – Rated peak, short time withstand current and Rated Conditional Short Circuit Current, Effectiveness of Protective Circuits and submit the copy of type test reports for Polycarbonate Thermoplastic Board only. Test Reports submitted of other material of construction like MS, SS will not be applicable. Each Board shall have individual routine test report of the manufacturer. The panel should passed glow wire test 960oC in accordance with 60695-2-11 [flame retardant and self-extinguishing. One Main Incomer MCCB 100A TP 25KA Adj. Thermal /Magnetic Release with spreader link. MCCB/MCB Nob Operated by Flip Cover. Indicator Provided on each phase. provisin to fix Six Nos Three Phase Sub-Meters. Output supply by MCB DP 32Amp 6 Nos. Meter Enclosures & Enclosures Accessories as per RAL 7035. Ten Nos Terminal Blocks Provided for output Supply. Note :-(1) Contractor will Submit the Meter Panel Drawings for Approval and Switchgear Make :- Legrand,Schneider,L&T. (2) Taking down of existing meter panel or TPN DB is included in the quoted rate.(3) Taking out old meter and refixing that in new meter panel is included in the quoted rate.
Supply and fixing in replacement of sheet metal enlosure for DBs when MCBs to be used double door factory made flush fixed complete with 200 amps rated bus-bar 240 volts single phase 12 ways including necessary brick work and plaster to match with the existing surface complete all as specified and directed.
S&F in replacement MCBs single pole (SP) 6 to 32 Amps with 10 KA breaking capacity of 'B' series in distribution boards complete all as specified and directed.
S&F in replacement MCBs single pole and neutral (SPN) 40 to 63 Amps with 10 KA breaking capacity of 'C' series in distribution boards complete all as specified and directed.
S&F in replacement MCBs single pole 40 to 63 Amps with 10 KA breaking capacity of 'C' series in distribution boards complete all as specified and directed.
Supply and fixing in replacement of MCCB 100 Amps , AC 415 Volts 16KA 4 pole,ics=100% icu, Thermal and magnetic adjustable with spreader terminal including making connections with suitable size lugs complete all as specified and directed.
Supply and fixing in replacement of sheet steel enclosure distribution boards, double door factory made TPN Vertical 4 way 3 phase 415 volts 4 way with 200 amps rating copper bus bar and PVC insulated copper jumpers of suitable size from the MCCB to the out going circuits one incoming MCCB and 12 outgoing MCBs circuits comprising of 3 phase 4 wire of suitable rating complete all as specified and directed with the following accessories :- (a) MCCB 100 amps, 16 KA, ics=100% icu,thermal and magnetic adjustable with spreader terminal, FP, 415 volts, 50 Hz = 01 No. (Note:- Out going MCB shall be measured and paid for separately)
S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 6.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 6.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed. Note : Two Nos of 6.0 Sqmm Wire and one No of 6.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length.
S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 4.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 4.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed. Note : Two Nos of 4.0 Sqmm Wire and one No of 4.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length.
Supply & fix in replacement of LED building security Light Luminaire 25 watt 6000K with .high power LED cool white,CRI 75,+/- 5% supply voltage 220/240 50 Hz, light engine driver base.pole adapter,powder coated pressure die cast aluminium with heat resistant toughened glass with lens complete all as specified and directed.
Supply and fixing in replacement bracket made out of GI pipe suitable size for mounting building security light of medium grade 1.2 mtr long made to shape with fixing clamps of MS flat 40x6mm nut bolts etc for street light complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode of size 600 mm x 600 mm x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below ground level, connected to galvanized earth lead wire 4.00 mm dia by means of bolts nuts check nuts & washers of galvanized iron or steel , procteded by GI pipe 15 mm bore( light grade) and watering pipe 20 mm bore GI pipe (light grade ) and chamber of pcc 1:4:8 type D2 using 40 mm graded stone aggregate and coping shall be in PCC 1:3:6 type C1 using 20mm graded stone agg. 50 mm thick cover of RCC 1:2:4 type B1 using 20 mm graded stone agg. reinforced with 8 mm dia MS tor bar @ 80 mm c/c both ways including excvation and earth work and removal of surplus soil complete all as shown in electrical plate no 3 of SSR PART 1 , with charcoal dust and salt complete and earth lead connected to earthing test point (up to main switche, DBs) complete all as specified & testing on completion.
S&F in repairs Sub Main Wiring two single core PVC insulated cable of size 10.0 Sqmm multistranded copper conductor two run drawing into and including concealed rigid non-metallic PVC conduit, medium grade not less than 25mm dia with all conduit fitting,fixing accessories and one run of 10.0 Sqmm multistrand copper conductor cable as continuous earth wire complete all as specified and directed. Note :-Two Nos of 10.0 Sqmm Wire and one No of 10.0 Sqmm Earth wire and PVC Conduit in One RM length Measured as one unit length.
M&L in replacement of single core wiring 6 Sqmm multi-strand PVC insulated copper conductor FRLS cable including connections of cable with MCBs or bus bars complete all as specified and directed.
Santokh Singh and Associates (BID ID -3482377)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.74 MB
75T.pdf
Tender Documents • 1.68 MB
BOQ_825478.xls
BOQ • 5.96 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .