Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.5 LAccepted-AOC NO 6 1 ALAGAR PERUMAL KOIL MAIN STREET VADAPALANI CHENNAI 600 026 | CHENNAI | CHENNAI | TAMIL NADU | 600026 | L1 | Accepted-AOC Being lowest tenderer | |
| 2 | L2₹26.0 L+₹1.6 L (6.50%)Rejected-Finance | L2 | Rejected-Finance Being other than lowest tenderer | |
| 3 | L3₹26.7 L+₹2.2 L (9.15%)Rejected-Finance 27 1ST STREET PERIYAR NAGAR 1ST STREET PERIYAR NAGAR ADAMBAKKAM KANCHIPURAM TAMIL NADU 600088 | CHENNAI | TAMIL NADU | 600088 | L3 | Rejected-Finance Being other than lowest tenderer |
Tender Value
₹24.5 L
EMD Value
₹49,000
Closing Date
15 Feb 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Shri. Narinder Singh, IDSE, SE(SAG)
COMMANDER WORKS ENGINEERS CHENNAI PALLAVAN SALAI CHENNAI 600 002
PROVISION OF RMG AND ALLIED WORKS AT 11 KVA MAIN RECEIVING POINT AT MH CHENNAI UNDER GE STM CHENNAI
2023_MES_574387_1
86499
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
STM CHENNAI
As per tender documents
7 documents required · 7 mandatory
₹500
GE STM CHENNAI
₹49,000
Yes
28 Feb 2023
11 Jan 2023
20 Feb 2023
11 Jan 2023
15 Feb 2023
29 Jan 2023
11 Jan 2023 - 17 Jan 2023
Amount
BOQ UPLOADED ON 11 JAN 2023
Excavation in trenches not exceeding 1.5m wide and exceeding 1.5m but not exceeding 3.0m in depth for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc not exceeding 10 sqm on plan and getting out in any type of soil complete all as specified and as directed.
Earthwork is deemed to be carried out by manual method. However mechanised method may be adopted without any extra cost to the government.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in any type of soil complete all as specified and as directed.
Removing excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Fine sieved excavated dry soil laid to required width of trench at bottom and top for cable cushioning all as specified and as directed.
(a) Punned thickness only shall be measured.
(b) The soil used shall be free from sharp grains and deletrious materials like dry / decayed plants etc.,
Supply and lay Precast concrete cable cover un-reinforced. class HV, Type 1, flat, size 300mmx l80mm x 40mm complete all as specified and as directed.
Supply, laying, connecting and testing HT UG cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor, 11000 volts grade, (Earthed), 3 core, cross sectional area 120 sqmm in bridges / culvert / trenches / drawn through pipe / fixed on walls / bare in road crossings / paths / drains / ducts / floors / fixed on poles / equipments complete all as specified and as directed.
(a) Earthwork, sand cushioning, protection for cable etc., as required shall be measured and paid separately.
(b) Lugs and glands shall be used appropriately wherever required while connecting cables to the panel board and the quoted rates are deemed be include for the same.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm complete all as specified and as directed.
Material and labour for Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm complete all as specified and as directed.
Earthing complete with galvanised iron earth plate electrode 600mm X 600mm X minimum 6mm thick, with and including earthing of 32mm x 6mm GI strip protected by 40mm dia GI pipe light grade upto a length of 7.5m. The plate shall be buried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level, connected to earth lead as described here-in-before by means of bolts, nuts, washers and checknuts made out of galvanised iron or mild steel, earthing lead protected by as described here-in-before and connected to main switch board or main control board or electric pole all as shown on electrical plate No.3 of MES Sch Part-I including necessary earth work and excavation in any type of soil, plain cement concrete 1:3:6, type C1 chamber, reinforced cement concrete cover slab with locking arrangement and handle of 10mm dia MS round bars 450mm long, 1:2:4 type B1, 50mm thick with 8mm dia TMT bars at 140mm centre to centre both ways, GI pipe of bore 20mm medium grade for watering with funnel, wiremesh, salt, charcoal, lugs including testing complete all as specified and as directed.
Supply, installation, testing and commissioning of RMG unit, HT, 11 kV, 3 phase, 50 Hz, 630 Amps totally enclosed metal clad duly epoxy powder coated housing the following switch gear complete with three panel RMG 600 kVA metering system, Vacuum circuit breaker having rupturing cacacity of 350 MVA - 01 No, overload and earth fault protection, ammeter and voltmeter of rating upto 630 Amps, load break switch - 02 Nos, cubicle type, having degree of protection of IP-54, outdoor type, copper busbars complete and including civil worrks like PCC foundation (as per manufacturers design and specification), Mild Steel sections like angles, channels and fasteners required for grouting, painting complete all as following specifications:-
(a) VCB with 3 Nos vacuum interrupters of rating 11 kV, 3 phase, 50 Hz, 350 MVA, 630 Amps, mounted on common base segregated epoxy body of higher electrical insulation and to maintain pole discrepancy as per IEC-56 and self aligned type isolating contacts manual and motor operating (230 Volt AC), spring charged mechanism, manual closing and tripping push button, emergency trip push buttons, mechanical indication for circuit breaker close / open, mechanical operation counter 8 NO + 8 NC Breaker operating auxillary switch, spring charged / discharged indication, circuit breaker service / test position indication.
(i) Rated voltage : 11 kV
(ii) Phase : 3
(iii) Rated frequency : 50 Hz
(iv) System maximum voltage : 12 kV
(v) Rated bus bar current : 630 Amps
(vi) AC control voltage : 230 Volt AC
(vii) Input voltage : 230 Volt AC
(viii) DC control voltage : 110 Volt DC from power pack.
(ix) Rated current : 630 Amps
(x) Rated breaking capacity : 350 MVA
(xi) Short time duration: 3 sec
(xii) Rated operating duty : 0-0.3 sec-CO-3 min-on
(xiii) No of poles : 3
(xix) Closing coil:110 V DC
(xx) Tripping coil:110 V DC
(xxi) Type of charging : Manual as well as motorised spring charging mechanism with 230 V AC operated motor.
(b) Load Break Switch LBS The LBS (Isolator) shall be 630 Amps, 25 kA, 11 kV, 3 Phase, 50 Hz, 500 MVA - 02 Nos, enclosed metal clad, cubicle type, having degree of protection of IP-66, outdoor type, with extended handle mounted with RMG unit free standing weather proof compartmentalised. The Isolator switch board frame load bearing members shall be fabricated out of mild steel structural sections, pressed and shaped CRCA sheet. The operating mechanism shall be spring assisted mechanism with operating handle for ON / OFF. Earth positions with 5 arrangment for padlocking in each position. Also independent manual operations with mechanically operated indicator. Each load break switch shall be quick break contacts and with integral earthing arrangement. The isolator shall be at an ambient temperature 50 degree centigrade.The LBS shall be fully type tested by CPRI conforming to IEC 265 / IS 9920.
(i) The LBS shall have ON / OFF mechanical indications and electrical indications.
(ii) Auxillary switch 2 NO + 2 NC.
(iii) LBS ON Red Colour, LBS OFF Green Colour
(iv) Space heater 2 Nos, 230 V AC with ON-OFF switch with thermostat.
(c) RMG UNIT WITH ENERGY METER COMPARTMENT :- A separate meter compartment shall be made CRCA sheet minimum 2mm thick and all the compartments shall be welded from inside and full size clear toughened glass shall be provided on the door of the meter compartment so as to have complete visibility. The metering compartment shall be provided beside the CTPT compartment and the 10 core armoured service cable shall run inside the cubicle and the excess to the metering compartment comprising of the following:-
(i) POTENTIAL TRANSFORMERS
(1) Voltage ratio 11 kV/110 V with HRC fuse.
(2) Mounting draw out type
(3) Insulation : Epoxy resin cast
(4) Type 3 phase, 3 Limb
(5) Accuracy class / burden 0.2/50 VA
(6) Insulation level 12 kV / 75 kV Peak / 28 kV rms
(ii) CURRENT TRANSFORMERS
(1) Protection Class 5 P 20, Burden 15 VA
(2) Metering Class 0.2 S, Burden 5 VA
(3) Insulation level 12 kV / 75 kV Peak / 28 kV rms
(4) Ratio 75 / 5-5A
(5) No of core : dual
(6) Insulation : Class B
(7) Insulation : Epoxy resin cast
(8) PTR - 11 kV/110 V
(9) Reference standards IS 2705
(f) After acceptance, the Contractor shall produce OEMs drawing, detailed specification, constructional and safety features, technical parameters on drawing for approval of GE.
(g) The contractor shall liase with TENGEDCO/TNEB for shifting existing metering unit to RMG with provision of suitable size CT/PT and cost of the same deemed to include in the rate quoted.
Supply, installation, testing and commissioning of HT panel, 11 kV, 3 phase, 50 Hz, 630 Amps totally enclosed metal clad duly epoxy powder coated housing the following switch gear complete Vacuum circuit breaker having rupturing cacacity of 350 MVA - 01 No, overload and earth fault protection, ammeter and voltmeter of rating upto 630 Amps,cubicle type, having degree of protection of IP-54, outdoor type, copper busbars complete and including civil worrks like PCC foundation (as per manufacturers design and specification), Mild Steel sections like angles, channels and fasteners required for grouting, painting complete all as following specifications:-
(a) VCB with 3 Nos vacuum interrupters of rating 11 kV, 3 phase, 50 Hz, 350 MVA, 630 Amps, mounted on common base segregated epoxy body of higher electrical insulation and to maintain pole discrepancy as per IEC-56 and self aligned type isolating contacts manual and motor operating (230 Volt AC), spring charged mechanism, manual closing and tripping push button, emergency trip push buttons, mechanical indication for circuit breaker close / open, mechanical operation counter 8 NO + 8 NC Breaker operating auxillary switch, spring charged / discharged indication, circuit breaker service / test position indication.
(b) Self powered microprocessor based numeric relay (over current + Earth fault + IDMT + Inst) with high set for both phase and earth and with fault memory, universal auxillary supply conforming to IS-3231 8686. The setting of over shall be 50% to 200% in the step of 10% and for earth fault element from 10% to 40% in the step of 10%.
(e) AC static HT 11 kV Tri-vector meter with Back lit LCD / LED display of measured values on seven segment, seven digit liquid crystal display (LCD) / LED unit / register complete in all respects.
(f) Current Transformer Dry Cast Resin, 11 kV,Triple Ratio 50-25-15/5 Amps, 15 VA burden, Class I accuracy for metering and protection CT with Clamp of accuracy Class 5P10 of IS-2705-Part-III-1992 complete in all respects and suitable for measuring the load of Transformer - 03 Nos.
(g) Potential Transformer Dry Cast Resin, 11 kV / 110V with HT and LT fuses, minimum 200 VA burden- Set of three - 01 No.
(h) Power pack equipment with backup for 15 minutes including maintenance free batteries (24-30 Volts, upto 80 AH) complete suitable for protection / operation of relays - 01 No.
(j) Set of LED indicating lamp operating at 110 V single phase as below:-
(i) RED / GREEN : VCB ON/OFF indication
(ii) AMBER: Trip indication
(iii) WHITE : Trip circuit healthy indication with push button.
(iv) BLUE : VCB mechanism spring charged indication.
(k) One set of heat shrinkable PVC sleeved 800 Amps copper busbar
(l) Strip heat 100 watt (continuously rated) - 01 No with thermostat control for breaker / CT compartment with manual ON-OFF switch - 01 Set
(m) 3 way breaker control switch with positions TRIP-NEUTRAL-CLOSE - 01 No.
(n) Manual charging / operating arrangement.
(i) Auto trip
(ii) Motor / manual charged spring operating / closing mechanism.
(iii) Fault alarm
(iv) Manual tripping
(o) Complete wiring of control panel with copper wiring of suitable section.
(p) Test terminal block (TTB) to test meters and relays with sealing arrangement.
(q) Armoured copper cable 1100 Volts, of suitable section from LT panel / DB to VCB panel as per OEM recommendations.
(r) Alarm system : Common alarm with reset system to be provided on panel board for circuit breaker trip, DC auxillary supply failure and AC auxillary supply failure, 230 V AC auxillary supply.
(s) After acceptance, the Contractor shall produce OEMs drawing, detailed specification, constructional and safety features, technical parameters on drawing for approval of GE.
Supply, installation, testing and commissioning of HT panel, 11 kV, 3 phase, 50 Hz, 630 Amps totally enclosed metal clad duly epoxy powder coated housing the following switch gear complete with Vacuum circuit breaker having rupturing cacacity of 350 MVA - 01 No, overload and earth fault protection, ammeter and voltmeter of rating upto 630 Amps, load break switch - 03 Nos, cubicle type, having degree of protection of IP-54, outdoor type, copper busbars complete and including civil worrks like PCC foundation (as per manufacturers design and specification), Mild Steel sections like angles, channels and fasteners required for grouting, painting complete all as following specifications:-
(a) VCB with 3 Nos vacuum interrupters of rating 11 kV, 3 phase, 50 Hz, 350 MVA, 630 Amps, mounted on common base segregated epoxy body of higher electrical insulation and to maintain pole discrepancy as per IEC-56 and self aligned type isolating contacts manual and motor operating (230 Volt AC), spring charged mechanism, manual closing and tripping push button, emergency trip push buttons, mechanical indication for circuit breaker close / open, mechanical operation counter 8 NO + 8 NC Breaker operating auxillary switch, spring charged / discharged indication, circuit breaker service / test position indication.
(b) Self powered microprocessor based numeric relay (over current + Earth fault + IDMT + Inst) with high set for both phase and earth and with fault memory, universal auxillary supply conforming to IS-3231 8686. The setting of over shall be 50% to 200% in the step of 10% and for earth fault element from 10% to 40% in the step of 10%.
(e) AC static HT 11 kV Tri-vector meter with Back lit LCD / LED display of measured values on seven segment, seven digit liquid crystal display (LCD) / LED unit / register complete in all respects.
(f) Current Transformer Dry Cast Resin, 11 kV,Triple Ratio 50-25-15/5 Amps, 15 VA burden, Class I accuracy for metering and protection CT with Clamp of accuracy Class 5P10 of IS-2705-Part-III-1992 complete in all respects and suitable for measuring the load of Transformer - 03 Nos.
(g) Potential Transformer Dry Cast Resin, 11 kV / 110V with HT and LT fuses, minimum 200 VA burden- Set of three - 01 No.
(h) Power pack equipment with backup for 15 minutes including maintenance free batteries (24-30 Volts, upto 80 AH) complete suitable for protection / operation of relays - 01 No.
(j) Set of LED indicating lamp operating at 110 V single phase as below:-
(i) RED / GREEN : VCB ON/OFF indication
(ii) AMBER: Trip indication
(iii) WHITE : Trip circuit healthy indication with push button.
(iv) BLUE : VCB mechanism spring charged indication.
(k) One set of heat shrinkable PVC sleeved 800 Amps copper busbar
(l) Strip heat 100 watt (continuously rated) - 01 No with thermostat control for breaker / CT compartment with manual ON-OFF switch - 01 Set
(m) 3 way breaker control switch with positions TRIP-NEUTRAL-CLOSE - 01 No.
(n) Manual charging / operating arrangement.
(i) Auto trip
(ii) Motor / manual charged spring operating / closing mechanism.
(iii) Fault alarm
(iv) Manual tripping
(o) Complete wiring of control panel with copper wiring of suitable section.
(p) Test terminal block (TTB) to test meters and relays with sealing arrangement.
(q) Armoured copper cable 1100 Volts, of suitable section from LT panel / DB to VCB panel as per OEM recommendations.
(r) Alarm system : Common alarm with reset system to be provided on panel board for circuit breaker trip, DC auxillary supply failure and AC auxillary supply failure, 230 V AC auxillary supply.
(s) Load Break Switch LBS The LBS (Isolator) shall be 630 Amps, 25 kA, 11 kV, 3 Phase, 50 Hz, 500 MVA - 03 Nos, enclosed metal clad, cubicle type, having degree of protection of IP-66, outdoor type, with extended handle mounted with VCB free standing weather proof compartmentalised. The Isolator switch board frame load bearing members shall be fabricated out of mild steel structural sections, pressed and shaped CRCA sheet. The operating mechanism shall be spring assisted mechanism with operating handle for ON / OFF. Earth positions with 5 arrangment for padlocking in each position. Also independent manual operations with mechanically operated indicator. Each load break switch shall be quick break contacts and with integral earthing arrangement. The isolator shall be at an ambient temperature 50 degree centigrade.The LBS shall be fully type tested by CPRI conforming to IEC 265 / IS 9920.
(i) The LBS shall have ON / OFF mechanical indications and electrical indications.
(ii) Auxillary switch 2 NO + 2 NC.
(iii) LBS ON Red Colour, LBS OFF Green Colour
(iv) Space heater 2 Nos, 230 V AC with ON-OFF switch with thermostat.
(t) After acceptance, the Contractor shall produce OEMs drawing, detailed specification, constructional and safety features, technical parameters on drawing for approval of GE.
M/S.RANGA AND CO
EVEREST ENGINEERING WORKS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .