Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical CHANDRONA TEHSIL NOHRADHAR DISTRICT SIRMOUR H P | Accepted-Technical Technocommercial Responsive |
| 2 | Accepted-Technical BILASPUR | Accepted-Technical Technocommercial Responsive |
| 3 | Accepted-Technical 0 MATADIN KAKRAHI KAKRAHI BHARTHANA ETAWA ETAWAH UTTAR PRADESH 206242 | ETAWAH | UTTAR PRADESH | 206242 | Accepted-Technical Technocommercial Responsive |
Tender Value
₹12.4 L
EMD Value
₹12,380
Closing Date
18 Nov 2026, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Sr. Executive Engineer
Sr. Executive Engineer ED HPSEBL Amb
AED/121/2026-27.
2026_HPSEB_146565_2
AED/121/2026-27
Open Tender
Electrical Works
Percentage
120 days
Sr. Executive Engineer ED HPSEBL Amb
Please refer a tender document.
2 documents required · 2 mandatory
₹590
₹12,380
18 Nov 2026
6 Nov 2026
18 Nov 2026
6 Nov 2026
18 Nov 2026
6 Nov 2026
180 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Outdoor IP55 36kV Kiosk VCB Switchboard, The Cubicle should be made from Aluzinc or GI/GP (120 Micron Galvanized) Sheets, duly Powder Coated PP type (Shade 631 of IS 5) with base frame, 36kV Bushing of suitable current capacity (6 Nos) at the top of the switched for connecting the panel through ACSR Wolf Conductors with terminal connectors, fitted with following items to make fully ready to operate panel for use under independent feeder control and Auto-recloser to the feeder: -
Vacuum Circuit Breaker: -
36kV, 1250A, 26.3kA for 3 Sec. Fixed Type VCB with Manual & Electrically operated, Spring Charging Mechanism with 230V AC Motor and Manual Handle, Mechanical ON/OFF indicator, Operation Counter, as per IEC/IS 62271-100.
Shunt Opening & Closing Coils 24V DC ( (2 tripping circuits, 1 closing circuit) , Auxiliary contact 6NO+6NC, Anti-pumping Device 24V DC.
Potential Transformer: -
Single Phase, Resin Cast, Dry type, Fixed type Potential Transformer (3 Nos) with one set of HTFS / LTFS and one no. Neutral Link (11 kV√ 3/110√ 3-110√ 3V), (Metering Class 0.2, 30VA, Protection Class 5P10)
Current Transformer: -
Single Phase, Resin Cast, Dry type Current Transformer (3 Nos.) Ratio 400-200/1-1-1A) (Core 1: for meter 0.2S (Burden: 10 VA), Core 2: for Protection 5P10 (Burden: 15 VA), Core 3: for Protection 5P10 (Burden: 15 VA))
Metering: -
96 sq.mm Digital Ammeter with Inbuilt Selector Switch: (1 No.)
96 sq.mm Digital Voltmeter with Inbuilt Selector Switch: (1 No.)
Tri-vector Meter Phase 4Wire system: (1 No.)
Protections: -
1) Numerical Non-Directional lDMT combined 3 O/C+1 E/F relay with low set, high set, instantaneous feature, Broken Conductor, Auto-reclose feature, communicable type (IEC-61850), 2) High speed/Master trip relay (1 No.)
3) TCS Relay (2 No.) | 1 | No. | 10,73,800 | ₹10,73,800 |
| 2 | Indication Lamps: -
VCB OFF/ON/Auto trip, Trip Circuit Healthy, Spring Charge, & R,Y,B Phase Indication Lamps (1 set)
Control Switches & Push Buttons
Breaker Control Switch (Close-Neutral-Trip) (1 No.)
Local Remote selector switch (1 No.)
Flush Head type Trip Circuit Healthy Push Button (1 No.)
Control wiring with appropriate colors (1 Set)
Complete switchboard wiring to be carried out with Cu flexible wires, lugs, identification ferules, marking tags as per approved drawing and standard practice of relays / meters. For CTs and DC Circuit minimum 2.5 mm² and for other AC Circuits minimum 1.5 mm² shall be used. Every wire should be routed through terminal blocks. For CTs and PTs TTB type are mandatory to test relays and meters for injection of current and voltage from Secondary Injection Test Kit.
Busbar Ratings: -
36kV, 630A Al Busbar (Rectangular or Round) (Conductivity should be above 55%) with 36kV Rated Insulation Sleeves Hot/Cold Shrink type 1 Set)
Earth bus 40x6 mm (Aluminium) (1 Set)
Other Equipments: -
Heater ON/OFF switch with filament type 80Watts space heater & thermostat, single phase switch with socket, Cubicle LED Lamp for panel illumination with snap type door limit switch, Fuses / MCBs for AC / DC control. (1Set)
Approved Make: -
a) VCB – ABB/Schnieder/Siemens.
b) CT, PT & VT – Pragati/ECS/Savio.
c) INDICATOR / METERS / MCB – ABB/Schnieder/Siemens
d) CONTROL SWITCHES – Salzer/Kaycee
e) HEATER & THERMOSTAT – Reputed
f) BUSBAR – Hindalco/Jindal
NOTE: -
24V DC for operation of the circuit breaker and protection relays shall be taken from the integrated power pack/supply with suitable capacity battery and charging circuit arrangement. This is to ensure the operation of the breaker in case of power supply failure (2 open and 2 close operations). | - | - | - | - |
| 3 | Civil Work (Construction of Concerete base for Auto Re-closer Panel) | 1 | Job | 46,136 | ₹46,136 |
| 4 | Erection Charges including providing and fixing of 4C Control Cable for AC Supply from CRB to proposed site of Kiosk. (5% of Material Cost) | 1 | Job | 53,690 | ₹53,690 |
| 5 | Transportation / Mannual carriage of material at destination site.(5% of Material Cost) | 1 | Job | 64,428 | ₹64,428 |
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.66 MB
Technical Specification.pdf
Tender Documents • 11.67 MB
Bid121.docx
Tender Documents • 0.45 MB
BOQ_220256.xls
BOQ • 0.29 MB
Crndem.pdf
PDF • 3.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .