Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Infra Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance 0 ADAMPUR MUBARAKPUR AZAMGARH AZAMGARH UTTAR PRADESH 276404 | AZAMGARH | UTTAR PRADESH | 276404 | Admitted-Finance |
| 3 | Not Admitted-Fee/PreQual/Technical | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹10 L
EMD Value
₹15,000
Closing Date
5 Feb 2024, 9:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE EDC CHITRAKOOT
Dwarikapuri Purani Bazar Karwi Chitrakoot
Work of installation 01 NOs 05 MVA additional Power transformers in S/S Pahadi Under EDD-Rajapur
2024_DVVNL_877252_3
45/SE/EDCCKT/2023-24
Open Tender
Electrical Works
Piece-work
180 days
KARWI CHITRAKOOT
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,540
www.dvvnl.org
₹15,000
22 Feb 2024
27 Jan 2024
5 Feb 2024
27 Jan 2024
5 Feb 2024
27 Jan 2024
The work of 01 Nos Additional 05 MVA installetion at 33/11 KV S/S Pahadi under BUSINESS PLAN SCHEME 2024-25 under EDD, Rajapur, including carriage of all required material/Transformers from ESC/Workshop Chitrakoot to work site, alongwith its loading, unloading & dragging at the respective ends and also safe carriage of old T/Fs from site to store centre/workshop, if any. Material like cable box, hoisting clamps of appropriate size is to be arranged by contractor on his own cost, details of the work as given below ;-
Carriage of all the concerning material from store centre to the site of work including loading, unloading and proper satcking at site etc.
33 KV Bus isolator
33 KV Post insulator
33 KV Line isolator
33 KV Lightenning Arrestor
11 KV 3X300 sq. mm XLPE cable
11 KV 3X185 sq. mm XLPE cable
Plinth of 33/11 Kv T/Fs Suitable for 01 no. 5MVA Construction of Plinth of size 2x2x1.5 Mtr for 5 MVA T/f. The work includes Excavation of foundation, Base concreting in C.C. 1:6:12 ratio ( cement,fine sand and Brick ballast) 1ST Class bricks work in cement mortar of ratio 1:4 foundation, C.C. in 1:4:8 ratio( cement, fine sand and brick ballast) and RCC working ratio 1:2:4 ( cement, coarse sand and stone grit of 20 mm gauge) using MS Bars of 10 mm Dia (Tor) in reinforcement including its cutting, bending and binding in required shape. The work also includes laying of 2 Nos. 3.46 mts long each rail pieces complete with cutting, welding and proper fitting etc. The plinth will be made as per Drawing and shall be plastered/ finished on Top and Side of the plinth.
Fabrication, Erection & Grouting of Sub station structure (a) Terminal Gantry Digging two No. pits of size 2.2 Mtrx 1.4Mtrx0.75 Mtr providing stone pad at the bottom of trench and grouting of the two legs of the Terminal Gantry in CC ( cement, coarse sand and stone grit of 20 mm gauge) in the ratio 1:3:6 including supply of all T&P shuttering etc. In a block of size 2.2mtx 1.4 mtx0.75 mt. The work consist of dragging , shifting up to 40 mtr raising and erecting the Two pre fabricated legs of terminal gantry in proper alignment, level and plumb. Both the plinth of the Terminal Gantry shall be properly finished with champering of edges. The work includes fabrication of terminal gantry 8.23Mtrlong as per RESSPO Manual (All Material supplied by Contractor on his own cost).
(b)Bus Bar Gantry Digging of 2 Nos Pits of size 2.2mt x1.4mt x 0.75 Mtr providing stone pad at the bottom of the trench and grouting of the two legs of the Bus Bar Gantry in CC ( cement, Coarse sand and stone grit of 20mm gauge) in the ratio 1:3:6 including supply of all T&P shuttering etc. in a block of size 2.2 mtx1.4 mtx0.75 mt. The work consists of dragging , shifting up to 40 mtr raising and erecting the two pre fabricated legs of Bus Gantry in proper allingment level and plumb. Both the plinths of the termainal gantry shall be properly finished with champering of edges. The work includes fabrication of Bus Bar Gantry 6.23 MtrLong as per RESPO Manual (bus structure MS steel will be supplied by Contractor on his own cost).
(c) Bus Isolator/Line Isolator Structure Fabrication of isolator structures 3.5mtr in height as per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.9 x0.3 Mtr providing stone pad at the bottom of the pit and grouting pad at the bottom of the pit and grouting of two legs of the isolator structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 mtX 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with runner of isolator in proper allingment level and plumb. Both plinths of the Isolator structure shall be properly finished with champering of edges. (structure MS steel will be supplied by Contractor on is own cost).
(D)LighteningArrestor Structure Fabrication of Lightening Arrestor per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure's in proper allingment level and plumb. Both plinths of the structure shall be properly finished with champering of edges etc.(Lightening Arrestor structure MS steel will be supplied by Contractor on is own cost).
(E)Post Insulator/C.T.Structure Fabrication of Post Insulator per drawing No. RES 39 Digging of two Nos. Pits of size 1.075 x 0.3 x0.3 Mtr providing stone pad at the bottom of the pit and grouting of two legs of the above structure in CC ( cement, coarse sand and stone grit of 20 mm gauge) of ratio 1:4:8 in block of 1.075 Mtr X 0.3 Mtr x 0.3 Mtr including supply of all T&P complete in all respect. The work includes dragging, Shifting upto 40 Mtr. Raising and erecting the two legs with Top frame above structure's in proper allingment level and plumb. Both plinths of the structure shall be properly finished with champering of edges etc. (Post insulator structure steel will be supplied by Contractor on is own cost).
Fabrication and grouting of M.S. channel 100x50x6 mm in L shape & in proper size and allignment to provide support for the two separate earthing strips for power transformer neutral including supply & fixing of two Nos. Flexible Copper bonds for neutral earthing.
Fabrication and erection of cable support made of two pieces of M.S. Strip 65x65x6 mm, 3.0 Mtr long joined to each other by means of 5 Nos M.S. Flat 50x6 mm pieces of size 150 mm long each by welding at equal intervals as per drawing and grouting in a block of size 300x300x700 mm complete with one coat of ready mixed primer and two coats of Al. paint. This includes providing of four Nos. M.S.clamp made of M.S. flat for holding the cable including nuts and Bolts and fixing of XLPE cable.
Special Earthing by way of boring and lowering of "B" class G.I. pipe 50 mm Dia 20mtr long from ground upto the water level and it will be connected to the G.S. strip for transformer neutral connection. The earth strip will be welded to the G.I. Pipe. The work also includes Cap & Clamps for pouring water, the cost of all material with all labour & T&P etc. Complete in all respect.
Lightening- Arrestor
Neutral of T/F
P.T. of Incoming S/G
33 KV C.T. 200/100/1-1A
Earth filling in the Switchyard of size 20x25 mtr including cost of earth handling and cartage upto Switcyard from outside with its unloading and laying in the yard, Leveling, Watering and Ramming till its Compactness
Installation of Isolators Assembling and installation of line/Bus isolator on the Isolator structure , adjusting of opening mechanism in proper alignment so as to ensured smooth operation of the same. In case of line Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
Installation of Lightening Arrestors Assembling and installation/ mounting of three Nos.Lightening Arrestors on the L.A. structure/ complete with making earth connection ( Separate ) and line connections. The work includes fabrication for proper fixing if required.
Installation of CTs Installation of 3 Nos CTs of ratio 200/100/1A on the CTs structure. The work includes fabrication for proper fixing if required.
33 kv VCB with Singal T/F control pannel and CT 200/100/1A with structure :- (1) 33 kv VCB (II) Control pannel I/C for 33 kv Singal T/F (III) CT 200/100/1A (IV) Steel structure Installation of 33 Kv VCB, complete in all respect including commissioning (Steel structure provide by Contractor on his own cost)
33KV Bus Bar & Stringing. Stringing of 33Kv Bus Bar by using and laying of ACSR Dog Conductor including fixing of Disc Insulator. Strings and tension fitting complete with sagging of Bus Bar etc. and making Vertical/Horizontal jumper connection through PG clamps and connecting all the equipments with each other through connecting clamps.
Painting of Structure Painting of following structure with one coat of ready mixed primer and 2 coats of AL.Paint of good quality including cost of material, Labour and T&P complete in all respect.
Bus Gantry ( Complete set )
Terminal Gantry-2
Bus/Line Isolator Structure
Lightening Arrestor
CT structure
Cable Stand
Neutral Strand
Laying of Double Circuit 11 KV 3X300 sq. mm/3X185 sq. mm XLPE cable
In Normal soil by digging of trench 1050 mm deep, 750 mm wide including supply of required material as fine a sand, Ist class bricks, Inter axial spacing between the two cable should be ing between 0.25 m to 0.40m , the two cables should be separated by a partiton of singhle bricks (All the material will be supplied by the contractor except 11 KV XLPE cable)
High Pressure testing with D.C. Test Voltage to which cable shall able to be stand for duration of 5 minutes after completion of laying, joints & termination up to 60 kv (Testing equipment will be arranged by the contractor)
Hoisting of 33 KV Cable on existing/erected support with provision of MS Pipe 150 mm dia 3 mtr long suitable for 3x185 sq mm cable fixing of proper support and its clamping, jumpering properly as per RESSPO Norms. (All material will be supplied by the contractor).
Installation of Heat Shrinkable Type cable jointing kits O/D end Termination suitable for 33 KV XLPE cable confirming to IS ESI-09-13-IS-13573 of 1992 amendment I&II VDE-0278 of latest version there of if any. (Jointing Kit supplied by Contractor)
Fixing & Commisioning of 24 Volt Battery with Cabinet as per norms complete in all respect as per RESPO manual and as per direction of Engineer Incharge including the cost of labour, T&P and carrier etc. required for proper completion of work. (All Material shall be Arrange by Contractor on his own cost)
Commissioning of 5 MVA T/F and its equipments installed in switchyard and 11 KV Incoming and Outgoing Pannels complete in all respect upto energising.
M/S PRAKASH ENTERPRISES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .