Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.2 LAccepted-AOC AT SELECTED DHORI COLLIERY POST PHUSRO BAZAR DIST BOKARO JHARKHAND 829144 | PHUSRO BAZAR | BOKARO | JHARKHAND | 829144 | L1 | Accepted-AOC L1 bidder is techno commercially qualified. | |
| 2 | Rejected-Technical | - | Rejected-Technical Bid not be opened as per NIT terms | |
| 3 | Rejected-Technical AT AWADH CINEMA ROAD PHUSRO BAZAR PO PHUSRO BAZAR DIST BOKARO JHARKHAND 829144 | BOKARO | JHARKHAND | 829144 | - | Rejected-Technical Bid not be opened as per NIT terms. |
Tender Value
₹8.4 L
EMD Value
₹10,500
Closing Date
22 Jan 2024, 9:00 amClosed
Staff Officer (EnM)
Office of the General Manager, Dhori Area
Erection of pole along with making of bus bar structure, lighting arrestor, Chemical earthpits in P.O. office under Dhori Khas UG minesin Dhori Area
2024_CCL_297981_7
GM(D)/SO(EnM)/DA/2023-24/113
Open Tender
Electrical and Maintenance Works
Item Wise
21 days
Dhori (K), Dhori Area
Please refer Tender documents.
2 documents required · 2 mandatory
₹10,500
21 Feb 2024
9 Jan 2024
23 Jan 2024
9 Jan 2024
22 Jan 2024
9 Jan 2024
9 Jan 2024 - 15 Jan 2024
Amount
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.Above 10.00 metre and upto 12.00 metre
Erection of metallic pole of following length in cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) foundation including excavation and refilling etc. as required.Above 6.5 metre and upto 8.0 metre
Dismantling of cable & Stacking at a place as per instruction of EIC 90 sqm cable
Dismantling of cable & Stacking at a place as per instruction of EIC 70 sqm cable
Dismantling of cable & Stacking at a place as per instruction of EIC 120 sqm cable
Dismantling of over head lines comprising of copper/ aluminium over headconductor, G.I. wire, cross arms, insulators etc. as required
Departmental Supply of channel Angle etc iron materials to be used in Bus bar structure (Departmental Supply) (Do not fill rate for this item or fill '0')
Cutting & wielding of iron materials
Supplying of clamps
Supply and fixing of horizontal type heavy duty GOS, 11 KV 800A double break
Erection of angle iron/ channel iron cross arm on wood/ RCC/ PCC/ steel tubular/ rail pole etc. as required.
Erection of AAA conductor of 7/3.35 mm to 7/4.00 diameter and above including binding etc. as required.
Dismantling of pole/ street light standard/ strut embedded in cement concrete foundation etc. as required
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)used for horizontal types
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. Used Vertical types
Supplying and erection of three piece nonlinear resistor type lightning arrestor suitable for 3 wire, 11 KV overhead lines with rated voltage 9 KV (rms) with a nominal discharge current rating of 5 KA and complete with galvanised clamping arrangement, G.I. bolts, nuts, washers etc. as required
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing of nuts and bolts
Providing of different size washers
Providing of T connector
Dismantling, maintaining & refitting of horngap
Providing of Bus bar alluminium dia 40.8 mm & outer 48.30 inch lengh 3.6 m
Fixing of Bus bar as per Inst. of EIC
Providing of Bus bar connector
Supplying & fixing of cable pad
Fixing of bus bar support post insulater with nuts & bolts
Providing & fixing of aluminium jointer
Supplying and erection of a set of cross bracing FRLSame work for 11 KV over head line double pole structure having four members fabricated out of 50 mm X 50 mm X 6 mm angle iron to form a rectangle of minimum size 1400 mm width X 2500 mm height, complete with 50 mm X 6mm M.S. flat iron clamps, bolts and nuts including drilling holes for insulator pins, bolts and nuts etc (as per drawing) and painting with primer and finish paint as required
Providing & fixing of copper lugs 10mm
Supplying and erection of 11 KV disc insulator for 11 KV over head lines with galvanised insulator fittings, ball and socket type and complete with galvanised strain clamps, bolts, nuts, washers etc. as required+Erection of disc/ pin insulator for 11 KV over head lines as required.
Supplying and erection of 11 KV pin insulator complete with large steel head G.I. pin, nuts, washers etc. as required.+Erection of disc/ pin insulator for 11 KV over head lines as required.
Applying priming coat :With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel galvanised iron/ steel works +Painting with aluminium paint of approved brand and manufacture to give an even shade Two or more coats on new work.
Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :Two or more coats on new work over an under coat of suitable shade with ordinary paint of approved brand and manufacture for jalli Painting
Dismantling of Gang operating switch different type
Machanised drills for making of holes over iron channel/angle as per required for structure of bus bar
Total impact of GST for the purpose of CTC
M/s engineer associates
Aadi Enterprises
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .