| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.8 LAccepted-Finance A 111 JHILMIL COLONY EAST DELHI 110095 | SHAHDARA | DELHI | 110095 | L1 | Accepted-Finance L1 Accepted | |
| 2 | L2₹9.9 L+₹4,929.51 (0.50%)Rejected-Finance | L2 | Rejected-Finance L2 Rejected | |
| 3 | L3₹9.9 L+₹8,827.26 (0.90%)Rejected-Finance F 1 1ST FLOOR EAST JYOTI NAGAR SHAHDARA DELHI DELHI 110093 | NORTH EAST | DELHI | 110093 | L3 | Rejected-Finance L3 Rejected | |
| 4 | L4₹10.5 L+₹73,942.67 (7.54%)Rejected-Finance | L4 | Rejected-Finance L4 Rejected |
Tender Value
₹11.5 L
EMD Value
₹22,950
Closing Date
31 Dec 2025, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer (Elect)-II
OFFICE OF THE Ex. ENGINEER (ELECT)-II, SHAHDARA (N) ZONE, KeshavChowk, Delhi-110053
Provision of lighting arrangement at various dark spots in area/ Parks under EEE-ll SNZ
2025_MCD_260392_1
EE(E)-II/SNZ/MCD/25-26/TC-31/1
Open Tender
Electrical Works
Percentage
90 days
As per NIT
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
₹22,950
7 Apr 2026
24 Dec 2025
31 Dec 2025
24 Dec 2025
31 Dec 2025
24 Dec 2025
Supply of PVC insulated and FR PVC Sheathed multicore copper conductor 1.1KV grade, conforming to grade IS 694 as required . 3*1.5 Sq.mm
Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt) as required.
Providing and Fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/submain wiring/ cable as required.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/HUME/ METAL pipe as required. Up to 35 sq.mm.
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Up to 35 sq.mm.
Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres lengthalong the pole for protection of under ground cable as required.
Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
Fabrication, supply & erection of 5.0 mtr height, minimum 3 mm thick, bottom dia of 130mm & top die of 70mm, base plate of size 225 x 225 x 12 mm thick flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full vertical window cover at appropriate height from the base plate on existing cement concrete pedestal as required. Uc supplying and fitting of 6 mm thick laminated mounted sheet inside the window and I/c providing and welding 3 nos. Gl strips 4 mm thick of suitable length and having suitable size tapped holes as reqd, terminal block suitable for 25 sq mm conductor 4 nos. & shorting links on DIN channel Uc providing and fixing DIN channel of suitable length, 6 Amp. SPMCB 'C' Curve characteristics, earth stud, cable support clamp suitable for upto 4x25 sqmm cable. Logo/Name of manufacturer shall be either embossed or Riveted plate on the pole.Galvanization as per relevant lS code etc es required
Supplying, installation, Testing & Commissioning of Street light LED fixture powder coated pressure die cast aluminum body with driver as per the requirement with Driver efficiency >85%, Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , P. F.≥0.95, IP- 66,IK-10, CRI >80, under voltage and over voltage protection, EMIEMC As per CISPR -15, lenses for beam angle as per IESNA type I/II/III as per the width of the road and the project requirement., suitable to fit in up to 65mm dia pipe, life time (LED, Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report, CCT 3000°K / 4000°K / 5700°K /6000°K/6500°K (As per ANSI (min),SDCM(Standard Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with Minimum 5 year OEM warranty System lumen efficacy ≥120 <135lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junctiontemperature shall not rise above 90°C). 72 watt
Supply of XLPE insulated and PVC Sheathed Al conductor armoured cable 1.1KV grade confirming to IS-7098. a) 2Cx10 sqmm.
Supply and fixing of 32mm dia X 1 meter long G.I. Pipe (Medium Class) bracket for mounting of uorescent/HPMV/HPSV Street Light fitting on pole including bending the pipe to the required shape , 2 nos 25mm X 6mm flat iron clamps with nuts, bolts and washer , painting the flat iron with primer and finish paint etc. as reqd
Fabrication, supplying and fixing class B galvanised single overhang arm bracket made out of 250mm long galvanised top tube with cap and 250mm long 32 mm dia galvanised pipe with tightening bolts complete as required.
Fabrication, supplying and fixing class B galvanised double overhang arm bracket made out of 250 mm long galvanized top tube with cap and 250 mm long 32 mm dia galvanized pipe with tightening bolts complete as required.
Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm (L) ×450 mm wide and 1000 mm deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia- 960 mm long(approx)-8 nos. and reinforcement of cold twisted bars of 8 mm dia- 1400 mm (approx) -6 nos.(with 150 mm spacing) as required with supplying and positioning of 4 nos. foundation bolts 16 mm dia,600 mm long, J type i/c 2 nos. template anchor plates of size 225mm×225mm×3mm and providing DCW HDPE for cable entry and exit as required for 3 m and 5 mtr pole.
stage.html
html • 0.04 MB
techsummary_301149.pdf
BOQ Comparative Chart
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.23 MB
genral_condition.pdf
Tender Documents • 0.11 MB
GCC2024.pdf
Tender Documents • 9.36 MB
Circular.pdf
Tender Documents • 1.41 MB
BOQ_301149.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .