GE Khumbathang
GE Khumbathang
SPECIAL REPAIRS TO BLDG NO T-8 AND POWER HOUSE AT LAMAYURU AND BIAMAH UNDER AGE B/R-II, GE KHUMBATHANG
2023_MES_574213_1
GE-KHU-23-2022-23
Open Tender
Miscellaneous Works
Item Rate
180 days
Khaltsi
As per tender and NIT doc
8 documents required · 8 mandatory
₹300
GE Khumbathang
₹7,840
30 Mar 2023
10 Jan 2023
13 Feb 2023
10 Jan 2023
12 Feb 2023
24 Jan 2023
Amount
Excavation in trenches, getting out in soft/loose soil not exceeding 1.5m deep and not exc 1.5m wide for taking out the existing cable of poles etc any size at places complete all as specified and directed.
Description all as per Ser item No. 1 here-in before but exceeding 1.5 mtr upto 3.0 mtr in depth.
Removing of surplus soil to a distance not exceeding 50 mtr complete all as specified and deposited where directed at a level not exceeding 1.5m above the starting point all as specified.
Returning filing in including spreading levelling, watering & well ramming in layers not exceeding 25 Cm thick all as specified.
Material & Labour for sand cushioning 15 cm below and 8 cm above the U/G cable laid (total depth of send shall be 23 cm) complete all as specified & directed by Engr-in-Charge.
M & L for providing PCC cable cover class LV type-I of size 250x150x40mm laid in perpendicular to the cable abutting each other all as specified and directed at site.
M&L for cement concrete type D2 1:4:8 (40mm graded aggregate) in pole/stay/ plinth etc in foundation filling completed all as directed by Engr-in-Charge.
M&L for cement concrete type C2 1:3:6 (40mm graded aggregate) in copping of poles all as directed by Engr-in-Charge.
M&L for steel tubular swaged pole complete with cast iron base plate finial taper plug, bolts, nuts and screws as specified type 410 SP-31 (9.0 mtr long) including painting with two coats of aluminium paint over one coat of red oxide primer, with black and white strips 30 cm each starting with black strip upto 1.5 mtr complete all as specified and as directed.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint.
M&L pin type insulator, porcelain, vitreous, white, brown or green insulator including one galvanized mild steel spindle, two GI washers and one GI nut, 100mm height, 65mm dia for 1100 volts grade complete.
M&L for shackle type, porcelain, vitreous, white, brown or green insulator including galvanized mild steel straps, washers, insulator bolts, washers and nuts of size 75mm height and 90mm dia size of strap 31x3mm and dia of bolts 12mm for working pressure 1100 volts grade complete all as specified and as directed.
M&L for loop type insulator, vitreous porcelain white, brown or green large size with overall dimensions 90mmx140mm clearance of hole 25.5mm complete.
M&L for stay assemby complete with accessories such as stay plate 230mmx230mmx6mm, stay rod 180cm long 16mm dia with nuts including GI bow, turn buckle etc. all as per electrical plate No. 01 of SSR Part-I 2009 (loop type insulator, stay strands, excavation, PCC will be measured & paid separately) complete all as specified and as directed.
S&F galvanized steel stranded wire size 7/3.15mm for stay assembly complete.
M&L for galvanized steel wire 3.15/4.0mm dia continuous earth wire/guard cradle horizontal/rectangular fabricated with 4mm dia galvanized mild steel binding wire complete all as specified and as directed.
M&L for aluminium conductor steel reinforced (ACSR) of any size for OH line including stretching, binding with aluminium binding wire, jumpers, line taps etc complete all as specified.
Supply and laying XLPE insulated screened PVC bedded galvanised steel strip armoured electric power dable heavy duty 1100 Volt grade with stranded aluminium conductor of size 35 Sqmm 3.5 core complete all as directed.
Supply and laying XLPE insulated screened PVC bedded galvanised steel strip armoured electric power dable heavy duty 1100 Volt grade with stranded aluminium conductor of size size 25 sq mm 4 core complete all as directed.
Material and labour for Earthing complete with galvanised steel earth plate electrode 60×60cm.× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel connected to earthing test point including testing on completion all as directed by Engr-In-Charge, complete all as shown in electric plate No 3 of MES SSR Part I of 2010.
SONAM ANGCHOK
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .