Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 LAccepted-AOC 108 AND 111 COMMERCIAL ROAD 133001 | AMBALA | HARYANA | 133001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹8.7 L+₹3,500 (0.40%)Rejected-Finance AAR KEY INDUSTRIES V K GOEL PLOT NO 109 POCKET C SECTOR 2 DSIIDC BAWANA INDUSTRIAL AREA BAWANA DELHI 110039 CONTACT NO 9868206531 NORTH WEST DELHI NATIONAL CAPITAL TERRITORY OF DELHI 110039 INDIA | NORTH DELHI | DELHI | 110039 | L2 | Rejected-Finance L2 | |
| 3 | L3₹8.8 L+₹10,000 (1.16%)Rejected-Finance | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | Instruments and Equipment Co L1 | AAR KEY INDUSTRIES L2 | H S Enterprises L3 |
|---|---|---|---|---|---|---|
| 1.01 | SITC of High frequency IGBT based Emergency Rescue Device having following specifications (Make: Toshiba / ABB / Aar Key / Hi-Shine / IECO) capacity : 30KVA
AC input: 340-460 Volts AC Three phase (3PH-N-PE)
DC input: 360 Volts DC
AC output: 400 volts AC Three Phase pure Sine wave
Stability: plus -1%
Cooling: Forced Air cooled
Frequency: 50Hz plus - 0.5Hz
Total harmonic Distortion: less than 2% on linear load
Power factor: 0.8
Static by pass: 100% rated in built bypass system
Manual byepass: Provided
Input . Output termination: Provided
Switching Frequency: 10 Khz
KW rating: Shall be 0.7 times the KVA rating
IP rating: IP 20
Overload: The system shall with stand 20% overhead for 10 minute and 50% overload for 1 minute
Protection: Over voltage, short circuit and overload at output terminal, low battery and high battery, cut off
Indicators: Mains, battery charging / Discharging, output overload, low battery voltage
DIgital meter shall be provided for: Input AC voltage, output AC voltage, Current and frequency, battery voltage and current
Isolation Transformer: Built in isolation tranformer at inverter output shall be provided
Lead Acid SMF VRLA Battery bank consisting of 12V 42Ah 30 nos. battery (Make: Quanta / Exide)
Matching cabinet / open rack to house 30 nos. 12V 42Ah SMF batteries complete with battery interlinks 30KVA ERD system
MCCB 125Amps. Four pole with enclosure (2 nos.) (Make: LandT / Schneider)
16Sqmm 4 Core Copper wire (20 mtrs.) (Make: Grandlay / Havells / Polycab) | 1 | Each | 8,65,000 ₹8,65,000 Lowest | 8,68,500 ₹8,68,500 | 8,75,000 ₹8,75,000 |
Tender Value
₹8.1 L
EMD Value
₹16,200
Closing Date
24 Dec 2025, 5:00 pmClosed
RAVI Ladwal
ED - Rewari
Construction of Academic Teaching block at Regional Centre Krishan Nagar (Lula Ahir) in Rewari District (Pdg. ERD for 01 No. lift only).
2025_HRY_491356_1
202575A9E2D7 3AFB 4562 BF84 7C3A451347C4668BAR
Open Tender
Civil Works
Works
90 days
LULA AHIR
2 documents required · 2 mandatory
₹1,000
₹16,200
Yes
8 Jun 2026
18 Dec 2025
25 Dec 2025
18 Dec 2025
24 Dec 2025
18 Dec 2025
SITC of High frequency IGBT based Emergency Rescue Device having following specifications (Make: Toshiba / ABB / Aar Key / Hi-Shine / IECO) capacity : 30KVA AC input: 340-460 Volts AC Three phase (3PH-N-PE) DC input: 360 Volts DC AC output: 400 volts AC Three Phase pure Sine wave Stability: plus -1% Cooling: Forced Air cooled Frequency: 50Hz plus - 0.5Hz Total harmonic Distortion: less than 2% on linear load Power factor: 0.8 Static by pass: 100% rated in built bypass system Manual byepass: Provided Input . Output termination: Provided Switching Frequency: 10 Khz KW rating: Shall be 0.7 times the KVA rating IP rating: IP 20 Overload: The system shall with stand 20% overhead for 10 minute and 50% overload for 1 minute Protection: Over voltage, short circuit and overload at output terminal, low battery and high battery, cut off Indicators: Mains, battery charging / Discharging, output overload, low battery voltage DIgital meter shall be provided for: Input AC voltage, output AC voltage, Current and frequency, battery voltage and current Isolation Transformer: Built in isolation tranformer at inverter output shall be provided Lead Acid SMF VRLA Battery bank consisting of 12V 42Ah 30 nos. battery (Make: Quanta / Exide) Matching cabinet / open rack to house 30 nos. 12V 42Ah SMF batteries complete with battery interlinks 30KVA ERD system MCCB 125Amps. Four pole with enclosure (2 nos.) (Make: LandT / Schneider) 16Sqmm 4 Core Copper wire (20 mtrs.) (Make: Grandlay / Havells / Polycab)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.00 MB
BOQ_569676.xls
BOQ • 0.23 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .