Military Engineer Services, Commander Works Engineer, Udhampur, PO - Garhi, Udhampur-182121
ROVN OF 33KV RING MAIN SYSTEM AT MULTI-STORY MODERN HOSPITAL COMPLEX UNDER GE (UTILITIES) UDHAMPUR
2024_MES_671367_1
CWE/U(U)-44/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Udhampur
As per NIT
6 documents required · 6 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹70,700
Yes
10 Oct 2024
4 Sept 2024
8 Oct 2024
4 Sept 2024
1 Oct 2024
19 Sept 2024
4 Sept 2024 - 14 Sept 2024
Amount
Excavating in trenches, n exc 1.5 m wide and n.exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, and for laying of cable or pipes etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out in any type of soil, complete all as specified and as directed.
Returning, filling in (soil) including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in any type of soil,complete all as specified and as directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and as directed.
Dry coarse sand as cushioning to under ground cable provided with layer of 8 cms deep before laying the cable and 15 cms deep after laying and stretching the cable, punned to 18 cm thick complete all as specified and as directed. NOTE Only punned thickness shall be measured for payment purpose.
Precast in reinforced Concrete cable covers Class HV, type B-1 flat of size 300mm x 180mm x 40 mm for HT cable, complete all as specified and as directed.
Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 33000 volts grade, of size 3 core 300 sq mm, complete all as specified and directed.
Supply,installation,testing & commissioning of 33 KV Outdoor type Non-Extensible floor mounted Gas Insulated Switchgear with internal copper bus bars, consisting of with 3 nos motorised Vacuum Circuit Breaker as 2 INCOMER & 1 OUTGOING. All live parts, bus bars,VCBs connections, ON-OFF offload switch, Earth switch of of feeder should be enclosed in one tank sealed for life robotically welded non magnetic and non ferrite grade stainless steel tank Grade 304 of minimum 2 mm thick having IP67 degree of protection filled with SF6 gas as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200.The unit shall have front cable entry for ease of installation and shall have site replaceable bushings for ease of troubleshooting during breakdown.The Gas Insulated switchgear should be complete with all accessories such as Terminal kits suitable for 1Cx300sqmm Cable, VPIS, cable supports, all front cable terminations, mechanical indications for VCB, OFF load switch & Earth switch , Manometer as per with IEC standards 62271-1, 100, 200. Altitude of installation up to 1000m as per IEC 60120.Cable termination Kit must be screen seperable touchproof type.The unit shall include the following with all necessary standard fitting required at site.License partnar / Authorized Integrators are not accepted. Complete commissioning must be supervised by OEM only.
Cont..... item No 7.00:- VACUM CIRCUIT BREAKER feeder 630A VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-1 Nos. Motor operated 630 A Vacuum circuit breaker having spring stored mechanism. ON-OFF off load switch and earthing switch downstream vacuum circuit-breaker. Menometer per tank per feeder. “Live Cable” LED Indicators through Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 25KA/ 3 sec Making Capacity - 62.5KA VCB must confirm operating sequence O-0.3sec-CO-3Min-CO and 10000 mechanical operation. Power frequency withstand voltage - 70KV & Impulse withstand voltage - 170KV Minimum operating gas pressure - 1.2 Bar abs. Front cover mechanism - IP2X and VPIS to be given. Green(ON)/Red(OFF) push buttons to operate VCB. Indication Lamp for ON, OFF, TCS, TRIP, SPRING CHARGE etc. Auxiliary powered numerical protection relay having Over Current, erath fault protection. Auxiliary relays are required for Transformer feeder for OTI, WTI, BUCHLOZ Alarm & Trip.
Cont..... item No 7.00:- Sutable Ammeter with ASS and Multifunction meter 6/8 window Annunciator with Hooter scheme. RMU Gas Tank and cable chamber should be tested for an internal arc fault of 25kA for 1 sec with AFLR classification Resin cast ring core CT on cables 50/1-1A, Class: 0.5 & 5P10 , 2.5 VA - 3 Nos Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. RMU, VCB, Vaccum Interrupter must be of same make. Interlock to be provided between 2 nos Incomer so that only one Incomer can be made ON at a time. Mechanical Interlock to be provided for followings: - Earthswitch can be operated in CB OFF codition. - Earthswitch Can not be operated when Cable is Chared.
Cont..... item No 7.00:- One Bus Connected equipment / metering cubical consisting of following 3 nos. Single Phase PTs - 33kV/V3/110/V3 ,Cl-0.5 & 3 P ,50VA 1 Nos Single Phase Auxiliary PT- 33kV/V3/230V, 500 VA Space Heater with thermostat Sutable Analog Voltmeter with VSS. Bus Under Voltage & Over Voltage Relay- 1Nos. 2X12V, 26AH Battary with 7 Amps Charger - 1set
PCC 1:3:6 type C-1 (using 20 mm graded stone aggregate for sub base) for foundation of RMU and PCC 1:4:8 type B-0 (using 12.5 mm grade stone aggregrate in foundation for mass concrate) of Size 2mtr X 2mtr X 0.70 Mtr including necessary form work and finishing the surface of PCC above ground level with cement mortar 1:4, 5mm thick complete all as specified and directed. Note: Size & Shape of Plinth will be change as per OEM recommendation.
HT gang operated air break switch 33 KV, 3 pole horizontaly mounted type, mechanically operated, mounted on insulators and steel frame with operating mechanism, worked from ground level for current rating 200 Amps switch having 100 MVA rating at 33 KV and 9 insulators suitable for 33 KV, 50 C/s including mounting on steel structure and necessary electrical connections and including Gl pipe handle, clamps bolls, nuts, jumper wire connecting with stranded conductors with locking arrangement, complete all as specified and as directed.
Plain cement concrete (1:4:8) type D2 using 40mm graded stone aggregate as in foudation, filling, sub base and mass concrete all as specified and as directed.
PCC 1:2:4 (nominal mix) type B-1, using 40 mm graded crushed stone aggregate as in coping and the like including weathering, slightly rounded or chemfered angles and throating including necessary from work, complete all as specified and as directed.
Earthing with GI earth plate electrode 600 X 600 X 6.3mm buried directly in ground (earth pit not less than 2.25M deep below ground level ) with top edge of the earth plate not less than 1.5M below ground level connected to GI strip 32 x 4 mm thick for earthing lead fixed by means of nuts,bolt,washers etc connected to earth test point complete all as specified in electrical plate NO 3 of SSR1996 part 1 ,including necessary excavation and earth work in any strata of soil,comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel &wire mesh , PCC pit with CI cover and frame etc all as specified and directed by Engineer-in-charge. Note:- All the joints shall be made with welding to get proper conductivity. Note: On testing after completion of earthing, if desired earth resistance is not obtained, the earthing will be re-done by the contractor at his own risk & cost to the entire satisfaction of Engineer-in-charge
Mild Steel work as in heavy sizes such as trusses built up gates, door frames, record racks, roof work gates etc wrought to required form including holes rivetting or welding where necessary and also fixing in proper position and alignment including supply of steel bolts nuts, wastage etc. and their fixing required for proper completion of the work, complete all as specified and as directed.
Supply and fixing cable jointing kit for 33 KV (Earthed) grade cable for End joint Heat shrinkable type joint complete with jointing material and acessories suitable for 3 core XLPE armoured aluminium conductor cable 240-400 sq.mm, complete all as specified and as directed.
slathia construction works (BID ID -3110924)
M/S BHARAT LIGHT ELECRIC.CO (BID ID -3101397)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .