Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAccepted-AOC | ₹1.1 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹1.2 Cr+₹11.2 L (10.4%)Rejected-AOC | ₹1.2 Cr+₹11.2 L (10.4%) | L2 | Rejected-AOC L2 |
| 3 | L3₹1.2 Cr+₹12.6 L (11.8%)Rejected-AOC FRIENDS COLONY STREET A DHANGU ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹1.2 Cr+₹12.6 L (11.8%) | L3 | Rejected-AOC L3 |
| 4 | L4₹1.2 Cr+₹12.7 L (11.9%)Rejected-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | ₹1.2 Cr+₹12.7 L (11.9%) | L4 | Rejected-AOC L4 |
| 5 | L5₹1.2 Cr+₹16.6 L (15.5%)Rejected-AOC 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | ₹1.2 Cr+₹16.6 L (15.5%) | L5 | Rejected-AOC L5 |
Tender Value
Refer Docs
EMD Value
₹2.2 L
Closing Date
20 Mar 2021, 6:00 pmClosed
SH A P SINGH, IDSE, SE
HQ CWE CHANDIMANDIR
CWE/CHM(U)-96/2020-21 PROVN OF LT UNDERGROUND UG CABLES INCL CONVERSION OF OVERHEAD CONDUCTORS WITH UG CABLES IN SECTOR D AT CHANDIMANDIR MIL CANTT
2021_MES_424021_1
CWE/CHM(U)-96/2020-21
Open Tender
Miscellaneous Works
Item Rate
180 days
HQ CWE CHANDIMANDIR
Class B cat a(i)
8 documents required · 8 mandatory
₹1,000
Yes
GE (U) CHANDIMANDIR
₹2.2 L
Yes
8 Apr 2021
20 Feb 2021
22 Mar 2021
20 Feb 2021
20 Mar 2021
13 Mar 2021
Amount
Dismantling old over head ACSR conductors and earth wire any size from over head lines on poles and removing from site complete all as specified and as directed.
Dismantling old structural steel or MS work like old cross arms, channel/ angles sections or bracings nuts bolts washers etc from elelctric poles, any position and removing from site complete all as specified and directed.
Dismantling old insulators any type and any size from OH electric poles and removing from site complete all as specified and as directed.
Excavating in trenches, for foundation of poles, stays or for laying of cables, not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in hard/dense soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm in hard/dense soil complete all as specified and directed.
Removing excavated material (soil) n.exc.50m and depositing where directed at a level n.exc. 1.5m above the starting point complete all as specified and directed.
Supply and laying un-reinforced precast cement concrete cable covers class LV, type-2 flat, size 300mm x 180mm x 40mm in trenches for cable protection laid for UG cable complete all as specified and as directed.
M & L for sand cushioning for protection of cable (below, above and around the cable laid in trenches) complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3½ core complete all as specified and as directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core complete all as specified and as directed.
Supply, installation, testing and commissioning of new out door type LT feeder pillar box of size not less than 2.0mx1.6mx0.75m, factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated 2.00mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories:-
INCOMING (a) ACB 4 pole, 415 Volts, 800 Amps, 50 KA Electrically Drawout type 4 pole 415 V, Micro processor based trip units equipped with complete sets of LSIG protection, the release should be self-powered type with LCD type display and provide last 20 trip history with date and time stamping and last 60 events, the breaker release should have individual fault trip LED indications shall be available on the trip unit and should have breaking capacity Icu=Ics=Icw (1 sec) not less than 50 KA.-01 No OUTGOING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 320 Amps, 36 KA - 03 Nos with adjustable thermal and magantic release with Ics=100 Icu. (c) MCCB 4 pole, 415 Volts, 250 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu. (d) Panel mounted multifunctional digital meter 3 lines LCD display in 96x96 mm flush mounted case accuracy class-I. complete with all accessories including 3 Nos 200/5A CT =1 No. (e) Phase indicator lamp RBY complete with copper control wiring = 01 set of three, (f) The panel should have Arc guard system.
Supply, installation, testing and commissioning of new out door type LT feeder pillar box of size not less than 2.0mx1.6mx0.75m, factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated 2.00mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories:-
INCOMING (a) ACB 4 pole, 415 Volts, 800 Amps, 50 KA Electrically Draw Out type 4 pole 415 V, Micro processor based trip units equipped with complete sets of LSIG protection the release should be self-powered type with LCD type display and provide last 20 trip history with date and time stamping and last 60 events the breaker release should have individual fault trip LED indications shall be available on the trip unit should have breaking capacity Icu=Ics=Icw (1 sec) not less than 50 KA. - 01 No OUTGOING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 320 Amps, 36 KA - 03 Nos with adjustable thermal and magantic release with Ics=100 Icu. (c) Panel mounted multifunctional digital meter 3 lines LCD display in 96x96 mm flush mounted case accuracy class-I. complete with all accessories including 3 Nos 200/5A CT =1 No. (d) Phase indicator lamp RBY complete with copper control wiring = 01 set of three, (e) The panel should have Arc guard system.
Supply, installation, testing and commissioning of new out door type LT feeder pillar box of size not less than 2.0mx1.6mx0.75m, factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories:-
INCOMING (a) ACB 4 pole, 415 Volts, 630 Amps, 50 KA EDO type 4 pole 415 V, Micro processor based trip units equipped with complete sets of LSIG protection, the release should be self-powered type with LCD type display and provide last 20 trip history with date and time stamping and last 60 events, the breaker release should have individual fault trip LED indications shall be available on the trip unit and should have breaking capacity Icu=Ics=Icw (1 sec) not less than 50 KA. - 01 No OUTGOING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 320 Amps, 36 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu. (c) MCCB 4 pole, 415 Volts, 250 Amps, 36 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu. (c) Multifunctional meter flush mounting type 96 x 96 mm - 01 Nos (d) Phase indicator lamp RBY complete with copper control wiring = 01 set of three, (e) The panel should have Arc guard system.
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 960 degree C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of board/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1. The report shall mention the following tests performed and passed out satisfactory:-
(a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits. (f) Clearance & creepage distance. (g) Mechanical operation. Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2. It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories . All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F (G) protection. INCOMING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 No with Micro processor based release with Ics=100 Icu. OUTGOING (a) MCCB 3 pole, 415 Volts, 125 Amps, 25 KA - 03 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 3 pole, 415 Volts, 100 Amps, 25 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu.
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 960 degree C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of board/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1. The report shall mention the following tests performed and passed out satisfactory:- (a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits. (f) Clearance & creepage distance.
(g) Mechanical operation. Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2. It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/C (S&I) and E/F (G) protection. INCOMING (a) MCCB 4 pole, 415 Volts, 320 Amps, 36 KA-01 No with Micro processor release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 125 Amps, 36 KA - 03 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 100 Amps, 36 KA-01 No with adjustable thermal and magantic release with Ics=100 Icu.
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 960 degree C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of board/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1. The report shall mention the following tests performed and passed out satisfactory:- (a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits.
(f) Clearance & creepage distance. (g) Mechanical operation. Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2. It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F (G) protection. INCOMING (a) MCCB 4 pole, 415 Volts, 320 Amps, 36 KA - 01 No with Micro processor release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 125 Amps, 36 KA - 03 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 160 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu.
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 960 degree C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of board/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1. The report shall mention the following tests performed and passed out satisfactory:- (a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits. (f) Clearance & creepage distance. (g) Mechanical operation. Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2. It shall be tested at Glow wire test for 960 deg. Cent.
The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F (G) protection. INCOMING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 No with Micro processor release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 125 Amps, 25 KA - 03 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 160 Amps, 25 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu.
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 960 degree C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of board/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1. The report shall mention the following tests performed and passed out satisfactory:- (a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits. (f) Clearance & creepage distance. (g) Mechanical operation.
Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2. It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F (G) protection. INCOMING (a) MCCB 4 pole, 415 Volts, 250 Amps, 36 KA - 01 No Micro processor release based with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 100 Amps, 25 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 160 Amps, 25 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu.
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 960 degree C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of board/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1. The report shall mention the following tests performed and passed out satisfactory:- (a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits. (f) Clearance & creepage distance. (g) Mechanical operation. Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2.
It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F (G) protection. INCOMING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 No with Micro processor based release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 160 Amps, 25 KA - 04 Nos with adjustable thermal and magantic release with Ics=100 Icu.
Supply, installation, testing and commissioning of out door type LT feeder pillar/ distribution boards thermoplastic polycarbonate IP 65 in accodance with EN 60 529, dust proof, rust proof, water proof & weatheproof, metering panel shock proof, rust proof, corrosion free, acid & chemical resistant, fire retardant & self extinguishing, UV resistant, Silica and halogen free recyclable material, glow wire tested at 960 degree C in accordance with IEC 60 695-2-11. Type tested as per IEC 60 439-1. Total insulated with system. The manufacture of board/panel shall submit a copy of CPRI test report of degree of ingress protection IP 65 in accordance with IEC 60529. The gasket material shall be Polyurethane ; while the gasket shall be internally embedded. The manufacture of board/ panel shall submit a copy of type test report of a board made out of polycarbonate thermoplastic panel in accordance with IEC60439-1. The report shall mention the following tests performed and passed out satisfactory:- (a) Degree of protection. (b) Temperature rise. (c) Dielectric Properties. (d) Short circuit withstand current. (e) Effectiveness of protective circuits. (f) Clearance & creepage distance. (g) Mechanical operation. Polycarbonate enclosure shall be fire retardant & self extinguishing in accordance with IEC 60 695-2-11, DIN VDE 0304 part 3,UL subject 94 for Flammability V-2.
It shall be tested at Glow wire test for 960 deg. Cent. The impact strength of polycarbonate enclosures/ boards i.e. the degree of protection against mechanical load shall be in accordance with EN 50298-98 for IK 08. The lid closing and opening shall be done by quick fastering spring mechanism latches. Suitable accessories for armoured cable shall be supplied with the panel. These accessories shall not be fitted with screws, so that there is no loss of IP, but should be auto fit. The board manufacturer shall submit the copy of type test reports for polycarbonate thermoplastic board only. Each board shall have individual routine test report of the manufacture & the panel board will have the following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F protection. INCOMING (a) MCCB 4 pole, 415 Volts, 160 Amps, 36 KA - 01 No with Micro processor based release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 100 Amps, 25 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 63 Amps, 25 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu.
Supply, installation, testing and commissioning of new out door type LT feeder pillar box factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated not less than 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F protection.
INCOMING (a) MCCB 4 pole, 415 Volts, 250 Amps, 36 KA - 01 No with Micro processor based release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 125 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu. (b ) MCCB 4 pole, 415 Volts, 200 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu. (c) Multifunctional meter flush mounting type 96 x 96 mm - 01 Nos (d) Phase indicator lamp RBY complete with copper control wiring = 01 set of three,
Supply, installation, testing and commissioning of new out door type LT feeder pillar box factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated not less than 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F (G) protection.
INCOMING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 No with Micro processor based release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 200 Amps, 36 KA - 03 Nos with adjustable thermal and magantic release with Ics=100 Icu. (b) Multifunctional meter flush mounting type 96 x 96 mm - 01 No (c) Phase indicator lamp RBY complete with copper control wiring = 01 set of three,
Supply, installation, testing and commissioning of new out door type LT feeder pillar box factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated not less than 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories. All the incoming MCCB should be Micro Processor based with LSIG protection with fault LED indication for O/L(L), S/c (S&I) and E/F (G) protection.
INCOMING (a) MCCB 4 pole, 415 Volts, 400 Amps, 36 KA - 01 No with Micro processor based release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 320 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu. (b) MCCB 4 pole, 415 Volts, 100 Amps, 36 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu. (c) Multifunctional meter flush mounting type 96 x 96 mm - 01 No (d) Phase indicator lamp RBY complete with copper control wiring = 01 set of three,
Supply, installation, testing and commissioning of new out door type LT feeder pillar box factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated not less than 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising of following accessories:-
INCOMING (a) MCCB 4 pole, 415 Volts, 100 Amps, 36 KA - 01 No with adjustable thermal and magantic release with Ics=100 Icu. OUTGOING (a) MCCB 4 pole, 415 Volts, 100 Amps, 36 KA - 02 Nos with adjustable thermal and magantic release with Ics=100 Icu. ( b) Multifunctional meter flush mounting type 96 x 96 mm - 01 No (c) Phase indicator lamp RBY complete with copper control wiring = 01 set of three,
Supply, installation, testing and commissioning of new out door type LT feeder pillar box factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated not less than 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising with including incoming MCCB 4 pole, 415 Volts, 200 Amps, 36 KA - 01 Nos alongwith 1.5 times ams rated 4 Nos aluminum bus bar of incoming MCCB suitable for 6 nos outgoing 25 sqmm 4 core XLPE aluminum armoured cable complete all as specified and directed.
Supply, installation, testing and commissioning of new out door type LT feeder pillar box factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated not less than 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising with including incoming MCCB 4 pole, 415 Volts, 125 Amps, 36 KA - 01 Nos alongwith 1.5 times ams rated 4 Nos aluminum bus bar of incoming MCCB suitable for 6 nos outgoing 25 sqmm 4 core XLPE aluminum armoured cable complete all as specified and directed.
Supply, installation, testing and commissioning of new out door type LT feeder pillar box factory made CPRI approved ; openable from front & rear, double door with flush type hinges and flush cylindrical locks, dust and vermin proof, fabricated not less than 3.00 mm thick CRCA sheet, duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete with 4 Nos heat shrinkable insulated aluminum bus bars of capacity not less than 1.5 times of incoming MCCB/ACB including all MCCB connections with suitable rating aluminum busbar strip. The panel shall be suitable for 415 Volts, 50 HZ, 3 Phase 4 wire system and shall be complete with danger notice plate with skull & bone sign, making all electrical incoming and out going electrical cable connection with new lugs, glands to be provided at cable entries, including 04 No. legs of not less than 50cm long each below the base of panel made of angle iron support 50x50x6mm for grouting purpose and grouted in PCC (1:2:4) type B1 (using 20 mm graded stone aggregate) complete all as specified and as directed and comprising with including incoming MCCB 4 pole, 415 Volts, 100 Amps, 36 KA - 01 Nos alongwith 1.5 times ams rated 4 Nos aluminum bus bar of incoming MCCB suitable for 6 nos outgoing 25 sqmm 4 core XLPE aluminum armoured cable complete all as specified and directed.
Supply and fix Galvanised steel tubing, light grade, with fittings and MS clamps, nuts, bolts etc of 40 mm dia bore for cable protection on pole/wall, road crossing/driange/footpath alongwith PCC work making the disturbed surface as per existing surface complete all as specified and directed.
Supply and fix Galvanised steel tubing, light grade, with fittings and MS clamps, nuts, bolts etc of 80 mm dia bore for cable protection on pole/wall, road crossing/driange/footpath alongwith PCC work making the disturbed surface as per existing surface complete all as specified and directed.
M&L for cutting of Road not less than 30 cm in depth and 30 cm in width underneath the road for passing the cable/pipe and making good with PCC 1:2:4 type B-1 where road cutting done to make the road surface fair and level complete all as specified and directed by Engr-in Charge.
M& L for providing earthing complete with galvanised steel earth electrode plate of size 600x 600 x6 mm thick burried directly in ground in a earth pit not lessthan 2.25 mtr deep below ground level with the top edge of the earth plate at a depth not less than 1.5 mtr below ground level , connected to and including galvanised iron strip of size 32 x6 mm earth strip by means of bolts & nuts ,check nuts and washers and connected to earth test point connected to earth point / transformer /panel / feeder pillor box all as specified and directed by Engr-in-charge including necessary earth work in any type of soil ,disposal of surplus soil not exceeding 50 m ( the rate also includes for cost of charcoal & salt in alternate layers of 15 cm thickness , providing suitable size of GI pipe (medium grade) for watering ,funnel, wirmesh, PCC sconnected PCC chamber(1:3:6) type C1 , RCC pit cover , charcoal ,salt including provision of earth lead protected by 40 mm dia medium grade GI pipe and 20 mm medium grade GI pipe for watering complete all as specified and directed by Engr-in-charge.
Supply and laying 40mm outer dia, double walled, corrugated HDPE duct pipe conforming to IS- 14930 Pt-II with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
unique power & control system
M/S SINGH AND ASSOCIATES
R D Bansal
Raman Electric Trading Co
kailu construction co
Bal Singh and Sons
KATWAL TECHNOCRATS
M/S BALWINDER SINGH
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .