Ex. ENGINEER (ELECT)-I
OFFICE OF THE Ex. ENGINEER (ELECT)-I, SHAHDARA (N) ZONE, KeshavChowk, Delhi-110053
Repair of Fancy Lights in Various Mpl. Parks at Vivek Vihar, Jhilmil Colony and Jwala Nagar in Ward No. 216 Under Shahdara (North) Zone
2024_MCD_182739_1
EE(E)-I/Sh.N/MCD/23-24/TC-69/1
Open Tender
Electrical Works
Item Rate
90 days
As per NIT
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
₹9,497
24 Mar 2025
23 Jan 2024
29 Jan 2024
23 Jan 2024
29 Jan 2024
23 Jan 2024
Amount
DSR & A.R. ITEMS
122.1.2:Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm
122.1.43:Supply of 17/18 Watt LED retrofit lamp suitable for B22 holder
122.2.2: P/F Hot press sheet moulded compound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof pole box of inner dimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nos of 6 to 32 amp single pole MCB & 63 Amp. Double pole isolator (MCB/Isolator excluded) with neutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc as reqd. as reqd.
122.2.21:SITC of 25 watt LED IP65 post top fitting made of die cast aluminium spigot spun aluminium powder coated top cover and clear acrylic diffuser with high voltage protection low power LED's connected in series and parallel combination with better heat sink arrangement input voltage 160-260 volts AC, 50 Hz AC Supply power factor >0.95, luminious efficacy >100 lumens/watt, CCT 5700°K ±300°K, Surge protection not less than 10KV complete etc as requred.
122.2.25:Providing and fixing of Stainless steel name plate of size 6×8 sq inch made of 20 gauge sheet including engraved name of area representative duly painted along with SS clamp nut bolt etc as required
OD23340/2023-2024:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amp
OD23341/2023-2024:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 KA "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with Supplying and fixing brass batten/ angle holder including connection etc. as required. (Single Pole)
OD23342/2023-2024:Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
OD23343/2023-2024:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm
OD23344/2023-2024:Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
OD23345/2023-2024:Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
OD23346/2023-2024:Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
OD23347/2023-2024:Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required
OD23348/2023-2024:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required. 3 x 1.5 sq. mm
OD23349/2023-2024:1.58 Supplying and fixing PVC batten/angle holder including connections etc. as required.
Bidder Name
M/S. A.K. Electricals
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .