Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.9 LAccepted-AOC 901 GH 83 SECTOR 20 PANCHKULA 134116 | PANCHKULA | HARYANA | 134116 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹16.9 L+₹41,235.70 (2.51%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹18.0 L+₹1.6 L (9.50%)Rejected-AOC 5B FF NAND VIHAR AZAD NAGAR NEAR GODARA PETROL PUMP HISAR HARYANA 125001 | HISAR | HARYANA | 125001 | L3 | Rejected-AOC NOT LOWEST | |
| 4 | L4₹18.2 L+₹1.7 L (10.4%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L4 | Rejected-Finance NOT LOWEST |
Tender Value
₹21 L
EMD Value
₹42,000
Closing Date
28 May 2020, 6:00 pmClosed
CWE PATIALA
HQ CWE BLDG NO 26, NEW LAL BAGH PATIALA-147001
SPECIAL REPAIR TO LT DISTRIBUTION NETWORK AT MIL STN DAPPAR UNDER GE PROJECT DAPPAR
2020_MES_340826_1
8320/PAT/T-13/E8
Open Tender
Civil Works
Lump-sum
180 days
Dappar
As per cover 1
6 documents required · 6 mandatory
₹500
Yes
GE PROJECT DAPPAR
₹42,000
Yes
22 Jun 2020
25 Apr 2020
30 May 2020
25 Apr 2020
28 May 2020
14 May 2020
25 Apr 2020 - 2 May 2020
Amount
Schedule 'A'Section-I (EXINTERNAL ELECTRIFICATION WORKS)
Total amount of Sch 'A' Sec I (ExInternal Electrification Works)
Schedule 'A'Section-II (Misc Items of Works) Note : This schedule is not pre-priced by MES and the pre-priced rate indicated as "Rs 0.00" under Col. 5 siginifies this fact only.
Supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6MM duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
Supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6MM duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The ACB/MCCB's shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- INCOMING - a) MCCB 200 Amps, 415 volts, 4 Pole, 36KA, 50 Hz, (Incoming) with Ics=100% Icu and thermal magnetic adjustable type all as per L&T Make, Cat No. CM92009OON1OG - 01 No. and including spreader terminals - set of 06, direct rotary handle - 01 No. or equivalent in Legrand/Schenider/ABB/Seimens
Supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6MM duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The ACB/MCCB's shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- INCOMING - (a) MCCB 200 Amps, 415 volts, 4 Pole, 36KA, 50 Hz, (Incoming) with Ics=100% Icu and thermal magnetic adjustable type all as per L&T Make, Cat No. CM92009OON1OG - 01 No. and including spreader terminals - set of 06, direct rotary handle - 01 No. or equivalent in Legrand/Schenider/ABB/Seimens
Supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6MM duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The ACB/MCCB's shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- INCOMING - (a) MCCB 250 Amps, 415 volts, 3 Pole, 36KA, 50 Hz, (Incoming) with Ics=100% Icu and thermal magnetic adjustable type all as per L&T Make, Cat No. CM92009OOP1OG - 02 Nos. and including spreader terminals - set of 06, direct rotary handle - 01 No. or equivalent in Legrand/Schenider/ABB/Seimens
Supplying, installing, testing and commissioning of factory fabricated CPRI approved, floor mounted, IP 65 grade, outdoor type LT cubical panel, double door type made out of 3mm thick CRCA MS sheet duly powder coated with Seimens grey shade RAL 7032 all as per IEC 609413-1&2, dust and vermin proof with suitable size TPN PVC sleeved aluminium bus bar, incld. aluminium bus bars for incoming and outgoing MCCBs connections supported on glass fiber reinforced thermosetting plastic insulated support with lifting lugs of suitable size. The panel should be fully compartmentalised for each control gear having back side of panel openable and should be provided with suitable louvers for ventilation Panel should be mounted on base frame made out of angle iron 40x40x6MM duly grouted to PCC floor complete. The bottom of the panel (space between bottom of panel and top of PCC floor) shall be covered with 2 mm thick CRCA sheet covering all the sides of the base frame duly painted with two coats of synthetic enamel paint of approved shade over one coat of red oxide primer. Bus bars provided shall be adequately supported on insulators to withstand dynamic stresses due to short circuit current and shall be suitably colour coded with heat shrinkable sleeve for phase indication. The standard phase arrangement when facing the switchgear shall be R-Y-B from left to right.
The bus bar connections and their insulated supports shall be mechanically strong, and shall withstand all the stresses which shall be imposed upon them in ordinary working due to fixing, vibration, fluctuation in temp., shot-circuit or other causes. The bus bar will be supported on DMC. Provision shall be made for expansion and contraction of the bus bars and connections with variation of temp. Internal wiring should be done with multi-stranded copper conductors and shall be properly bunched, tied, ferruled for proper identification, crimped and shall be connected with suitable lugs and PVC sleeves, etc. The bottom of the panel should contain detachable plate having provision for entry of armoured cable of adequate size with glands. Threaded earthing studs - 02 Nos shall be provided at the bottom and lifting lugs of suitable size at top to lift the panel safely shall be made. The ACB/MCCB's shall have copper TPN/TP extension links of current rating not less than 1.5 times the rated capacity of individual feeders. The panel should have following accessories fitted in :- INCOMING - (a) MCCB 125 Amps, 415 volts, 3 Pole, 36KA, 50 Hz, (Incoming) with Ics=100% Icu and thermal magnetic adjustable type all as per L&T Make, Cat No. CM92108OOM1OG - 01 No. and including spreader terminals - set of 06, direct rotary handle - 01 No. or equivalent in Legrand/Schenider/ABB/Seimens
S & F in replacenment of old unvs box Street light control junction box 280x170x130mm from cable looping box to the connector of the luminarie made out of FRP sheet and arrangement 3 phase 4 wire system with R.Y.B.& N studs and control for incoming & outgoing cables with MCB SP 6 Amps 230 volts with neutral link including flat iron 25x3 mm “D” clamps (2 Nos) suitable for mounting of box to pole of required size & shape including bolts nuts & washers.”NOTE: - The quoted rate is deemed to be inclusive of cost of suitable size incoming & outgoing cable glands & lugs.
AK Construction Co
SUN MANN ENGINEERS
Raman Electric Trading Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .