Chandrapur Cancer Care Foundation
Chandrapur Cancer Care Foundation
F4-CCCF/Air Cooled Split DX System
2024_CHDPR_1003737_1
F4-CCCF/AC/2024
Open Tender
General Repair Works
Item Rate
70 days
Chandrapur
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
25 Jul 2024
13 Feb 2024
1 Mar 2024
13 Feb 2024
29 Feb 2024
13 Feb 2024
Amount
F4. AIR COOLED SPLIT DX SYSTEM
AIR COOLED - SPLIT UNITS (Inverter Type)- UPS/SERVER/HUB ROOM Supply, installation, testing and commissioning of INVERTER ROTARY TYPE / INVERTER SCROLL TYPE Air cooled DX, Split type air conditioning units each comprising of : An Oudoor unit and an Indoor unit can be: High wall type/Ductable, The unit shall be with R32 / R410 refrigerant.The split unit shall be only cooling or (Heat Pump) heating & cooling as mentioned below in the BOQ. The unit shall be with hand held IR remote or corded remote as may be required.The unit shall be with hand held IR remote or corded remote as may be required. Outdoor condensing unit shall comprise of single / multi inverter, rotary / scroll compressor & air cooled condenser with fan & motor. Evaporating unit shall consist of a blower section with dynamically balanced centrifugal blower driven by induction motor, multirows deep copper cooling coil with aluminium fins, thermostatic expansion valve etc. The evaporating unit shall be equipped with synthetic fibre filters, insulated drain pan, safety controls, thermostat all complete in a unit. Ductable units / Fured-in units shall have fire retardant canvass connection at fan outlet. The enclosure shall be factory painted to a smooth finish. The quoted price shall be inclusive of interconnected insulated refrigerant piping, insulated drain piping, vibration isolation pads / vibration isolators and associated electrical cabling & earthing between indoor & outdoor units and MS powder coated base frame work made of angle iron for mounting of outdoor / indoor units. The units shall be suitable for 230V±6%, or 415V±10%, 50 ± 3%,Hz supply & complete with electrical controls & panels, if required. Hi wall units (Only Cooling) - (Noise Level 32-39 db) Hi wall Type -2.0 TR (720 CFM)(10W+7S)
AIR COOLED - SPLIT UNITS (Inverter Type)- UPS/SERVER/HUB ROOM Supply, installation, testing and commissioning of INVERTER ROTARY TYPE / INVERTER SCROLL TYPE Air cooled DX, Split type air conditioning units each comprising of : An Oudoor unit and an Indoor unit can be: High wall type/Ductable, The unit shall be with R32 / R410 refrigerant.The split unit shall be only cooling or (Heat Pump) heating & cooling as mentioned below in the BOQ. The unit shall be with hand held IR remote or corded remote as may be required.The unit shall be with hand held IR remote or corded remote as may be required. Outdoor condensing unit shall comprise of single / multi inverter, rotary / scroll compressor & air cooled condenser with fan & motor. Evaporating unit shall consist of a blower section with dynamically balanced centrifugal blower driven by induction motor, multirows deep copper cooling coil with aluminium fins, thermostatic expansion valve etc. The evaporating unit shall be equipped with synthetic fibre filters, insulated drain pan, safety controls, thermostat all complete in a unit. Ductable units / Fured-in units shall have fire retardant canvass connection at fan outlet. The enclosure shall be factory painted to a smooth finish. The quoted price shall be inclusive of interconnected insulated refrigerant piping, insulated drain piping, vibration isolation pads / vibration isolators and associated electrical cabling & earthing between indoor & outdoor units and MS powder coated base frame work made of angle iron for mounting of outdoor / indoor units. The units shall be suitable for 230V±6%, or 415V±10%, 50 ± 3%,Hz supply & complete with electrical controls & panels, if required. Hi wall units (Only Cooling) - (Noise Level 32-39 db) Hi wall Type -1.5 TR (575 CFM)(0W+0S) (RO)
AIR COOLED - SPLIT UNITS (Inverter Type)- UPS/SERVER/HUB ROOM Supply, installation, testing and commissioning of INVERTER ROTARY TYPE / INVERTER SCROLL TYPE Air cooled DX, Split type air conditioning units each comprising of : An Oudoor unit and an Indoor unit can be: High wall type/Ductable, The unit shall be with R32 / R410 refrigerant.The split unit shall be only cooling or (Heat Pump) heating & cooling as mentioned below in the BOQ. The unit shall be with hand held IR remote or corded remote as may be required.The unit shall be with hand held IR remote or corded remote as may be required. Outdoor condensing unit shall comprise of single / multi inverter, rotary / scroll compressor & air cooled condenser with fan & motor. Evaporating unit shall consist of a blower section with dynamically balanced centrifugal blower driven by induction motor, multirows deep copper cooling coil with aluminium fins, thermostatic expansion valve etc. The evaporating unit shall be equipped with synthetic fibre filters, insulated drain pan, safety controls, thermostat all complete in a unit. Ductable units / Fured-in units shall have fire retardant canvass connection at fan outlet. The enclosure shall be factory painted to a smooth finish. The quoted price shall be inclusive of interconnected insulated refrigerant piping, insulated drain piping, vibration isolation pads / vibration isolators and associated electrical cabling & earthing between indoor & outdoor units and MS powder coated base frame work made of angle iron for mounting of outdoor / indoor units. The units shall be suitable for 230V±6%, or 415V±10%, 50 ± 3%,Hz supply & complete with electrical controls & panels, if required. Hi wall units (Only Cooling) - (Noise Level 32-39 db) Hi wall Type -1.0 TR (470 CFM)(4W+0S) (RO)
AIR COOLED DUCTABLE SPLIT UNITS (High Static) Supply, installation, testing and commissioning of Split type air-conditioning unit, each comprising of an outdoor unit and a single ductable type /floor standing type indoor unit. Outdoor condensing unit shall comprise of single / multi, scroll compressor & air cooled condenser with fan & motor. Evaporating unit shall consist of a blower section with dynamically balanced centrifugal blower driven by induction motor, multirows deep copper cooling coil with aluminium fins, thermostatic expansion valve etc. The evaporating unit shall be equipped with synthetic fibre filters, insulated drain pan, safety controls, thermostat all complete in a unit. Ductable units shall have fire retardant canvass connection at fan outlet. The enclosure shall be factory painted to a smooth finish. The quoted price shall be inclusive of interconnected insulated refrigerant piping, insulated drain piping, vibration isolation pads / vibration isolators and associated electrical cabling & earthing between indoor & outdoor units and MS powder coated base frame work made of angle iron for mounting of outdoor / indoor units. The units shall be suitable for 230V±6%, or 415V±10%, 50 ± 3%,Hz supply & complete with electrical controls & panels.The unit shall be with R32 / R410 refrigerant. The split unit shall be only cooling or (Heat Pump) heating & cooling as mentioned below in the BOQ. The unit shall be with hand held corded remote . The Unit shall be complete with micro-processor based controller & shall be cable of BMS connectivity for operation & control through BMS. Ceiling Suspended Ductable Units(High Static ) - (ONLY COOLING) Ceiling Suspended Type 16.7 TR (5800-6600 CFM) ( 2W+2S )
AIR COOLED DUCTABLE SPLIT UNITS (High Static) Supply, installation, testing and commissioning of Split type air-conditioning unit, each comprising of an outdoor unit and a single ductable type /floor standing type indoor unit. Outdoor condensing unit shall comprise of single / multi, scroll compressor & air cooled condenser with fan & motor. Evaporating unit shall consist of a blower section with dynamically balanced centrifugal blower driven by induction motor, multirows deep copper cooling coil with aluminium fins, thermostatic expansion valve etc. The evaporating unit shall be equipped with synthetic fibre filters, insulated drain pan, safety controls, thermostat all complete in a unit. Ductable units shall have fire retardant canvass connection at fan outlet. The enclosure shall be factory painted to a smooth finish. The quoted price shall be inclusive of interconnected insulated refrigerant piping, insulated drain piping, vibration isolation pads / vibration isolators and associated electrical cabling & earthing between indoor & outdoor units and MS powder coated base frame work made of angle iron for mounting of outdoor / indoor units. The units shall be suitable for 230V±6%, or 415V±10%, 50 ± 3%,Hz supply & complete with electrical controls & panels.The unit shall be with R32 / R410 refrigerant. The split unit shall be only cooling or (Heat Pump) heating & cooling as mentioned below in the BOQ. The unit shall be with hand held corded remote . The Unit shall be complete with micro-processor based controller & shall be cable of BMS connectivity for operation & control through BMS. Ceiling Suspended Ductable Units(High Static ) - (ONLY COOLING) Ceiling Suspended Type 5.5 TR (2045 CFM) (RO)
AIR COOLED DUCTABLE SPLIT UNITS (High Static) Supply, installation, testing and commissioning of Split type air-conditioning unit, each comprising of an outdoor unit and a single ductable type /floor standing type indoor unit. Outdoor condensing unit shall comprise of single / multi, scroll compressor & air cooled condenser with fan & motor. Evaporating unit shall consist of a blower section with dynamically balanced centrifugal blower driven by induction motor, multirows deep copper cooling coil with aluminium fins, thermostatic expansion valve etc. The evaporating unit shall be equipped with synthetic fibre filters, insulated drain pan, safety controls, thermostat all complete in a unit. Ductable units shall have fire retardant canvass connection at fan outlet. The enclosure shall be factory painted to a smooth finish. The quoted price shall be inclusive of interconnected insulated refrigerant piping, insulated drain piping, vibration isolation pads / vibration isolators and associated electrical cabling & earthing between indoor & outdoor units and MS powder coated base frame work made of angle iron for mounting of outdoor / indoor units. The units shall be suitable for 230V±6%, or 415V±10%, 50 ± 3%,Hz supply & complete with electrical controls & panels.The unit shall be with R32 / R410 refrigerant. The split unit shall be only cooling or (Heat Pump) heating & cooling as mentioned below in the BOQ. The unit shall be with hand held corded remote . The Unit shall be complete with micro-processor based controller & shall be cable of BMS connectivity for operation & control through BMS. Ceiling Suspended Ductable Units(High Static ) - (ONLY COOLING) Ceiling Suspended Type 8.5 TR (3400 CFM) ( 1W+1S )(RO)
AIR COOLED DUCTABLE SPLIT UNITS (High Static) Supply, installation, testing and commissioning of Split type air-conditioning unit, each comprising of an outdoor unit and a single ductable type /floor standing type indoor unit. Outdoor condensing unit shall comprise of single / multi, scroll compressor & air cooled condenser with fan & motor. Evaporating unit shall consist of a blower section with dynamically balanced centrifugal blower driven by induction motor, multirows deep copper cooling coil with aluminium fins, thermostatic expansion valve etc. The evaporating unit shall be equipped with synthetic fibre filters, insulated drain pan, safety controls, thermostat all complete in a unit. Ductable units shall have fire retardant canvass connection at fan outlet. The enclosure shall be factory painted to a smooth finish. The quoted price shall be inclusive of interconnected insulated refrigerant piping, insulated drain piping, vibration isolation pads / vibration isolators and associated electrical cabling & earthing between indoor & outdoor units and MS powder coated base frame work made of angle iron for mounting of outdoor / indoor units. The units shall be suitable for 230V±6%, or 415V±10%, 50 ± 3%,Hz supply & complete with electrical controls & panels.The unit shall be with R32 / R410 refrigerant. The split unit shall be only cooling or (Heat Pump) heating & cooling as mentioned below in the BOQ. The unit shall be with hand held corded remote . The Unit shall be complete with micro-processor based controller & shall be cable of BMS connectivity for operation & control through BMS. Ceiling Suspended Ductable Units(High Static ) - (ONLY COOLING) Ceiling Suspended Type 11 TR (3850-4400 CFM) ( RO )
Packaged Floor Mounted Unit (High Static) - ( ONLY COOLING) Floor Mounted Type Type 16.7 TR (5800-6600 CFM) ( 1W+1S ) Notes:- Hi-walls shall be with cordless remote.Final requirement on type of remotes shall be decided during execution stage. Tenderer to consider this fact in the costing.
Final requirement on type of remotes shall be decided during execution stage. Tenderer to consider this fact in the costing. Cordless Remotes Controller
Final requirement on type of remotes shall be decided during execution stage. Tenderer to consider this fact in the costing. Corded Remotes Controller
SEQUENTIAL CONTROLLER Supply,installation,testing and commissioning of Sequential Controller for controlling Split Unit's. The controller shall ensure cyclic operation of AC units. It shall also have inbuilt temperature sensor & temperature display. Sequential Controller for (2W+1S) units (RO)
SEQUENTIAL CONTROLLER Supply,installation,testing and commissioning of Sequential Controller for controlling Split Unit's. The controller shall ensure cyclic operation of AC units. It shall also have inbuilt temperature sensor & temperature display. Sequential Controller for (1W+1S) units
SEQUENTIAL CONTROLLER Supply,installation,testing and commissioning of Sequential Controller for controlling Split Unit's. The controller shall ensure cyclic operation of AC units. It shall also have inbuilt temperature sensor & temperature display. Sequential Controller for (1W+1S) units (Ductable & Package AC)
ODU Anti Corrosive Coating Carrying out Anti Corrosive coating through spray painting process on coil, fins, joints & header of each ODU as per paint manufacturer's recommendation including supply of paint: Product: Promak Coating: Ultra Corr ACX 4000 For 16.7TR Ductable Split (RO)
ODU Anti Corrosive Coating Carrying out Anti Corrosive coating through spray painting process on coil, fins, joints & header of each ODU as per paint manufacturer's recommendation including supply of paint: Product: Promak Coating: Ultra Corr ACX 4000 For Hiwall Split Units (RO)
ODU Anti Corrosive Coating Carrying out Anti Corrosive coating through spray painting process on coil, fins, joints & header of each ODU as per paint manufacturer's recommendation including supply of paint: Product: Promak Coating: Ultra Corr ACX 4000 For 5.5 TR Ductable split(RO)
ODU Anti Corrosive Coating Carrying out Anti Corrosive coating through spray painting process on coil, fins, joints & header of each ODU as per paint manufacturer's recommendation including supply of paint: Product: Promak Coating: Ultra Corr ACX 4000 For 8.5 TR Ductable split(RO)
ODU Anti Corrosive Coating Carrying out Anti Corrosive coating through spray painting process on coil, fins, joints & header of each ODU as per paint manufacturer's recommendation including supply of paint: Product: Promak Coating: Ultra Corr ACX 4000 For 11 TR Ductable split(RO)
Refrigerant Piping Supply, Installation, commisioning of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. 34.9 mm O.D. (insulation : 13 mm)
Refrigerant Piping Supply, Installation, commisioning of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. 28.6 mm O.D. (insulation : 13 mm)
Refrigerant Piping Supply, Installation, commisioning of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. 22.2 mm O.D. (insulation : 13 mm)
Refrigerant Piping Supply, Installation, commisioning of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. 15.9 mm O.D. (insulation : 9 mm)
Refrigerant Piping Supply, Installation, commisioning of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. 12.7 mm O.D. (insulation : 9 mm)
Refrigerant Piping Supply, Installation, commisioning of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. 9.5 mm O.D. (insulation : 9 mm)
Refrigerant Piping Supply, Installation, commisioning of Interconnecting refrigerant pipe work with closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported with MS hanger & clamps. Exposed refrigerant copper piping shall be with uv coating. 6.4 mm O.D. (insulation : 9 mm)
CONDENSATE DRAIN PIPING Supply,installation,testing and commissioning of rigid uPVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber. Density of uPVC pipe shall not be less than 10 kg / m3 25 mm NB
Supply installation, testing and commissioning of all control and data cables between indoor unit, outdoor unit and central remote controler laid in hard PVC conduit with proper supporting arrangement.
VRV UNITS FOR HUB ROOM - GF / FF /SF Supply Installation, testing and commissioning of Variable Refrigerant System outdoor units with heat pump, with scroll compressors with all compressors with capacity controlling type compressor, copper tube and alumnium finned aircooled condenser, electrical & microprocessor panel, isolating valves and all the necessary accessories for proper functioning of the units. Refrigerant R-410a - Capacity - 16 HP (8+8)
Supply Installation, testing and commissioning of Variable Refrigerant System Hiwall type indoor units with copper tube and alumnium finned evaporator, and all the necessary accessories for proper functioning of the units. Capacity 2.0 TR
Supply installation , testing and commissioning of all refrigerant Joint Set of suction & liquid line required for the system to connect VRF Condensing Unit to multiple Indoor Units(IDU).
Testing & Commisioning charges alongwith topping-up of refrigerant for VRF system
BREEZEWELL ENGINEERING
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .