| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.1 LAccepted-Finance | L1 | Accepted-Finance Rate quoted is lowest | |
| 2 | L2₹25.1 L+₹2,999.30 (0.12%)Accepted-Finance | L2 | Accepted-Finance Rate quoted is second lowest | |
| 3 | L3₹25.2 L+₹7,358 (0.29%)Accepted-Finance | L3 | Accepted-Finance Rate quoted is highest |
Tender Value
Refer Docs
EMD Value
₹26,000
Closing Date
7 Dec 2020, 4:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
SE ETC Sultanpur 400KV S/S Campus Payagipur Sultanpur
SHIFTING OF OLD and USED 132/33KV 20MVA T/F (TA MAKE) AT 132KV S/s, JALALPUR, Its CARRIAGE FROM 132KV S/s, JALALPUR TO 220KV S/s, NEW TANDA AND UNLOADING AT 220KV S/s, NEW TANDA, UNDER ETD AYODHYA
2020_UPTCL_529064_2
T. NO. 81/ETCS/2020-21
Open Tender
Electrical Works
Item Wise
90 days
Sultanpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹3,068
SE ETC Sultanpur
₹26,000
8 Dec 2020
2 Dec 2020
8 Dec 2020
2 Dec 2020
7 Dec 2020
2 Dec 2020
2 Dec 2020 - 7 Dec 2020
180 days
Amount
Following Works are to be carried out for the work of Shifting & Loading of old & used 132/33KV 20MVA T/F (Technical Associate make) at 132KV S/S Jalalpur Ambedkar Nagar, its Carriage from 132 K.V. S/S Jalalpur to 220 K.V. S/S New Tanda Ambedkar Nagar and unloading at 220 K.V. S/S New Tanda including all cost of men, misc. consumables, T&P, Crane, Carriage Vehicle etc. to complete the job satisfactorily as per direction of Supervising Engineer :
Shifting/ Dragging of Oil filled Main Tank of 20MVA 132/33KV T/F (Technical Associate make) including turning of the T/F Tank, as required alongwith associated accessories from existing place to near open space / safe loading place at 132KV S/S Jalalpur (upto 20 meter distance), with all due care of safety & precautions.
Additional Shifting of 5 Meter.
Loading of Tank of above 20MVA T/F on Trailer at 132 K.V. S/S Jalalpur, jacking the T/F Tank for placing of Wooden Sleepers / Planks under the T/F Tank and lifting the T/F Tank by continuous jacking & placing the Wooden Sleepers / Planks, till the Wooden Platform comes upto height of the Trailer's bed, then placing of Rails over Wooden Sleepers / Planks & Trailer's bed for shifting the T/F Tank from Wooden Platform to Trailer's bed and removal of Rails after proper placing of T/F Tank on Trailer's bed and finally, proper tightening / anchoring of the T/F Tank on Trailer with the help of Steel Wire Rope & Heavy Turn Buckle for safe transportation including loading of other accessories of the T/F on Trailer / Trucks, with all due care of safety & precautions.
Safe carriage of Oil filled Main Tank of above 20MVA T/F alongwith all accessories e.g. 132 K.V., 33 K.V. & Neutral Bushings, Conservator Tank and Oil Drums of the T/F by Trailer & Trucks arranged by the Contractor from 132 K.V. S/S Jalalpur to 220 K.V. S/S New Tanda (approx. travel distance 30 Km), with all due care of safety & precautions including arrangement of Transit Insurance.
Unloading of Main Tank of above 20MVA T/F from Trailer after opening of lashing of Main Tank, jacking the T/F Tank for placing the Rails under the Tank for shifting of same to Wooden Platform, removing the Rails after shifting of the Tank on Wooden Platform, lowering the T/F Tank towards ground by slowly jacking & removing the Wooden Sleepers / Planks from under the Tank including all accessories from the Trailer / Trucks at safe unloading place at 220 K.V. S/S New Tanda, with all due care of safety & precautions, with all cost of men, T&P and other associated works required to complete the job satisfactorily.
Shifting of Main Tank of 20MVA Transformer to plinth from place of storage upto 20mtr. distance including turning of tank if required.
Additional shifting of transformer tank upto 50 mtr distance (1 Job for every 5 mtr.)
Erection of 20MVA Transformer RTCC Panel including shifting from storage place to control room.
Complete erection of 20MVA Transformer including Radiators, Conservator tank, Bushing, Connecting pipe lines, Cooling fans and pumps, Marshalling box, OTI, WTI, Capillary pipes etc.
Applying vacuum to above transformer tank upto 760mm of HG for 24hrs. With adequate capacity vacuum pumps after necessary blanking/ erection as per requirement.
Filling of dry nitrogen gas having dew point (-)70˚C to (-)75˚C under vacuum from top value of the transformer upto pressure of 3 PSI and maintain the same in the main tank for 12hrs. Including cost of Nitrogen gas and Nitrogen gas filling device.
Create the vacuum inside the tank for period for 12 hours and filling of centrifuged oil step by step upto core & winding conservator tank radiator.
Centrifuging/ Dehydration of the complete transformer oil of 20MVA transformer by ultra high vacuum oil filtration plant after connecting the centrifuging pipes with transformer tank to oil filtration plant including taking the BDV & PPMvalues of oil and megger value of the transformer periodically till the required value is achieved. Including filling and topping up of the transformer oil under vacuum in main tank, radiators, conservator tank etc. and attending the oil leakage if any, will all cost of centrifuging machine, CFM operator, lubricant etc.
Top-up transformer oil after centrifuging in Transformer
Complete earthing of 20MVA transformer with 50x6mm/ 75x10mm size MS Flat as per standard practice at two points.
Earthing of main tank, marshalling box and drive mechansm of cooling fans etc. and its onnection of with earthmat as per standard practice
Earthing of HV & LV Neutrals with separate 75x10mm size MS Flat as of 20MVA transformer with the help of 75x10mm size MS Flat to be provided by department, its jointing with earthmat/ delta including making of 2 new delta earthing for 132KV and 33KV Neutral bushing by 3 Mtr. long 36mm/40mm dia MS round bar after digging pits of size 1x1x1 CuM and necessory modification in existing support for earthing of neutral bushing support for its earthing work and then painting of earthing strips as per technical specification/ standard practice.
Erection of Control & Relay Panel making necessary holes in the glands plates or box wherever required, supply & fixing of cable glands of appropriate size, providing of ferrules and cable termination as per standard practice & all other associated works as per technical specification.
Termination of Control and Power cable as per cable schedule of 20MVA transformer RTCC Panel, Control and Relay Panel, Cooling fan, Marshaling box etc. including cost of cable glands, lugs & ferruls complete and both end as per site and panel requirement.
Laying of following 1.1KV unarmoured copper control cable:
Erection of following equipments including shifting of material from store to site:
145KV SF6 Circuit Breaker
36KV VCB
145KV Current Transformer
145KV C.T. Junction Box
145KV P.T. Junction Box
36KV Current Transformer
36KV C.T. Junction Box
36KV Potential Transformer
36KV P.T. Junction Box
145KV Bus Isolator
145KV Tandem Isolator
36KV Bus/ Line Isolator
145KV Post Insulators
120KV Surge Arrester
30KV Surge Arrester
33KV Tripple Feeder Control & Relay Panel as per technical specification
Laying of following 1.1KV unarmoured copper control cable:
Termintion of following 1.1KV unarmoured copper control cable:
132/33KV Transformer Bay Control Cable termination including cost of cable glands, lugs & ferrules complete and both end as per site and panel requirement
33KV Bay Control cable termination including cost of cable glands, lugs & ferruls complete and both end as per site and panel requirement
Dismentling of Lattice type main and auxiliary structures
Erection of Lattice type main and auxiliary structures
Earthing of structures and equipments:
Earthing of 50mmx6mm MS flat (including painting)
Earthing of 25mmx6mm MS flat (including painting)
0.2 class accuracy ABT energy meters (Main + Check)
Stringing/ Re-stringing of following Bus with specified ACSR conductors, tension fittings, suspension fittings & PG clamps to complete the work satisfactory as per technical specification (including cost of hoisting insulators, cutting of conductors and shifting of materials from store to site):
132KV Jack Bus for 20MVA Transformer
33KV Old main Bus dismantling and re-stringing including all associated works
33KV old Transfer Bus dismantling and re-stringing including all associated works
33KV Transfer Bus
Bay wise interconnection (jumpering) of equipments with specified conductors
20MVA Transformer bay including 132KV & 33KV side
33KV Feeder Bay
Shifting of 250KVA 33/0.4KV Station Transformer and Section tower conductor (R &Y Phase) of 132KV Jalalpur Line due to site requirements.
Shifting of 250KVA 33/0.4KV Station Transformer. The work includes opening of jumpers, dismantling of station transformer isolator etc. then erection of 250KVA 33/0.4KV station transformer, isolator structure, jumpering and earthing.
Laying of following size 3.5 core Aluminium Power cable below the minimum 50 cm. from ground level through the trench to be made of first class bricks and filling of sand after laying of cable & covering by bricks as per technical specification and ramming the earth
Termination of following size 3.5 core Aluminium Power cable at both ends (including Lugs)
Fixing/ Erection of 0.4KV AC Cubical
Lowering of R & Y Phase condutor of existing circuit of 132KV New Tanda- Jalalpur line by opening tension fitting from tower to gantry at 220 S/S New Tanda end.
Rehoisting of R & Y Phase conductor on the other circuit of 132KV New Tanda- Jalalpur line from tower to gantry at 220KV S/S New Tanda end.
Following Clamps & Connectors are to be procured for Works of Construction of 132K.V. and 33K.V. Bays for Installation of 132/33KV 20MVA Transformer at 220K.V. Sub Station New Tanda:
Bolted type single Tension fitting for Moose Conductor suitable for Porcelain Disc Insulator with hardware set as per technical specification.
Bolted type single Tension fitting for Panther Conductor suitable for Porcelain Disc Insulator with hardware set as per technical specification.
Bolted type single Suspension fitting for Moose Conductor Suitable for Disc with hardware set as per technical specification.
Bolted type single Suspension fitting for Panther Conductor Suitable for Disc with hardware set as per technical specification.
4 Bolted Type PG Clamp suitable for Moose to Moose Conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Moose to Panther Conductor Complete with HDG nut bolt & washer as per technical specification.
4 Bolted Type PG Clamp suitable for Panther to Panther Conductor Complete with HDG nut bolt & washer as per technical specification.
Bus Post Clamp suitable for single Panther conductor complete with hot dip galvanized nut, bolts & washer as per technical specification.
132 KV Isolator Clamp for single Panther conductor with nut, bolts and washer as per technical specification.
132 KV Breaker Clamp for single Panther conductor with nut, bolts and washer as per technical specification.
132 KV Tandem Isolator Clamp for single Panther conductor with nut, bolts and washer as per technical specification.
33 KV Isolator Clamp for single Moose conductor with nut, bolts and washer as per technical specification.
33 KV Isolator Clamp for single Panther conductor with nut, bolts and washer as per technical specification.
33 KV Breaker Clamp for single Moose conductor with nut, bolts and washer as per technical specification.
33 KV Breaker Clamp for single Panther conductor with nut, bolts and washer as per technical specification.
Galvanised Perforated Cable Tray duly made of 18 SWG G.I. Sheet of following sizes :
SHIVAM ENGINEERS
ARYA ASSOCIATE AND GENERAL ORDER SUPPLIERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .