Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹6.9 L
Closing Date
12 Nov 2021, 2:00 pmClosed
Executive Engineer
Office of the Executive Engineer EDD,Leh
Supply, installation, testing and commissioning for Creation of 100KVA Substation along with allied material and laying of HT line at NTPHC, Hanu Yokma Leh on full turnkey basis.
2021_PDNRE_5130_1
NIT NO. 127 Dated 05.11.2021
Open Tender
Electrical Works
Turn-key
30 days
Leh
Please refer Tender documents.
6 documents required · 6 mandatory
₹300
Payable To Executive Engineer EDD Leh
Exempted
19 Mar 2022
5 Nov 2021
13 Nov 2021
6 Nov 2021
12 Nov 2021
6 Nov 2021
Amount
Distribution Transformer Substation
100 KVA, 11/0.433kV, 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level- 2, (Aluminium wound upto 200kVA, Copper wound for 250kVA or higher kVA ratings) , and with LV Cable Box having detachable Aluminium Gland plate
Gapless Surge Arrestor,9 kV, 10kA, LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
120mm²(2Ckt) Cable, 1.1kV Grade, PVC Insulated Stranded Conductor FRLS type for 100KVA DT
9 Mtr. Long Pole,ST-410 SP33)
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
GI Channel/Angle/Flat of sizes including clamps (Refer REC Construction Standard F2)
Galvanized Nuts and Bolts.
LT Distribution Box Out door mounting type for 3 Ph 100kVA DTR having 200A TPN isolator, 200A HRC fuse (incomer) and 6 Nos 90A SP MCCB (outgoing)
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
3-Ø, 4-Wire Trivector Meter with CT(LTCT AMR compatible)
Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Wedge Connectors / PG Clamps
Danger Plates with Clamps
GI Barbed Wire for Anti Climbing
Cement bottoming 1:2:4 mix as per REC standards .5cum/pole
Painting of Poles Red Oxide
Painting of Poles Aluminium Paint
Sundry items like aluminium lugs, Jumpers, binding Tape etc
Laying of 11KV Line
9 Mtr. Long Pole( ST-410 SP33)
GI V cross-arm (75x40x6mm) with GI top Bracket (50x8 mm) including GI clamp (50x8)mm the standard as per enclosed drawing and specification as per Annexure "A")
Channel 8ft long with clamps and braces
30 mm² ACSR weasel Conductor (Single conductor length)
33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm
Galvinized Nuts and Bolts
Earthing Complete by GI Spiral/Rod 20mm 2.5 mtr long through GI Strip.
Red Oxide
Aluminium Paint
Cement bottoming 1:2:4 mix as per REC standards 0.5cum /pole including muffing 0.2Mtr above the ground level plaster and curing of concrete as per drawing/Annexure "D"
M/S CHHEIRPON ENTERPRISES
M/S LOBZANG GURMET GOVT CONTRACTOR
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .