Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.3 LAccepted-AOC | ₹20.3 L Quoted ₹17.1 L | L1 | Accepted-AOC L1 |
| 2 | L2₹17.4 L+₹34,088.22 (2.00%)Rejected-AOC | ₹17.4 L+₹34,088.22 (2.00%) | L2 | Rejected-AOC L2 |
Tender Value
₹20.3 L
EMD Value
₹40,597
Closing Date
27 Dec 2021, 5:00 pmClosed
EXECUTIVE ENGINEER
ELECT. DIVN.V, BICHOLIM
Tender for the work of enhancement of transformer centre from 63 KVA to 100 KVA at Ambeshi Pale and Supply and erection of 1 no. 100KVA Distribution Transformer Centre alongwith HT/LT line at Chinchwada Pale, in the jurisdiction of S.O. Pale,
2021_ED_1274_1
Tender-03/Div-V
Open Tender
Electrical Works
Item Rate
180 days
ELECT. DIVN.V, BICHOLIM
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,500
₹40,597
26 Sept 2022
18 Nov 2021
31 Dec 2021
20 Nov 2021
27 Dec 2021
30 Nov 2021
Amount
COST OF MATERIAL
A) Work under Renovation & Improvement for enhancement of transformer centre from 63 KVA to 100KVA at Ambeshi Pale, in the jurisdiction of S.O. Pale, under the Sub Division-II(R ), Sankhali.
Cement Concrete1:2:4
Supply of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A
Supply of 11 KV Disc Insulators ball and socket type, A porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze "W" split pin as per IS 731-1971 as amended upto date. Minimum failing load 45 KN Pin ball diameter 16 mm. Minimum Creepage distance 320 mm with 2 bolted type hardware fitting 70KN suitable for 11 KV ball and socket type disc insulators of 16 mm pin, failing load of 70 KN and suitable for ACSR conductor of size upto 18 mm diameter. The metal parts shall be as per drg No CC/E-482-Rev-2 Benclosed and conform to IS-2486 part 1-1993, 2486 Part-2-1989 as amended upto date.
Supply of Single core XLPE Insulated PVC Sheathed cable 120sqmm 1.1kV grade
Supply of 11 KV , 200 A Horn gap fuse unit (Set of three) shall be as per enclosed drg No. CEE/E-786. Revision 3 and detailed specifications enclosed herewith.
Supply of 9 KV, 5 KA nominal discharge current metal oxide gapless distribution class Lightning arrestor conforming to IEC-600994-4 and IS: 3070 part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arragements and connector suitable to connect ASCR conductor upto overall diameter 12.30 mm
Supply of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A
Supply of HDGI structure material for 12 DPS. Each trasformer centre DP consist of HDGI structure material as follows: a) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for incoming line & installation of disc insulators b) GI channel ISMC75x40x7.3mm 2.75mtrs long 2 pieces for GOAB switch c) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for HG fuses d) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for installation of lightening arrestor e) GI channel ISMC 100x50x7.3mm 2.75 mtrs long 2 pieces for installation of Trasformer f) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for side support of trasformer g) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 4 pieces for installation of any other items h) GI channel ISMC 100x40x7.3mm 0.52 mtrs long 2 pieces for installation of Transformer base channel
Supply of HDG earthing pipe 8ft long 40mm. Dia. Class B fabricated & perforated including alternate layers of 30cms thick of charcoal,salt & earth( charcoal & salt 10kgs each per pit inclusive of excavation,bacfilling& spreading the earth evenly)
Supply of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Supply of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Supply of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 9mtr Rcc pole
Supply of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-492 with clamp and nut bolt for 7.5 mtr Rcc pole
Supply of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.
Supply of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN
Supply of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 9 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Supply of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 7.5 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
B) Work of supply and erection of 1 no of 100KVA Distribution transformer Centre along with HT/LT line for improving the LT Distribution Network in villge of Chinchwada Pale, under the jurisdiction of Village Panchayat Pale- Cothambi, under the Sub Division-II(R ), Sankhali.
Supply of RCC pole 11.0 mtr as per the drawing No.CEE/E-698, REV-1 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982
Cement Concrete1:2:4
Supply of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 11.0 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Supply of HDG 11KV "V" shape cross arm of channel ISMC 75 x 40 x 7.3mm as per gdr. No. CEE/E-408-R1
Supply of HDGI Top fitting X-arm channel 75X40,0.7mts long(4.74kgs)
Supply of HDGI Cut point channel 75X40X 6mm,1.3 mts long (8.84kgs)
Supply of HDGI Guard X-arm channel 75X40X 6mm,1.5mts long(10.2kgs)
Supply of 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the minimum creepage distance of 320mm conforming to IS 731-1971 as amended upto date. And forged GI pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS 731/71 as amended upto date. GI pin shall conform to reference S-165 N fig 5 of IS 2486/(part-II)/74 as amended upto date. Dimension X in said fig shall be 150mm (screwed 100mm). Pin shall be supplied along with one suitable GI hexagonal nut and GI spring washer. Minimum failing load of pin shall be 10 KN.
Supply of 11 Disc Insulators ball and socket type, A porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze "W" split pin as per IS 731-1971 as amended upto date. Minimum failing load 45 KN Pin ball diameter 16 mm. Minimum Creepage distance 320 mm with 2 bolted type hardware fitting 70KN suitable for 11 KV ball and socket type disc insulators of 16 mm pin, failing load of 70 KN and suitable for ACSR conductor of size upto 18 mm diameter. The metal parts shall be as per drg No CC/E-482-Rev-2 Benclosed and conform to IS-2486 part 1-1993, 2486 Part-2-1989 as amended upto date.
Supply of DTC metering unit with moderm
Supply of Single core XLPE Insulated PVC Sheathed cable 120sqmm 1.1kV grade
Supply of 11 KV , 200 A Horn gap fuse unit (Set of three) shall be as per enclosed drg No. CEE/E-786. Revision 3 and detailed specifications enclosed herewith.
Supply of 9 KV, 5 KA nominal discharge current metal oxide gapless distribution class Lightning arrestor conforming to IEC-600994-4 and IS: 3070 part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arragements and connector suitable to connect ASCR conductor upto overall diameter 12.30 mm
Supply of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A
Supply of HDGI structure material for 12 DPS. Each trasformer centre DP consist of HDGI structure material as follows: a) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for incoming line & installation of disc insulators b) GI channel ISMC75x40x7.3mm 2.75mtrs long 2 pieces for GOAB switch c) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for HG fuses d) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for installation of lightening arrestor e) GI channel ISMC 100x50x7.3mm 2.75 mtrs long 2 pieces for installation of Trasformer f) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for side support of trasformer g) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 4 pieces for installation of any other items h) GI channel ISMC 100x40x7.3mm 0.52 mtrs long 2 pieces for installation of Transformer base channel
Supply of HDG earthing pipe 8ft long 40mm. Dia. Class B fabricated & perforated including alternate layers of 30cms thick of charcoal,salt & earth( charcoal & salt 10kgs each per pit inclusive of excavation,bacfilling& spreading the earth evenly)
Supply of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Supply of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Supply of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for11mtr Rcc pole
Supply of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 9mtr Rcc pole
Supply of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-492 with clamp and nut bolt for 7.5 mtr Rcc pole
Supply of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.
Supply of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN
Supply of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 9 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Supply of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 7.5 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
COST OF ERECTION
A) Work under Renovation & Improvement for enhancement of transformer centre from 63 KVA to 100KVA at Ambeshi Pale, in the jurisdiction of S.O. Pale, under the Sub Division-II(R ), Sankhali.
Erection of RCC pole 7.5 mtr as per the drawing No.CEE/E-698, REV-1 as per annexure confirming to IS 785-1998 as amended upto date.
Erection of RCC pole 9.0 mtr as per the drawing No.CEE/E-698, REV-1 as per annexure confirming to IS 785-1998 as amended upto date.
Erection of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A
Erection of 11 Disc Insulators ball and socket type, A porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze "W" split pin as per IS 731-1971 as amended upto date. Minimum failing load 45 KN Pin ball diameter 16 mm. Minimum Creepage distance 320 mm with 2 bolted type hardware fitting 70KN suitable for 11 KV ball and socket type disc insulators of 16 mm pin, failing load of 70 KN and suitable for ACSR conductor of size upto 18 mm diameter. The metal parts shall be as per drg No CC/E-482-Rev-2 Benclosed and conform to IS-2486 part 1-1993, 2486 Part-2-1989 as amended upto date.
Erection of ACSR 'Weasel' conductor confirming ISI specification IS: 398 (part-1/96) as amended upto date of following sizes 6/1/2.59 mm for guarding
Erection of Distribution Transformer 100 KVA 11/0.44 KVA Aluminium wound Star rated
Erection of Distribution box (Thermosetting Plastic i.e. Sheet Moulding Compound - SMC) I/C:- 160 Amps TP MCCB O/G 200 Amps KIT KAT Rewirable Fuse 6 Nos.
Removing & Refixing DTC metering unit with moderm
Erection of Single core XLPE Insulated PVC Sheathed cable 120sqmm 1.1kV grade
Erection of Three and half core armoured XLPE cable of size 95 Sq.mm cross linked polyethelene insulated, PVC shealthed 3.5 core 95 sqmm cable with galvanized steel strip armoured aluminium cable of 1100 volts grade suitable for 3 phase earthed system and conforming to IS: 7098 (Part-I)/1988 as amended upto date.
Erection of 11 KV , 200 A Horn gap fuse unit (Set of three) shall be as per enclosed drg No. CEE/E-786. Revision 3 and detailed specifications enclosed herewith.
Erection of 9 KV, 5 KA nominal discharge current metal oxide gapless distribution class Lightning arrestor conforming to IEC-600994-4 and IS: 3070 part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arragements and connector suitable to connect ASCR conductor upto overall diameter 12.30 mm
Erection of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A
Erection of HDGI structure material for 12 DPS. Each trasformer centre DP consist of HDGI structure material as follows: a) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for incoming line & installation of disc insulators b) GI channel ISMC75x40x7.3mm 2.75mtrs long 2 pieces for GOAB switch c) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for HG fuses d) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for installation of lightening arrestor e) GI channel ISMC 100x50x7.3mm 2.75 mtrs long 2 pieces for installation of Trasformer f) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for side support of trasformer g) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 4 pieces for installation of any other items h) GI channel ISMC 100x40x7.3mm 0.52 mtrs long 2 pieces for installation of Transformer base channel
Erection of HDG earthing pipe 8ft long 40mm. Dia. Class B fabricated & perforated including alternate layers of 30cms thick of charcoal,salt & earth( charcoal & salt 10kgs each per pit inclusive of excavation,bacfilling& spreading the earth evenly)
Erection of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Erection of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Erection of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 9mtr Rcc pole
Erection of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-492 with clamp and nut bolt for 7.5 mtr Rcc pole
Erection of HDG L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 9 mtr Rcc pole
Erection of HDG L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 7.5 mtr Rcc pole
Erection of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.
Erection of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN
Erection of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 9 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Erection of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 7.5 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Erection of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases
Erection of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.
Removing of RCC pole 9 mtr as per the drawing No.CEE/E-565 REV-3 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982
Removing of RCC pole 7.5 mtr as per the drawing No.CEE/E-565 REV-3 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982
Removing HDGI Top fitting
Removing HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491
Removing of HDG L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491
Removing of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.
Removing of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN
Removing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases
Removing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.
Removing of ACSR 'Weasel' conductor confirming ISI specification IS: 398 (part-1/96) as amended upto date of following sizes 6/1/2.59 mm for guarding
Removing & Restringing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases
Removing & Restringing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.
Removing 63KVA Distribution Transformer
Removing Old deteriorated DP Distribution Box
Removing of 3.5Cx 95Sqmm cable
Removing old deteriorated 11KV Horn Gap Unit
Removing old deteriorated GOAB Switch
Removing Old deteriorated structural Material
Removing 11KV Disc Insulator
B) Work of supply and erection of 1 no of 100KVA Distribution transformer Centre along with HT/LT line for improving the LT Distribution Network in villge of Chinchwada Pale, under the jurisdiction of Village Panchayat Pale- Cothambi, under the Sub Division-II(R ), Sankhali.
Erection of RCC pole 9.0 mtr as per the drawing No.CEE/E-698, REV-1 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982
Erection of RCC pole 11.0 mtr as per the drawing No.CEE/E-698, REV-1 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982
Erection of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A
Erection of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 11.0 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Erection of HDG 11KV "V" shape cross arm of channel ISMC 75 x 40 x 7.3mm as per gdr. No. CEE/E-408-R1
Erection of HDGI Top fitting X-arm channel 75X40,0.7mts long(4.74kgs)
Erection of HDGI Cut point channel 75X40X 6mm,1.3 mts long (8.84kgs)
Erection of HDGI Guard X-arm channel 75X40X 6mm,1.5mts long(10.2kgs)
Erection of 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the minimum creepage distance of 320mm conforming to IS 731-1971 as amended upto date. And forged GI pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS 731/71 as amended upto date. GI pin shall conform to reference S-165 N fig 5 of IS 2486/(part-II)/74 as amended upto date. Dimension X in said fig shall be 150mm (screwed 100mm). Pin shall be supplied along with one suitable GI hexagonal nut and GI spring washer. Minimum failing load of pin shall be 10 KN.
Erection of 11 Disc Insulators ball and socket type, A porcelain brown glazed duly cemented at factory with MCI socket cap, forged steel ball pin and supplied with Phosphor bronze "W" split pin as per IS 731-1971 as amended upto date. Minimum failing load 45 KN Pin ball diameter 16 mm. Minimum Creepage distance 320 mm with 2 bolted type hardware fitting 70KN suitable for 11 KV ball and socket type disc insulators of 16 mm pin, failing load of 70 KN and suitable for ACSR conductor of size upto 18 mm diameter. The metal parts shall be as per drg No CC/E-482-Rev-2 Benclosed and conform to IS-2486 part 1-1993, 2486 Part-2-1989 as amended upto date.
Erection of ACSR 'Weasel' conductor confirming ISI specification IS: 398 (part-1/96) as amended upto date of following sizes 6/1/2.59 mm for guarding
Erection of ACSR "Racoon Conductor confirming ISI specification as amended upto date of following sizes 6/1/4.09mm for three phases
Erection of Distribution Transformer 100 KVA 11/0.44 KVA Aluminium wound Star rated
Erection of MS Distribution box as per drg No. CEE/E-689 Revision No. 3 along with MCCB 200 A, Bus bar made out of Aluminium strips 40 x 10 mm,aluminium 'J' type fuse links (Set of 3) for 4 feeder arrangement with 1 no of moulded case circuit breaker (MCCB) of 200A, 415V, AC 50 Hz for 100 KVA Distribution Transformer centre
Erection of DTC metering unit with moderm
Erection of Single core XLPE Insulated PVC Sheathed cable 120sqmm 1.1kV grade
Erection of Three and half core armoured XLPE cable of size 95 Sq.mm cross linked polyethelene insulated, PVC shealthed 3.5 core 95 sqmm cable with galvanized steel strip armoured aluminium cable of 1100 volts grade suitable for 3 phase earthed system and conforming to IS: 7098 (Part-I)/1988 as amended upto date.
Erection of 11 KV , 200 A Horn gap fuse unit (Set of three) shall be as per enclosed drg No. CEE/E-786. Revision 3 and detailed specifications enclosed herewith.
Erection of 9 KV, 5 KA nominal discharge current metal oxide gapless distribution class Lightning arrestor conforming to IEC-600994-4 and IS: 3070 part 3 1993 as amended upto date suitable for 11 KV 50 HZ effectively earthed neutral system with necessary mounting arragements and connector suitable to connect ASCR conductor upto overall diameter 12.30 mm
Erection of 11 KV rated voltange GOAB switches tilting type, outdoor, manually operated, triple pole, single break, conforming to IS: 9921-Part 1 to V as amended up to date and detailed specification eclosed herewith. Each set shall comprise of six pedestal and three tilting post insulators. Insulator should be factory cemented by the manufacturer of the insulators and have minimum 320 mm creepage distance and AB switchs contacts shall be of copper/ copper alloy. The AB switch shall be of following current rating: 200 A
Erection of HDGI structure material for 12 DPS. Each trasformer centre DP consist of HDGI structure material as follows: a) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for incoming line & installation of disc insulators b) GI channel ISMC75x40x7.3mm 2.75mtrs long 2 pieces for GOAB switch c) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for HG fuses d) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for installation of lightening arrestor e) GI channel ISMC 100x50x7.3mm 2.75 mtrs long 2 pieces for installation of Trasformer f) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 2 pieces for side support of trasformer g) GI channel ISMC 75x40x7.3mm 2.75 mtrs long 4 pieces for installation of any other items h) GI channel ISMC 100x40x7.3mm 0.52 mtrs long 2 pieces for installation of Transformer base channel
Erection of HDG earthing pipe 8ft long 40mm. Dia. Class B fabricated & perforated including alternate layers of 30cms thick of charcoal,salt & earth( charcoal & salt 10kgs each per pit inclusive of excavation,bacfilling& spreading the earth evenly)
Erection of Enamelled danger boards 11000 Volts as per drg no. CEE/E-490
Erection of Anti climbing device alongwith suitable two stay clamps & two pairs of H.D.G.I nuts bolts as per drg No. CEE/E-478
Erection of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for11mtr Rcc pole
Erection of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 9mtr Rcc pole
Erection of HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-492 with clamp and nut bolt for 7.5 mtr Rcc pole
Erection of HDG L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 11 mtr Rcc pole
Erection of HDG L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 9 mtr Rcc pole
Erection of HDG L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491 with clamp and nut bolt for 7.5 mtr Rcc pole
Erection of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.
Erection of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN
Erection of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 9 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Erection of H.D.G.I. stay rod of 1200mm long & 16mm dia with an eye band of internal dia 40mm at one end & threaded up to length of 200mm at the other end, H.D.G.I. stay plate 450x450x8mm size with a hole for at the centre to suit above stay rod, H.D.G.I. stay wire of size 7/5.15mm (7/8SWG) conforming to IS-2141/1979 grade- I, IS:4826-1979 & IS:6594-1974 or latest version thereof with tensile grade 4 & having minimum tensile strenght of 700N/mm2, H.D.G.I. turn buckle made out of 16mm dia H.D.G.I. rod & H.D.G.I. angle of size ISA 50x50x6mm, eye bolt made out of 20mmdia H.D.G.I. rod with 40mm dia inner dia eye at one end & threaded up to 300mm lenght from other side, along with H.D.G.I. hexagonal nuts suitable for above rod , break insulator of 16KV & minimum failing load of 44KN, & along with suitable H.D.G.I. stay clamps suitable for 7.5 mts RCC pole, H.D.G.I. nut bolts & of specifications as specified in drg nos. CEE/E-797, CEE/E-466, CEE/E-524, CEE/E-523 & CEE/E-711
Erection of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases
Erection of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.
Removing of RCC pole 9 mtr as per the drawing No.CEE/E-565 REV-3 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982
Removing of RCC pole 7.5 mtr as per the drawing No.CEE/E-565 REV-3 as per annexure confirming to IS 785-1998 as amended upto date. The component used for pole shall conform to following IS amended up to date. 1) Ordinary Port land cement 53 grade IS 12269 2) Aggregate IS 383-1970 3) Torsteel IS 1786-7985 4) MS bar IS 432 p 1 & 2-1982
Removing HDG 11KV "V" shape cross arm of channel ISMC 75 x 40 x 7.3mm as per gdr. No. CEE/E-408-R1
Removing HDGI Top fitting
Removing 11 KV brown glazed porcelain Pin Insulator with minimum failing load of 5 KN and the minimum creepage distance of 320mm conforming to IS 731-1971 as amended upto date. And forged GI pin conforming to IS 2486 part 1 & 2 as amended upto date suitable for 11 KV glazed porcelain pin insulators conforming to IS 731/71 as amended upto date. GI pin shall conform to reference S-165 N fig 5 of IS 2486/(part-II)/74 as amended upto date. Dimension X in said fig shall be 150mm (screwed 100mm). Pin shall be supplied along with one suitable GI hexagonal nut and GI spring washer. Minimum failing load of pin shall be 10 KN.
Removing HDG L.T. 4 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491
Removing of HDG L.T. 2 pin cross arm Channel type made of ISMC 75x40x7.3mm as per drg No.CEE/E-491
Removing of LT brown glazed shackle Insulator of size 100 mm x 115 mm conforming to fig No. 4 and type 2 fo IS: 1445/77 as amended upto date. Minimum failing load shall be 16 KN with GI hardware suitable for LT shackle insulator of size 100 x 115 mm conforming to type 2 fig 4 of IS: 1445/77 as amended upto date. Hardware or fitting shall conform to fig 4 of IS: 7935-1975 as amended upto date comprise fo 2 GI strips, 2 GI bolts and 2 nuts with spring washers.
Removing of L.T. brown glazed porcelain pin insulators of size 100mmx70mm conforming to type 1 fig 1 of IS: 1445/1977 with amendment 2 of Feb 1981 (second revision) as amended upto date. Minimum failing load shall be 3.5 KN with Forged GI pin conforming to IS 7935/1975 as amended upto date suitable for LT porcelain pin insulator type 1 conforming to fig 1 of IS: 1445/77 with amendment no 2 feb 1981, of size 100 x 70 mm. GI pin shall comprise of GI nut and spring washer and conform to fig No 2 of IS: 7935/1975. Minimum failing load of pin shall be 3.5 KN
Removing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases
Removing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.
Removing & Restringing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/3.10 mm ANT conductor for phases
Removing & Restringing of AAC conductor hard drawn stranded all aluminium conductor conforming IS 398(Part-1/96) as amended upto date of following sizes 7/2.21 mm GNAT conductor for double neutral & guadings.
M/s. RAJA ELECTRICALS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .