Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.5 LAccepted-AOC MILITARY HOSPITAL ROAD UDHAMPUR 182101 J K | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹23.9 L+₹2.0 L (8.91%)Rejected-Finance WARD NO 1 HOUSE NO 04 SUBASH NAGAR UDHAMPUR 182101 J K | UDHAMPUR | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L2 | Rejected-Finance BEING L2 | |
| 3 | L3₹23.9 L+₹2.0 L (8.99%)Rejected-Finance GROUND FLOOR MH ROAD UDHAMPUR 182101 | UDHAMPUR | JAMMU AND KASHMIR | 182101 | L3 | Rejected-Finance BEING L3 | |
| 4 | L4₹24.0 L+₹2.1 L (9.44%)Rejected-Finance B 56 LANE NO 4A SECTOR 7 VASHNAVI ENCLAVE CHANNI HIMAT JAMMU 180015 | JAMMU | JAMMU AND KASHMIR | 180015 | L4 | Rejected-Finance BEING L4 |
| Sl No | Description | Qty | Unit | ANIKET TRADERS L4 | DAVINDER SINGH L2 | RANBIR ENTERPRISES L1 | M/S DHARAM & SONS ENTERPRISES L3 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, Installation and Fixing Floor Mounting MCC PANEL shall be OEM made out of GRP, Glass-fiber reinforced as per EN 14598-1-UP FR2 material with Protection class IP 66 in accordance with IEC 60529 and Color code RAL 7032 completely dyed in mass and box shall be made out of insulating, slow-burning and self-extinguishing composite (polyester + glass fiber) characterized with resistance to atmospheric agents (UV). Protection class II (EN 61140) when correctly installed on the base and Panel internal size should be not less than 800x600x300mm. GRP material shall be Anti-corrosive suitable for saline atmosphere and have ambient temperatures of -50°C up to +120°C, Flammability HB 40 a, b (EN 60695-11-10),V-1. Glow wire tested at 960°C/ 3 mm as per EN 60695-2-12. The dimensional stability under heat is more than 200 °C as per ISO 75 – 2 method A . The enclosure is Halogen-free, resistant to termites. GRP cabinet should withstand minimum Di-Electric strength of 130KV/Cm as per IEC 60243-1. FRP Not accepted. The Panel box shall have shall be equipped with GRP handle lock with THREE point locking mechanism and the provision to insert various type of locking cylinders provided to avoid unauthorized access. RoHS Directive (EU) 2015/863 (extension to directive 2011/65/EU),REACH Regulation (EC) no. 1907/2006. The Panel mounted on suitable MS Angle Stand Ground Clearance 450mm height and Copper Bus-bar with Heat Shrinkable Sleeves of capacity 100 Amp, wiring of Panel with suitable size of Copper Conductor Cable, Cable Glands , Thimbles, etc. having size of the Panel suitable for fixing the Items/Materials mentioned at here-in-below, complete all as specified and as directed . Make-Hensel/ABB/Siemens/Schneider.
Note :- (i) GRP Panel shall be build from OEM Only.
(ii) Switchgear & other items shall be purchased and installed by panel builder only. | 2 | Each Job | 2,80,000 ₹5,60,000 | 2,65,000 ₹5,30,000 | 2,90,000 ₹5,80,000 | 2,35,000 ₹4,70,000 Lowest |
| 1.01All as per item No 1.00 hereinbefore but (Location - SMC Bore Pump House, Air Force MT Pump House) | |||||||
| 1.02INCOMER: | |||||||
| 1.0363 Amp, 4 pole MCCB, 25 KA 415V Thermal & Magnetic Released with Spreader Links - 01 No, | |||||||
| 1.04Digital Multifunction Meter, Volt, Amp, Frequency, kW, kVA, Old energy, On and Run hours, Site Selectable kWh/kVAh (As per Description MFM 4405 LED meter Cl 1 Cat No WL4405100000 - 01 No. (Make : L&T or equivalent) | |||||||
| 1.05Set of three LED type indicating lamps-01 set (for each LT Panel) | |||||||
| 1.06OUTGOINGS: | |||||||
| 1.0750 Amp, MCCB TP 16 KA 415 V,with Spreader Links - 02 Nos. (LK Cat No. CM98944OOFO or equivalent. ) | |||||||
| 1.08Digital Soft Starter suitable for 20 HP motor, current Rating 28 to 32 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 01 Nos. ( Submersible Pump 20HP) Make ABB Cat No 30 APSR30-600-70 | |||||||
| 1.09MCB 40A TPN C-Curve Type - 2 Nos | |||||||
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
14 Jul 2026, 6:00 pmClosed
GE AF UDHAMPUR
GE (AF) STN UDHAMPUR
REPAIR / REPLACEMENT OF STAR/DELTA STARTER, LT PANEL, AVIATION LIGHT, DOZING PLANT AND ASSOCIATED E/M WORKS AT AF STN UDHAMPUR
2026_MES_772456_1
GEAFU-44/2026-27
Open Tender
Civil Works
Item Rate
180 days
GE (AF) STATION UDHAMPUR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE (AF) UDHAMPUR
₹50,000
25 Jul 2026
16 Jun 2026
16 Jul 2026
16 Jun 2026
14 Jul 2026
30 Jun 2026
16 Jun 2026 - 23 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation and Fixing Floor Mounting MCC PANEL shall be OEM made out of GRP, Glass-fiber reinforced as per EN 14598-1-UP FR2 material with Protection class IP 66 in accordance with IEC 60529 and Color code RAL 7032 completely dyed in mass and box shall be made out of insulating, slow-burning and self-extinguishing composite (polyester + glass fiber) characterized with resistance to atmospheric agents (UV). Protection class II (EN 61140) when correctly installed on the base and Panel internal size should be not less than 800x600x300mm. GRP material shall be Anti-corrosive suitable for saline atmosphere and have ambient temperatures of -50°C up to +120°C, Flammability HB 40 a, b (EN 60695-11-10),V-1. Glow wire tested at 960°C/ 3 mm as per EN 60695-2-12. The dimensional stability under heat is more than 200 °C as per ISO 75 – 2 method A . The enclosure is Halogen-free, resistant to termites. GRP cabinet should withstand minimum Di-Electric strength of 130KV/Cm as per IEC 60243-1. FRP Not accepted. The Panel box shall have shall be equipped with GRP handle lock with THREE point locking mechanism and the provision to insert various type of locking cylinders provided to avoid unauthorized access. RoHS Directive (EU) 2015/863 (extension to directive 2011/65/EU),REACH Regulation (EC) no. 1907/2006. The Panel mounted on suitable MS Angle Stand Ground Clearance 450mm height and Copper Bus-bar with Heat Shrinkable Sleeves of capacity 100 Amp, wiring of Panel with suitable size of Copper Conductor Cable, Cable Glands , Thimbles, etc. having size of the Panel suitable for fixing the Items/Materials mentioned at here-in-below, complete all as specified and as directed . Make-Hensel/ABB/Siemens/Schneider. ( NOTE : GRP Panel shall be build from OEM Only) | 2 | Each Job | - | - |
| 1.01 | All as per item No 1.00 hereinbefore but (Location - SMC Bore Pump House, Air Force MT Pump House) | - | - | - | - |
| 1.02 | INCOMER: | - | - | - | - |
| 1.03 | 63 Amp, 4 pole MCCB, 25 KA 415V Thermal & Magnetic Released with Spreader Links - 01 No, | - | - | - | - |
| 1.04 | Digital Multifunction Meter, Volt, Amp, Frequency, kW, kVA, Old energy, On and Run hours, Site Selectable kWh/kVAh (As per Description MFM 4405 LED meter Cl 1 Cat No WL4405100000 - 01 No. (Make : L&T or equivalent) | - | - | - | - |
| 1.05 | Set of LED type indicating lamps - 01 No | - | - | - | - |
| 1.06 | OUTGOINGS: | - | - | - | - |
| 1.07 | 50 Amp, MCCB TP 16 KA 415 V,with Spreader Links - 02 Nos. (LK Cat No. CM98944OOFO or equivalent. ) | - | - | - | - |
| 1.08 | Digital Soft Starter suitable for 20 HP motor, current Rating 28 to 32 Amps, with inbuilt protections, Start and Stop push buttons & Red (Trip) and Green (Run) indicating lamps mounted on panel door for each starter, - 01 Nos. ( Submersible Pump 20HP ) | - | - | - | - |
| 1.09 | MCB 40A TPN C-Curve Type - 2 Nos | - | - | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
TENDER44.pdf
Tender Documents • 1.43 MB
BOQ_864962.xls
BOQ • 1.78 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .