Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹39.2 LAccepted-AOC ASTBAL MOHALLA BANASAR BAGH ROAD PATIALA GATE SANGRUR 148001 | SANGRUR | SANGRUR | PUNJAB | 148001 | L1 | Accepted-AOC Low | |
| 2 | L2₹48.9 L+₹8.9 L (22.4%)Rejected-AOC 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L2 | Rejected-AOC High | |
| 3 | L3₹53.3 L+₹13.3 L (33.2%)Rejected-AOC | L3 | Rejected-AOC High |
Tender Value
₹59.9 L
EMD Value
₹1.1 L
Closing Date
27 Jan 2024, 6:00 pmClosed
CWE Chandimandir
CWE Chandimandir 134107
REPAIR AND MAINTENANCE OF DG SETS (LT) INCLUDING CONNECTED WORKS AND ITEMS UNDER GE (U) CHANDIMANDIR
2023_MES_629930_2
CWE/CHM(U)-77/2023-24
Open Tender
Civil Works
Item Rate
180 days
CWE Chandimandir
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
GE (U) Chandimandir
₹1.1 L
Yes
5 Mar 2024
5 Jan 2024
31 Jan 2024
5 Jan 2024
27 Jan 2024
13 Jan 2024
5 Jan 2024 - 10 Jan 2024
Amount
Servicing of DG Set 320 KVA capacity of Make- Kirloskar, taking down worn out replaceable parts such as fuel filters (Primary and secondary) wth 'O' rings assy, by pass filter wth 'O' rings assembly, lub oil filter wth 'O' rings assembly, air cleaner filters,water separators filters, lub oil flexible pipe, hose turbo, clamps , painting of parts and body with suitable matching colour etc and replacing the same with same size, make and capacity of parts, including testing of DG Set to entire satisfaction of Engr-in Charge.
Note:- (i) Spare parts shall be measured and paid for saperately under respective items here in after. (ii) Servicing shall be carried out by OEM or authorised agent of manufacturer as approved by GE.
Supply only Fuel filter assembly wth 'O' rings for 320 KVA capacity DG set
Supply onlyLube oil filter assembly wth 'O' rings for 320 KVA capacity DG set
Supply only Bypass filter assembly wth 'O' rings for 320 KVA capacity DG set
Supply only water separator wth 'O' rings for 320 KVA capacity DG set
Supply only Air cleaner element set for 320 KVA capacity DG set
All as per item No 1 here-in-before but 200 KVA capacity DG set.
Supply only Fuel filter assembly wth 'O' rings for 200 KVA capacity DG set.
Supply onlyLube oil filter assembly wth 'O' rings for 200 KVA capacity DG set.
Supply only Bypass filter assembly wth 'O' rings for 200 KVA capacity DG set.
Supply only water separator wth 'O' rings for 200 KVA capacity DG set.
Supply only Air cleaner element set for 200 KVA capacity DG set.
All as per item No 1 here-in-before but 180 KVA capacity DG set.
Supply only Fuel filter assembly wth 'O' rings for 180 KVA capacity DG set.
Supply onlyLube oil filter assembly wth 'O' rings for 180 KVA capacity DG set.
Supply only Bypass filter assembly wth 'O' rings for 180 KVA capacity DG set.
Supply only water separator wth 'O' rings for180 KVA capacity DG set.
Supply only Air cleaner element set for 180 KVA capacity DG set.
All as per item No 1 here-in-before but 166 KVA capacity DG set.
Supply only Fuel filter assembly wth 'O' rings for 166 KVA capacity DG set.
Supply onlyLube oil filter assembly wth 'O' rings for 166 KVA capacity DG set.
Supply only Bypass filter assembly wth 'O' rings for 166 KVA capacity DG set.
Supply only Air cleaner element set for 166 KVA capacity DG set.
All as per item No 1 here-in-before but 125 KVA capacity DG set.
Supply only Fuel filter assembly wth 'O' rings for 125 KVA capacity DG set.
Supply onlyLube oil filter assembly wth 'O' rings for 125 KVA capacity DG set.
Supply only Bypass filter assembly wth 'O' rings for 125 KVA capacity DG set.
Supply only water separator wth 'O' rings for 125 KVA capacity DG set.
Supply only Air cleaner element set for 125 KVA capacity DG set.
All as per item No 1 here-in-before but 100 KVA capacity DG set.
Supply only Fuel filter assembly wth 'O' rings for 100 KVA capacity DG set.
Supply onlyLube oil filter assembly wth 'O' rings for 100 KVA capacity DG set.
Supply only Bypass filter assembly wth 'O' rings for 100 KVA capacity DG set.
Supply only Air cleaner element set for 100 KVA capacity DG set.
All as per item No 1 here-in-before but 20/30 KVA capacity DG set.
Supply only Fuel filter assembly wth 'O' rings for 20/30 KVA capacity DG set.
Supply onlyLube oil filter assembly wth 'O' rings for 20/30 KVA capacity DG set.
Supply only Bypass filter assembly wth 'O' rings for 20/30 KVA capacity DG set.
Supply only Air cleaner element set for 20/30 KVA capacity DG set.
Disconnecting and taking down the defective self starter of any make from the DG set , dismantling the same to take out defective parts and repairing by replacement of carbon brushes, armature coil, field coil, bush, bearings and bendix pinion, clutch assembly and other related components, reassembling & shifting to original location, refixing on the DG set , making all connections and testing for smooth functioning complete all as directed for DG set of capacity 20 KVA to 125 KVA.
Note :- Self starter of same type and capacity shall be arranged by the contractor and fixed at the DG set for the duration the original one is under repairs. Unit rate quoted will be deemed to include the expenditure for the same and no extra payment shall be made on this part.
All as per item No 40 here-in-before but capacity 160 KVA to 200 KVA.
All as per item No 40 here-in-before but capacity 320 KVA.
Supply and replacement of Automatic Voltage Regulator ( AVR ) Diode forward and reverse, rotating rectifier assembly, half wave phase controlled thyristor type, complete all as per existing type & size for the 20 KVA to 125 KVA capacity of DG set complete all as specified.
All as per item No 43 here-in-before but capacity 160 KVA to 200 KVA.
All as per item No 43 here-in-before but capacity 320 KVA
Disconnecting and taking down the leaking radiator from DG set engine for repairs , cleaning the complete radiator for detecting the leakage and repairing the leaking portion (Tubes/fins/tank etc) by soldering/brazing ,cleaning of all water tube with suitable cleaning agent & water preasure & removing the complete sludge and dust from inside the tank, replacing worn out hose pipes & clamps etc, shifting & refixing at original site and testing for proper working complete all directed for 20 KVA to 125 KVA capacitiy of DG set.
All as per item No 46 here-in-before but capacity 160 KVA to 200 KVA.
All as per item No 46 here-in-before but capacity 320 KVA.
Disconnecting and taking down the defective dynamo from the DG set engine for repairs, strip opening to remove unserviceable parts, repairing by replacing of armature coil, carbon brush, field coil, clutch patti bearing, refixing magnetic steel laminates, replacing pole head and pole shoe, bearing of shaft ball/roller/sleeve type and other related items, of assembly, re-assembling and refxing the same on original position and testing complete for 20 to 125 KVA DG set complete all as specified.
All as per item No 49 here-in-before but capacity 160 KVA to 200 KVA.
All as per item No 49 here-in-before but capacity 320 KVA.
Material & Labour for opening the tappet covers of the engine of the DG set of capacity 20 KVA to 125 KVA of any make and carry out repair works such as checking and adjustment of tappet clearance, cleaning piston and cylinder heads by removing carbon deposits , checking general condition of the engine, checking and adjustment of operating parammeters, checking and adjustment of fuel timings, checking and adjustment of fault warning system, checking & tightening of various fasteners and connections, refixing the tappet covers incl replacing the worn out gaskets/ nuts/ bolts/ washers etc complete all as directed.
All as per item No 52 here-in-before but capacity 160 KVA to 200 KVA.
All as per item No 52 here-in-before but capacity 320 KVA.
Material and labour of overhauling of injecter nozzles including replacement of nozzles, washers, etc and pressure setting as required and replacement of timing shaft with coupling all as directed by Engineer-in-charge for DG set of capacity 20 KVA to 125 KVA
All as per item No 55 here-in-before but capacity 160 KVA to 200 KVA.
All as per item No 55 here-in-before but capacity 320 KVA.
Disconnecting and taking down the fuel pump from the DG engine and repair & calibration of FIP of flollowing DG Sets including replacement of plungers, washer manifold, injection nozzles etc all as required and testing after refixing on engine and setting the rated RPM all as specified and directed for 20 KVA to 125 KVA capacity DG set.
All as per item No 58 here-in-before but capacity 160 KVA to 200 KVA.
All as per item No 58 here-in-before but capacity 320 KVA.
M&L for draining out the engine oil from the sump, opening the sump cover cleaning properly to remove old oil stocked to the surfaces, replacing the worn out gaskets/nuts/bolts/washers & refixing the sump cover complete all as directed for 20 KVA to 125 KVA capacity DG set engine complete all as directed.
All as per item No 61 here-in-before but of capacity 160 KVA to 200 KVA
All as per item No 61 here-in-before but of capacity 320 KVA
Supply & filling engine oil grade 15W/40 premium grade complete all as directed. Make: Servo/ Shell/ Castrol/ HP or equivalent approved by GE.
Supply and filling distilled water for filling in batteries for top up complete all as specified and as directed.
M&L for draining out old coolant from the engine radiators of DG Sets of any capacity and make, flushing the radiator tubes with distilled water and finally with new coolant, refixing the drain plug properly and filling the complete radiator with new pre mixed coolant complete all as specified and as directed. Make: Servo/HP/Castrol or equivalent approved by GE
Supply and fixing in repairs heavy duty copper cable battery leads (as per sample approved by GE ) compete all as specified and as directed.
Supply and fixing in repairs heavy duty brass terminals (as per sample approved by GE) suitable for battery terminals compete all as specified and as directed.
M & L for cleaning of in-built diesel tanks of 320 KVA capacity DG set by emptying the tank using suction pump of suitable capacity, washing the internal walls & bottom with diesel to remove any dust / deposits etc complete all as specified and as directed.
All as per item no. 69 here in before but 125 KVA to 200 DG set.
All as per item no. 69 here in before but 20 KVA to 100 KVA DG set.
M&L for reparing the doors of sound proof encouser of 20 KVA to 100 KVA DG Set for proper closing and locking using new SS hinges/door handles / in built locks complete all as per existing and as directed.
All as per item No 72 above but 125 KVA to 200 KVA DG set
All as per item No 72 above but 320 KVA DG set
Supply & Fixing in replacement change over switch, 400 Amp capacity, 3 phase, 4 pole, 415 volts, 50Hz,front handle operated, with and including MS sheet metal enclosure having advance neutral complete all as specified and as directed.
Supply & Fixing in replacement, LED indicator lamp assembly red, yellow, blue complete all as specified and as directed.
Supply and replacing V belt set ( for fan & alternator) for 20 KVA to 100 KVA DG set engine of make Kirloskar etc all as per existing complete all as specified and directed.
All as per item No 77 above but 125 KVA to 200 KVA DG set
All as per item No 77 above but 320 KVA DG set
Supply & Fixing in replacement, digital type 3 phase ammeter/voltmeter of size 96x96mm complete all as specified and as directed. Make : AE/ Schnieder/ Legrand or equivalent approved by GE
Supply & Fixing in replacement lead acid battery 12 volts 180 AH complete all as specified and as directed. Make : Exide/ TATA GREEN/ Amaron or equivalent approved by GE
Supply & Fixing in replacement lead acid battery 12 volts 130 AH complete all as specified and as directed. Make : Exide/ TATA GREEN/ Amaron or equivalent approved by GE
Supply, laying, jointing and testing LT underground cable XLPE insulated, PVC sheathed, armoured heavy duty 1100 volts grade with multistranded aluminium conductor of size 400 sqmm 3.5 core in trenches/duct etc including taking out old unserviceable cable complete all as specified and as directed.
All as per item No 83 above but 300 sqmm 3.5 core
All as per item No 83 above but 240 sqmm 3.5 core
All as per item No 83 above but 185 sqmm 3.5 core
All as per item No 83 above but 95 sqmm 3.5 core
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits,manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth in any type of soil and getting out complete all as specified and as directed. Note: Nothing extra will be paid or measured to the contractor if hard or rocky soil is encountered during execution .
Returning, filling in soils, in trenches, including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified and as directed
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed. Note: Nothing extra will be paid or measured to the contractor if hard or rocky soil is encountered during execution .
S& F in replacement Double wall corrugated HDPE duct pipe of 150 mm outer dia conforming to IS:14930 Pt-II with antirodant and non flame propergating properties of make and colour as approved by Engineer-in-Charge with fittings as protection to cable, laid in tranches or fixed to poles/walls complete with and including taking up/ down old damaged pipe and removing from site of work complete all as directed.
M & L for disconnecting of burnt out cables from panels , cutting out the burnt out ends , making new end joints by supply and fixing new aluminium lugs/insulation tapes etc and reconnecting using new nuts/bolts/washer etc complete all as directed for LT underground armoured cable of size 400 sqmm 3.5 core.
All as per item No 92 above but 300 sqmm 3.5 core
All as per item No 92 above but 240 sqmm 3.5 core
All as per item No 92 above but 185 sqmm Sqmm 3.5 core
All as per item No 92 above but 95 sqmm Sqmm 3.5 core
S&F in replacement, MCCB, four pole, 400 Amp 415 volts, 50 Hz breaking capacity not less than 36 kA with thermal magnetic release, adjustable thermal and adjustable magnetic setting with spreader links, Ics = 100% of Icu complete all as specified and as directed.
All as per item No 97 here-in-before but four pole, 250 Amp breaking capacity not less than 36 kA
All as per item No 97 here-in-before but four pole, 160 Amp breaking capacity not less than 25 kA with adjustable thermal and fixed magnetic setting
S&F in replacement, battery charger with auto cut off indicater suitable for 2x12 volts DC complete all as specified and as directed.
S&F in replacement, speed controller board suitable for 320 KVA DG set as per existing make and model complete all as specified and as directed.
M&L earthing complete with galvanized steel plate electrode 60cmx60cmx6mm surrounded by charcoal & salt buried directly in a pit of depth not less than 2.25m below ground level with top edge of the earth plate at a depth of not less than 1.50m below ground level, connected to and including GI srtip 32x6mm. upto 7.5m length by means of bolts, nuts, check nuts & washers of galvanized iron, earth wire protected by galvanized steel pipe 15mm bore (medium grade) & connected to main control board including necessary excavation & earth work, disposal of surplus soil not exceeding 50m, in any type of soil. (The rate also includes for cost of charcoal & salt in alternate layers of 15 cm thickness, 20 mm bore GI pipe (medium grade) for watering, funnel, wiremesh, PCC chamber in cement concrete (1:2:4) type B-1, CI cover & frame etc) complete all as indicated in electric plate No 3 of SSR 2009 Part I including testing complete all as specified and as directed.
Note- (i) Earthing result/data sheet will be prepared by the Contractor and submitted to Engineer-in-charge. Earth resistance shall be to the entire satisfaction of engineer-in-charge and contractor will make all arrangements & provisions to get the desired reduction of resistance by artificial treatment/replacement of soil etc at no extra cost to department.
Attending defective/ non functional DG Set complaints of capacty 20 KVA to 320 KVA (all type of error/fault alarms displayed on screen of the control panel/in case of stopage of DG set) by service engineers/technically qualified teams from respective OEMs for rectify the defects by made adjustments/settings in control panel, repairing and/ or replacing the defective parts/electrical items of any type as per existing, checking of connections, testing and DG Set should working in good conditions etc complete all as specified and as directed.
Notes :- (a) On receiving of complaint, it should be attended by service Engineer /rep of OEM within 2 Hrs, if not attended penalty @ Rs 500 per hour will be recovered from contractor. Failure on the part of contractor to make the DG Set functional on very same day after receipt of complaint penalty @ Rs 3000 per day will be recovered from contractor. (b) All type of T & P, minor nuts/bolts/washers etc required for maintaining the services shall be provided by the contractor without any extra cost to department. (c) All connected defects rectification/diagnosed associated with one fault shall be measured as one job and no extra cost shall be be paid to the contractor.
M/L for Shifting of 20 KVA to 320 KVA Kirloskar Green Canopy type DG Set complete with all its attachments (by dismantling and refixing of its sensitive parts as required) using suitable mechanical pulling / lifting devices / cranes etc from its original location and relocating to a new position within 1 KM by disconnection of its power supply cables from its existing location and reconnection at new location by providing all requisite connection materials and all as directed by Engr-in-charge.
Supply & fix in replacement MCB, Single Pole, 6-32 Amps suitable for existing (make & model) DG set AMF Panels complete all as specified and as directed.
Servicing of AMF panel of DG set 320 KVA of capacity installed at CMS by cleaning the complete panel with suitable cleaning agent and checking the controller relays, timer, contactors for proper functioning, replacing defective spare parts, replacement of defective small wires of existing size, tightening of all connections and applying jelly on contactors complete all as specified and directed by Engineer-in-Charge:-
Note : (i) Spare parts as required will be measured and paid separately as 'Supply Only' Here-in-after. (i) cost of small wires shall be included in the quoted rate. Nothing extra on this account shall be paid to contractor. (iii) Earth work including hardstanding like grouting with nuts, bolts and washers , trenching & PCC for erecting/shifting the panel if need will be included in the unit rate.
Supply Only 4 pole contactor 550 Amps, suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only bus bar suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only auto changeover suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only volt meter suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only ammeter suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only AMF Logic controller relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Control relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Timer complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Battery Charging Unit 12 / 24 Volts complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Auto / Manual switch complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Start/stop push button complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only HRC fuse unit 630A, 415V complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 320 KVA, 3 Phase, 415 Volts, 50 Hz.
Servicing of AMF panel of DG set 180-200 KVA of capacity installed at CMS by cleaning the complete panel with suitable cleaning agent and checking the controller relays, timer, contactors for proper functioning, replacing defective spare parts, replacement of defective small wires of existing size, tightening of all connections and applying jelly on contactors complete all as specified and directed by Engineer-in-Charge:-
Note : (i) Spare parts as required will be measured and paid separately as 'Supply Only' Here-in-after. (i) cost of small wires shall be included in the quoted rate. Nothing extra on this account shall be paid to contractor. (iii) Earth work including hardstanding like grouting with nuts, bolts and washers , trenching & PCC for erecting/shifting the panel if need will be included in the unit rate.
Supply Only 4 pole contactor 400 Amps, suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only bus bar suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only auto changeover suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only volt meter suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only ammeter suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only AMF Logic controller relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Control relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Timer complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Battery Charging Unit 12 / 24 Volts complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Auto / Manual switch complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Start/stop push button complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only HRC fuse unit 315A, 415V complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 180-200 KVA, 3 Phase, 415 Volts, 50 Hz.
Servicing of AMF panel of DG set 125 to 166.25 KVA of capacity installed at CMS by cleaning the complete panel with suitable cleaning agent and checking the controller relays, timer, contactors for proper functioning, replacing defective spare parts, replacement of defective small wires of existing size, tightening of all connections and applying jelly on contactors complete all as specified and directed by Engineer-in-Charge:-
Note : (i) Spare parts as required will be measured and paid separately as 'Supply Only' Here-in-after. (i) cost of small wires shall be included in the quoted rate. Nothing extra on this account shall be paid to contractor. (iii) Earth work including hardstanding like grouting with nuts, bolts and washers , trenching & PCC for erecting/shifting the panel if need will be included in the unit rate.
Supply Only 4 pole contactor 400 Amps, suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only bus bar suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only auto changeover suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only volt meter suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only ammeter suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only AMF Logic controller relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Control relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Timer complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Battery Charging Unit 12 / 24 Volts complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Auto / Manual switch complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Start/stop push button complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only HRC fuse unit 315A, 415V complete assembly or suitable for existing (make & model) AMF Panel of DG Set cap 125-166.5 KVA, 3 Phase, 415 Volts, 50 Hz.
Servicing of AMF panel of DG set 100 KVA of capacity installed at CMS by cleaning the complete panel with suitable cleaning agent and checking the controller relays, timer, contactors for proper functioning, replacing defective spare parts, replacement of defective small wires of existing size, tightening of all connections and applying jelly on contactors complete all as specified and directed by Engineer-in-Charge:-
Note : (i) Spare parts as required will be measured and paid separately as 'Supply Only' Here-in-after. (i) cost of small wires shall be included in the quoted rate. Nothing extra on this account shall be paid to contractor. (iii) Earth work including hardstanding like grouting with nuts, bolts and washers , trenching & PCC for erecting/shifting the panel if need will be included in the unit rate.
Supply Only auto changeover suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only display digital meter (with volt & ammeter meter) suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only AMF Logic controller relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Control relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Timer complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Battery Charging Unit 12 / 24 Volts complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Auto / Manual switch complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Start/stop push button complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only CT unit, class-1 (200/5A ratio ) complete assembly or suitable for existing (make & model) AMF Panel of DG Set cap 100 KVA, 3 Phase, 415 Volts, 50 Hz.
Servicing of AMF panel of DG set 30 KVA of capacity installed at CMS by cleaning the complete panel with suitable cleaning agent and checking the controller relays, timer, contactors for proper functioning, replacing defective spare parts, replacement of defective small wires of existing size, tightening of all connections and applying jelly on contactors complete all as specified and directed by Engineer-in-Charge:-
Note : (i) Spare parts as required will be measured and paid separately as 'Supply Only' Here-in-after. (i) cost of small wires shall be included in the quoted rate. Nothing extra on this account shall be paid to contractor. (iii) Earth work including hardstanding like grouting with nuts, bolts and washers , trenching & PCC for erecting/shifting the panel if need will be included in the unit rate.
Supply Only 4 pole contactor ,MCX-11 suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only auto changeover suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only display digital meter (with volt & ammeter meter) suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only AMF Logic controller relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Control relay complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Timer complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Battery Charging Unit 12 / 24 Volts complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Auto / Manual switch complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only Start/stop push button complete assembly suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only HRC fuse unit 32A, 415V complete assembly or suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Supply Only CT unit, class-1 (100/5A ratio ) complete assembly or suitable for existing (make & model) AMF Panel of DG Set cap 30 KVA, 3 Phase, 415 Volts, 50 Hz.
Material and labour for repair, repalcement, dismatling, re-assembling, overhauling and shifing to and from workshop at site if need of DG set engine capacity 200KVA to 320 KVA including replacement of following spare parts and all connected works all as directed by Engineer-in-charge.
Note: Spare parts as required will be measured and paid separately as 'Supply Only' Here-in-after. Minor spares except these items like nut,bolts, washers,wiring, PCC, grouting etc will be included in the unit rate.
Supply Only Cylinder Liner Assembly suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Piston Assembly suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Crankshaft Assembly With Gear suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Bearing C/R suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Supply Only Bearing Bush S/E suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Cylinder Head Gasket suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Joint For Rocker Cover suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Valve Seat Insert (Inlet) suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Valve Seat Insert (Exhaust) suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Inlet And Exhaust Valve Pair suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Valve Seal. suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Valve Guide. suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Valve Collet.(Pair) suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Thermostat Element(74 Deg) suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Joint For Inlet Manifold suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Joint For Exhaust Manifold suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz..
Supply Only Set Of 'O' Rings suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz..
Supply Only Set Of Copper Washers .suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only K Sealent suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Flex.Hose For Vent suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Rubber Hoses suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only T-Bolt Clamp Jupiter suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Hose For Thermostat To Water Tank suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Rubber Hose(Compressor Outlet) Turbo suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Worm Drive Clamp ( Jupitor Jw7B13, 29 To 45 Dia) suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Sub Assembly Of Vent Pipe suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Banjo Bolt - M14X1.5 suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Banjo Bolt.(Hollow Bolt) suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Supply Only Rubber Hose For Main Air Pipe suitable for existing (make & model) DG set Engine, 3 Phase, 415 Volts, 50 Hz.
Material and labour for winding of rotor and exciter coil in replacment of DG set alternator capacity 200KVA to 320 KVA alongwith repairing, dismatling, reassembling, overhauling and shifing to and from workshop at site including all connected works all as directed by Engineer-in-charge. Note: Minor spares items like nut,bolts, washers,wiring, PCC, grouting etc will be included in the unit rate.
R D Bansal
M/S W R traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .