Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.4 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹5.5 L+₹8,170 (1.52%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹5.8 L+₹40,535 (7.53%)Rejected-Finance | L3 | Rejected-Finance L3 | |
| 4 | L4₹6.8 L+₹1.4 L (25.9%)Rejected-Finance NULL | L4 | Rejected-Finance L4 | |
| 5 | L5₹7.7 L+₹2.3 L (43.2%)Rejected-Finance 2817 20 GURU NANK AUTO MKT KASHMERI GATE DELHI 6 | L5 | Rejected-Finance L5 |
Tender Value
₹7.3 L
EMD Value
₹15,750
Closing Date
4 Nov 2022, 11:00 amClosed
Ex. Engineer(Elect.)/CNZ
C-Block Defence Colony, New Delhi 110024
Provision of Lighting arrangement by Poles and SHM ( along with fittings) at Pet Park under Jungpura Flyover in ward no. 58-S Under Central Zone.
2022_SDMC_133730_1
EE(Elect.)/CNZ/2022-23/70-01
Open Tender
Electrical Works
Item Rate
90 days
C-Block Defence Colony, New Delhi
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
₹15,750
6 Feb 2024
28 Oct 2022
4 Nov 2022
28 Oct 2022
4 Nov 2022
28 Oct 2022
Amount
Supplying & drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required .(a) 3x2.5 sqmm
Supplying & drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/PVC conduit as required .(a) 5x2.5 sqmm
Earthing with GI earth pipe 4.5 metre long ,40 mm dia including accessories,and providing massonary encloser with cover plate having locking arrangement and watering pipe etc. (but without charcoal /cock and salt as required.)
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of following size in the existingRCC/HUME/METAL pipe as required. Up to 35 sqmm
Laying of one number PVC insulated and PVC sheathed/XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Up to 35 sqmm
Supplying and fixing of light class GI pipe of 50 mm dia (nominal) 3 meters length along the pole for protection of under ground cable as required.
S/L of following size DWC HDPE Pipe ISI marked along with all accessories like socket ,bend ,couplers etc.conforming to IS 14930 ,part II complete with fitting and cutting ,jointing etc .direct in ground (75 cm below ground level )including excavation and refilling the trench but excluding sand cushioning and protective covering etc, complete as required (a)63mm dia (OD-63mm ID -51mm nominal ).
Supply of XLPE insulated, PVC sheathed Al. Conductor Armoured cable 1.1 KV grade confirming to IS-7098 of following Size (a) 2 X 10 Sq. mm
Fabrication,supply & errection of following size flange mounted hot dip galvanized octagonal pole made from HT steel plate, window with flash cover with full vertical window cover at appropriate hight from the base plate on existing cement concrete pedestal as required. i/c supplying and fixing of 6 mm thick laminated mounted sheet inside the window mounted on and i/c providing and welding 3 nos. G.I strips 4 mm thick of suitable length and having suitable size tapped holes as reqd., terminal block suitable for 25 sqmm conductor-4 nos & shorting links on DIN channel i/c pdg and fixing DIN channel of suitable lenth,6 amps SP MCB "c" characteristics,earth stud,cable support clamp suitable for upto 4x25 sqmm cable. Logo/Name of manufacturer shall be embossed on the pole. Galvanization as per relevant IS.( a) 5.o mtr. hight,3 mm thick,bottom dia of 130 mm & top dia of 70 mm, base plate of size 225 mm x 225 mm x 12 mm thick.
Providing and laying in position M25 grade reinforced cement concrete foundation of size 450 mm (L)x450 mm wide and 1000 deep i/c excavation of earth, providing cutting, bending and placing in position, reinforcement of cold twisted bars of 12 mm dia- 960 mm long (approx)-8 nos . and reinforcement of cold twisted bars of 8 mm dia 1400 mm (approx) - 6 nos. (with 150 mm spacing) as required with supplying and positioning of 4 no. foundation bolts of size 16 mm dia ,600 mm long, J type i/c 2 nos. template anchor plates of size 225 mm X 225 mm X 3 mm and providing 63mm dia DCW, HDPE for cable entry and exit as required for 5 mtr pole.
Fabrication, supplying and fixing class B galvanised single overhang arm bracket made out of 250 mm long galvanized top tube with cap and 1000 mm long 32 mm dia galvanised pipe with tightening bolts complete as required.
Providing and Laying of HDPE pipe of 40 mm outer dia with PN 4 rating by Hand moling/ Mannual method confirming to IS 4984.
Fabrication,Supplying,Installation,testing,Commissioning of 12 mts.high mast System with its accessories ,Mast shaft shall be in one section , hot dip galvanized 4mm thick (Single dip ) inside and out sides and suitable for wind velocity as per IS 875 part3 .There shall be in longitudinal seam weld per section and No circufrential weld. It should also included accessories for High Mast head frame ,2 point suspension system with steel wire rope 5mm dia. (7/19construction) single drum winch ,galvanized lantern carriage arrangement suitable for 4/6 Nos. flood light luminaries luminaries symmitrically and its control gears boxes and lighting finial ,the mast shall have integral type manual tool mounted at the base compartment of its raising and lowering operation with foundation bolts and Anchor plate and control panel housing suitable RCC (1:2:4) shallow foundation of size 1m(L)X1m (W)X2m deep i/c excavation of earth i/c excavation of earth, providing cutting, bending and placing in position, rewinforcement of cold twisted bars of 12 mm dia -2100 mm long (approx.) - 16 nos.and reinforcement of cold twisted bar of 8 mm dia - 3700 mm (approx.) - 13 nos. (with 150 mm spacing) as required with positioning of 4 nos foundation bolts and providing DWC HDPE pipe for cable entry & exit as required for high mast considering. The safe soil bearing capacity at site as 10T/sqm at 2mts. Depth with all material i/c, 4Nos S.P MCB, 63Amp.DPIsolator etc as reqd. Logo/Name of manufacturer shall be embossed on the pole. galvanized as per relevant IS.
Supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size25mmx75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh and grounding the protection system in suitable quality of CC etc as reqd.
SHRIRAM SHARMA
A.J ENTERPRISES
S.N. Enterprises
KHANNA SALES CORPORATION
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .