| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹20.2 LAccepted-AOC | L-1 | Accepted-AOC Lowest Bidder | |
| 2 | L-2₹26.3 L+₹6.2 L (30.5%)Rejected-Finance | L-2 | Rejected-Finance Other than lowest bidder | |
| 3 | L-3₹31.9 L+₹11.8 L (58.3%)Rejected-Finance | L-3 | Rejected-Finance Other than lowest bidder | |
| 4 | L-4₹32.6 L+₹12.4 L (61.6%)Rejected-Finance | L-4 | Rejected-Finance Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹73,600
Closing Date
16 Aug 2023, 6:00 pmClosed
GE Jammu
GE Jammu c/o 56 APO Pin-900277
CERTAIN SPECIAL REPAIRS OF E/M NATURE AT MIRAN SAHIB UNDER GE JAMMU
2023_MES_610121_1
GEJC-55/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AoR of GE Jammu
Please refer Tender Documents
8 documents required · 8 mandatory
₹500
GE Jammu
₹73,600
Yes
13 Sept 2023
21 Jul 2023
18 Aug 2023
21 Jul 2023
16 Aug 2023
4 Aug 2023
Amount
Taking out existing unserviceable / old steel / mild steel angle iron frame of any size from the wall by dismantling bricks and making the surface good complete with brick works, plaster, white wash, patch work matching with existing colour complete all as specified and directed.
Taking out serviceable electric meter from the panel board after disconnecting all incoming / outgoing connection carefully and refixing the same in position complete all as specified and directed.
Material and labour for replacement distribution board sheet steel powder coated for MCB with copper bus bar and neutral link earthing stud SPN 12 way 240 volts double door complete all as specified and directed by Engineer-in-Charge. Note: - Distribution board and MCB's should be of same make.
Material and labour for replacement distribution board sheet steel powder coated for MCB with copper bus bar and neutral link earthing stud SPN 8 way 240 volts double door complete all as specified and directed by Engineer-in-Charge. Note: - Distribution board and MCB's should be of same make.
Material and labour for replacement of distribution board sheet steel powder coated for MCB with copper bus bar and neutral link earthing stud SPN 4 way 240 volts double door complete all as specified and directed by Engineer-in-Charge. Note: - Distribution board and MCB's should be of same make.
Material and labour for replacement of distribution board double door sheet steel phosphatised powder painted for MCB / DB with copper bus bar and neutral link earthing stud TPN 4 way 415 volts double door complete all as specified and directed.
Supply and fixing in replacement of Vertical Distribution Board (TP&N) 4 way double door suitable for and including MCCB 125 Amp 16 KA four pole as incomer and outgoing MCB's and should be IP 43 protected with copper bus bars, neutral links, earthing bar including taking down old unserviceable DB / MCB any type complete all as specified and directed. Notes: - (i) Rate includes MCCB four pole 125 Amp, 16 KA, 415 volts with adjustable thermal settings. (ii) MCB's shall be measured and paid separately. (iii) TPN DB and MCCB should be of same make.
Supply and fixing in replacement of MCCB 4 pole, 415 Volt fixed thermal and fixed magnetic setting of capacity 125 Amps, 16 KA complete all as specified and directed.
Supply and fixing in replacement 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 Amp, in the MCB DB complete with connection, testing and commissioning complete all as specified and directed.
Supply and fixing in replacement 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 40 Amp, in the MCB DB complete with connection, testing and commissioning complete all as specified and directed.
Supply and fixing in repair for SPN 32 Amp rating 240V, 10 KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection, testing and commissioning complete all as specified and directed.
Supply and fixing in repair for SPN 40 to 63 Amp rating 240V, 10KA 'B' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection, testing and commissioning complete all as specified and directed.
Supply and fixing in repair for 415V 10KA 'B' curve TPN 100 Amp miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection, testing and commissioning complete all as specified and directed.
Material and labour in replacement for sub main wiring with proper colour coding, insulated, unsheathed, multistranded, copper conductor FRLS, cable of 2 run 6 Sqmm for phase and neutral and one run of 6.0 Sqmm for earth wire unsheathed, multistranded, copper conductor FRLS, drawn through the existing rigid PVC concealed conduit fixed on wall. Two runs of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length complete all as specified and directed. Note: - Wiring shall be done in proper colour coding.
Material and labour in replacement for sub main wiring with proper colour coding, insulated, unsheathed, multistranded, copper conductor FRLS, cable of 2 run 4 Sqmm for phase and neutral and one run of 4.00 Sqmm for earth wire unsheathed, multistranded, copper conductor FRLS, drawn through the existing rigid PVC concealed conduit fixed on wall. Two runs of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length complete all as specified and directed. Note: - Wiring shall be done in proper colour coding.
Supply and fixing in replacement of PVC enclosure DP complete with MCB SPN 32 Amp, 10 KA, 230 volt including taking down old one complete all as specified and directed.
Supply and fixing in replacement of sheet steel cable and box (bus bar) 4 way 440 volt, 50 Hz single door with 200 Amp rated bus bar mounted on insulator including taking down old one complete all as specified and directed.
Excavating in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation of poles, taking out / laying of cables, poles etc and getting out in soft / loose soil complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick in soft / loose soil complete all as specified and as directed.
Removing excavated materials not exceeding 50 metre and depositing where directed at a level not exceeding 1.5 metre above the starting point in soil complete all as specified and as directed.
Supply and laying including replacement of well burnt bricks, sub class 'B' bricks, laid breadth wise in trenches for protection of underground cable complete all as specified and directed.
Material and labour for sand cushioning for protection of cable (below, above and around the cable laid in trenches) complete all as specified and directed.
Supply and fixing in repair for GI tube light grade 40 mm bore laid in trenches / road / drain / wall alongwith all fittings complete with mild steel clamp and nut bolts and washers etc, including taking down old GI tubing alongwith all fixing accessories complete all as specified and directed.
Supply and laying in trenches, fixing or passing through pipe, fixed to wall/pole, connecting and testing including replacement for XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing/connection, suitable thimble should be used as per site situation.
Supplying and fixing in replacement of PVC flat serviceable cable 10 Sqmm 2 core multi stranded conductor 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular including taking down old one complete all as specified and directed.
Supply and fix in replacement of polycarbonate meter boxes and complete enclosure of size 4 feet X 6 feet for TPN boxes, DB boxes and meter enclosure, vermin proof, rust proof having locking arrangement complete all as specified and directed.
Supplying and fixing in replacement of PVC flat serviceable cable 16 Sqmm 2 core stranded multi conductor 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat or circular including taking down old one complete all as specified and directed.
Material and labour in repair for earthing complete with galvanized steel plate elecrode of size 60 cm x 60cm x 6.3 mm thick burried directly in ground vertically to a depth not less than 2.5 metre below the ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level. Earth plate surrounded by 15mm thick packed alternative layers of charcoal dust and comman salt, earth lead GI wire of 4mm dia (8 SWG) by means of bolts, nuts, check nuts and washers of galvanised iron with thimbles. The other end of GI earth wire is connected to main switch board and protected by light grade GI pipe of 15 mm bore, provision of 20mm bore light grade GI pipe for watering including GI funnel and wire mesh. Pipe shall be provided vertically upto top level of earth pit and then taken horrizontally to the earth pit. Cement concrete chamber of PCC (1:3:6) type C-2 (using 40 mm graded crushed stone aggregate) complete all as specified and directed.
NOTE NO 1: - Samples of materials as approved will be kept in GE's sample room. NOTE NO 2: - All fittings and fixtures mentioned above will be fixed to the satisfaction of Engr-in-Charge and GE. NOTE NO 3: - Warranty certificate to the Engineer-in-Charge where ever applicable shall be submitted by the Contractor at the time of fittings.
M/S MANJIT SINGH AND SONS
BMMJ TRADERS AND ENGINEERS
M/S SALARIA ASSOCIATES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .