Executive Engineer (Electrical)
Works Department, IIT Delhi, Hauz Khas, New Delhi - 110016
SITC of VRF / VRV AC Unit in UG Drive and Transfer Research Lab at IIT Delhi (including CAMC)
2022_IIT_718628_1
IITD/WORKS(SP- 3986)/2022
Open Tender
Miscellaneous Works
Works
50 days
Indian Institute of Technology Delhi
Please refer Tender documents.
15 documents required · 15 mandatory
₹0
₹54,150
24 Nov 2022
18 Oct 2022
2 Nov 2022
18 Oct 2022
1 Nov 2022
18 Oct 2022
Amount
SUB HEAD 1 (SITC) OUTDOOR UNIT: Supply Installation, Testing & Commissioning of modular type Variable Refrigerant Flow / Variable Refrigerant Volume air cooled Outdoor units suitable for cooling and heating, having all hermetically sealed inverter type Scroll Compressor(s), minimum two compressors for above 14 HP modules, microprocessor based Controller, top discharge type condensing unit(s), with R-410 A Refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall deliver the rated capacity at AHRI conditions and work even at 50°C ambient temperature without tripping. The unit shall be suitable to work on 400 V+/-10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5.(Acceptable make: Mitsubishi / O-General / Toshiba / LG / Carrier / Bluestar / Daikin)
Location: B-3/172 Transfer Research Lab
Location: B-2/133 UG Drives Lab
INDOOR UNIT HIGH WALL TYPE: Supply, installation, testing and commissioning of following minimum capacity VRV / VRF High wall type Indoor unit equipped with washable synthetic media pre-filter, fan section with low noise fan / dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, cordless remote control including batteries, drain pan, necessary accessories etc., suitable for operation on 230 V ± 10%, 50Hz, single phase AC supply, complete as required. The unit shall have automatic force shutdown provision in case of fire on receiving signal from BMS System. The cooling capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and 19 Degree C WB temperature. (Make of the indoor unit shall be same as outdoor unit)
INDOOR UNIT CASSETTE TYPE: Supply, installation, testing and commissioning of following minimum capacity 4 - way flow VRV / VRF cassette type indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan / dynamically balanced blower, multispeed motor, coil section with DX copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cordless remote control (with batteries) etc., suitable for operation on single phase 230 V±10%, 50 Hz ac supply, complete as required. The unit shall have automatic force shutdown provision in case of fire on receiving signal from BMS system. The cooling capacity of indoor unit will be at air inlet conditions of 27 degree centigrade dry bulb (DB) an 19 degree centigrade wet bulb (WB) temperature. (Make of the indoor unit shall be same as outdoor unit)
Supply Installation, Testing & Commissioning of 4 Ton (not less than 48000 BTU/Hr) Inverter Cassette AC comprising air cooled Outdoor unit suitable for cooling, having all hermetically sealed inverter type Scroll Compressor(s), microprocessor based controller, top / side discharge type condensing unit(s), with R 410 A refrigerant, vibration isolators, with suitable foundation etc. complete as required. The unit shall be suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power supply. The unit shall be filled with first charge of the refrigerant and ready for use as required. The unit shall be complete with 4-way flow Cassette Type indoor ceiling mounted unit equipped with synthetic washable media pre-filter, fan section with low noise fan/dynamically balanced blower, multispeed motor, coil section with DX Copper coil, electronic expansion valve, outer cabinet, drain pump, grill, necessary supports, vibration isolation, cord less remote control (with batteries) etc., suitable for operation on single phase 230 V +/- 10%, 50Hz AC supply, complete, as required. The cooling capacity of indoor unit will be at air inlet conditions (return air) of 27 degree C DB and 19 Degree C WB temperature. Cutting and mending good of existing false ceiling shall be done by the contractor during installation of ceiling mounted indoor unit. Location: LHC UG Section. (Acceptable make: Mitsubishi / O-General / Toshiba / LG / Carrier / Bluestar / Daikin)
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft / hard drawn copper refrigerant piping for VRV / VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing / brazing including accessories, cutting of glass window wherever required with proper finishing, insulated with XPLE Class-O tubular insulation / with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquidlines, all accessories as per specifications etc. packing of all leakage either on wall or window with silicon / insulation, as required :
NOTE: (1) The copper piping and piping circuit should be with minimum number of joints, which shall be attained by: (a) Using one end expanded tubes (b) bending the tubes instead of using elbow joints wherever 90 degree bending is required (2) Piping should be routed at site in such a manner, that brazed joints in the refrigeration piping are kept to a minimum (3) The makes of tube fittings shall be same as that of tubes (4) The thickness of fittings used shall be same as that of the pipe
6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
9.5 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
15.86 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm with 19 mm thick insulation
19 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
22.2 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
28.58 mm dia (OD) (Hard drawn) with tube thickness 1.2 mm with 19 mm thick insulation
GI TRAY SUPPORT: Supplying and installing following size of perforated Hot Dipped Galvanised Iron Cable tray (galvanisation thickness not less than 50 microns) with perforation not more than 17.5% in convenient sections, joined with connectors, suspended / supported from the ceiling / wall with GI suspenders including GI bolts and nuts, GI C-Channels, etc. including GI protective sheet covering outside the room as required. (Only for outdoor portion)
225 mm width x 50 mm depth x 1.6 mm thickness
150 mm width x 50 mm depth x 1.6 mm thickness
DRAIN PIPE: Supplying and laying of ISI marked CPVC pipe of 32 mm dia for draining of sweated water from AC evaporator (indoor) unit including providing tee, joints, elbows, supports, etc. insulated with XLPE class - O tubular insulation / woth Class-O closed cell elastomeric nitrile rubber tubular sleeves sections of 19 mm thick etc. complete as required.
Supplying and fixing of following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc as required. (but without MCB/RCCB/Isolator) (Acceptable make: Havells / Standard / HPL/ Legrand / L&T / Polycab / C&S / ABB / Siemens / Schneider)
12 Way, Double door
16 Way, Double door
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Acceptable make: Havells / Standard / HPL/ Legrand / L&T / Polycab / C&S / ABB / Siemens / Schneider)
Single Pole
Double pole (as incomer to DB)
Supplying and fixing DP sheet steel enclosure on surface / recess alongwith 5 / 10 / 16 A, 240 V "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing cable end box (loose wire box) suitable for 12 / 16 way double door SPN MCB DB on surface / recess complete with testing and commissioning etc. as required.
Providing and fixing 4 mm dia dia copper wire on surface or in recess for loop earthing along with existing surface / recessed conduit / submain wiring / power cable as required.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in sheet steel enclosure including drilling holes, duly factory painted as required, making connections, etc. as required. (Acceptable make: Havells / Standard / Legrand / HPL / L&T / Polycab / C&S / ABB / Siemens / Schneider) For main power connection.
32 A, 16 kA, FPMCCB
Fabricating, Providing and fixing M.S. iron frame fabricated with M.S. C-channel of size 100 mm x 50 mm x 6 mm (thick) for resting the condenser unit on the roof / floor of the building duly supported from the bottom as required including painting and grouting the framework with cement concrete etc. complete as required.
Supplying and laying of ISI marked FRLS industrial multistranded flexible copper cable of following size of 1.1 kv grade conforming to IS694:2010 including making connection etc. for communication / indoor power supply between indoor and outdoor unit and other units, etc. through conduit complete as required. (for communication) (Acceptable make: Polycab / Havells / Gloster / RR Kabel / Nicco / Skytone / Finolex / KEI / Universal / Anchor) [NB: Single stranded cable not to be used]
2 core x 1.5 sqmm
3 core x 2.5 sqmm
Supplying and laying of following size FRLS industrial multistranded flexible copper conductor cable of 1.1 kV grade conforming to IS694:2010 of following sizes including making connections etc. as required. (Acceptable make: Polycab / Havells / Gloster / RR Kabel / Nicco / Skytone / Finolex / KEI / Universal / Anchor) [NB: Single stranded cable not to be used]
4 core x 16 sqmm
Supplying and making end termination with brass compression gland and tinned copper lugs for following size of pvc insulated and pvc sheathed / XLPE copper conductor cable of 1.1 kV grade as required.
4 core x 16 sqmm
Supplying and fixing of weather proof non-metallic 4P enclosure on surface / recess with 16/25/32 amp, 415 V, "C" curve Four Pole MCB with IP-65 rating complete with connections, testing and commissioning as required. (Reference similar product: Legrand 4 Module Plexo Box for MCB, IP-65) - For outdoor units (Acceptable Make: ABB / Legrand / L&T / Havells / Anchor / Finolex) - For outdoor unit
Providing nad laying in position cement concrete 1:3:6 (1 cement: 2 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of outdoor condenser unit including form work etc. as required.
SUB HEAD - 2 (AMC) (Supplementary agreement shall be formed) under ARMO Fund
Comprehensive (Routine, Preventive and Breakdown) maintenance of 10 & 22 HP VRF / VRV and 4 TR Cassette Type AC including its all accessories, condensers, evaporator units, time to time checking of refrigerant leakage, electrical circuits, etc. for smooth operation of the entire AC units during the defect liability period of 1 year after date of commissioning as per maintenance schedule. (No payment shall be made separately for this period): 1st Year Total 1 Job
Comprehensive (Routine, Preventive and Breakdown) maintenance of 10 & 22 HP VRF / VRV and 4 TR Cassette Type AC including its all accessories, condensers, evaporator units, time to time checking of refrigerant leakage, electrical circuits, etc. for smooth operation of the entire AC units after defect liability period of 1 year from the date of commissioning as per maintenance schedule. Any breakdown shall be attended within 4 hours of reporting. Spare parts required during breakdown maintenance shall be arranged and replaced by the Contractor. This is applicable for the whole system of AC units installed. (N.B.: 01 Job means during a period of one year)
2nd year (For 12 months)
3rd year (For 12 months)
4th year (For 12 months)
5th year (For 12 months)
6th year (For 12 months)
M/S COOLREF ENGINEERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .