Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.4 LAccepted-AOC INDEX NO E 29 CWE JRC 352 3 GURU NANAK PURA EAST JALANDHAR CITY PIN 144001 | JALANDHAR CITY | JALANDHAR | PUNJAB | 144001 | L1 | Accepted-AOC L1 | |
| 2 | L2₹39.8 L+₹2.4 L (6.30%)Rejected-Finance | L2 | Rejected-Finance Other than lowest. | |
| 3 | L3₹42.8 L+₹5.3 L (14.3%)Rejected-Finance | L3 | Rejected-Finance Other than lowest. | |
| 4 | L4₹43.1 L+₹5.7 L (15.3%)Rejected-Finance | L4 | Rejected-Finance Other than lowest. | |
| 5 | L5₹43.6 L+₹6.2 L (16.4%)Rejected-Finance | L5 | Rejected-Finance Other than lowest. |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
21 Sept 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE AF Adampur
Military Engineer services AF Stn Adampur 144103
MISC REPAIRS TO ELECTRICAL EQUIPMENTS AND CONNECTED WORKS AT AF STN ADAMPUR
2023_MES_616824_1
GE/AF/ADM-32/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Under GE AF Adampur
Refer NIT and Tender Documents
8 documents required · 8 mandatory
₹500
GE AF Adampur
₹80,000
Yes
30 Oct 2023
1 Sept 2023
22 Sept 2023
1 Sept 2023
21 Sept 2023
15 Sept 2023
2 Sept 2023 - 14 Sept 2023
Amount
Excavation in trenches n. exc 1.5 metre wide for taking out/ laying pipe line, cable, foundation etc. exceeding 1.5 metre but exceeding 3.00 metre deep and getting out as in soft/ loose soil complete all as specified. NOTES : Excavation work will be carried out by contractor manually and very carefully without endangering existing underground cables, pipe lines and adjoining structures, if any. In case any damage is caused, the same shall be made good by the contractor without any extra cost to the Govt.
Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete, all as specified.
Removal of excavated surplus spoil to a distance n. exc. 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete, all as specified.
Clean dry sand ( locally available) as cushioning for under ground cable 230 mm thick (one layer of 80 mm thickness before laying the cable and other layer of 150 mm thickness after laying the cable) complete all as specified. NOTE:- Punned down thickness (over all 180 mm) shall be considered for measurement and payment.
Factory made unreinforced pre-cast concrete cover block HV type-1 flat of size 300x180x40mm laid flat and dry in trenches over the cable for protection as length perpendicular to the direction of cable adjacent to each other IN REPLACEMENT complete, all as specified.
GI pipe light grade with all fittings fixed as termination postal ,fixed to poles/ walls/ under floors/ under road etc including takind down existing pipe complete all as specified of following size: -
50mm bore
80mm bore
100mm bore
Boring holes under road pavement / hardstanding by trenchless technology using ultrasound technique and necessary machine for inserting & including 80-100mm bore HDPE pipe complete, all as specified.
Supplying, laying, jointing and testing XLPE insulated screened PVC bedded galvanised steel strip or wire armoured heavy duty electric power cable (HT) 11000 volt earthed grade with aluminium conductor of cross sectional area 95 Sq.mm 3 core laid in trenches/ ducts/ along poles/ through pipes including taking out existing userviceable cable complete all as specified.
Taking up or down defective/faulty HT underground cable 11000 volts 95 Sq.mm 3 core from the existing trench/duct/pole etc and re-laying the same in the trenches/duct/pole etc after rectification of defects, including meggering of cable, provn of cable lugs, glands, thimble, insulation tape and connecting up with existing control gears, panels etc as per site requirement, complete all as specified.
NOTE FOR SERAL ITEM 8 to 9 :- Excavation, returning filling etc shall be measured and paid seperately under respective item of BoQ.
Cable jointing kit for 11 kV (Earthed) grade cable complete with jointing material and accessories suitable for 3 core 95 sqmm XLPE armoured aluminium conductor cable including taking down unserviceable termination complete all as specified of following size: -
Indoor termination heat shrinkage type joint.
Out door termination heat shrinkage type joint.
Straight through heat shrinkage type joint.
Cable route indicator showing "MES HT U/G cable 11 kV " (all words emposed) on route of cable with arrow made of CI insuitable shape and fixed on 50x6 mm angle iron not less than length of 450mm and embedded in PCC (1:2:4) concrete block of size 230x230x150mm, fixed in position including taking out old unserviceable indicators complete all as specified.
Repair, Maintenance & overhauling of HT (11 kV) VCB of capacity 400 to 630 Amp, indoor type after taking out trolley, checking of all fixed and moving parts for smooth operations, cleaning with CTC or CRC 226 and rustlick, air blower, replacement of minor parts, checking and repair to locking system, alignment & closing / triping & charging system including replacement of FRP phase barrier and providing re-insulation to bus bar with HT tape including SF6 gas filling, insulation compounding, repair to heaters and making the complete VCB functional with free and operating mechanism, including commissoning & testing complete. NOTE:- (i) Replacement of unserviceable spars will be measured & paid separately under Serial item No.13 here-in-after. (ii) Cost of SF6 gas and insulation compounding shall be deemed to be included in quoted rates. (iii) To maintain utmost security at AF Station, contractor will arrange his workmen along with T&P in a manner that nonfunctional VCB is made functional swiftly within 24 hour of receiving of complaint from the MES, during entire contract period. (iv) Not withstanding with the provision of "Compensation for Delay' envisaged under condition 50 of IAFW-2249, General Conditions of Contracts, additional compensation @ Rs. 500/- day will be charged from contractor in case he fails to make theVCB functional to the entire satisfaction of Engineer-in-Charge within 24 hour of receiving of complaint from the MES regarding non working VCB.
Replacement of the following unseerviceale parts of HT 11 kV VCB with new parts as under: - NOTE:- All parts of VCB should be as per OEM & approved by GE.
Vacuum bottle suitable for 630 Amp, 11 kV HT VCB.
Tripping coil suitable for 11 kV 400 to 630 Amp HT VCB.
Auxiliary switch NO/NC suitable for 11kV HT VCB.
Shunt trip coil 24-30 Volts DC suitable for 11 kV VCB.
Spring charging motor with gear assembly with rear spring charging motor with gear assembly 110-230 Volts AC 50 Hz suitable for 11kV VCB.
Heater spacer suitable for 11kV VCB.
Bus insulator suitable for 11kV VCB.
PT unit of HT VCB 11 kV/110V, 50 VA conforming to IS and CPRI/NABL approved.
CT unit, 200/5Amps, 15VA burden, accuracy 8.5 as per IS 2705 for metering / protection of HT VCB 11kV.
Volt meter 0-15kV with PT, digital type, suitable for HT VCB 11kV/110V.
Ammeter, digital type, 200/5Amps & 100/5Amps, suitable for HT VCB 11kV.
Frequency metre 50c/s, confirming to IS 1248 as per the existing specification.
Battery 12 volts DC 100/80AH
Over current & earth fault relay, digital self power relay showing earth fault & over current etc, including taking down old defective, removal and modification to existing panel to fix the new relay etc, complete all as specified. MAKE: Crompton Greaves (Type- CG-I 14 N) or equivalent make mentioned in Appendix 'B'.
Microprocessor based numerical relay with O/L, E/F and S/C protection suitable to work on 24 volt DC supply in renewal of any type relay including modifications to existing panel so as to accommodate the new relay complete all as specified. MAKE: Schneider (Formely Areva) cat part No. Schneider MICOMP 111L without communication or equivalent make mentioned in Appendix 'B'.
Trip circuit supervision relay with hand reset contacts, operating voltage 24 to 27 volt DC with 03 No + 02 NC, including connectingwith existing system commissioning and testing. MAKE: ALSTOM cat part No. VAX 31ZG8071BCH or equivalent make mentioned in Appendix 'B'.
Single element high speed tripping relay with hand reset contacts, operating voltage 24 to 27 Volt DC with 02 NO + 01 NC including connecting with existing system commissioning and testing. MAKE: ALSTOM cat part No. VAJH13YF0002BBA or equivalent make mentioned in Appendix 'B'.
LT ACB cut off/ ON relay, repair to ON/OFF system.
Repair to air circuit breaker 1250 A capacity including testing complete all as specified including replacement of the following spares: - (i) Spring charging motor -01 No. Make Havells or equivalent make mentioned in Appendix 'B'. (ii) Under Voltage Release -01 No's. Make Havells or equivalent make mentioned in Appendix 'B'.
REPAIR WORKS TO TRANSFORMERS
Dismantling and removing of transformer and shifting from site to local workshop for repair, opening in the presence of Engineer-in-Charge, taking out coil and detaching core & core assembly for estimation of repair and damaged parts, cleaning/washing of tank and removing the dust from all parts including cores, tanks, cooling tubes, removal of damaged parts, shifting to site and re-fixing in position after repairs, provision of cork sheets, making connections, including testing and commissioning, complete of rating:-
150 to 500 kVA
NOTE: (i) Supply and fixing of new spare parts shall be measured and paid for separately under serial item No. 16 here-in-after. (ii) Pre & post workshop inpection will be done by Engineer-in-charge & contractor will inform the Engineer-in-charge accordingly in advance.
Replacement of unserviceable spares / parts of the transformer with new parts as under: -
Aluminium coil of required size and quantity as per existing, made of super enamelled superior quality aluminium wire.
Copper winding coils of required size with super enamelled superior quality copper wire of suitable size on primary side of transformer (HV side)and specification, complete with insulation, varnishing, vaccum impregnation and baking of coil assembly etc complete.
Copper wound strips of required size and specification, wound with super quality copper wire of suitable size, on secondary side of transformer (LV side), complete with insulation, varnishing, vaccum impregnation and baking of coil assembly etc complete.
HT bushing insulator complete with brass stud washers & nuts etc, for transformers of capacity upto 500kVA.
LT bushing insulator complete with brass studs washer & nuts etc, for transformer of capacity upto 100 kVA.
LT bushing insulator complete with brass studs washer & nuts etc, for transformer of capacity 150 kVA to 500 kVA.
Breather assembly complete with fresh silicagel, for transformer of capacity 50 kVA to 100 kVA.
Breather assembly complete with fresh silicagel, for transformer of capacity 150 kVA to 500 kVA.
Supply and filling, silica gel to transformers, complete all as specified
Gun Metal globe/gate valve with iron wheel head, screwed both ends for iron pipe of size 25mm bore.
Filteration & Dehydration of HV grade transformer oil (On line/off line), minimum three cycles to achieve dielectric strength upto 60kV at 4mm gap and upto 40kV 2.5mm gap complete. NOTE - Oil filteration machine with all T&P & testing equipment required for filtration to be arranged by contractor without any extra cost to the department.
Transformer oil superior quality having di-electric strength not less than 50 kV at 2.0mm gap, ISI marked, 200 litre sealed drum, and filling, topping up into transformers and other equipments installed at various locations.
Spray machine painting to transformer from outside after cleaning of exposed surface by sand blasting or steel grit blating, with one coat of priming paint followed by two coats of high voltage insulation paints conforming to IS and as per existing colour including writing MES No/SM No, complete all as specified for capacity: -
Upto 100 kVA .
150 kVA to 500 kVA.
REPAIR WORKS TO HT RING MAIN UNIT
Disconnecting, taking out and removing of RMU 11 kV, 50Hz, 3 to 5 way, with CT/PTs from site to workshop for repair, opening in the presence of Engineer-in-Charge, checking of old fixed & moving parts, cleaning with CTC or CRC 226 & rustlick, air blower and removal of unserviceable parts of RMU, replacement of minor parts, adjustment of earth switches, checking & adjustment / repair to locking system, setting of alignment, closing & charging system, trip catch assembly and replacement of bushing of bus bar chamber including gas filling and insulation compounding etc and making functional, testing & commissioning, complete (Make of existing RMU: Crompton Greaves, ABB, Schneider) for the following type: - NOTE:- (i) To maintain utmost security at AF Station, contractor will arrange his workmen along with T&P in a manner that nonfunctional RMU is made functional swiftly within 24 hour of receiving of complaint from the MES, during entire contract period. (ii Not withstanding with the provision of "Compensation for Delay' envisaged under condition 50 of IAFW-2249, General Conditions of Contracts, additional compensation @ Rs. 500/- day will be charged from contractor in case he fails to make the RMU functional to the entire satisfaction of Engineer-in-Charge within 24 hour of receiving of complaint from the MES regarding non working RMU.
Indoor type of rating 630 Amp.
Outdoor type of rating 630 Amp .
Indoor type of rating 400 Amp .
NOTES: - (i) Cost of SF6 gas and insulation compounding shall be deemed to included in quoted rates. (ii) Supply and fixing of new spare parts shall be measured and paid separately (iii) All parts of RMUs should be as per OEM & approved by GE.
Replacement of unserviceable parts of the RMU with new parts as under: -
Cable Terminal Protector Boots, suitable for RMU 11 kV 630/400Amps, complete all as specified.
Indicator LED type (R/Y/B), suitable for RMU 11 kV 630Amps, complete all as specified.
Trip coil/close coil 24 Volts DC suitable for 11 kV RMU
Bus coupling bush suitable for 11 kV RMU
Earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 32 mm x 6 mm GI strip earthing lead complete all as shown in electrical plate No. 3 and as specified in Particular Specifications clause 19B.17 of contract, IN REPAIR.
NOTES: - (i) The unit rate includes earthing lead and protection pipe upto 7.5 metre from top of earth plate. (b) Factoy fabricated precast PCC pit & cover shall be fixed at least 500 mm away from earth pit. (iv) Earth resistance should not be less than 3Ohm. In case the test results are not found below 3 Ohm, complete earthing will be redone by the contractor without any extra cost to Govt.
Triple pole, switch air break, gang operated, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 400 amp and working pressure of 11000 volt grade, consisting of 09 single pole 11000 volts grade outdoor use insulators per pole, with 20mm dia medium grade GI pipe operating handle and locking arrangement fixed with down rod operating brackets, IN REPLACEMENT complete all as specified.
Drop out expulsion fuse, single pole, suitable for 11000 volts grade, AC supply, upto 50 Amps, IN REPLACEMENT complete all as specified.
Lightning arresters, high tension, expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11000volts, including brackets, nuts, washers and connecting to GI earth wire 4mm dia, IN REPLACEMENT complete all as specified.
Cross arms, bracing, supports, clamps and back plates, fabricated from structural steel section Fe-290 grade E-165 quality including nuts, bolts, washers, and welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of alminium paint over a coat of red oxide primer and taking down old unserviceable material complete all as specified..
Steel tubular swaged poles complete with cast iron/mild steel base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9 metre long) including drilling of necessary holes, & painting, IN REPLAEMENT complete, all as specified. NOTE: Excavation & earthwork & foundation concrete will be meaured & paid for separately under respective item(s) of BoQ.
Plain cement concrete (1:3:6) type C-2 using 40 mm graded stone aggregate in foundation filling & mass concrete for poles/struts/stays assembly complete all as specified.
Plain cement concrete (1:2:4) type B-1 using 20mm graded stone aggregate as in coping to poles poles, bases of out door panel boards etc., including ncessary form work with fair finishing surface of concrete complete, all as specified.
Opening connections of 11 kV faulty cable at both ends and re-connecting the same after rectification of cable fault, rectifying the cable fault by means of cable fault detector mounted on the vehicle, charging capacity 15 kV passing through the cable to detect exact location of faulty point of the cable. Each fault should be traced at a maximum distance of one metre of exact fault point. NOTE: (i) Cost of transporation charges for the vehicle, T&P required is deemed to be included in the quoted rate. (ii) To maintain utmost security at AF Station, contractor will arrange his workmen along with T&P in a manner that nonfunctional HT line is made functional swiftly within 24 hour of receiving of complaint from the MES, during entire contract period. (iii Not withstanding with the provision of "Compensation for Delay' envisaged under condition 50 of IAFW-2249, General Conditions of Contracts, additional compensation @ Rs. 500/- day will be charged from contractor in case he fails to make the HT line functional to the entire satisfaction of Engineer-in-Charge within 24 hour of receiving of complaint from the MES regarding non working HT line.
Factory made (CPRI approved), HT Bus bar panel, size 1200mm x1200mm x 750 mm, cubical, outdoor type, weather, dust and vermin proof having IP-65 protection, fabricated out of 3.15mm thick MS CRCA sheet mounted on frame of appropriate size angle iron, welded below frame, front & double door having locking arrangements, bottom space for cable end provision of glands, with copper bus bars 400 Amp rating-01 set (set of threee) mounted on 6 Nos. HT post type insulators, 11000 volts grade, suitable size (not less than 36mmx5mm) duly sleeved wtith relevant colour code insulation & provision of 01 No incoming & outgoing as directed. Entire exposed surfaces of sheet metal work including frame & legs shall have anti corrosive coating and finally epoxy polyester powder coatig of flint grey shade (RAL-7032) all as specified in relevant IS. Legs of panel shall be embedded in ground in PCC (1:2:4) block of size 300x300x300 mm IN REPLACEMENT complete, all as specified.
Supply, fixing & connecting, Opening of 11 kV Bus bar chamber and Replacement of HT 11 kV insulator , refiixing the same complete with testing and commissioning of bus bar chamber complete all as specified.
NOTE: Amount of credit for retrieved materials is mentioned in tender documents in pdf form which will be deducted while acceptance of tender offline.
Building Block Constructions
Kaul Enterprises
Bains Enterprises
N S ENGINEERS
J.K & Company
MALHOTRA AND ASSOCIATES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .